Professional Documents
Culture Documents
Research Paper
h i g h l i g h t s
Frictional pressure drops in helical coils with small coil diameters are investigated.
The frictional pressure drop multiplier is insensitive to the curvature ratio.
Impact of heat flux on the flow boiling frictional pressure drop is not significant.
Correlations for single and two-phase frictional pressure drops in helical coils are proposed.
a r t i c l e i n f o a b s t r a c t
Article history: The pressure drop characteristics of helical coils are important to the design optimization of helically
Received 29 October 2017 coiled steam generators. Single-phase and two-phase flow pressure drop characteristics have been exper-
Revised 20 December 2017 imentally investigated in coiled tubes of inner diameters of 12.5 mm and 14.5 mm. The helical diameters
Accepted 20 December 2017
of the helical coils are 180, 280 and 380 mm and the system pressure range from 2 to 8 MPa. The effects
Available online 21 December 2017
of flow and geometry parameters on two-phase frictional pressure drop multiplier are discussed. For flow
parameters, the two-phase frictional pressure drop multiplier decreases with higher system pressure and
Keywords:
is insensitive to mass flux and heat flux. For geometric parameters, the two-phase frictional pressure drop
Helically coiled tube
Small coil diameter
multiplier is insensitive to the curvature ratio under the investigated conditions. Comparison with corre-
Two-phase flow lations reported in the literature is performed. A single-phase friction factor correlation and a two-phase
Frictional pressure drop frictional pressure drop multiplier correlation for helical coils with small coil diameters at high pressure
Two-phase frictional pressure drop are proposed and give good agreements with the experimental data.
multiplier Ó 2017 Elsevier Ltd. All rights reserved.
1. Introduction high as 1.37 has been reported for flow boiling in helical coils by
Wongwises and Polsongkram [12] for vertical helical coils.
Coiled tube heat exchangers were used in a wide variety of The pressure drop characteristics of helical coils are important
industries. In particular, helically coiled once-through steam gen- to the design optimization of helically coiled steam generators.
erators have been used widely during the past several decades in Many researchers have conducted experimental studies for a wide
the nuclear industry, especially in small modular reactors. The range of system parameters and a number of correlations for the
main advantages of helically coiled heat exchangers as compared frictional pressure drop in helical coils are reported in the litera-
with straight tube heat exchangers are heat transfer efficiency ture [11,13]. Fsadni et al. conducted a review of the two-phase
[1–7], compact design [8–10], and ease of manufacture [7,11]. In pressure drop characteristics and correlations. He concluded that
helical coils, the geometry induced centrifugal force exerts upon the curvature ratio does not appear to have a significant influence
the fluid, and vortices arise. The vortices format a secondary flow, on the two-phase frictional pressure drop multiplier whilst there is
which is one of the most important differences between the flow in some controversy surrounding the influence of the coil orientation
coiled tubes and that in straight tubes. The secondary flow has and heat flux [11].
been found to exist in both single and two-phase flows, which For the range of experimental parameters of the correlations for
enhances the heat transfer in helical coils. Enhancement ratio as two-phase frictional pressure drop of steam-water in helically
coiled tubes, most correlations, such as Owhadi et al. [14], Kozeki
et al. [15], Nariai et al. [16], Guo et al. [17] and Hardik et al. [18],
⇑ Corresponding author. are developed for low system pressure (P < 3.5 MPa). For the
E-mail address: yxiao@sjtu.edu.cn (Y. Xiao).
https://doi.org/10.1016/j.applthermaleng.2017.12.074
1359-4311/Ó 2017 Elsevier Ltd. All rights reserved.
