GE WCPU Models Compressor unit MCA,Max Fuse Size & MCB Calculation
Fan Motor + Compressor FM Comp
Item Qty Unit Power Input, Unit Running Unit Max. Starting Unit Power Input, Unit Running Max. Starting Current, A Unit Max Fuse kW Current, A (FLA) Current, A (FSA) Quantity kW Current, A (RLA) (CSA) Unit MCA Size & MCB MCA MCB MCA MCB WCV 250 1 3.51 6.1 45.8 2 6.43 x 2 12.78 x 2 118 x 2 35 48 8 24 29 42 6.43 x 2 12.78 x 2 118 x 2 WCV 350 3 6.26 10.6 79.5 3 3.69 x 1 6.95 x 1 74 x 1 46 59 13 42 36 48 7.26 x 3 13.86 x 3 118 x 3 WCV 450 2 8.44 13.8 100.7 4 3.69 x 1 6.95 x 1 74 x 1 66 80 17 55 52 66 7.26 x 3 13.86 x 3 118 x 3 WCV 500 11 8.44 13.8 100.7 4 3.69 x 1 6.95 x 1 74 x 1 66 80 17 55 52 66 WCV 550 11 11.11 18.4 136.2 4 7.26 x 4 13.86 x 4 118 x 4 78 129 23 74 59 73 7.26 x 4 13.86 x 4 118 x 4 WCV 650 1 12.20 20.2 149.5 5 3.69 x 1 6.95 x 1 74 x 1 88 143 25 81 66 80 WCV 700 1 13.75 22.5 168.8 5 7.26 x 5 13.86 x 5 118 x 5 97 159 28 90 73 87
Unit circuit breaker size selection should > calculate unit MCA and ≤ calculate unit max fuse size & MCB