Professional Documents
Culture Documents
GB_2016_49
GB_2015_31
Table of Contents page
General Information
1 Produced Versions of the Boilers ............................................................................................................ 4
2 Boiler Application and Benefits ................................................................................................................ 4
3 Technical Data ......................................................................................................................................... 5
4 Boiler Description .................................................................................................................................. 16
4.1 Boiler Design .................................................................................................................................... 16
4.2 Control Features ............................................................................................................................... 16
4.2.1 Removing the front cover ........................................................................................................... 17
4.3 Main Boiler Parts .............................................................................................................................. 18
4.4 A diagram showing flue gas flow in the exchanger .......................................................................... 20
4.5 Delivery and Accessory .................................................................................................................... 21
4.6 Instructions before Putting into Operation ........................................................................................ 21
User
2
General Information
Servicing
10 Placement and Installation .................................................................................................................... 33
10.1 Standards and regulations ............................................................................................................... 33
10.2 Possible Placement .......................................................................................................................... 34
10.3 Boiler Installation .............................................................................................................................. 35
10.4 Connecting to the Heating System and Water Filling ...................................................................... 37
10.5 Gas Connection ................................................................................................................................ 37
10.6 Electric Power Supply Connection ................................................................................................... 37
10.7 Condensate Discharge ..................................................................................................................... 37
10.8 Flue Gas Ducting .............................................................................................................................. 37
10.9 Boiler Electrical Wiring ..................................................................................................................... 38
10.9.1 Main components of boiler electrical equipment........................................................................ 38
10.9.2 Connection of the higher-level regulation and external boiler sensors ...................................... 38
10.9.3 Connecting terminal ................................................................................................................... 39
11 Flue Gas Ducting ................................................................................................................................... 46
11.1 Flue gas ducting – examples of correct connection of flue duct and air supply............................... 48
11.2 Flue gas ducting – examples of incorrect connection of flue duct and air supply ............................ 48
11.3 STARR D80 and FLEX 80 system connection................................................................................. 48
11.3.1 STARR, 2 x D 80 mm flue ducting diagram ............................................................................... 49
11.3.2 FLEX, 2 x D 80 mm flue ducting diagram .................................................................................. 50
11.4 LIK 60/100, 80/125 system connection ............................................................................................ 51
11.4.1 Diagram for flue gas ducting of the LIK type, version 60/100 mm (max. length 5 m), or 80/12552
11.5 Pressure Losses of Chimney Flue Elements in Case of VIADRUS K4 Boiler Usage...................... 53
12 Commissioning ...................................................................................................................................... 54
12.1 Instructions before Putting into Operation ........................................................................................ 55
12.2 Boiler Setting .................................................................................................................................... 56
12.3 Conversion to a different type of fuel ............................................................................................... 57
12.4 Boiler Electronics Setting ................................................................................................................. 58
12.4.1 K4GXH24X - Honeywell electronics parameters set in the manufacturing factory (service parameters
list neXsys S4962V3224)........................................................................................................... 58
12.4.2 K4GXH33X - Honeywell electronics parameters set in the manufacturing factory (service parameters
list neXsys S4962V3224)........................................................................................................... 59
13 Servicing Inspection of the Boiler .......................................................................................................... 61
3
General Information
Dear Customer
Thank you for your purchase of the VIADRUS K4 boiler and for your confidence in VIADRUS a.s.
To become familiar with a proper operation of your new product since the beginning, please read carefully the
presented user´s manual, especially Chapter No. 5 – Boiler Attendance by the user, Chapter No. 6 – Maintenance,
and Chapter No. 7 – IMPORTANT NOTICES. We ask you to follow the information presented below and especially
to perform the prescribed annual inspections to be performed by an authorized specialized company, which
guarantees a long-term boiler operation free of failures to both your and our satisfaction.
VIADRUS K4 X1X2X3X4X5X6
X1 Exchanger: G: stainless Sermeta
X2 Water heating: 1: without installed three-way valve with a pump
2: three-way valve, pump, HSW exchanger
3: with a three-way valve with a pump
X3 Electrical equipment: H: Honeywell
X4 Output: 24: 24 kW
33: 33 kW
X5 Fuel: Z: natural gas
P: propane
X6 Cover color: W: white
R: red
S: silver
B: black
Conversion of the VIADRUS K4 boiler from natural gas to propane and vice-versa can be performed by a
contracted service provider only.
Chimney flue made by ALMEVA has been certified for this boiler. If you use chimney flue made by a
different producer, it is necessary to use a system with identical parameters as for the certified type of the
chimney flue.
