You are on page 1of 12

IET Power Electronics

Research Article

ISSN 1755-4535
Sliding mode harmonic compensation Received on 31st October 2014
Revised on 27th January 2015
strategy for power quality improvement of a Accepted on 26th February 2015
doi: 10.1049/iet-pel.2014.0833
grid-connected inverter under distorted grid www.ietdl.org

condition
Sung-Wook Kang, Kyeong-Hwa Kim ✉
Department of Electrical and Information Engineering, Seoul National University of Science and Technology, 232 Gongneung-ro,
Nowon-gu, Seoul 139-743, Korea
✉ E-mail: k2h1@seoultech.ac.kr

Abstract: A novel sliding mode harmonic compensation (SMHC) scheme is proposed for the enhanced power quality in
distributed generation systems under distorted grid condition. The harmonic pollution caused by non-linear loads in
electrical networks brings about distorted grid voltage, power losses and heating in electrical equipments. The
proposed SMHC scheme is composed of a harmonic detector and a sliding mode harmonic current controller based on
the integral sliding mode control. By using the fourth order band pass filter, the proposed harmonic detector can
effectively extract harmonic components without phase delay. These harmonic components can be notably suppressed
by adopting the sliding mode harmonic current controller with fast dynamic response. Whereas the conventional
sliding mode schemes have been developed to control the entire current value, the proposed SMHC scheme controls
only the harmonic components by dividing inverter voltage model into the fundamental and harmonic models. Since
the fundamental component in charge of power flow is controlled by proportional-integral controller, the chattering can
be quite reduced. The proposed scheme is a non-selective harmonic compensation, which reduces the computational
burden than the conventional selective schemes. The validity of the proposed scheme is demonstrated through
simulations and experiments using 2 kVA laboratory prototype grid-connected inverter.

1 Introduction use the resonant controller or the proportional-resonant (PR)


controller either in the stationary or rotating reference frame.
As the capability of renewable energy is growing rapidly, the The PI-R current controllers in the rotating reference frame have
improvement of power quality has become a very important issue been proposed for selective harmonic compensation in an active
in distributed generation (DG) systems. The harmonic pollution power filer or in a grid-connected inverter [1–4]. The PR current
caused by non-linear loads in electrical networks brings about controllers have been researched for harmonic compensation with
distorted grid voltage, power losses and heating in the electrical LCL filter [5–7]. These harmonic controllers are designed to
equipment [1]. To limit the amount of harmonic current injected compensate each harmonic term selectively. These schemes are
into utility grid to be below the specified values, the harmonic known to be more flexible than non-selective methods, resulting in
restriction standards such as IEEE-519 or IEC 61000-3-2 have a good harmonic mitigation performance. However, these methods
been published [2]. increase the computational burdens of controller because they
When the generated electrical energy from renewable energy require the implementation of separate controllers for each
resources is delivered to grid through the grid-connected inverter, harmonic component.
the inverter should be operated with high performance in the sense As an alternative way, non-selective harmonic compensation
of a fast dynamic response, robustness to disturbance and zero strategies such as the repetitive control [8–12], predictive control
tracking error. In most of grid-connected operation, the inverter is [13–15] and sliding mode control (SMC) have been presented.
primarily designed to control the DC-link voltage as well as The repetitive control scheme is a simple solution that can reject
inverter output current. In addition, the inverter should provide periodic harmonics.
supplementary control functions such as the compensation method An active power filter has been designed using the repetitive
for harmonic, imbalance and reactive power under specific control to compensate the harmonic current by composing infinite
condition. number of resonant peaks in the frequency response [8]. The
The proportional-integral (PI) control method is widely used to harmonic compensation using the discrete-time plug-in repetitive
control the grid-connected inverter because it is simple and has controller has been presented for a shunt active power filter to
zero steady-state error using the DC quantities in d- and q-axis. compensate the reactive power and imbalance [9]. To improve the
However, the PI controller naturally has some disadvantages total harmonic distortion (THD) performance of the inverter
which are inability to track a sinusoidal reference and poor through the harmonic elimination, a repetitive control scheme is
disturbance rejection capability. Thus, the PI control is not a analysed in the viewpoint of the frequency response [10]. The
suitable way to compensate the harmonic voltage and current. hybrid PI control and repetitive control scheme in the synchronous
To achieve a high power quality of DG, several research works on reference frame (SRF) has been proposed to reduce the harmonics
the harmonic compensation strategies have been investigated. The in the inverter output currents [11]. The improved repetitive
harmonic compensation methods are classified as two major control scheme using one-sixth of the system fundamental period
groups, namely, selective [1–7] and non-selective schemes [8–15]. delay time has been introduced for the harmonic suppression with
Several selective harmonic compensation techniques employ the PI fast transient [12]. Nevertheless, the repetitive control scheme
control in the rotating reference frame of each harmonic. Others gives slow response and performance degradation in disturbance

