Professional Documents
Culture Documents
Tata Power
Tata Power
Website: www.ijetae.com (ISSN 2250-2459, ISO 9001:2008 Certified Journal, Volume 5, Issue 2, February 2015)
135
International Journal of Emerging Technology and Advanced Engineering
Website: www.ijetae.com (ISSN 2250-2459, ISO 9001:2008 Certified Journal, Volume 5, Issue 2, February 2015)
Operator
Alarm/Event
Workstation
Dual Redundant Dual Redundant
Gateway Gateway
Copper Wires
IV. DIGITAL SUBSTATION All the digital input and output are configurable and can
Digital substations comprise of intelligent primary be processed by IEDs through Ethernet switch via optic
devices and networking IEDs to achieve information fiber.
sharing and interoperations based on IEC61850 protocol. The Digital Substation architecture can be described in
Digital substations has introduced GOOSE scheme the following levels as shown in the Fig 2.
which enables the replacement of traditional binary inputs a. Process Level
and binary outputs by digital models. b. Protection & Control Level
c. Station Level
136
International Journal of Emerging Technology and Advanced Engineering
Website: www.ijetae.com (ISSN 2250-2459, ISO 9001:2008 Certified Journal, Volume 5, Issue 2, February 2015)
138
International Journal of Emerging Technology and Advanced Engineering
Website: www.ijetae.com (ISSN 2250-2459, ISO 9001:2008 Certified Journal, Volume 5, Issue 2, February 2015)
Powai Substation, as Tata Power’s operational The basic assumption in this case is that feeders will be
philosophy monitored and controlled from PSCC (Power operated in sectionalized or non-parallel mode beyond this
System Control Center) which is geographically distant. substation. In case any PIED picks up on feeder fault (Fault
Thus the data exchange is not only constrained to the C), it will send a GOOSE message to the incomer-1 & Bus-
substation and a different protocol IEC 104 is used for Coupler. It will also send the blocking GOOSE message to
communication upto remote master. This conversion of the other Incomer-2 if bus coupler is closed.
protocols from IEC 61850, Modbus to IEC 104 is done by On receipt of GOOSE signal from any of the feeder
the gateway. PIED, the Incomer will go in block state of the protection
Bus Bar Protection, LBBU Protection, under frequency till the GOOSE changes state. For fault at Location A, none
load shedding protection, Overload trimming protection are of the feeder PIEDs will pick up except incomer-1 AND
implemented by using GOOSE logics in addition to events bus coupler, incomer -2 if bus coupler is closed. In such
& Fault Disturbance Record handling. condition, the bus coupler will send a blocking GOOSE to
Incomer-2 and trip instantaneously. Incomer-1 will also trip
a) Bus Bar Protection by Reverse blocking Method
instantaneously causing Tripping of Zone A on bus fault
It may not be possible to implement the Directional Bus and avoiding tripping of zone B.
bar protection in the distribution system as many of the The high-speed operation of GOOSE, demands fast
Protection IEDs (PIED) are non-direction in nature by their switching peer-to-peer communications. Addition of any
application. The schematic below shows a typical switch will increase the delay. To improve the reliability of
Distribution network with two transformers as incomers. the scheme in case of a critical location, we may need to
Three phase over current and earth fault function in subscribe to redundant messages. In such a case, a loss of
PIED are already provided for conventional time-graded one device should not affect the performance of the
protection as shown. A busbar blocking scheme needs to be scheme. The presence of GOOSE messages and the status
configured which will give fast tripping of the incomer T1 of the individual IEDs should be monitored and considered
for the busbar fault shown at “A” whilst remaining stable into the proposed scheme to ensure a contingency plan in
for the feeder fault at “C”. The feeder fault would be case of system component failure.
cleared by over current protection tripping only the relevant
outgoing feeder breaker.
