Parcial # 2

HVAC Load Analysis


for

Prepared By:

lunes, 20 de noviembre de 2017


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Elite Software Development Parcial # 2
College Station, TX 77845 Page 2

Building Summary Loads


Building peaks in March at 3pm.
Bldg Load Area Sen %Tot Lat Sen Net %Net
Descriptions Quan Loss Loss Gain Gain Gain Gain
Roof 1,056 0 0.00 0 10,333 10,333 17.81
Wall 495 0 0.00 0 7,022 7,022 12.10
Glass 185 0 0.00 0 3,057 3,057 5.27
Floor Slab 0 0 0.00 0 0 0 0.00
Skin Loads 0 0.00 0 20,412 20,412 35.18
Lighting 1,795 0 0.00 0 6,125 6,125 10.56
Equipment 1,056 0 0.00 0 3,603 3,603 6.21
Pool Latent 0 0 0.00 0 0 0 0.00
People 24 0 0.00 4,800 6,000 10,800 18.62
Partition 650 0 0.00 0 2,295 2,295 3.95
Cool. Pret. 0 0 0.00 0 0 0 0.00
Heat. Pret. 0 0 0.00 0 0 0 0.00
Cool. Vent. 180 0 0.00 9,732 4,551 14,283 24.62
Heat. Vent. 0 0 0.00 0 0 0 0.00
Cool. Infil. 0 0 0.00 0 0 0 0.00
Heat. Infil. 0 0 0.00 0 0 0 0.00
Draw-Thru Fan 0 0 0.00 0 499 499 0.86
Blow-Thru Fan 0 0 0.00 0 0 0 0.00
Reserve Cap. 0 0 0.00 0 0 0 0.00
Reheat Cap. 0 0 0.00 0 0 0 0.00
Supply Duct 0 0 0.00 0 0 0 0.00
Return Duct 0 0 0.00 0 0 0 0.00
Misc. Supply 0 0 0.00 0 0 0 0.00
Misc. Return 0 0 0.00 0 0 0 0.00
Building Totals 0 0.00 14,532 43,485 58,017 100.00

Building Sen %Tot Lat Sen Net %Net


Summary Loss Loss Gain Gain Gain Gain
Ventilation 0 0.00 9,732 4,551 14,283 24.62
Infiltration 0 0.00 0 0 0 0.00
Pretreated Air 0 0.00 0 0 0 0.00
Room Loads 0 0.00 4,800 38,435 43,235 74.52
Plenum Loads 0 0.00 0 0 0 0.00
Fan/Duct/Misc Loads 0 0.00 0 499 499 0.86
Building Totals 0 0.00 14,532 43,485 58,017 100.00

Check Figures
Total Building Supply Air (based on a 17° TD): 2,083 CFM
Total Building Vent. Air (8.64% of Supply): 180 CFM
Total Conditioned Air Space: 1,056 Sq.ft
Supply Air Per Unit Area: 1.9730 CFM/Sq.ft
Area Per Cooling Capacity: 218.4 Sq.ft/Ton
Cooling Capacity Per Area: 0.0046 Tons/Sq.ft
Heating Capacity Per Area: 0.00 Btuh/Sq.ft
Total Heating Required With Outside Air: 0 Btuh
Total Cooling Required With Outside Air: 4.83 Tons

C:\Users\jonhy\Desktop\JONATHAN\4TO AÑO\Aire Acond\PARCIAL#2.CH8 lunes, 20 de noviembre de 2017, 03:44 p.m.


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Elite Software Development Parcial # 2
College Station, TX 77845 Page 3

Air Handler #1 - Ue-1 - Summary Loads


Rm Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
No Room Peak Time People Htg.CFM Clg.CFM S.Exh Req.CFM Req.CFM
Volume CFM/Sqft CFM/Sqft W.Exh Act.CFM Act.CFM
1 Area 1 1,056 0 38,435 4,800 None 7.5/P
3pm March 24 0 2,083 0 0 180
9,504 0.00 1.97 0 0 180
Room Peak Totals: 1,056 0 38,435 4,800
Total Rooms: 1 24 0 2,083 0 0 180
Unique Rooms: 1 9,504 0.00 1.97 0 0 180

C:\Users\jonhy\Desktop\JONATHAN\4TO AÑO\Aire Acond\PARCIAL#2.CH8 lunes, 20 de noviembre de 2017, 03:44 p.m.


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Elite Software Development Parcial # 2
College Station, TX 77845 Page 4