IET Power Electron., 2015, Vol. 8, Iss. 8, pp. 1461–1472


& The Institution of Engineering and Technology 2015 1461
rejection under non-periodic harmonics because of the delay deals with the entire current, the proposed SMHC scheme only
requirement. controls the harmonic current, which helps to reduce the chattering
The predictive control scheme ensures fast dynamic response and phenomenon. The proposed SMHC scheme is a non-selective
high accuracy. Deadbeat control scheme was introduced to the direct harmonic compensation method which can significantly reduce
power control for low THD and imbalance compensation [13]. An major harmful harmonics with robustness and fast dynamic
active power filter using the predictive control has been response. The computational burden of processor is relatively
implemented in four-leg grid-connected inverter to compensate the decreased as compared with the conventional selective method
unbalanced condition [14]. For improved robustness under the such as the resonant control. To verify the effectiveness of the
parameter change and the fault condition in grid voltage, a proposed SMHC scheme, a 2 kVA laboratory prototype
deadbeat current control has been studied to obtain low THD [15]. grid-connected inverter has been constructed using digital signal
However, the predictive control scheme may provide an instability processor (DSP) TMS320F28335 [24]. The performance of the
problem caused by parameter variations. proposed scheme has been proven through the simulations and
An SMC has been employed for a grid-connected inverter since experimental results.
this method features fast dynamic response, good disturbance
rejection and robustness under parameter variations. Several SMC
schemes have been proposed for voltage and current control in 2 Modelling of inverter and ISMC
power electronics converters [16–23].
A number of research works that combines SMC with the Fig. 1a shows the configuration of a grid-connected inverter with an
conventional control have been introduced for harmonic L filter in DG system. Considering the utility grid and the output of a
compensation. The active and reactive power control using the three-phase voltage source inverter as ideal voltage sources, Figs. 1b
SMC combined with the PI control has been investigated for fast and c show the simplified equivalent circuits of a grid-connected
load-voltage regulation and unbalanced voltage compensation [20]. inverter in the SRF. According to these figures, the voltage
To regulate the load voltage rapidly under unbalanced and equations of a grid-connected inverter in the SRF can be obtained
distorted voltage, the voltage controller has been designed based as follows
on the combination of SMC and PR control strategy [21].
To enhance the transient and steady-state responses in a di dq
stand-alone mode, the sliding mode repetitive control scheme is udq = Ri dq + L + vLi qd + vdq (1)
employed for the elimination of periodic harmonic disturbance dt
[22]. Multiresonant SMC scheme has been implemented to reduce
where udq = [ud uq]T, idq = [id iq]T, iqd = [ − iq id]T, vdq = [vd vq]T, the
tracking error and THD under grid-connected mode [23]. Even
subscript ‘dq’ denotes d- and q-axis frame, u and i are the inverter
though SMC scheme is an attractive way of reducing harmonics
output voltage and line current, respectively, L is the filter
under distorted grid voltage condition, the undesired chattering
phenomenon is a main drawback of SMC, causing low power inductance, R is the filter resistance, ω is the grid angular
frequency and v is the grid voltage.
quality and instability of systems.
A SMC scheme with variable structure forces the system state
In this paper, a novel sliding mode harmonic compensation
(SMHC) scheme is proposed to improve the power quality in a trajectory onto the sliding surface in the state space. The main
control objective is to track along predefined trajectory. Once on
grid-connected inverter under distorted grid voltage. The proposed
SMHC scheme consists of a harmonic detector and a harmonic the sliding surface, the control structure is changed
discontinuously in accordance with the switching rule to maintain
current controller based on the integral SMC (ISMC). Since the
the system on the sliding surface. At this stage, the system is in
harmonic detector is achieved by the fourth order band pass filter
(BPF) in the stationary reference frame, the harmonic components the sliding mode, which means that the controlled system is robust
to external disturbances [17, 25].
can be extracted exactly without phase delay. Unlike the
Using an additional integral term of error in the sliding surface to
conventional existing methods, the inverter voltage equation is
eliminate the steady-state error, the sliding surface can be expressed
decomposed of the fundamental and harmonic components in the
as follows
proposed scheme. Based on the obtained models, while the
fundamental component of the current is controlled with the PI 
controller, the harmonic components are suppressed by the ISMC S = e + K1 e (2)
scheme. As compared with the conventional SMC scheme which

Fig. 1 Configuration of a grid-connected inverter and the simplified equivalent circuits in the SRF
a Configuration of a grid connected inverter with an L filter in DG system
b d-axis equivalent circuit
c q-axis equivalent circuit

