SPECIFICATION P-117: 88
(UDC 621.315.5:669)
ALUMINIUM ALLOY STRANDED CONDUCTOR
PAKISTAN
WATER AND POWER DEVELOPMENT AUTHORITY
DESIGN DEPARTMENT (T&G) POWERSPECIFICATION P-117:88
ALUMINIUM ALLOY STRANDED CONDUCTOR
AMENDMENT NO. 2 DATED 12TH FEBRUARY, 1990
CLAUSE 3.1
Please add the sentence “The maximum value permitted
25 0.0328 ohm. mu2/m at 20°C" at the end of this clause.
CLAUSE 3.4
ij Please add the word "a" at the end of the heading
of this clause.
il) Please add the word "a" after the words “coeffi-
cient of resistance," in the second line of this
clause,
CLAUSE 9.5.4.1
Please replace the word "sampel“ in 3rd line with
“sample.
CLAUSE 6.4.1
i) Please replace the formula for resistence at 20°C
(R20) as under:—
gosh, -
Pea (i307
ii) In Lhe second last line of this clause, please
write the word "a" in the blank space which is
after the word “and" & on the left side of the
sign of equality.
R20 Rt (-
)
iii) Please replace “{ s 0.003 60)" with 9.00360)"
in the last line of this clause after the words
“of resistance”.
Please replace the word "not" in 3rd tine with "no".
CLAUSE 10.1
a)
lease repiace the word "
rigours".
igors" in 4th line with
i) Please add the sentence “the reels should be suit-
able for tension stringing and capable to with
stand its rigonrs” after 2nd sentence in the fifth
line of this clause.
iii) Please veplace the word "entachlorophenol” in 3rd
ast line of this clause witn “pentachlorephenol™.iit
DIMENSIONS
Please replace the value "2200" for Nominal
length of Caire Conductor with "2220" in table
of fig te
Please replace the value "4g9g" with "4593"
fer Nominal weight of Greely Conductor in the
table of fig 1.10.
CONTENTS
Foreword
Scope
Definition
Standards for Aluminium Alloy
Conductor
Material
Dimensions and Characteristics
Test Methods
Tests by Manufacturer
Acceptance Tests
Acceptance and Rejection
Packing and Marking
PRINTING HISTORY
First approved on 15th July, 1979.
First revised on Aprii, 1988.
Amendment No.
i Dated 12th February, 1990.
3999888 %SPECIPICATION P~117: 88
(UDC 621.315.5:669)
ALUMINIGM ALLOY STRANDED CONDUCTORS
POREWORD
This standard specification has been prepared by the
Besign Department Power Wing, WAPDA and lays down speci-
fications for Aluminium Alloy Stranded Conductors.
This specification is based on 1.8.C. 208 and ASTH B399
and is subject to revision as and when required.
This specification is intended for procurement of material
and does not include provisions of contract.
SCORE
This specification covers concentric layers stranded
conductors, made from round aluminium alloy wires, for
use as overhead conductors in polluted area.
DEFINITIONS
For the purpose of this specification the following defi-
nitions shall apply.
Stranded Conductor
Conductor consisting of seven or more aluminium alloy wires
of the same nominal diameter twisted together in concen
tric layers. hen the conductor consists of more than one
layer, successive layers are twisted in opposite directions.
Diameter
Mean o£ two measurements at right angles taken at the same
cross-section.
Direction of Lay
The direction of lay is defined as right-hand or left-
hand. With right hand lay, the wire conform to the direc~
tion of the central part of the letter "Z" when the con-
ductor is held vertically. With left-hand lay, the wires
conform to the direction of the central part of the letters
"s" when the conductor is held verticall.
Lay Ratio
Ratio of the axial length of 2 complete turn of the helix
formed by an individual wire in 2 stranded conductor to
the external diameter of the helix.
AX2.6
Heat-Treatment Batch
Purnace load of material heat-treated at the sane time,
at the sane temperature and for the same length of time.
STANDARDS FOR ALOMINIUM ALLOY WIRES
Resistivity
For the purposes of this specification, the standard
value of resistivity of aluminium alloy wire which shail
be used for calculation is to be taken az 0.0325 ohn.
maZ/m at 20°C.
Density
At a temperature of 20% the density of aluminium alloy
wire is to be taken as 2.70 ka/dm?.