Y. Xiao et al. / Applied Thermal Engineering 132 (2018) 18–29 19
Nomenclature
correlations developed for high system pressures (P > 3.5 MPa), a maximum heating capability of 200 kW. The outer wall of the
such as Ruffell [19], Unal et al. [20], Chen and Zhou [21], Santini pre-heater 2 is carefully insulated with rock wool, and the small
et al. [22], Ju et al. [23] and Colombo et al. [24], most coil diameters thermal losses were determined by dedicated calibration experi-
of their helical coils are greater than 400 mm. ments. The inlet enthalpy of pre-heater 2 is keeping subcooled in
As mentioned above, only few experiments have been per- the tests. Thus, the inlet enthalpy of test section can be obtained
formed to investigate the two-phase frictional pressure drop in accurately even under two-phase condition. Another flow is led
helical coils with small coil diameters less than 400 mm at system through the bypass line to the mixing chamber. The water temper-
pressure in excess of 3.5 MPa. In this study, various experiments ature is reduced after relieving heat in the reheater and mixing
are performed to investigate two-phase flow frictional pressure with the low temperature fluid from the bypass line before it
drop characteristics in helically coiled tubes with small coil diam- enters into the heat exchanger. The water exiting the heat exchan-
eters at high pressure. The helical diameters of the helical coils, ger goes back to the water tank. Two Venturi flow meters with dif-
having inner diameters of 12.5 mm and 14.5 mm, are 180, 280 ferent ranges are installed in parallel in the main flow loop to
and 380 mm and the system pressure range from 2 to 8 MPa. The measure the mass flow rate of water entering the test section.
effects of flow and geometry parameters on two-phase frictional The pressure at the inlet of the test section is controlled by adjust-
pressure drop multiplier are discussed in detail. A single-phase ing the pressure regulator valve at the exit of the main loop. The
friction factor correlation and a two-phase frictional pressure drop pressure at the inlet of the test section is measured by a
multiplier correlation for helical coils with small coil diameters at capacitance-type pressure transducer. The pressure drop over the
high pressure are proposed and give good agreements with the test section is obtained using a capacitance-type differential pres-
experimental data. sure transducer. Fluid temperatures at the inlet and the outlet of
the test section are measured by two ungrounded N-type thermo-
couples with a sheath outer diameter of 0.5 mm. All data are col-
2. Experimental apparatus and test section lected and recorded using a National Instrument data acquisition
system.
Fig. 1 shows a schematic diagram of the test facility SWAMUP-II As shown in Fig. 2, the helically coiled tubes were made of
at Shanghai Jiao Tong University, which is designed to perform stainless steel pipes having heated lengths about 8000 mm. The
heat transfer tests with a supercritical water or steam-water coil diameters of the six test sections were 180, 280 and 380
two-phase flow. The design pressure of the SWAMUP-II is 35 mm, and the inner diameters were 12.5 and 14.5 mm. The helically
MPa. Distilled and deionized water from the water tank is driven coiled tubes were vertical in the tests. Table 1 shows the dimen-
through a filter by two high pressure plunger-type pumps. The sions of the test sections in detail. The design pressure and temper-
main flow goes through the re-heater to absorb the heat of the ature of the test sections were 10 MPa and its saturation
hot fluid coming from the test section. It passes the pre-heater temperature, respectively. The outer wall of the test section was
where it is heated up to a pre-defined temperature and enters into carefully insulated with rock wool, and the small thermal losses
the test section. It exits the test section with a high temperature up were determined by dedicated calibration experiments.
to 550 °C. The pre-heater 1 is directly heated by AC power with a A group of differential pressure transducers was employed to
maximum heating capability of 600 kW. The pre-heater 2, which measure the pressure drop of the test sections. To determine pres-
power is accurately measured, is directly heated by AC power with sure drops at different qualities, the inlet quality was increased at a
20 Y. Xiao et al. / Applied Thermal Engineering 132 (2018) 18–29
Test DP Cooling
section water tank
T
P
Cooling pump
Pressure regulator
Heat exchanger
Pre-heater 2 Deionized
water tank
Mixer
Bypass way
Pre-heater 1
Re-heater
Piston pump
Venturi flowmeter
Table 1
Dimensions of the test section.
constant inlet mass flow rate and system pressure step by step.
