Professional Documents
Culture Documents
Benefits Functions
• Communicates electrical • Communications via Modbus
system data and circuit and Eaton’s INCOM protocol;
breaker status compatible with Eaton’s PXG
for Web page and Ethernet
• Meets ANSI C12.1 revenue
capabilities
grade standard with a current
and voltage accuracy of 0.5% • Works in 240 Vac PM3, 480 Vac
of reading and 600 Vac applications
• Calculates power and • 480 Vac PM3 has internal
energy to an accuracy of power supply to power
1.0% of reading electronics (INCOM only)
• Configurable with thermal- • 600 Vac PM3 requires 24 Vdc
magnetic or electronic auxiliary power
trip units • Seamlessly integrates with
• Suitable for reverse-feed thermal-magnetic or electronic
applications trip units
• Easy to install
Product selection
PM3 benefits when combined Catalog Number
with 310+ electronic trip unit Frame 480V 600V
Frequency
Frequency 50/60 Hz
Accuracy ±0.1 Hz
Resolution 0.1 Hz
Isolation
All inputs and outputs are galvanically isolated to 2500V
Environmental Ratings
Operating temperature –20°C to +50°C
Storage temperature –20°C to +50°C
Operating humidity 5 to 95% RH noncondensing
Sensing Method
Voltage, current True rms
Sampling rate 13.02K samples per second
Update Rate
Watts, Var and VA 1.03 sec at 60 Hz
All other parameters 1.07 sec at 60 Hz
Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com
© 2013 Eaton
All Rights Reserved Eaton is a registered trademark.
Printed in USA
Publication No. PA01222003E / Z13866 All other trademarks are property
June 2013 of their respective owners.