Application Note 6001

"DOP6001" (beam detector) connected to UniPOS conventional


interface units

Contents:
1. Wiring Map ........................................................................................................................ 2
1.1. FD7201(S) ................................................................................................................... 2
1.2. FS4000 ......................................................................................................................... 2
1.3. FS5100/FS5200 ........................................................................................................... 3
2. Panel programming ............................................................................................................ 3
2.1. IFS7002 with FD7201(S) interface unit for DOP-6001 .............................................. 3
2.2. FS4000 interface with DOP-6001................................................................................ 5
2.3. FS5100/FS5200 interface with DOP-6001 .................................................................. 5
3. DOP6001 configuration ...................................................................................................... 6
3.1. Jumpers set-up ............................................................................................................. 6
3.2. Calibration ................................................................................................................... 6
3.3. Validation..................................................................................................................... 7

1
Rev. 01.0614
1. Wiring Map
1.1. FD7201(S)
End of line element (EOL-1/EOL-2) must be REMOVED from the conventional line:

1.2. FS4000
End of line element 3Kohms/0.6W must be CHANGED with 5.6Kohms/0.25W:

2
Rev. 01.0614
1.3. FS5100/FS5200
End of line element 3.9Kohms/0.25W must be REMOVED from the conventional
line:

2. Panel programming
2.1. IFS7002 with FD7201(S) interface unit for DOP-6001
2.1.1. Disable the check for Removed Fire Detector on the Conventional line:
From menu "Setup > Loops > Loop 1/2 > Device Parameters > address of the
FD7201/FD7201S":

FIRE CONTROL PANEL IFS7002


UniPOS

Loop parameters
List devices
LoopDevice
1 parameters
LoopCheck
2 up
Panel Configuration
Manual addressing
Panel Parameters
Lists
Loops
System functions
Zones
Setup
Inputs

MODE DAY LOC 15:09:10 Mon 21

Device parameters menu location


3
Rev. 01.0614
Check for removed detector – change to “NO”:

SetUp Device X Loop X

Device Type: FD7201


State: ON

Class: A1R
Type : Adapter

Check for removed detector: NO


Current of interruption : 2 mA

Mode DAY Local 16:13:30 Tue 22 Mar 2005

FD7201/FD7201S parameters

2.1.2. The conventional line status could be referred from menu: “lists > Devices
status”:
The parameter to monitor is the conventional line current:

[0 – 2], mA – Open conventional line;


[2 – 10], mA – Duty mode;
[10 – 50], mA – Fire mode;
> 50mA – Short Circuit in the conventional line;

FIRE CONTROL PANEL IFS7002


UniPOS

List of values Devices Total: 8 Go to:


Loop X Addr: XXX Zone XX
Device Type: FD7201
Line: I = 6 mA
Temperature +022 С Клас: A1R
Status: Izolator OFF LED OFF

0 1 2 3 4 5 6 7 8 9 С

Mode DAY Local ActIN:0000 14:22:00 Sat 12 Mar 2005


FD7201/FD7201S status

4
Rev. 01.0614
2.2. FS4000 interface with DOP-6001
2.2.1. From dip-switch, pos.3 turn-On pin1:

2.3. FS5100/FS5200 interface with DOP-6001

2.3.1. FS5200 sub-menu “System functions > Set parameters > Lines > Line NN”:

5200 sub-menu
Disable Check for Removed Fire Detector

2.3.2. FS5100 sub-menu “System functions > Setup mode > Line Parameters”:

5100 sub-menu
Disable Check for Removed Fire Detector

5
Rev. 01.0614
3. DOP6001 configuration
3.1. Jumpers set-up

Jumpers
Three pcs. (3 pcs.) of jumpers are required for the compatibility mode of the DOP-
6001 and the UniPOS conventional line interfaces:
• Jumper for Sensitivity mode – the sensitivity of the beam should be set
according to the distance between the DOP-6001 head and the reflector:
o distance from 5 m to 20 m – 18 % sensitivity is recommended;
o distance from 20 m to 50 m – 30 % sensitivity is recommended;
o distance from 50 m to 100 m – 50 % sensitivity is recommended;
• Jumper for compatibility mode – ADC-1 and ADC-38 must be set;

3.2. Calibration
Using 9V battery and the 3 position regulators male screws, we focus the red RAY
towards the mirror.

Calibration setup tools

6
Rev. 01.0614
Remove the battery and hold the “START button”:

StartUp button

3.3. Validation

Test the Beam for fault and fire status:

- Fault – 100% cover (with no transparent cover)


- Fire – 75 % cover using the pattern below. We can supply you with such pattern:

7
Rev. 01.0614