After steady-state conditions had been reached for each inlet qual-
ity level, all measurements were collected. Tests were carried out
systematically for different inlet qualities and mass flow levels at
different system pressure levels. The uncertainty of different
parameters used in the experimental analysis is presented in
Table 2. The uncertainties in the diameter and length of the test
section are obtained by measuring the values at different locations.
The uncertainties of heat flux depend on the accuracy of the
ampere and volt meters. The uncertainties of mass flow rate are
obtained by the accuracy of the Venturi flow meter, having a max-
imum error of 0.4%, in the range of the explored flow rates. Bulk
temperatures are measured with thermocouple, having a maxi-
mum error of 0.7 °C. The inlet pressure is measured by an absolute
Fig. 2. Scheme of the helically coiled tube test sections. pressure transducer with a 10 MPa range, and a maximum error of
Y. Xiao et al. / Applied Thermal Engineering 132 (2018) 18–29 21
Table 2 5
Uncertainties of primary parameters.
about 0.2%. The pressure drops between the taps are measured by a 0
group of differential pressure transducers with a 500 kPa range and 0 1 2 3 4 5
a maximum error of about 0.1%. The uncertainties of local equilib-
Exp. frictional pressure drops (kPa)
rium quality are derived from the uncertainty analysis of heat flux
and temperature measurement. Uncertainty of friction factor is Fig. 3. Comparison of experimental single-phase frictional pressure drop results
analyzed based on the method reported in Ref. [25] and the error with Blasius’s correlation.
propagation theory [26].
3.1. Single-phase frictional pressure drop and geometry parameter
effects
3. Results and discussion Accuracy single-phase frictional pressure drop data is the basis
for the investigation of two-phase frictional pressure drop. The
Experiments of helically coiled tube were carried out with friction factor is calculated by following equation in this work:
test parameters shown in Table 3. In the single-phase tests,
the properties of local bulk fluid were derived by the inlet 2Dq
f ¼ DP f ð1Þ
enthalpy of the test sections, system pressure and the heat loss. G2 L
In the two-phase tests, the saturated properties of local bulk In helical coiled tubes, the critical Reynolds number is much
fluid were calculated using the system pressure. The local greater than that in straight tubes and is a function of De (De =
enthalpies in the two-phase tests were calculated by the mass Re(D/DC)0.5) [27]. In the present work, the Re number ranges from
flow rate, the inlet enthalpy, the heating power and the heat 2 105–10 105 and the entire test conditions are in the turbu-
loss. In the present work, the heat losses were accurately cali- lent flow region. Figs. 4 and 5 indicate the effects of geometry
brated for each two-phase test by performing a single-phase test parameters, the tube diameter and coil diameter, on single-phase
with an outlet temperature near the saturation temperature at friction factor. The presence of secondary flow in the helical coils
the same system pressure. Then, the losses were derived by dissipates kinetic energy, thus increasing the resistance to flow.
the flow rate and the temperature drop of hot pressurized water As a result, the friction factor in a helically coiled tube is much
flowing into the helical coils and the values were correlated with higher than that in the straight tube with the same hydraulic diam-
the outer wall temperature. The heat losses were subsequently eter. Increase in hydraulic diameter or decrease in coil diameter
incorporated into the data reduction process. Finally, the local increases the curvature ratio (D/De) and the secondary flow
equilibrium qualities in a two-phase test were calculated by induced by the centrifugal force, which increases the energy dissi-
the local enthalpies of the mixture and the system pressure.
The thermo-physical properties used in data reduction were cal- 0.045
culated from the tabulated values of the National Institute of Dc=280 mm
Standards and Technology (NIST).
Besides, single-phase frictional pressure drop data measured in
D=12.5 mm
Single-phase friction factor
0.030
Table 3
Thermal-hydraulic conditions for pressure drop measurements.
Table 4 0.050
Srinivasan
Single-phase friction factor correlations reported in the literature.
