Professional Documents
Culture Documents
Standby Prime
550 ekW 500 ekW
600 ekW 545 ekW
650 ekW 600 ekW
700 ekW 635 ekW
750 ekW 680 ekW
Image shown might not reflect actual configuration
Cat generator set packages have been fully prototype tested and
Engine Model Cat® C18 ACERT In-line 6, 4-cycle diesel
certified torsional vibration analysis reports are available. The
packages are designed to meet the NFPA 110 requirement for Bore x Stroke 145mm x 183mm (5.7in x 7.2in)
loading, conform to the ISO 8528-5 steady state and fill transient
Displacement 18.1 L (1106.3 in³)
response requirements.
14.5:1 (550-600 ekW); 14:1 (650-750
Compression Ratio
ekW)
. CAT DIESEL ENGINES Aspiration Turbocharged Air-to-Air Aftercooled
The four-cycle Cat diesel engine combines consistent performance
with excellent fuel economy and transient response that meets or Fuel Injection System Electronic Unit Injection
exceeds ISO 8528-5. The engines feature a reliable, rugged, and Governor Electronic ADEM™ A4
durable design that has been field proven in thousands of
applications worldwide in emergency standby installations. Emission
EPA TIER II
Certifications
COOLING SYSTEM
The cooling system has been designed and tested to ensure proper GENERATOR SET SPECIFICATIONS
generator set cooling, and includes the radiator, fan, belts, and all
guarding installed as standard. Contact your Cat dealer for specific
ambient and altitude capabilities. Alternator Design Brushless Single Bearing, 4 Pole
Stator 2/3 Pitch
FEATURES
SUB BASE
• UL Listed for United States (UL 142) and Canada • The sub-base fuel tank mounts below the
(CAN/ULC S601) generator set wide base.
• Facilitates compliance with NFPA 30 code, NFPA 37 and
110 standards and CSA C282 code
INTEGRAL
• Dual wall
• Lockable fuel fill cap, 4” (101.6 mm) NPT • Integral diesel fuel tank is incorporated into the
• Low fuel level warning standard, customer configurable generator set base frame
warning or shutdown • Robust base design includes linear vibration
• Primary tank leak detection switch in containment basin isolators between tank base and engine
• Tank design provides capacity for thermal expansion of generator.
fuel
• Fuel supply dip tube is positioned so as not to pick up
OPTIONS
fuel sediment
• Fuel return and supply dip tube is separated by an • Audio/visual fuel level alarm panel
internal baffle to prevent immediate re-supply of heated • 5gal (18.9 L) spill containment
return fuel • 5gal (18.9 L) spill containment with fuel fill drop
• Pressure washed with an iron phosphate solution tube with in 6” (152 mm) from bottom of tank
• Interior tank surfaces coated with a solvent-based thin- • 5gal (18.9 L) spill containment with overfill
film rust preventative prevention valve and fuel fill drop tube with in
• Heavy gauge steel gussets with internal lifting rings 6” (152 mm) from bottom of tank
• Primary and secondary tanks are leak tested at 20.7 kPa • ULC Listed 7.5gal (28.4 L) spill containment with
(3 psi) minimum vent extensions, vent whistle, and drop tube
• Compatible with open packages and enclosures facilitating compliance with CSA B139-09
• Gloss black polyester alkyd enamel exterior paint • ULC Listed 7.5gal (28.4 L) spill containment with
• Welded steel containment basin (minimum of 110% of overfill prevention valve, vent extensions, vent
primary tank capacity) whistle and drop tube facilitating compliance
• Direct reading fuel gauge with variable electrical output with CSA B139-09
• Emergency vents on primary and secondary tanks are
sized in accordance with NFPA 30.