IET Power Electron., 2015, Vol. 8, Iss. 8, pp. 1461–1472


1462 & The Institution of Engineering and Technology 2015
where S is the sliding surface, e is the system error between the components are regulated as zero by the SMC, thereby reducing
reference and actual values and K1represents the coefficient of the the uncertainty that the SMC should deal with.
sliding surface. Fig. 2 shows the control block diagram of the proposed SMHC
If the system error reaches the sliding surface, it is obtained as scheme. The overall control scheme consists of the DC-link
voltage controller, harmonic detector and the current controller.
dS de The current control strategy is divided into two parts which are the
S= = + K1 e = 0 (3) fundamental current control and the harmonic current control. The
dt dt
fundamental current control is in charge of the electrical energy
From (3), the system error dynamics in the sliding mode can be transfer from DG to grid. The reference value in this control loop
described as is obtained from the outer loop DC voltage controller. On the
other hand, the harmonic current controller is implemented to
de eliminate harmful low order harmonics in the presence of distorted
= −K1 e (4) grid. The harmonic components in the output currents and grid
dt
voltages are extracted through the harmonic detector and the
The coefficient of the sliding surface should be selected to meet the SMHC is designed using the extracted harmonic components.
required system transients. In the sliding mode, the system error
exponentially approaches to zero with the time constant of 1/K1. 3.1 Proposed harmonic detector
A Lyapunov approach is generally used in a SMC strategy to drive
the switching control function from the sliding mode existence Fig. 3 shows the configuration of the proposed harmonic detector. To
condition. If the quadratic Lyapunov function W is selected as extract the harmonic currents exactly without phase delay, the
harmonic detector is implemented using the fourth order BPF in
1 the stationary frame. The three-phase inverter currents are
W = S2 ≥ 0 (5) transformed into the values in the α- and β-axis and these currents
2
iαβ are processed through the BPFs to obtain only the fundamental
the time derivative of W can be obtained as follows components.
To extract the harmonic components in the α- and β-axis without
dW dS phase delay, the fundamental components are subtracted from iαβ as
=S ,0 (6) follows
dt dt

The switching control function can be selected from the stability i abh = i ab − i abf (7)
condition that the time derivative of W is negative.
where iαβh = [iαh iβh]T, iαβ = [iα iβ]T, iαβf = [iαf iβf ]T, the subscript ‘αβ’
denotes α- and β-axis using the Clarke’s transformation, and the
3 Proposed SMHC scheme subscript ‘f’ and ‘h’ denotes the fundamental and the harmonic
quantities, respectively.
To improve the power quality under distorted voltage condition, the The transfer function of the second order BPF can be described as
harmonic currents in the output of a grid-connected inverter should follows
be compensated. Generally, the harmonic components in DG system
are not significant as compared with the fundamental component. In Kbpf bs
the proposed scheme, while the fundamental component of the HBPF = (8)
current is controlled with the PI controller, the harmonic s2 + bs + v2c

Fig. 2 Control block diagram of the proposed SMHC scheme

IET Power Electron., 2015, Vol. 8, Iss. 8, pp. 1461–1472


& The Institution of Engineering and Technology 2015 1463
While the harmonic detection works well in the left-hand side
figure, the right-hand side figure shows a deteriorated harmonic
detection result because of the distorted phase angle by the
SRF-PLL.
This can be explained by Fig. 4c, which represents the process
obtaining the harmonic components in three-phase currents. When
the LPF is employed in the harmonic calculation, the measured
currents are transformed to dq values using the phase angle
information. If the SRF-PLL generates the distorted phase angle θ,
it may introduce further distortion in currents during dq
transformation. On the contrary, since the proposed harmonic
detection based on the BPF is normally implemented in the α- and
β-axis as shown in the right-hand side figure of Fig. 4c, it does not
require the phase angle information to calculate the harmonic
currents. Thus, even if the phase angle is distorted severely, the
harmonic currents can be obtained exactly. The results of the
harmonic detection based on the BPF are shown in Fig. 4b where
iah,BPF represents the detected harmonic current using BPF. Unlike
Fig. 4a, the harmonic currents are extracted effectively irrespective
of distortion in phase angle of the grid.
In this paper, to detect the harmonic components accurately under
the distorted voltage condition, the fourth order BPF is implemented
in the α- and β-axis.

3.2 Proposed sliding mode harmonic current controller

An ISMC scheme is employed to reduce tracking error effectively,


while retaining the disturbance rejection capability. By using the
Fig. 3 Proposed harmonic detector proposed harmonic detection scheme based on the BPF, all the
a Block diagram harmonic components can be extracted without phase delay. To
b Bode plot of the fourth order BPF achieve stable operation of the grid-connected inverter with less
chattering, the PI controller regulates the fundamental component
of the inverter current, while the harmonic currents are suppressed
where β is the bandwidth, ωc is the centre frequency and Kbpf is the to zero by the ISMC.
filter gain. In this paper, the fourth order BPF is implemented by For this purpose, the grid voltages vdq and the inverter output
cascading two second order BPF s in a digital manner. For the currents idq in the SRF are defined as follows
digital implementation, (8) is discretised using the bilinear
transform method where the Laplace operator s is replaced as [26]
vdq = V dq + vdqh (10)