0.045
Ruffel
No. Authors Correlation Reference Schmidt
1 Blasius f ¼ 0:3164 [28] 0.040 Ju
Re0:25
2 Ito 0:5 [29]
0
f ¼ Re 0:25 þ 0:00725 D
0:076 D
c 0.035
3 Srinivasan 0:1 [30]
0
f ¼ Re0:2 Dc
0:084 D
0:275 0.030
4 Ruffel [19]
f ¼ 0:015 þ Re 2:53 D
0:4 Dc
0.025
5 Schmidt 0:45 [31]
Rec ¼ 2300 1 þ 8:6 DDc
0.020
When Re < Rec
0:97
f ¼ 1 þ 0:14 DDc Rea 64
Re
0.015
0:312 20000 40000 60000 80000 100000
a ¼ 1 0:644 DDc
Re
When Rec Re 22000,
0:62
f ¼ 1 þ 28800 D 0:3164 Fig. 6. Comparison of measured data with single-phase friction factor correlations.
Re Dc Re0:25
Re > 22000
0:53
f ¼ 1 þ 0:0823 1 þ DDc DDc Re0:25 0:3164
Re0:25
Table 5
pffiffiffiffiffiffiffiffiffiffiffiffi Results of comparison with single-phase friction factor correlations reported in the
6 Ju et al. De ¼ Re D=Dc [23]
0:45 literature.
Rec ¼ 2300 1 þ 8:6 DDc
No. Authors Average error (%)* RMS (%)*
When De < 11.6,
0 1 Blasius 36.5 4.2
f s ¼ 16
Re , f =f s ¼ 1
2 Ito 18.9 3.1
When De > 11.6, Re < Rec
0:4 3 Srinivasan 13.8 3.7
0 0:75
f s ¼ 16
Re , f =f s ¼ 1 þ 0:015Re
D
Dc 4 Ruffel 10.4 3.2
When De 11.6, Re > Rec, 5 Schmidt 19.1 3.0
6 Ju 20.6 7.0
0:25 ;
0:0791
smooth tube
f s ¼ Re
0:25 Pn
0:025 1:46 DD þ 100
Re ; rough tube error ¼ f cal =f exp 1 Av g:error ¼
*
i¼1
error i
n 100%.
0:14 qffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffi
0
f =f s ¼ 1 þ 0:11Re0:23 DDc Pn ðerrori Av g:errorÞ2
RMS ¼ i¼1 n1 100%.
Y. Xiao et al. / Applied Thermal Engineering 132 (2018) 18–29 23
0.045 0.045
0.040
0.040
0.035
0.035
fcal
0.030
fcal
0.030
0.025
0.020 0.025
0.015 0.020
0.015 0.020 0.025 0.030 0.035 0.040 0.045 0.020 0.025 0.030 0.035 0.040 0.045
fexp fexp
0.040 0.040
0.035 0.035
fcal
fcal
0.030 0.030
0.025 0.025
0.020 0.020
0.020 0.025 0.030 0.035 0.040 0.045 0.020 0.025 0.030 0.035 0.040 0.045
fexp fexp
0.045 0.050
0.045
0.040
0.040
0.035
fcal
fcal
0.035
0.030
0.030
0.025
0.025
0.020 0.020
0.020 0.025 0.030 0.035 0.040 0.045 0.020 0.025 0.030 0.035 0.040 0.045 0.050
fexp fexp
0.045 1000
P=4.8 MPa
G=600 kg/m2s
0.040 q=200 kW/m2
q=300 kW/m2
100 q=400 kW/m2
0.035
+10% q=500 kW/m2
fcal
lo
2
0.030
-10%
10
0.025
0.020
0.020 0.025 0.030 0.035 0.040 0.045 1
0.1 0.2 0.3 0.4 0.5 0.6 0.7
fexp
x
Fig. 8. Comparison of the new friction factor correlation and measured data.
Fig. 11. Effects of heat flux on two-phase frictional pressure drop multiplier.