Boiler Benefits:
• Low gas consumption
• High combustion efficiency
• Smooth output modulation
• Easy attendance and maintenance
• The boiler enables connecting to a reservoir of hot service water heater and ensures its preferential heating
• Reliability of the regulation and safety components
• Low weight
• Equithermal boiler regulation
4
General Information
3 Technical Data
Tab. №. 1 Sizes, operation temperature and electrical variables - VIADRUS K4GXH24XX
K4G1H24PX
K4G2H24PX
K4G3H24PX
K4G1H24ZX
K4G2H24ZX
K4G3H24ZX
Fuel type [-] ZP Propane ZP Propane ZP Propane
Category of appliance [-] I2H I2E I3P I2H I2E I3P I2H I2E I3P
Version C13,C33, C43, C53, C83
Weight [kg] 26 27.5 26.5
Water volume [l] 2 3 2
Boiler dimensions – width [mm] 460
– depth [mm] 350
– height [mm] 720
Ø of combustion air connection [mm] 80 / 100 (see fig. no 10)
Ø flue gas socket [mm] 80, 60
Working water overpressure [bar] 3
Testing water overpressure [bar] 5
Pressure loss [-] See diagram 1
Maximum permitted working
[°C] 85
temperature
Heating water setting range [°C] 25 - 85
Hot water setting range [°C] - 35 - 60 35 - 60
Connecting overpressure of fuel [mbar] 20 37 20 37 20 37
Noise level [dB] < 50
Boiler connection
- heating water output [Js] 3/4“
- heating water input to the heater [Js] - 1/2“ 1/2“
- return heating water input [Js] 3/4“
- return water input from the heater [Js] 1/2“ 3/4“
- system water filling inlet [Js] 1/2" - -
- condensate outlet [mm] Ø 25
- safety valve output [mm] Ø 21,2
- gas inlet [Js] 3/4“
Connecting voltage 1/N/PE 230VAC 50 Hz, TN-S
El. power input including pump [W] 110
El. covering IP 40
K4G2H24PX
K4G3H24PX
K4G1H24ZX
K4G2H24ZX
K4G3H24ZX
5
General Information
Tab. №. 3 Sizes, operation temperature and electrical variables - VIADRUS K4GXH33XX
K4G1H33PX
K4G2H33PX
K4G3H33PX
K4G1H33ZX
K4G2H33ZX
K4G3H33ZX
Fuel type [-] ZP Propane ZP Propane ZP Propane
Category of appliance [-] I2H I2E I3P I2H I2E I3P I2H I2E I3P
Version C13,C33, C43, C53, C83
Weight [kg] 28 29,5 28,5
Water volume [l] 3 4 3
Boiler dimensions – width [mm] 460
– depth [mm] 350
– height [mm] 720
Ø of combustion air connection [mm] 80 / 100
Ø flue gas socket [mm] 80, 60 (see fig. no 10)
Working water overpressure [bar] 3
Testing water overpressure [bar] 5
Pressure loss [-] See diagram 1
Maximum permitted working
[°C] 85
temperature
Heating water setting range [°C] 25 - 85
Hot water setting range [°C] - 35 - 60 35 - 60
Connecting overpressure of fuel [mbar] 20 37 20 37 20 37
Noise level [dB] < 50
Boiler connection
- heating water output [Js] 3/4“
- heating water input to the heater [Js] - 1/2“ 1/2“
- return heating water input [Js] 3/4“
- return water input from the heater [Js] 1/2“ 3/4“
- system water filling inlet [Js] 1/2" - -
- condensate outlet [mm] Ø 25
- safety valve output [mm] Ø 21,2
- gas inlet [Js] 3/4“
Connecting voltage 1/N/PE 230VAC 50 Hz, TN-S
El. power input including pump [W] 110
El. covering IP 40
K4G2H33PX
K4G3H33PX
K4G1H33ZX
K4G2H33ZX
K4G3H33ZX
6
General Information
7
General Information
K4G2H24..
K4G2H24.. HotOhřev
waterTV - ∆T 25°C
heating - ∆T 25 °C
16,50
14,50
12,50
Výkon kotle (kW)
Boiler power (kW)
10,50
8,50
6,50
4,50
2,50 3,50 4,50 5,50 6,50 7,50 8,50 9,50
Průtok
Hot TV flow
water (l/min)
rate (l/min)
K4G2H24..
K4G2H24.. Ohřev
Hot waterTV - ∆T=30°C
heating - ∆T 30 °C
24,00
19,00
Výkon kotle (kW)
Boiler power (kW)
14,00
9,00
4,00
2,00 3,00 4,00 5,00 6,00 7,00 8,00 9,00 10,00 11,00
Hot water
Průtok flow rate (l/min)
TV (l/min)
K4G2H24..