2 1 − z−1 i dq = I dq + i dqh (11)


s= (9)
T 1 + z−1
where Vdq = [Vd Vq]T, vdqh = [vdh vqh]T, Idq = [Id Iq]T, idqh = [idh iqh]T
where T is the sampling period. Fig. 3b shows the magnitude and and V and I represent DC quantities, respectively. By substituting
phase characteristic of the fourth order BPF. Even if the grid (10) and (11) into (1), the voltage equations can be rewritten as
frequency varies slightly, the designed BPF can extract the
fundamental component well with small attenuation in magnitude. d
If the currents in the α- and β-axis are transformed to the SRF, the udq = R(I dq + idqh ) + L (I + idqh ) + vL(I qd + iqdh )
dt dq
DC currents superimposed with the harmonic components are
obtained. In this case, the harmonic components can be extracted + (V dq + vdqh ) (12)
by the low pass filter (LPF) in the SRF. However, using the BPF
in the α- and β-axis can extract the harmonic components more where Iqd = [−Iq Id]T and iqdh = [−iqh idh]T.
accurately under the distorted voltage than using the LPF in the SRF. From (12), the inverter output voltage equation is decomposed as
In a grid-connected mode, the inverter requires the grid phase follows
angle to operate with the synchronisation to grid voltage where the
grid phase angle is generally obtained through the phase-locked dI dq
loop (PLL) scheme. The SRF-PLL is normally used in DG system U dq = RI dq + L + vLI qd + V dq (13)
dt
because of the simplicity and stability. The SRF-PLL method
generates the distorted phase angle under the disturbances such as di dqh
the harmonic distortion and imbalance, which results in an udqh = Ri dqh + L + vLi qdh + vdqh (14)
dt
incorrect generation of reference signal by the controller because
of the distorted phase angle [27]. where udq = Udq + udqh, Udq = [Ud Uq]T, udqh = [udh uqh]T, U is the
Fig. 4 shows the comparison results of the calculated harmonics in inverter output DC voltage in the SRF and udqh represents the
a-phase current between two methods when different PI controller inverter output voltage which is introduced to control the harmonics.
gains are used for the SRF-PLL. For simulation, the sampling To generate the q-axis current reference, the DC-link voltage is
period is set to 100 μsec. For the LPF, the cut-off frequency and controlled using the PI control as follows
damping ratio are selected as 10 Hz and 0.7, respectively. The
bandwidth and centre frequency are chosen as 20 Hz and 60 Hz,  
K
respectively, for the BPF. Fig. 4a shows the calculated harmonic i∗q = − Kpv + iv (VDC

− VDC ) (15)
currents using the fourth order LPF in the SRF with different PI s
gains. In these figures, iah is the actual harmonic current in a-phase
and iah,LPF represents the detected harmonic current using LPF. where the symbol ‘*’ denotes the reference quantity, VDC is the

IET Power Electron., 2015, Vol. 8, Iss. 8, pp. 1461–1472


1464 & The Institution of Engineering and Technology 2015
Fig. 4 Comparison results of the calculated harmonics in a-phase current
a Harmonic calculation using LPF with different PI gains
b Harmonic calculation sing BPF ith different PI gains
c Harmonic calculation process

DC-link voltage and Kpv and Kiv represent the proportional and harmonic model in (14). Considering the system disturbances
integral gains, respectively. because of the parameter variations or uncertainty, (14) can be
To control the main power flow in the fundamental component, rewritten as follows
the PI current controller is designed using (13) as the conventional
method. The output of the PI current controller can be expressed as
di dqh
  udqh = Ri dqh + L + vLiqdh + vdqh + f dq (17)
K dt
U ∗dq = K pc + ic (i ∗dq − i dq ) (16)
s
    where fdq = [ fd fq]T represents the system disturbance. From (17), the
Kpc 0 Kic 0 ∗ ∗ current dynamics can be expressed as follows
where K pc = , K ic = , U ∗dq = [ Ud Uq ]T
0 Kpc 0 Kic
Kpc and Kic are the PI controller gains, respectively, and Ud∗ and
Uq∗ are the controller outputs in d- and q-axis, respectively.To di dqh R udqh vdqh f dq
= − i dqh − vi qdh + − − (18)
alleviate the harmonic currents, the ISMC is designed using the dt L L L L

IET Power Electron., 2015, Vol. 8, Iss. 8, pp. 1461–1472


& The Institution of Engineering and Technology 2015 1465
The sliding surface for the harmonic control is chosen as follows Table 1 System parameters of the experimental setup

t Rated power 2 kVA Filter resistance 0.5 Ω


DC-link voltage 420 V Filter inductance 7 mH
S dq = x + K 1 x dt = 0 (19) DC-link capacitor 5500 μF Grid voltage 380 V
−1 Switching frequency 10 kHz Grid frequency 60 Hz

dS dq dx
= + K 1x = 0 (20)
dt dt
 
K1 0 sgn(Sdq) = [sgn(Sd) sgn(Sq)]T, K2 is a switching control gain and sgn
where K 1 =
0 K1 (.) is the switching function.
Sdq = [Sd Sq]T, x = i ∗dqh − i dqh is the harmonic current error, and K1 To obtain the switching control gain using the Lyapunov stability
is the coefficient of the sliding surface. To mitigate the harmonics, theory, the Lyapunov function is selected as
the harmonic reference current i ∗dqh is set to zero. The sliding
control inputs are composed of two inputs which are the V = 0.5S Tdq S dq ≥ 0 (24)
equivalent control input and the switching control input as follows
The time derivative of V can be obtained as
u∗dqh = ueq + usw (21)
T
V̇ = 0.5(Ṡ dq S dq +S Tdq Ṡ dq )
where ueq = [ud,eq uq,eq]T, usw = [ud,sw uq,sw]T and ueq and usw are the
equivalent control input and the switching control input in the SRF,  T  
1 1 1 1
respectively.The equivalent control input ueq can be obtained from = 0.5 f dq − K 2 sgn(S dq ) S dq +0.5S Tdq f dq − K 2 sgn(S dq )
L L L L
(18) using the conditions of fdq = 0 and Ṡ dq = 0 as
1  1