1000 1000
2
G=600 kg/m s P=4.8 MPa
P=2.0 MPa G=600 kg/m2s
P=4.8 MPa Dc=180 mm
P=7.6 MPa D=12.5 mm
100 100 D=14.5 mm
lo
lo
2
10 10
1 1
0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7
x x
Fig. 9. Effects of system pressure on two-phase frictional pressure drop multiplier. Fig. 12. Effects of hydraulic diameter on two-phase frictional pressure drop
multiplier.
1000 1000
P=4.8 MPa P=4.8 MPa
G=400 kg/m2·s G=600 kg/m2s
G=600 kg/m2·s D=12.5 mm
G=800 kg/m2·s Dc=180 mm
100 G=1000 kg/m2·s 100 Dc=280 mm
Dc=380 mm
lo
lo
2
10 10
1 1
0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
x x
Fig. 10. Effects of mass flux on two-phase frictional pressure drop multiplier. Fig. 13. Effects of coil diameter on two-phase frictional pressure drop multiplier.
Y. Xiao et al. / Applied Thermal Engineering 132 (2018) 18–29 25
The available range is the range of our experimental parame- DPf ;tp
/2lo ¼ ð3Þ
ters. The comparison of the new correlation with our measured DPf ;lo
data is shown in Fig. 8. It fits 100% of the data within ±10%. The
where DPf,tp is the two-phase frictional pressure drop. DPf,lo is
average error and root mean square of the new correlation are
the liquid-only single-phase frictional pressure drop, which con-
0.2% and 5.3%, respectively.
siders the fluid as entirely liquid at the mass flow rate. The friction
factor in DPlo processing is obtained by the previous new fiction
3.3. Two-phase frictional pressure drop and parameter effects factor correlation as shown in Eq. (2). Fig. 9 indicates the effects
of system pressure on the two-phase frictional pressure drop mul-
There is a general agreement amongst the previous researchers tiplier. Increase in system pressure increases the vapor density and
that the two-phase flow boiling frictional pressure drop increases the average density of the bulk fluid. Thus, at a specific equilibrium
with the equilibrium quality and mass flux whilst it decreases with quality, the volume fraction and mean flow velocity of the bulk
higher system pressure [11]. Thus, the present work focuses on the fluid both decrease with the increase in system pressure, which
effects of various flow parameters and geometry parameters on causes a remarkable decrease of the two-phase pressure drop.
two-phase frictional pressure drop multiplier. The liquid-only Although the reference single-phase liquid-only frictional pressure
two-phase frictional pressure drop multiplier is defined as:
Table 6
Correlations of two-phase frictional pressure drop multiplier reported in the literature.
DP
/2lo ¼ DPf ;lo
f
0
8 Zhao et al. /2lo ¼ 1 þ qq00 1 ½0:303x1:63 ð1 xÞ0:885 Re0:282 þ x2 [2]
lo
*
The single-phase friction factor is given by the new single-phase friction factor correlation proposed in Section 3.2.
26 Y. Xiao et al. / Applied Thermal Engineering 132 (2018) 18–29
Experiment drop also decreases with the increase in system pressure, due to
Chen Chen and Zhou the decreases of single-phase liquid friction factor and flow veloc-
Chisholm et al. Santini et al. ity, the total effect is negative to the two-phase friction pressure
100 Ju et al. Colombo et al. drop multiplier. Thus, the two-phase friction pressure drop multi-
Guo et al. Zhao et al.
plier decreases with the increase in system pressure, as shown in
Fig. 9.
Fig. 10 shows the effects of mass flux on the friction pressure
drop multiplier. Increase in mass flux increases both of the
lo
2
100 100
80 80
60 60
lo,cal
lo,cal
2
40 40
20 20
0 0
0 20 40 60 80 100 0 20 40 60 80 100
2 2
lo,exp lo,exp
125
80
100
60
lo,cal
lo,cal
75
2
40
50
20
25
0 0
0 20 40 60 80 100 0 25 50 75 100 125 150
2 2
lo,exp lo,exp
istics have little influence on the two-phase frictional pressure two-phase correlations adopted in this study are shown in Table 6.