K4G2H24.. HotOhřev
waterTV - ∆T 35°C
heating - ∆T 35 °C
23,00
21,00
19,00
Výkon kotle (kW)
17,00
Boiler power (kW)
15,00
13,00
11,00
9,00
7,00
2,50 3,50 4,50 5,50 6,50 7,50 8,50 9,50
Hot water
Průtok TV flow rate (l/min)
(l/min)
Graph No. 2 Dependence of boiler power on flow rate of heated hot water
(version VIADRUS K4G2H24XX)
8
General Information
K4G2H33..Hot
K4G2H33.. Ohřev TVheating
water -∆T 35°C- ∆T 25 °C
24,00
19,00
Výkon kotle (kW)
Boiler power (kW)
14,00
9,00
4,00
3,00 5,00 7,00 9,00 11,00 13,00 15,00
Průtok
Hot waterTVflow
(l/min
rate) (l/min)
K4G2H33..
K4G2H33.. Ohřev
Hot TV heating
water - ∆T 30°C - ∆T 30 °C
34,00
29,00
24,00
(kW)
kotle (kW)
19,00
power
Boiler Výkon
14,00
9,00
4,00
2,00 4,00 6,00 8,00 10,00 12,00 14,00 16,00
Hot water
Průtokflow rate (l/min)
TV (l/min)
K4G2H33..Hot
K4G2H33.. Ohřev TVheating
water -∆T 35°C- ∆T 35 °C
34,00
29,00
24,00
Výkon kotle (kW)
Boiler power (kW)
19,00
14,00
9,00
4,00
3,00 5,00 7,00 9,00 11,00 13,00
Průtok
Hot waterTVflow
(l/min
rate) (l/min)
Graph No. 3 Dependence of boiler power on flow rate of heated hot water
(version VIADRUS K4G2H33XX)
9
General Information
Information requirements for boiler space heaters, boiler combination heaters
and cogeneration space heaters
B1 boiler: no
Combination heater: no
Symbol
Symbol
Value
Value
Item
Item
Unit
Unit
Seasonal space heating energy
Rated heat output Prated 24 kW ƞs 90 %
efficiency
For boiler space heaters and boiler combination heaters: For boiler space heaters and boiler combination heaters:
Useful heat output Useful efficiency
At rated heat output and high- At rated heat output and high-
P4 24 kW ƞ4 97,53 %
temperature regime (*) temperature regime (*)
At 30 % of rated heat output
At 30 % of rated heat output and
and low-temperature regime P1 4 kW ƞ1 105,72 %
low-temperature regime (**)
(**)
VIADRUS a.s.
Contact details Bezručova 300
Bohumín
735 81
Czech Republic
(*) High-temperature regime means 60 °C return temperature at heater inlet and 80 °C feed temperature at heater
outlet.
(**) Low temperature means for condensing boilers 30 °C, for low-temperature boilers 37 °C and for other heaters 50 °C
return temperature (at heater inlet).
10
General Information
Information requirements for boiler space heaters, boiler combination heaters
and cogeneration space heaters
B1 boiler: no
Symbol
Value
Value
Item
Item
Unit
Unit
Seasonal space heating energy
Rated heat output Prated 24 kW ƞs 90 %
efficiency
For boiler space heaters and boiler combination heaters: For boiler space heaters and boiler combination heaters:
Useful heat output Useful efficiency
At rated heat output and high- At rated heat output and high-
P4 24 kW ƞ4 97,53 %
temperature regime (*) temperature regime (*)
At 30 % of rated heat output
At 30 % of rated heat output and
and low-temperature regime P1 4 kW ƞ1 105,72 %
low-temperature regime (**)
(**)
Daily electricity consumption Qelec 0,204 kWh Daily fuel consumption Qfuel 23,215 kWh
VIADRUS a.s.
Contact details Bezručova 300
Bohumín
735 81
Czech Republic
(*) High-temperature regime means 60 °C return temperature at heater inlet and 80 °C feed temperature at heater outlet.
(**) Low temperature means for condensing boilers 30 °C, for low-temperature boilers 37 °C and for other heaters 50 °C
return temperature (at heater inlet).
11
General Information
Information requirements for boiler space heaters, boiler combination heaters
and cogeneration space heaters
B1 boiler: no
Symbol
Value
Value
Item
Item
Unit
Unit
Seasonal space heating energy
Rated heat output Prated 24 kW ƞs 90 %
efficiency
For boiler space heaters and boiler combination heaters: For boiler space heaters and boiler combination heaters:
Useful heat output Useful efficiency
At rated heat output and high- At rated heat output and high-
P4 24 kW ƞ4 97,53 %
temperature regime (*) temperature regime (*)
At 30 % of rated heat output
At 30 % of rated heat output and
and low-temperature regime P1 4 kW ƞ1 105,72 %
low-temperature regime (**)
(**)
Daily electricity consumption Qelec 0,222 kWh Daily fuel consumption Qfuel 24,301 kWh
VIADRUS a.s.
Contact details Bezručova 300
Bohumín
735 81
Czech Republic
(*) High-temperature regime means 60 °C return temperature at heater inlet and 80 °C feed temperature at heater outlet.