= Sd fd −K2 sgn(Sd ) +Sq fq −K2 sgn(Sq ) , 0


udqh = Ridqh + vLi qdh + vdqh + K 1 Lx (22) L L
(25)
The switching control input usw to maintain the states on the sliding
surface is a discontinuous function and can be expressed as follows Since the time derivative of V should be negative for the stability, the
switching control gains can be selected as follows
usw = K 2 sgn(S dq ) (23)
K2 . fd (26)
where

  K2 . fq (27)
K2 0
K2 =
0 K2 In (26) and (27), fdq includes the parameter variations or uncertainty

Fig. 5 Experimental setup of DG system

IET Power Electron., 2015, Vol. 8, Iss. 8, pp. 1461–1472


1466 & The Institution of Engineering and Technology 2015
because of harmonics. These switching control gains should be Table 2 Comparison of the THD of three-phase inverter currents
larger than the magnitude of disturbances to guarantee the
Without compensation, With compensation,
robustness. % %
Even though a SMC strategy guarantees robustness, fast dynamic
response and good disturbance rejection, the undesired chattering THD of a-phase current 7.99 2.25
because of the switching control input may bring instability THD of b-phase current 7.92 2.29
problems to systems. To solve this phenomenon, a boundary layer THD of c-phase current 7.78 2.29
around the sliding surface is used in the switching function as

Fig. 6 Comparative simulation results of the inverter output currents under distorted grid voltage condition
a Three-phase distorted grid voltages
b Three-phase inverter currents without harmonic compensation scheme
c Three-phase inverter currents with the proposed SMHC scheme

IET Power Electron., 2015, Vol. 8, Iss. 8, pp. 1461–1472


& The Institution of Engineering and Technology 2015 1467
Fig. 7 Transient response of the proposed SMHC scheme
a Three-phase grid voltages
b Three-phase inverter currents

Fig. 8 Performance of the proposed SMHC scheme under sudden change of the grid impedance at 0.4 s

IET Power Electron., 2015, Vol. 8, Iss. 8, pp. 1461–1472


1468 & The Institution of Engineering and Technology 2015

follows ⎪ 1, if S . l THD of three-phase inverter currents are listed in the left-hand
⎨ side column of Table 2. Fig. 6c shows three-phase inverter
S
sgn(S) = , if |S | ≤ l (28) currents with the proposed SMHC scheme. It is observed that the

⎩l
−1 , if S , −l current waveforms are much more sinusoidal as compared with
Fig. 6b because the proposed scheme eliminates the harmonic
where l is a width of boundary layer. components effectively. The THD values of currents with the
Using the proposed SMHC input (21) with the PI control input in proposed scheme are listed in the right-hand side column of
(16) and decoupling control term, the inverter reference voltages can Table 2. It is clearly shown that THD values can be reduced
be givens as follows significantly with the proposed SMHC strategy.

u∗dq = (U ∗dq + vLI qd + V dq ) + u∗dqh (29)

Since the harmonic voltages and currents which are obtained through
the harmonic detector are dealt with in the proposed SMHC method,
only the fundamental components are considered as decoupling
terms as shown in Fig. 2.
The proposed SMHC method can substantially eliminate mainly
harmful low order harmonics with robustness and fast dynamics.
Furthermore, the proposed harmonic compensation method only
treats the harmonic component while the PI controller takes charge of
major power flow in the grid-connected inverter. Thus, the chattering
phenomenon can be reduced than the conventional SMC scheme
which deals with the entire current. Moreover, the computational
burden of the processor is relatively decreased as compared with the
conventional selective harmonic compensation method.