Coefficient of Linear Expansion e
The Coefficient of Linear expansion of aluminium alloy
wire is to be taken as 23x10" per centigrade degree.
Constant-mass Temperature Coefficient
At a temperature of 20°C the "Constant-mass" temperature
coefficient of resistance, , of aluminium alloy wire
measured between two potential points rigidly fixed to
the wire, is taken as 0.00340 per centigrade degree.
MATERIAL (6201 Aluminium Alloy}
The conductor chall be constructed of heat-treated alu-
minium-magnesium-silicon alloy wires containing approxiz
mately 9.5% magnesium and approximately 0.5% silicon and
having the mechanical and electrical properties specified
herein.
The wires shall be smooth and free from all imperfections e
hot Consistent with good commercial practice.
The ultimate tensile stress of wire before or after
stranding shall not be less than 30 kg/mmé.
DIMENSIONS AND CHARACTERISTICS
Standard Sizes
The dimensions and characteristics of the conductor
standardized for use by WAFDA and covered by this speci-
fication are given in Table-I.SABLE
DIMENSIONS AND CHARACTERISTICS
OF ALUMINLUM ALLOY CONDUCTORS
Cale bee
code Stranding Dia of — lated Rated DoS.
coes and wire complete area of ultimate [S3S57 weight
aia conductor complete strength 8
at 20°C
conducton
no/me mim mm? kg ohms/it kg/km
Aimoné 7/2034 7.02 30.10 903 1.084 82
Azoza 13.37 kos. 62.44 1873 0.527 ah
Alliance 7/4.77 14.31 428.09 3753 (0.263 342
cairo 19/3.98 19.80 236.38 7091 0.140 630
meGreeley 37/4.02 28.14 469.80 13835 9,071 1295
5.2 folerance on Nominal Diameters of Wires
5.2.1 The aluminium alloy wires shall not depart from the nomina
diameter by more than the following amounts.
Woatnar Tolerance
piameter —
2.501 sos
& greater
bess than
2.5 0k ++0.025m0
5.3 Joints in wires
5.3.1 Conductors Containing Seven wires
There shall be no joints in any wires of a stranded con—
ductor containing seven wires, except those made in the
base tod or wire before final drawing.
5.3.2
Conductors Containing more than Seven Wires
In stranded conductors containing wore than seven wires,
joints in individual wires are permitted in any layer
except the outermost layer (in addition to those made
in the base rod or wire before final drawing) but no two
guch joints shall be less than 15 m apart in the complete
stranded conductor. Such joints shall be made by re-
sistance butt-welding and shall, subsequent to welding,
be annealed over a distance of at least 200mm on each
side of the joint. They are not required to fulfill the
mechanical reguirements for unjointed wires.8.4.4
Stranding
The wires used in the construction of a stranded conductor
shall, before stranding, satisfy all the relevant requirc-
ments of this specification.
The lay ratio of the different layers shail be within the
limits given in Table-Ir.
TABLE ~ IE
Lay ratio for aluminium alloy stranded
Conductors
No. of Lay Ratio
wires
in Con- 6-wire Layer 12-wire Layer 18-wire Layer
ductor min max min max min max
7 210 14 - - ~ -
19 10 16 10 14 - -
37 210 a7 10 16 10 44
In all constructions, the successive layers shall have
opposite directions of lay, the outermost layer being
right-handed. The wires in eacn layer shall be evenly
ané closely stranded.
In aluminium alloy stranded conductors having multiple
layers of wires, the lay ratio of aay layer shall be not
greater than the tay ratio of the layer immediately beneat!
it.
Calculatio
of Conductor Properties
The properties of the conductors have been calculated in
accordance with clauses 5.5.2 through 5.3.4.
Increase in Length due to Stranding
When straightened out, each wire in any particular layer
of 2 stranded conductor, except the central wire, is
longer than the stranded conductor by an amount depending
on the mean lay ratio of that layer.
Resistance and Weight of Conductor
Tae resistance of any length of a stranded conductor is
the resistance of the same length of any one wire multi~
plied by a constant, as given in Table-II1.
The weight of each wire in any particular layer of a
length o£ stranded conductor, except the central wire will
be greater than that of an equal length of straight wireby an amount depending on the mean lay vatio of that
jayer (see 5.8.2 above). The total weight of any length
of stranded conductox is, therefore, obtained by miltil
plying the weight of en equal length of steaight wire
by constant, as set cut in Table-TIT.
