Professional Documents
Culture Documents
NeTSure Data Sheet
NeTSure Data Sheet
R48-3200e
R48-3200e
eSure™ Rectifier DC Power
for Business-Critical Continuity™
R48-3200e
% of output power
Input Voltage, Permitted Variation 85 to 300 V AC 100
Line Frequency 45 to 65 Hz 80
Max Input Current 17 A 60
40
Power Factor 0.99
20
THD (Total Harmonic Distortion) <5% from 50 to 100% of rated load 0
-40 -20 0 20 40 60 80 100
Temperature (°C)
DC Output
Output Voltage, Adjustment Range -42 to -58 V DC
Output Power 3200W@Vout >48VDC
Output Power, Derated for Input Voltage See Diagram Output power vs. Input voltage and Vo
Output Current 67A >48V at Temp≤45°C
120
% of output power
Output Current limit set Point 0 to 67 A
100
Efficiency 96.8% peak 80
Psophometric noise (system) <2 mV typical 60
<32 dBrnc typical 40
20
Temperature Derating See diagram
0
0 50 100 150 200 250 300 350
Output Voltaqe(V)
Environmental 50
Temperature Range, Operating -40 to +75°C, -40 to +167°F 40
Temperature Range, Storage -40 to +75°C, -40 to +167°F 30
20
Relative Humidity 0 to 95%
10
Altitude 2000 m, 6560 ft at full power
0
EMC ETSI EN 300 386 class B, FCC CFR 47 Part 15 class B, Telcordia GR-1089-CORE class B 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70
Safety IEC 60950, EN 60950, UL 60950
Output current(A)
Mechanics
Dimensions (H×W×D) 132×85.3×287mm / 5.2×3.36×11.3 inches Efficiency Efficiency Curve
Weight 3.1 kg / 6.8 lbs
97.5
97.0 96.69 96.80
96.53
96.5
96.11
96.0
Other parts 95.5 95.41
95.53
Controller Units See separate ACU/ACU+ and SCU/SCU+ datasheets 95.0
94.5
94.0
93.5 93.39
93.0
Ordering information 0 10 20 30 40 50 60 70 80 90 100
Description Product name
Load (% of rated load)
Rectifier 48V,3200W R48-3200e