4 Simulation and experimental results

To evaluate the performance of the proposed SMHC scheme, the


simulations and experiments have been done. Fig. 5 shows the
experimental setup of DG system. The overall DG system consists
of a DSP based controller, three-phase grid-connected inverter
with an L filter, a transformer and magnetic contactor for
grid-connected operation. The whole control algorithms including
the proposed SMHC strategy are implemented by 32-bit
floating-point DSP TMS320F28335 for 2 kVA laboratory
prototype three-phase grid-connected inverter [24].
The inverter reference voltages are applied using the symmetrical
space vector PWM method. The sampling period is set to 100 μsec
both in the simulations and experiments, which yields the
switching frequency of 10 kHz in the symmetrical space vector
PWM method. The intelligent power module is employed for
three-phase grid-connected inverter. The inverter phase currents
are detected by the Hall-effect devices and are converted through
internal 12-bit A/D converters, where the resolution of current is
18/211 [A].
To isolate between the grid-connected inverter and grid,
three-phase wye-delta double winding transformer is employed.
For simulations and experiments, the q-axis fundamental current
reference is set to 7.5 A and the d-axis fundamental reference
value is set to zero. The system parameters of the experimental
setup are listed in Table 1.
Even though the proposed scheme is a non-selective harmonic
compensation method, the magnitude of main harmful low order
harmonic components in the fifth and the seventh are used as a
performance index to evaluate the proposed SMHC method in the
simulations and experiments.
Fig. 6 shows comparative simulation results of the inverter output
currents under distorted grid voltage condition. The simulation is
developed using the PSIM software. For distorted condition, 20%
of the fifth and the seventh harmonics, respectively, 10% of the
eleventh and the thirteenth harmonics, respectively, are injected to
the grid voltage, which results in THD of 31.7%. Fig. 6a shows
the resultant distorted three-phase grid voltages. Fig. 6b shows
three-phase inverter currents without the proposed harmonic
Fig. 9 Experimental results under the distorted grid voltage without
compensation scheme. The PI decoupling control in the SRF is harmonic compensation scheme
used with the gains of Kpc = 9.3 and Kic = 7000, which yields the
a Actual three-phase grid voltages
system bandwidth of 1000 rad/sec and the damping ratio of 0.7. b Three-phase inverter currents
As is shown in this figure, the inverter currents are severely c q-axis current response
distorted because of the distorted grid voltage. In this case, the d Harmonic currents in dq-axis

IET Power Electron., 2015, Vol. 8, Iss. 8, pp. 1461–1472


& The Institution of Engineering and Technology 2015 1469
To demonstrate that the proposed scheme has a fast dynamic be obtained by using the proposed harmonic detector. These
response, Fig. 7 shows the transient response of the proposed waveforms clearly show the actual a-phase current is quite
SMHC strategy when the normal grid voltages are suddenly non-sinusoidal and distorted. Fig. 10b shows the FFT result of
distorted at 0.3 s in Fig. 7a. Even in the presence of large voltage a-phase current in Fig. 9a. Even though small even order
disturbance injected to grid, the harmonic currents can be harmonic and triplen harmonics are observed because of slight
suppressed instantly by the proposed scheme as is shown in Fig. 7b. imbalance in actual grid voltage, the main harmonic components
To prove that the proposed scheme has the robustness with respect are in the fifth and seventh order. It is clearly shown in Fig. 9
to uncertainties in supply impedance, Fig. 8 shows the performance through Fig. 10 that the PI control method has a limited capability
of the proposed SMHC scheme when the grid impedance is suddenly to suppress harmonics.
changed at 0.4 s to the inductance of 3 mH and the resistance of
0.5 Ω. Even in this case, the proposed scheme can still compensate
the harmonics except for initial transient period.
Fig. 9 shows the experimental results under the distorted grid
voltage without the harmonic compensation scheme. Fig. 9a
shows the measured actual three-phase grid voltages in the
laboratory configuration. The actual grid voltages are highly
distorted with major harmful low order harmonic components. The
currents are regulated only by the PI controller with the same
gains as the simulation conditions. Fig. 9b shows three-phase
inverter current responses and Fig. 9c shows the q-axis current
response. As can be shown, the actual q-axis current cannot
properly track the reference value using the PI controller under
such a distorted grid condition. Fig. 9d shows the extracted
harmonic currents idh and iqh in d- and q-axis. As a result of poor
disturbance rejection capability by the PI controller, the harmonic
currents are significantly large, where the main harmonic
component is in the sixth order since the fifth and the seventh
harmonics in the stationary reference frame are transformed to the
sixth harmonic in the SRF through the Park’s transformation.
Fig. 10 shows the harmonic characteristics in a-phase current
without the harmonic compensation scheme. Fig. 10a shows actual
a-phase current and the extracted fundamental current using the
BPF. It is observed that a pure sinusoidal fundamental current can

Fig. 11 Experimental results under the distorted grid voltage with the
proposed SMHC scheme
Fig. 10 Harmonic characteristics in a-phase current without harmonic
a Three-phase inverter currents
compensation scheme b q-axis current response
a Actual a-phase current and extracted fundamental current c Harmonic currents in dq-axis
b FFT result of a-phase current d Switching control inputs of the proposed SMHC scheme