SABLE - 173,
STRANDING CONSTANTS
Number of Stranding Constant
wires in =r
Conductor Herght
7 7,091 0.1447
19 19.34 0.09357
37 37.74 0.02787
Strength of Conductor
Phe strength of a styanded conductor, in terms of the
strengths of the individual component wires, may be taken
tu be 952 of the sum of the strength of the individual
wires calculated fromthe value of the minimum ultimate
tensile stress givne in Sub-clause 4.3.
For testing the ultimate strength of a complete stranded
conductor, suitable fittings shall be applied to the ends
of a sampel of conductor which shall be not less than 5m
long and the assembly chali then be pulled in a suitable
tensile testing machine. when so tested, the conductor
shall withstand at least 95¢ of its strength calculated
as indicated above.
TEST MBrHODS
Tensile vest
This test shall be made on aluminium atioy wires prior
to and after stranding. The breaking load of the specimen
cut from the sample shall be determined by means of a
tensile testing machine of which the accuracy can easily
be chacked and to which adjustments can be made if
necessary.
When automatic tensile testing machine is used, the load
shall be applied gradually and the rate of separation of
jaws of the testing machine shall not be greater than
Locam per minute.
When a hand operated lever testing machine is used, 90%
of the specified breaking load shall be applied quickly
and the load shall then be increased steadily until thegecimen breaks.
Q pazcent of the load shall be approximately 15 seconds
nd the total time fom first application of lead to
racture ghall be approximately 20 seconds.
Re time kaken dn applying the last
tha ea
when tested before and after stranding, the ultimate
tensile strengeh shall be not less than 36 ke/nm?.
Elongation Test
The englogation of a specimen tested as per clause 6.2
shali be determined as follows:
The specimen shail be straightened »y hand and an original
gauge length of 200m shail be marked on the wire. A
tensile load shall be applied as described in clause 6.1
above and the e!ongation shall be measured after the
fractured ends have been Fitted together. Tf the frac~
tured ende have been fitted together. If the fracture
occurs outside the guage marks, or within 25mm of either
marks, and the required elongation is not obtained, the
test Shall be disregarded ana another test made.
When tested before or after stranging, the elong
be not less than 4% on a guage length of 200mm.
on shal
Wrapping fest
Qhe aluminium alloy wire shall be wrapped round a manére}
of diameter equal to the wire diameter to form a close
helix of eight turns. Six turns shali then be unwrapped
and again closely wrapped.
The wire shall not break or show any cracks.
Resistivaty Test
Ghe electrical resistance of aluminium alloy wire shail
be minimus to an accuracy of at least one part in a
thousand. The length of the specimen shall be sufficient
to give the accuracy required and sha]] ke suitable for
the method of the testing used.
The electrical resistance of one specinen cut from ea:
of the samples taken from not less than 10¢ of the
individual lengths of aluminiom alloy wire included in
any one heat-treatment batch which will be included in
any one consignment of stranded conductor, shall be
measured at a temperature which shall be not less than
10°C and not more than 36°C. The measured resistanc:
shall be corrected to the value at 20°C by means of
formula:
nh
1
Rog * Ry OE TE=2Oy6.4.2
Woere: 2 * Temperature of measurement
R, = Lesistance at TC
resistance at 20°C
and conetant-wacs temperature coefficient
ef resistance ( = 9,003 50 }
whe resistivity at 20°C shall the:
the resistance at 208C, the re
not exceed 0.0323 ohm. xm2Z/m.
be calculated from
tivity at 290°C shali
YESTS BY MANUFACTURER
vel
The manufacturer shall progressively carry out tests
to waintain quality control and to ensure manufacture
of conductor in compliance with the specification, such
tests shall include the following, bub need not be res-
tricted to them.
1) Visual Inspection
2) Verification of Dimensions
3) Yensile and Blengation Tests
4) Wrapping Tests
5) Resistivity Tests
Visual inspection and verification of dimensions shall
be carriod out as routine Leste on wires end complete
conductors.
sefore the start of manufacture tae base rod shail be
tested for resistivity. One specimen shali he selected
at random ont of every 102 of the lengths aluginiam
alloy wire included in anyone consicnwent for test
Material not conforming te the strnaded shall not be used.