drop multiplier. The Chen’s correlation and Chisholm’s correlation are developed
Figs. 12 and 13 show the effects of tube diameter and coil diam- for straight tube and the others are for helical coils. It should be
eter on the friction pressure drop multiplier. Increase in hydraulic noted that the new single-phase friction factor correlation is
diameter or decrease in coil diameter increases the secondary flow adopted as the reference single-phase friction factor formula to
induced by the centrifugal force, and both of the single-phase and derive the liquid-only two-phase frictional pressure drop multi-
two-phase pressure drop increase. But for the friction pressure plier in the comparison, both for the experimental data and the
drop multiplier, it is insensitive to the tube diameter and coil diam- correlations reported in the literature. Besides, the multipliers of
eter in the investigated experiment range, which confirms the con- some correlations are transformed into liquid-only for the original
clusion of Fsadni that the curvature ratio does not appear to have a multipliers are only-liquid.
significant influence on the two-phase flow boiling frictional pres- Fig. 14 illustrates the comparison under a specific two-phase
sure drop multiplier [11]. test condition. It can be seen that Chen’s correlation meets well
with the experimental data in the low quality region, but under
3.4. Comparison of experimental two-phase pressure drop with the predicts the data significantly in the high quality region. The
available correlations Chisholm’s correlation over predicts the experimental data in the
low quality region, but under predicts in the high quality region.
The experimental conditions investigated in the present work The Ju’s correlation shows good prediction, which meets well with
are quite different from the previous works reported in the litera- measured data in the low quality region and is a little lower in the
ture, thus comparison with reported correlations is performed. The high quality region. The Guo’s correlation and Zhao’s correlation
400 100
350
80
300
250 60
lo,cal
lo,cal
200
2
2
40
150
100
20
50
0 0
0 50 100 150 200 250 300 350 400 0 20 40 60 80 100
2 2
lo,exp lo,exp
150 150
125 125
100 100
lo,cal
lo,cal
75 75
2
2
50 50
25 25
0 0
0 25 50 75 100 125 150 0 25 50 75 100 125 150
2 2
lo,exp lo,exp
Table 7 L G2
Results of comparison with two-phase friction multiplier correlations reported in the Dpf ¼ /2lo f
literature.
D 2q0
00 0:25 0
l q
No. Authors Average error (%)* RMS (%)* /2lo ¼ ð0:377 þ 6:79x 5:66x2 Þ 1 þ x 0 1 1 þ x 00 1
l q
1 Chen 24.0 21.2 0:404 !
2 Chisholm et al. 16.7 48.9 0:3164 D
3 Ju et al. 4.8 13.5 f¼ 1 þ Re0:053
lo
4 Guo et al. 70.0 85.3
Re0:25
lo
D c
4. Conclusion
over predict the measured data because the system pressures of
the experimental data deriving the two correlations are less than The single-phase and two-phase steam-water frictional pres-
3.5 MPa, which indicates that the two correlations do not apply sure drop in helical coiled tubes, having inner diameters of 12.5
at high system pressure. The Santini’s correlation under predicts mm and 14.5 mm and coil diameter of 180, 280 and 380 mm, were
the experimental data remarkably because Santini’s test section investigated under conditions of 2–8 MPa in system pressure and
has a very small curvature ratio. The Colombo’s correlation is 300–1000 kg/m2 s in mass flux. The effects of flow parameters
developed based on the experimental data from Santini et al. and geometry parameters on the frictional pressure drop are eval-
[22] and Zhao et al. [2]. It also over predicts the present uated. The single-phase experimental results indicate that the fric-
measured data. Chen and Zhou’s correlation is developed tion factor increases with curvature ratio. For flow parameter
based on an air-water experiment and over predicts the effects on the two-phase friction pressure drop multiplier, the
experiment data too. results show that the multiplier decreases with higher system
Liquid-only two-phase friction pressure drop multiplier predic- pressure whilst the mass flux and heat flux does not appear to have
tions are compared in Fig. 15 and Table 7. The Chen’s correlation a significant influence. For the geometry effects, the friction pres-
and Chisholm’s correlation show significant asymmetry, which sure drop multiplier is insensitive to the curvature ratio in the
indicates that the geometry effect of helical coiled tubes on the investigated experiment range. Comparison with correlations
two-phase flow pressure drop multiplier cannot be neglected. available in the literature is performed. A single-phase friction fac-
The correlations show significant differences in the predictions, tor correlation and a two-phase frictional pressure drop multiplier
which illustrates that it is difficult to predict two-phase friction correlation for helical coils with small coil diameters at high pres-
pressure drops in helical coils out of the range of explored experi- sure are proposed and give good agreements with the experimen-
mental conditions. The Ju’s correlation gives the best prediction tal data. The proposed correlations can be used for helically coiled
with the test data among the correlations, which has a small aver- steam generators design.