IET Power Electron., 2015, Vol. 8, Iss. 8, pp. 1461–1472


1470 & The Institution of Engineering and Technology 2015
responses. As compared with Fig. 9b, the inverter current has
more sinusoidal waveforms similar to the simulation results in
Fig. 6c. Figs. 11b and c show the q-axis current response and the
extracted harmonic currents idh and iqh. As a result of an effective
suppression of the harmonic components by the proposed scheme,
the harmonic currents are significantly decreased than Fig. 9d and
the q-axis current can be regulated to the reference better with a
small tracking error. Fig. 11d shows the switching control inputs
usw in (21) of the proposed SMHC scheme. Since the proposed
method treats only the harmonic components rather than entire
phase currents, the chattering is effectively decreased than the
conventional SMC method.
Fig. 12 shows the harmonic characteristics in a-phase current with
the proposed SMHC scheme. Fig. 12a shows actual a-phase current
and the extracted fundamental current. Owing to an effective
suppression of harmonics, the a-phase actual current is much
closer to sinusoidal fundamental current. Fig. 12b shows the FFT
result of a-phase current in Fig. 12a. It is clearly observed that the
fifth and the seventh harmonic components are considerably
reduced as compared with Fig. 10b. Fig. 12c shows the each
harmonic portion in a-phase compared with IEC 61000-3-2
standard.
To prove the transient performance, Fig. 13 shows the transient
response when the conventional PI control scheme is changed to
the proposed scheme. Before the proposed scheme, a-phase
current is highly distorted and the harmonic component is large.
However, as soon as the proposed scheme starts, the harmonic
component is quickly reduced and a-phase current becomes much
closer to sinusoidal. Moreover, the RMS value of the a-phase
harmonic current is also decreased as shown in Fig. 13.
As a result, the proposed SMHC method has a good disturbance
rejection capability with fast dynamic response and less chattering
in the presence of the distorted grid voltage condition.

5 Conclusions

In this paper, a novel SMHC scheme has been presented to enhance


the power quality in a grid-connected inverter when the grid is
polluted by non-linear loads in DG system. The proposed scheme
is composed of the harmonic detector and the sliding mode
harmonic current control. The harmonic detector is implemented in
a digital manner using the fourth order BPF in the stationary
reference frame. The sliding mode harmonic current control can
Fig. 12 Harmonic characteristics in a-phase current with the proposed effectively suppress the harmonic currents generated by distorted
SMHC scheme grid voltage. Since only the harmonic currents are treated by the
a Actual a-phase current and extracted fundamental current ISMC scheme while the fundamental current is regulated by the PI
b FFT result of a-phase current control, the chattering because of uncertainty can be considerably
c Each harmonic portion in a-phase current reduced. The proposed scheme has a good disturbance rejection
capability with fast dynamic response. Moreover, the
computational load is quite small. The simulation and
Fig. 11 shows the experimental results when the proposed SMHC
experimental results verify that the proposed SMHC scheme can
scheme is used to compensate the harmonic currents under the same
effectively reduce main harmful low order harmonics which are in
grid voltage in Fig. 9a. Fig. 11a shows three-phase inverter current
the fifth and the seventh order of three-phase system. As a result,
the proposed scheme is an attractive solution to control a
grid-connected inverter under distorted grid voltage condition.

6 Acknowledgment

This research was supported by Basic Science Research Programme


through the National Research Foundation of Korea (NRF) funded
by the Ministry of Education (NRF-2014R1A1A2056436).

7 References
1 Lascu, C., Asiminoaei, L., Boldea, I., Blaabjerg, F.: ‘High performance current
controller for selective harmonic compensation in active power filters’, IEEE
Trans. Power Electron., 2007, 22, (5), pp. 1826–1835
2 Trinh, Q-N., Lee, H-H.: ‘An advanced current control strategy for three-phase
shunt active power filters’, IEEE Trans. Ind. Electron., 2013, 60, (12),
Fig. 13 Transient performance of the proposed SMHC scheme pp. 5400–5410