Yhe tensile strength and elongation tests shall pe carried
out on wire finished to size bat before stranding. Samples
shall be drawn From not less than 10 percent of the
individua) lengths of aluminium alloy wire which will be
{neluded in any one consignment.
whe manufacturer shall maintain a record of all the tests
carried out by him for examination by the authorized
eepresentative of WAPDA.
The manufacturer shall furnish a certificate to the effect
that the aluminium ailoy stranded conductor manufactured
by him conforms in all respects to the requirements of
this standard.
ACCEPTANCE TRSTS:
g tests shall pe carried out on the aluca
1
10.4
8
alloy stranded conductor for acceptance.
3) Yisual Inspection
2) Verification of Dimensions
3) Tensile an@ Elongation Tests
4) wrapping Tests
5) Resistivity Tests
ACCERYANCE AND REJECTION
qhe manufactucer shall divide each consignment into tots
for inspection. These lots shall be so selected that
material in a lot is of reasonably uniform quality and
as far as possible , is manufactured at the same tine
and under the same conditions. the manufacturer shall
keep sufficient production records to ensure that this
can be done regularly. & lot may contain any number of @
lengths upto a maximum of 150.
From each lot, regardless of its size, samples of wires
shall be taken at random from approximately i0% lengths
of stranded conductor included in any one consignment.
One sample sufficient to provide one specimen for each
teets, shall be taken from each strand of the conductor
in each of the selected lengths.
The samples taken shall be subjected te each of the
prescribed in clause 8, The lot shal] be accepted, if
for each test, the sample complies with the requirements
of clauses 9.4 and 9.5.
if in any test three or more specinens f2il, the entire
tot shall be rejected.
1f two specimens fail in any tests, a further sample in
accordance with clause $.2, shall be taken fre the lot,
and the particular tests repeated. If there are not e
further failures the sample shali be considered accept~
able for the test.
I€ im any test three or mora epegimens fail, the entire
let shall be rejected.
The manufacturer shall afford to the inspector all
necessary test facilities and assistance for carrying
out the tests. The failities shail be provided free of
charge.
PACKING AND MARKING
Aluminium alloy stranded conductor shall be sugplied on
stranded wooden reels as per fig. i. The reels shail
be nade fom high auality wood anc shall be of sound
construction, able to withstand the usual rigors of
transportation and field construction. The complete10.4
y of the reels apart frow being orotected b.
en lagging nailed at each end of the reek
as per £iq 1, shall also be bound by two
straps. The weoden recis shal? be given two brush
suats of 8 percent entacnlorophennot solution in cd
before winding of conductor. Tne conductor shall pe
wound tightly.
reel
The conductor shall be supplicd in lengths specified
fig 1. ach reel shal] contain either one or two
ths only as specified. A tclerance of plus or minus
5 percent is permitted on the conductor length. Addi-
tionally it snail be persissible to supply not more
shan 5 percent of the lengths on any one order in random
jengths, none of which shail be shorter than one third
of the nominal length.
fhe manufacturer shall vrovide the following markings
om the reels in legible ang indelible letters.
2) Manufacturer’s nam
nd dasignation
2) Conductor designation
3} Address of the consignee and purchase
order number
4) Serial number of the reel
the manufacturer shall stamp the Eollowing information
on metallic plates which shall be secureiy nailed to the
real,
i) Size and designation of aluminium
alloy stranded conductor
2) Net weight, tare weight and
weight, in ke.
3) Total length of the conductor on the
reel , in meters
4) Serial numher of the reel.
of the reel shall have an arrow marking
the i ion of rolling.
\SiEEL $TRA:
SWIDTH 20 ota
1 MANUFACTURER'S NAME
. AND BES'GNAr! oN
UEOR DESIGN,
WEW SIDE VIEW
—
“STONSIGNEE'S ADDRESS &
LSERISL NUMER OF REEL
PURCHASE Of NUMBER
Reel Piangé | Flange | Drum|thside) Arbor | tanging [Norminall Rox
Conductor|lDesigny Bia fThicknesd Bia. [Width | Hole # Thiclmess Length | Height of
lation | L 1M G Motors | CoMductor
[em shai aa | eg
~ | i
Wr Aieore RRL | sie i sO | Bet7eo | 279
|
Azoza |raao7e | a7 so | axt600 |
i !
Alliance |ssaa70 | 70 80
—P caine femaseo | a5e0 | 80
j
renazoe | 2200 | 80