age error about 5%.
Based on the correction method of Ju’s correlation, a correla-
tion for two-phase frictional pressure drop multiplier in helical Acknowledgement
tubes with small coil diameters was obtained by regression
analysis: Acknowledge the financial support of Shanghai Sailing Program
(16YF1405600).
100 References
study in tube-in-tube helical heat exchanger, Chem. Eng. Sci. 61 (2006) 4403–
+20% 4416.
2
[4] C.-N. Chen, J.-T. Han, T.-C. Jen, L. Shao, Thermo-chemical characteristics of
40
R134a flow boiling in helically coiled tubes at low mass flux and low pressure,
-15% Thermochim. Acta 512 (2011) 163–169.
[5] H. Aria, M.A. Akhavan-Behabadi, F.M. Shemirani, Experimental investigation
on flow boiling heat transfer and pressure drop of HFC-134a inside a vertical
20 helically coiled tube, Heat Transf. Eng. 33 (2012) 79–87.
[6] J. Gou, H. Ma, Z. Yang, J. Shan, An assessment of heat transfer models of water
flow in helically coiled tubes based on selected experimental datasets, Ann.
Nucl. Energy 110 (2017) 648–667.
0 [7] A.M. Fsadni, J.P.M. Whitty, A review on the two-phase heat transfer
0 20 40 60 80 100 characteristics in helically coiled tube heat exchangers, Int. J. Heat Mass
2 Transf. 95 (2016) 551–565.
lo,exp [8] M. Mozafari, M.A. Akhavan-Behabadi, H. Qobadi-Arfaee, M. Fakoor-Pakdaman,
Condensation and pressure drop characteristics of R600a in a helical tube-in-
Fig. 16. Comparison of the new two-phase frictional pressure drop correlations and tube heat exchanger at different inclination angles, Appl. Therm. Eng. 90
measured data. (2015) 571–578.
Y. Xiao et al. / Applied Thermal Engineering 132 (2018) 18–29 29
[9] J.M. Gorman, E.M. Sparrow, J.P. Abraham, G.S. Mowry, Operating [21] X. Chen, F. Zhou, An investigation of flow pattern and frictional pressure drop
characteristics and fabrication of a uniquely compact helical heat exchanger, characteristics of air-water two-phase flow in helical coils, in: Proceedings of
Appl. Therm. Eng. 50 (2013) 1070–1075. 4th Miami International Conference on Alternate Energy Sources, 1981, pp.
[10] J. Gorman, E. Sparrow, G. Mowry, J. Abraham, Simulation of helically wrapped, 120–129.
compact heat exchangers, J. Renew. Sustain. Energy 3 (2011) 043120. [22] L. Santini, A. Cioncolini, C. Lombardi, M. Ricotti, Two-phase pressure drops in a
[11] A.M. Fsadni, J.P.M. Whitty, A review on the two-phase pressure drop helically coiled steam generator, Int. J. Heat Mass Transf. 51 (2008) 4926–
characteristics in helically coiled tubes, Appl. Therm. Eng. 103 (2016) 616–638. 4939.