IET Power Electron., 2015, Vol. 8, Iss. 8, pp. 1461–1472


& The Institution of Engineering and Technology 2015 1471
3 Lascu, C., Asiminoaei, L., Boldea, I., Blaabjerg, F.: ‘Frequency response analysis 15 Timbus, A., Liserre, M., Teodorescu, R., Rodriguez, P., Blaabjerg, F.: ‘Evaluation
of current controllers for selective harmonic compensation in active power filters’, of current controllers for distributed power generation systems’, IEEE Trans.
IEEE Trans. Ind. Electron., 2009, 56, (2), pp. 337–347 Power Electron., 2009, 24, (3), pp. 654–664
4 Liserre, M., Teodorescu, R., Blaabjerg, F.: ‘Multiple harmonics control for 16 Karaarslan, A., Iskender, I.: ‘Average sliding control method applied on power
three-phase grid converter systems with the use of PI-RES current controller in a factor correction converter for decreasing input current total harmonic distortion
rotating frame’, IEEE Trans. Power Electron., 2006, 21, (3), pp. 836–841 using digital signal processor’, IET . Power Electron., 2012, 5, (5), pp. 617–626
5 Teodorescu, R., Blaabjerg, F., Liserre, M., Loh, P.C.: ‘Proportional-resonant 17 Hu, J., Shang, L., He, Y., Zhu, Z.Q.: ‘Direct active and reactive power regulation of
controllers and filters for grid-connected voltage-source converters’, IEE Proc., grid-connected DC/AC converters using sliding mode control approach’, IEEE
Electr. Power Appl., 2006, 153, (5), pp. 750–762 Trans. Power Electron., 2011, 26, (1), pp. 210–222
6 Jinming, X., Ting, T., Shaojun, X.: ‘Research on low-order current harmonics 18 Matas, J., de Vicuna, L.G., Miret, J., Guerrero, J.M., Castilla, M.: ‘Feedback
rejections for grid-connected LCL-filtered inverters’, IET Power Electron., 2014, linearization of a single-phase active power filter via sliding mode control’,
7, (8), pp. 1227–1234 IEEE Trans. Power Electron., 2008, 23, (1), pp. 116–125
7 Li, B., Yao, W., Hang, L., Tolbert, L.M.: ‘Robust proportional resonant regulator 19 Martinez, M.I., Susperregui, A., Tapia, G., Xu, L.: ‘Sliding-mode control of a wind
for grid-connected voltage source inverter (VSI) using direct pole placement design turbine-driven double-fed induction generator under non-ideal grid voltages’, IET
method’, IET Power Electron., 2012, 5, (8), pp. 1367–1373 Renew. Power Gener., 2013, 7, (4), pp. 370–379
8 Escobar, G., Hernandez-Briones, P.G., Martinez, P.R., Hernandez-Gomez, M., 20 Mohamed, Y.A.-R.I., El-Saadany, E.F.: ‘A control scheme for PWM
voltage-source distributed-generation inverters for fast load-voltage regulation
Torres-Olguin, R.E.: ‘A repetitive-based controller for the compensation of 6l ±
and effective mitigation of unbalanced voltage disturbances’, IEEE Trans. Ind.
1 harmonic components’, IEEE Trans. Ind. Electron., 2008, 55, (8), pp. 3015–3158
Electron., 2008, 55, (5), pp. 2072–2084
9 Garcia-Cerrada, A., Pinzon-Ardila, O., Feliu-Batlle, V., Roncero-Sanchez, P.,
21 Mohamed, Y.A.-R.I.: ‘Mitigation of dynamic, unbalanced, and harmonic voltage
García-González, P.: ‘Application of a repetitive controller for a three-phase
disturbances using grid-connected inverters with LCL filter’, IEEE Trans. Ind.
active power filter’, IEEE Trans. Power Electron., 2007, 22, (1), pp. 237–246
Electron., 2011, 58, (9), pp. 3914–3924
10 Chen, S., Lai, Y.M., Tan, S.-C., Tse, C.K.: ‘Analysis and design of repetitive 22 Chen, S., Lai, Y.M., Tan, S.-C., Tse, C.K.: ‘Fast response low harmonic distortion
controller for harmonic elimination in PWM voltage source inverter systems’, control scheme for voltage source inverters’, IET, Power Electron., 2009, 2, (5),
IET Power Electron., 2008, 1, (4), pp. 497–506 pp. 574–584
11 Sha, D., Wu, D., Liao, X.: ‘Analysis of a hybrid controlled three-phase 23 Hao, X., Yang, X., Liu, T., Huang, L., Chen, W.: ‘A sliding-mode controller with
grid-connected inverter with harmonics compensation in synchronous reference multiresonant sliding surface for single-phase grid-connected VSI with an LCL
frame’, IET Power Electron., 2011, 4, (7), pp. 743–751 filter’, IEEE Trans. Power Electron., 2013, 28, (5), pp. 2259–2268
12 Chen, D., Zhang, J., Qian, Z.: ‘Research on fast transient and 6n ± 1 harmonics 24 TMS320F28335 Digital Signal Controller (DSC) - Data Manual. Texas Instrument,
suppressing repetitive control scheme for three-phase grid-connected inverters’, 2008
IET Power Electron., 2013, 6, (3), pp. 601–610 25 Lee, J.H., Ko, J.S., Chung, S.K., et al.: ‘Continuous variable structure controller for
13 Fischer, J.R., Gonzalez, S.A., Carugati, I., Herran, M.A., Judewicz, M.G., Carrica, BLLDDSM position control with prescribed tracking performance’, IEEE Trans.
D.O.: ‘Robust predictive control of grid-tied converters based on direct power Ind. Electron., 1994, 41, (5), pp. 483–491
control’, IEEE Trans. Power Electron., 2014, 29, (10), pp. 5634–5643 26 Ogata, K.: ‘Discrete-time control system’ (Prentice – Hall Inc., 1994, 2nd edn.)
14 Acuna, P., Moran, L., Rivera, M., Dixon, J., Rodriguez, J.: ‘Improved active power 27 Lee, S.H., Lee, J.H., Cha, H.J.: ‘Grid synchronization PLL robust to frequency
filter performance for renewable power generation systems’, IEEE Trans. Power variation, unbalanced and distorted voltage’. Proc. Int. Conf. Energy Conversion
Electron., 2014, 29, (2), pp. 687–694 Congress and Exposition, Phoenix, USA, September 2011, pp. 1150–1155

IET Power Electron., 2015, Vol. 8, Iss. 8, pp. 1461–1472


1472 & The Institution of Engineering and Technology 2015

You might also like