You are on page 1of 4

Consumer Meter specification with ABT Feature

Product General Specifications


 Model – Mk6E
 Make – Wallaby
 Reference frequency – 50Hz, Variation.- ±5%
 Rated voltage - 3x110V Ph-Ph, 3x110V/ 3 Ph-N,
 Secondary Current :

1. Model A: Class 0.2S, Ib:-/1A, Imax: 2A, 3P4W, Vn: 3 x 63.5V, 50Hz
2. Model B: Class 0.2S, Ib:-/5A, Imax: 10A, 3P4W, Vn: 3 x 63.5V, 50Hz
3. Model C: Class 0.2S, Ib:-/1A, Imax: 2A, 3P3W, Vn: 2 x 110V, 50Hz
4. Model D: Class 0.2S, Ib:-/5A, Imax: 10A, 3P3W, Vn: 2 x 110V, 50Hz
 Reference frequency – 50Hz, Variation.- ±5%
 4 True Quadrant measurements - Fundamental
 Integration interval for Load survey are configurable(Default 15mins)
 User friendly LCD Display configurable.
 Auxiliary Voltage 110-240VAC/DC
 Built in calendar and clock.

Measurand (s)
Time, Date, Frequency, Power ON/OFF hours.
Instantaneous Voltage, Current
Power Factor(Lag/lead)
Average Frequency coding for billing
(Two Digit code 00 to 99 for frequency from 49.0 to 51.0Hz)
Energy parameters – kWh, kVArh, kVAh – both Imp & Exp,
Power (kW, kVAr, kVA)
Fundamental Energy, Power
kVArh at 103% (High) voltage and 97% (low) voltage
Net Wh register during successive 15 mins Block, upto second decimal, with ‘+’ sign for
Export and ‘-’ sign for Import.

Wallaby Metering Systems Pvt. Ltd. Page 1 of 4


Consumer Meter specification with ABT Feature
Cumulative Wh register at each midnight in six digit including one decimal
Cumulative VArh register for Voltage High condition at each midnight in six digit including one
decimal
Cumulative VArh register for Voltage low condition at each midnight in six digit including one
decimal

For Model A & C measurement of Wh, Var and VArh will be computed directly in CT and
VT secondary quantities. These quantities will be directly recorded, displayed in meter and
BCS
For Model B & D measurement of Wh, Var and VArh will be computed directly in CT and VT
secondary quantities. These quantities will be directly recorded, displayed in meter but in BCS the
active energy will be displayed as one fifth of the Wh computed in CT and VT Secondary quantities.

Compatible Standards
o IS 14697:1999
o IEC 62052-11,62053-22
o CBIP
Temperature Range
o Operating : -25 to +60 C
o Storage : -25 to +80 C
Communication
o Optical Port- IEC 1107
o Remote-Modem(GPRS/GSM) - Internal Modem Power supply
o RS 232
o RS485 (Optional)
o CMRI – ASCII Format Incorporated.

Wallaby Metering Systems Pvt. Ltd. Page 2 of 4


Consumer Meter specification with ABT Feature
Available Surveys

 Load Surveys - Readings are stored every 15 minutes for a period of 40 days.

1 Record No. 4 Frequency Code


2 Date and Time 5 Status indication
3 Net Wh(Fund)

Status Indication:
VT failure - * Time retard - rr Time advanced - aa

 Daily Survey - Readings are stored every 1440 minutes (00.00 hours) for a period of 40 days.

1 Net Wh (Fund) Total 3 Cum VArh High (6 Digit with 2 Decimal)

Cumulative Net Wh (Fund)


2 4 Cum VArh Low (6 Digit with 2 Decimal)
(6 Digit with 2 Decimal)

 Event Log - An Event Log records events that occur to the meter and the time at which they
occur. A total of 100 entries can be stored.

1 System events 9 Firmware Change events

2 Power off/on events 10 Billing events

3 Battery/FLASH events 11 Automatic billing reset events

4 Meter Extension events 12 Manual billing reset events

5 Meter Database events 13 TOU cleared events

6 Time events 14 diagnostic events

7 EFA events 15 user events

8 Firmware Change events 16 Script events

Wallaby Metering Systems Pvt. Ltd. Page 3 of 4


Consumer Meter specification with ABT Feature

LCD Display Parameters


2-Line by 16 – Character Display with backlight

MODE A MODE B
1 Serial No. 16 Export Wh
2 Current Date 17 Import Wh
3 Current time 18 Export VAh
4 NET Wh 19 Import VAh
5 Previous 15 Mins Avgerage frequency 20 Import VArh Lag
6 Previous 15 Mins NET Wh 21 Import VArh Lead
7 Average % Voltage 22 Export VArh Lag
8 Reactive Power 23 EXport VArh Lead
9 Import VArh High
10 Import VArh Low
11 Export VArh High
12 Export VArh Low
13 Net VArh High
14 Net VArh Low
15 Voltage Healthy

LCD Display Settings Config


Cyclic Rate in Sec(1 to 255 Seconds) 15 Secs
Display Revert in Mins(1 to 255 Minutes) 15 Mins
Hold time in Secs (0 to 255 Seconds) 60 Secs
Back light On time (1 to 254 Secs) Always

Wallaby Metering Systems Pvt. Ltd. Page 4 of 4