Air Handler #1 - Ue-1 - Total Load Summary


Air Handler Description: Ue-1 Constant Volume - Proportion
Supply Air Fan: Draw-Thru with program estimated horsepower of 0.20 HP
Fan Input: 0% motor and fan efficiency with 0 in. water across the fan
Sensible Heat Ratio: 0.89 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 3pm in March.
Outdoor Conditions: Clg: 95° DB, 81° WB, 135.16 grains
Indoor Conditions: Clg: 72° DB, 50% RH
Summer: Ventilation controls outside air, ----- Winter: Exhaust controls outside air.
Room Space sensible loss: 0 Btuh
Infiltration sensible loss: 0 Btuh 0 CFM
Outside Air sensible loss: 0 Btuh 0 CFM
Supply Duct sensible loss: 0 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss: 0 Btuh
Heating Supply Air: 0 / (.999 X 1.08 X 0) = 0 CFM
Winter Vent Outside Air (0.0% of supply) = 0 CFM
Room space sensible gain: 38,435 Btuh
Infiltration sensible gain: 0 Btuh
Draw-thru fan sensible gain: 499 Btuh
Supply duct sensible gain: 0 Btuh
Reserve sensible gain: 0 Btuh
Total sensible gain on supply side of coil: 38,934 Btuh
Cooling Supply Air: 38,934 / (.999 X 1.1 X 17) = 2,083 CFM
Summer Vent Outside Air (8.6% of supply) = 180 CFM
Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: 4,551 Btuh 180 CFM
Blow-thru fan sensible gain: 0 Btuh
Total sensible gain on return side of coil: 4,551 Btuh
Total sensible gain on air handling system: 43,485 Btuh
Room space latent gain: 4,800 Btuh
Infiltration latent gain: 0 Btuh
Outside air latent gain: 9,732 Btuh
Total latent gain on air handling system: 14,532 Btuh
Total system sensible and latent gain: 58,017 Btuh

Check Figures
Total Air Handler Supply Air (based on a 17° TD): 2,083 CFM
Total Air Handler Vent. Air (8.64% of Supply): 180 CFM
Total Conditioned Air Space: 1,056 Sq.ft
Supply Air Per Unit Area: 1.9730 CFM/Sq.ft
Area Per Cooling Capacity: 218.4 Sq.ft/Ton
Cooling Capacity Per Area: 0.0046 Tons/Sq.ft
Heating Capacity Per Area: 0.00 Btuh/Sq.ft
Total Heating Required With Outside Air: 0 Btuh
Total Cooling Required With Outside Air: 4.83 Tons

C:\Users\jonhy\Desktop\JONATHAN\4TO AÑO\Aire Acond\PARCIAL#2.CH8 lunes, 20 de noviembre de 2017, 03:44 p.m.


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Elite Software Development Parcial # 2
College Station, TX 77845 Page 5

Zone Detailed Loads (At Zone Peak Times)


Load Unit -SC- CLTD U.Fac Sen. Lat. Htg. Htg.
Description Quan CFAC SHGF -CLF- Gain Gain Mult. Loss
Room 1-Area 1 - Air Handler 1 (Ue-1), Zone 0 peaks (sensible) in March at 3pm.
Roof-1-1-Susp.C-L 1,056 0.50 45.9 0.213 10,333 0.383 405
Wall-1-S-F-M 15 0.83 35.6 0.419 224 0.754 11
Wall-2-S-F-M 200 0.83 35.6 0.419 2,986 0.754 151
Wall-3-W-F-M 150 0.83 29.4 0.419 1,848 0.754 113
Wall-4-E-F-M 130 0.83 36.1 0.419 1,964 0.754 98
Partition-5-1 210 10/0 0.353 741 0.000 0
Partition-6-1 320 10/0 0.353 1,130 0.000 0
Partition-7-1 120 10/0 0.353 424 0.000 0
Gls-S-2-90-Tran 185.0 1.000 21 0.520 2,020 0.756 140
0%S-0-WS-Solar 185.0 0.190 59 0.500 1,037
Lights-Prof=1 1,795 1.000 6,125
Equipment-Prof=3 1,056 1.000 3,603 0
People-Prof=2 24.0 1.000 6,000 4,800
Sub-total 38,435 4,800 0
Safety factors: +0% +0% +0%
--------- --------- ---------
Total w/ safety factors: 38,435 4,800 0

C:\Users\jonhy\Desktop\JONATHAN\4TO AÑO\Aire Acond\PARCIAL#2.CH8 lunes, 20 de noviembre de 2017, 03:44 p.m.


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Elite Software Development Parcial # 2
College Station, TX 77845 Page 6

Room Detailed Loads (At Room Peak Times)


Load Unit -SC- CLTD U.Fac Sen. Lat. Htg. Htg.
Description Quan CFAC SHGF -CLF- Gain Gain Mult. Loss
Room 1-Area 1 peaks (sensible) in March at 3pm, Air Handler 1 (Ue-1), Zone 0, 33.0 x 32.0, Construction
Type: 1 (Light)
Roof-1-1-Susp.C-L 1,056 0.50 45.9 0.213 10,333 0.383 405
Wall-1-S-F-M 15 0.83 35.6 0.419 224 0.754 11
Wall-2-S-F-M 200 0.83 35.6 0.419 2,986 0.754 151
Wall-3-W-F-M 150 0.83 29.4 0.419 1,848 0.754 113
Wall-4-E-F-M 130 0.83 36.1 0.419 1,964 0.754 98
Partition-5-1 210 10/0 0.353 741 0.000 0
Partition-6-1 320 10/0 0.353 1,130 0.000 0
Partition-7-1 120 10/0 0.353 424 0.000 0
Gls-S-2-90-Tran 185.0 1.000 21 0.520 2,020 0.756 140
0%S-0-WS-Solar 185.0 0.190 59 0.500 1,037
Lights-Prof=1 1,795 1.000 6,125
Equipment-Prof=3 1,056 1.000 3,603 0
People-Prof=2 24.0 1.000 6,000 4,800
Sub-total 38,435 4,800 0
Safety factors: +0% +0% +0%
--------- --------- ---------
Total w/ safety factors: 38,435 4,800 0

C:\Users\jonhy\Desktop\JONATHAN\4TO AÑO\Aire Acond\PARCIAL#2.CH8 lunes, 20 de noviembre de 2017, 03:44 p.m.