[12] S. Wongwises, M. Polsongkram, Evaporation heat transfer and pressure drop of [23] H. Ju, Z. Huang, Y. Xu, B. Duan, Y. Yu, Hydraulic performance of small bending
HFC-134a in a helically coiled concentric tube-in-tube heat exchanger, Int. J. radius helical coil-pipe, J. Nucl. Sci. Technol. 38 (2001) 826–831.
Heat Mass Transf. 49 (2006) 658–670. [24] M. Colombo, L.P. Colombo, A. Cammi, M.E. Ricotti, A scheme of correlation for
[13] A. Cioncolini, L. Santini, Two-phase pressure drop prediction in helically coiled frictional pressure drop in steam–water two-phase flow in helicoidal tubes,
steam generators for nuclear power applications, Int. J. Heat Mass Transf. 100 Chem. Eng. Sci. 123 (2015) 460–473.
(2016) 825–834. [25] S. Zhang, H. Gu, X. Cheng, Z. Xiong, Experimental study on heat transfer of
[14] A. Owhadi, K.J. Bell, B. Crain, Forced convection boiling inside helically-coiled supercritical Freon flowing upward in a circular tube, Nucl. Eng. Des. 280
tubes, Int. J. Heat Mass Transf. 11 (1968) 1779–1793. (2014) 305–315.
[15] M. Kozeki, H. Nariai, T. Furukawa, K. Kurosu, A study of helically-coiled tube [26] P.R. Bevington, D.K. Robinson, J.M. Blair, A.J. Mallinckrodt, S. McKay, Data
once-through steam generator, Bull. JSME 13 (1970) 1485–1494. reduction and error analysis for the physical sciences, Comput. Phys. 7 (1993)
[16] H. Nariai, M. Kobayashi, T. Matsuoka, Friction pressure drop and heat transfer 415–416.
coefficient of two-phase flow in helically coiled tube once-through steam [27] A.M. Fsadni, J.P.M. Whitty, M.A. Stables, A brief review on frictional pressure
generator for integrated type marine water reactor, J. Nucl. Sci. Technol. 19 drop reduction studies for laminar and turbulent flow in helically coiled tubes,
(1982) 936–947. Appl. Therm. Eng. 109 (2016) 334–343.
[17] L. Guo, Z. Feng, X. Chen, An experimental investigation of the frictional [28] L.S. Tong, J. Weisman, Thermal Analysis of Pressurized Water Reactors, 1996.
pressure drop of steam–water two-phase flow in helical coils, Int. J. Heat Mass [29] H. Ito, Friction factors for turbulent flow in curved pipes, Trans. ASME, J. Basic
Transf. 44 (2001) 2601–2610. Eng., D 81 (1959) 123–134.
[18] B.K. Hardik, S.V. Prabhu, Boiling pressure drop and local heat transfer [30] P.S. Srinivasan, Pressure drop and heat transfer in coils, Chem. Eng. 218 (1968)
distribution of helical coils with water at low pressure, Int. J. Therm. Sci. 114 CE113–CE119.
(2017) 44–63. [31] D.I.E.F. Schmidt, Wärmeübergang und Druckverlust in Rohrschlangen, Chem.
[19] A. Ruffell, The application of heat transfer and pressure drop data to the design Ing. Tech. 39 (1967) 781–789.
of helical coil once-through boilers, in: IChemE. Symp. Ser, vol. 38, 1974, pp. 1– [32] L. Chen, Prediction of frictional pressure drop for two-phase flow, 1990.
22. [33] D. Chisholm, L. Sutherland, Prediction of pressure gradients in pipeline
[20] H. Ünal, M. Van Gasselt, P. Van’t Verlaat, Dryout and two-phase flow pressure systems during two-phase flow, in: Proceedings of the Institution of
drop in sodium heated helically coiled steam generator tubes at elevated Mechanical Engineers, Conference Proceedings, Vol. 184, SAGE Publications
pressures, Int. J. Heat Mass Transf. 24 (1981) 285–298. Sage UK: London, England, 1969, pp. 24–32.