3/9
LEHE1773-01 (08/18)
Cat C18 ®
INTEGRAL & SUB BASE FUEL TANKS
Integral & Sub-Base Fuel Tank Base Useable Capacities with Fuel Tank Dimensions & Weights
Integral – Width (W) 2014 mm (79.3 in)
Integral* – Width (W) 2315 mm (91.2 in)
Sub-base – Width (W) 2056 mm (81.0 in)
Overall Package
C18 Tank Total Useable Tank Only Height with
Feature Capacity Capacity Tank
Design
Code Dry Weight Height ‘H’ Length ‘L’ Enclosure
Litre Gallon Litre Gallon kg lb mm in mm in mm in
Integral FTDW003 1446 382 1422 376 1015 2237 635 25.0 3814 150.1 2560 100.8
Integral* FTDW031 5175 1367 4997 1320 2046 4510 762 30.0 6737 265.3 2675 105.3
Sub-Base FTDW005 3941 1041 3876 1024 1659 3657 635 25.0 5550 218.5 2905 114.3
Sub-Base FTDW007 8339 2203 8244 2178 2150 4134 889 35.0 7074 278.5 3209 126.3
Sub-Base FTDW011 2476 654 2435 643 1468 3236 635 25.0 3810 150.0 2905 114.3
The heights listed above do not include lumber used during manufacturing and shipping
Tanks with full electrical stub-up area include removable end channel. Tanks with RH stub-up include stubup area
directly below the circuit breaker or power terminal strips. Dimensions include weather-protective enclosure exhaust
system.
Dual wall sub-base tanks are UL Listed and constructed in accordance with UL Standard for Safety UL 142, Steel
Aboveground Tanks for Flammable and Combustible Liquids and Canada CAN/ULC S601, Standard for Shop Fabricated
Steel Aboveground Horizontal Tanks for Flammable and Combustible Liquids.
Fuel tanks and applicable options facilitate compliance with the following United States NFPA Code and Standards:
NFPA 30: Flammable and Combustible Liquids Code
NFPA 37: Standard for the Installation and Use of Stationary Combustion Engines and Gas Turbines
NFPA 110: Standard for Emergency and Standby Power Systems
Fuel tanks and applicable options facilitate compliance with the following Canadian Standard and Code:
CSA C282 – Emergency Electrical Power Supply for Buildings
CSA B139-09 – Installation Code for Oil-Burning Equipment
The following sub-base fuel tanks meet Chicago code for containment and labelling: FTDW005, FTDW008, FTDW011
FEATURES
Sound Pressure
Cooling Air Flow Ambient
Standby Levels (dBA) at
Enclosure Type Rate Capability*
ekW 7m (23 ft)
m3/s cfm °C °F 100% Load
550 8.1 17234 45 113 75
600 8.1 17234 43 109 75
Level 1 Sound Attenuated Enclosure (Steel) 650 12.7 26909 51 123 75
700 12.7 26909 48 118 75
750 12.7 26909 46 114 75
550 8.1 17234 45 113 76
Sound Attenuated Enclosure (Aluminium)
600 8.1 17234 43 109 76
550 9.1 17234 52 126 86
600 9.1 17234 50 122 87
Weather Protective Enclosure 650 12.7 26909 46 114 87
700 12.7 26909 46 114 87
750 12.7 26909 46 114 87
*Cooling system performance at sea level. Consult your Cat® dealer for site specific ambient and altitude capabilities.
Note: Sound level measurements are subject to instrumentation, installation and manufacturing variability, as well as ambient site conditions.
LEHE1773-01 (08/18)
7/9
Cat C18 ®
ENCLOSURES
Standby
Length, L Width, W Height, H Package Weights
Enclosure Type Ratings,
ekW mm in mm in mm in kg lb
Sound Attenuated Enclosure on 550/600 5187 204.2 2014 79.3 2561 101.0 6747 14874
a UL Listed Integral Fuel Tank
Base 650/700/750 6977 274.7 2315 91.1 2675 105.3 7989 17613
FINANCING
Caterpillar offers an array of financial products to help you succeed through financial service excellence. Options include loans, finance
lease, operating lease, working capital, and revolving line of credit. Contact your local Cat dealer for availability in your region.
Cat dealers provide extensive post-sale support including maintenance and repair agreements. Cat dealers have over 1,800 dealer branch
stores operating in 200 countries. The Caterpillar® S·O·SSM program effectively detects internal engine component condition, even the
presence of unwanted fluids and combustion by-products.
www.Cat.com/electricpower
©2018 Caterpillar All rights reserved. Materials and specifications are subject to change without notice. The International System of
Units (SI) is used in this publication. CAT, CATERPILLAR, their respective logos, ADEM, S•O•S, “BUILT FOR IT”, “Caterpillar Yellow”, the
“Power Edge” trade dress as well as corporate and product identity used herein, are trademarks of Caterpillar and may not be used
LEHE1773-01 (08/18)
9/9