139
International Journal of Emerging Technology and Advanced Engineering
Website: www.ijetae.com (ISSN 2250-2459, ISO 9001:2008 Certified Journal, Volume 5, Issue 2, February 2015)
b) USE of Goose Messages and IEC61850 for a distance 4. Protection Interlocking: The breaker status, isolator
protection status, spring & all other interlock status from the
1. Reverse Blocking scheme: All bay relays are required same compartment will be wired to the protection
to be directional & the bus coupler relay (if any) is relay as binary input. The status is further forwarded
required to be bi-directional. In case any of the OG to all other relays that are dependent on the status of
feeders relay picks-up on a particular hi set O/C stage, this feeder on GOOSE normal priority message. Also
it will issue a blocking command. The blocking the own status will be used for self-interlocking.
command will be sent to own incomer & the other 5. IN/OUT operations: If the SCADA Gateway is
incomer (if the bus coupler is closed) on GOOSE. If configured to be Master, it can enable or disable any
the OG breaker does not isolate the fault for application.
200mSec, the incomer will trip on particular Hi-set
6. Permissive for operations: Sync-check Permissive,
stage. (Indirect LBBU operation).
Breaker status, conditional permissive for auto reclose
2. Overload Trimming: If the incomer relay picks up on & normal breaker closing permissive will be sent on
Overload trimming settings, it will send a goose Goose.
command to bus coupler relay (If other incomer is in
7. Transfer trip/trip block: This information between
service) to trip. If the OLTS does not reset, it will
two relays can be sent on fast GOOSE depending on
issue trip goose to the selected OG breakers.
the applications.
3. Under frequency Tripping: If the incomer relay picks
8. Remote reset of LED, O/P relays, Lockout.
up on UFLS settings, it will issue trip goose to the
selected OG breakers. The selection of feeders, to 9. The Breaker failure or main protection failure
accept trip GOOSE or not will happen with a Binary scheme.
Input through a switch. 10. Differential protection working within the
substation
11. Distance carrier aided schemes.
140
International Journal of Emerging Technology and Advanced Engineering
Website: www.ijetae.com (ISSN 2250-2459, ISO 9001:2008 Certified Journal, Volume 5, Issue 2, February 2015)
VII. CHALLENGES / CONCERNS VIII. CONCLUSION
While implementing the IEC61850 in the substation, Digital substation is the developing trend of the future.
the relays are configured for particular application Application of digital technology can not only greatly
first & then a soft virtual station is developed on reduce costs but also bring much more convenience for
IEC61850 platform to define the GOOSE message management and maintenance. The solution provided and
matrix. also proposed for new substation facilitates above
If the station file is misplaced or appropriate file is not objectives and at the same time improves the reliability by
used while communicating with the relay, the reducing hardware cabling and logics. Digital substation is
GOOSE messaging & soft interlocking will not work an ideal solution for a power utility to meet the exponential
as the relay loses the GOOSE message service growth of energy demand and to survive the increasing
mapping. complexity of its Grid without compromising on the quality
Every time we change any configuration parameter or and availability of the Power.
activate/de-activate any function in a relay, the station
Acknowledgment
configuration file is required to be updated. (Only for
changing the relay settings, Station update is not We would like to thank Mr. Amok Agarwal, Chief
required). Manager, Automation Dept., Tata Power Co. Ltd. for his
constant support and moral guidance, without which this
Benefits Accrued paper would not have been possible. We would also like to
The advantages of digitizing data for all substation thank Tata Power Co. Ltd. and those people who have
control purposes are as follows: worked earlier on a similar topic, as their work has helped
Substantial cost savings related to secondary cable us a lot.
circuits and their trench routing as digital data sources
move closer to the primary equipment; REFERENCES
Increased electromagnetic compatibilities of modern [1] J. D. McDonald, "Substation Automation, IED integration and
availability of information", IEEE Power&Energy, Vol. I, No. 2,
secondary equipment, such as microprocessor devices March/April 2003.
and secondary circuits, due to transition to optic [2] S. akovljevi , . e unovi , Advanced Substation ata
connections; Collecting and Processing for State Estimation Enhancement," IEEE
Simplified and less expensive electronic PES Summer Meeting, Chicago, July 2002.
microprocessor devices due to removal of analogue [3] http://en.wikipedia.org/wiki/IEC_61850
signal input leads; [4] http://univagora.ro/jour/index.php/ijccc/article/viewFile/329/pdf_66
Unified IED device interfaces and better [5] http://www.schneider-
interchangeability (including device replacement electric.com/solutions/ww/en/med/20340568/application/pdf/1485_s
e-whitepaper-letter-scadaoverview-v005.pdf
regardless of manufacturer).
Enhanced security in smart grid-enabled digital
substations
Enhanced operational efficiency through optimized
automation architecture
141