(**) Low temperature means for condensing boilers 30 °C, for low-temperature boilers 37 °C and for other heaters 50 °C
return temperature (at heater inlet).
12
General Information
Information requirements for boiler space heaters, boiler combination heaters
and cogeneration space heaters
B1 boiler: no
Combination heater: no
Symbol
Symbol
Value
Value
Item
Item
Unit
Unit
Seasonal space heating energy
Rated heat output Prated 33 kW ƞs 90 %
efficiency
For boiler space heaters and boiler combination heaters: For boiler space heaters and boiler combination heaters:
Useful heat output Useful efficiency
At rated heat output and high- At rated heat output and high-
P4 30,3 kW ƞ4 98,4 %
temperature regime (*) temperature regime (*)
At 30 % of rated heat output
At 30 % of rated heat output and
and low-temperature regime P1 6 kW ƞ1 104,8 %
low-temperature regime (**)
(**)
VIADRUS a.s.
Contact details Bezručova 300
Bohumín
735 81
Czech Republic
(*) High-temperature regime means 60 °C return temperature at heater inlet and 80 °C feed temperature at heater
outlet.
(**) Low temperature means for condensing boilers 30 °C, for low-temperature boilers 37 °C and for other heaters 50 °C
return temperature (at heater inlet).
13
General Information
Information requirements for boiler space heaters, boiler combination heaters
and cogeneration space heaters
B1 boiler: no
Symbol
Value
Value
Item
Item
Unit
Unit
Seasonal space heating energy
Rated heat output Prated 33 kW ƞs 90 %
efficiency
For boiler space heaters and boiler combination heaters: For boiler space heaters and boiler combination heaters:
Useful heat output Useful efficiency
At rated heat output and high- At rated heat output and high-
P4 30,3 kW ƞ4 98,4 %
temperature regime (*) temperature regime (*)
At 30 % of rated heat output
At 30 % of rated heat output and
and low-temperature regime P1 6 kW ƞ1 104,8 %
low-temperature regime (**)
(**)
Daily electricity consumption Qelec 0,180 kWh Daily fuel consumption Qfuel 22,66 kWh
VIADRUS a.s.
Contact details Bezručova 300
Bohumín
735 81
Czech Republic
(*) High-temperature regime means 60 °C return temperature at heater inlet and 80 °C feed temperature at heater outlet.
(**) Low temperature means for condensing boilers 30 °C, for low-temperature boilers 37 °C and for other heaters 50 °C
return temperature (at heater inlet).
14
General Information
Information requirements for boiler space heaters, boiler combination heaters
and cogeneration space heaters
B1 boiler: no
Symbol
Value
Value
Item
Item
Unit
Unit
Seasonal space heating energy
Rated heat output Prated 33 kW ƞs 90 %
efficiency
For boiler space heaters and boiler combination heaters: For boiler space heaters and boiler combination heaters:
Useful heat output Useful efficiency
At rated heat output and high- At rated heat output and high-
P4 30,3 kW ƞ4 98,4 %
temperature regime (*) temperature regime (*)
At 30 % of rated heat output
At 30 % of rated heat output and
and low-temperature regime P1 6 kW ƞ1 104,8 %
low-temperature regime (**)
(**)
Daily electricity consumption Qelec 0,190 kWh Daily fuel consumption Qfuel 25,742 kWh
VIADRUS a.s.
Contact details Bezručova 300
Bohumín
735 81
Czech Republic
(*) High-temperature regime means 60 °C return temperature at heater inlet and 80 °C feed temperature at heater outlet.
(**) Low temperature means for condensing boilers 30 °C, for low-temperature boilers 37 °C and for other heaters 50 °C
return temperature (at heater inlet).
15
General Information
4 Boiler Description
4.1 Boiler Design
The boiler elementary structure consists in a condensing exchanger made of stainless steel pipes. It is checked for
tightness by test overpressure 5 bar. The boiler is further equipped with a premix burner. The combustion mixture is
mixed in a mixer in the preset air-gas ratio within the entire output range. Air is supplied to the mixer by a
modulation fan.
The Honeywell automatics is an electronic control and ignition automatics designed for gas-fired central heating
boilers with a modulated fan and burner with preliminary mixing.
The combustion air inlet and the flue gas outlet may be implemented by several means as follows:
- to the chimney,
- through the wall,
- through the roof (either inclined or horizontal),
- to a joint shaft.
The boiler is an appliance in version C, i.e., a closed appliance with electronic ignition and flame ionization.
16
General Information
4.2.1 Removing the front cover
17
General Information
4.3 Main Boiler Parts
18
General Information
Fig. №. 5 VIADRUS K4G1HXXXX with only water heating for the system
(hydraulic diagram of the version and the sketch of the hydro-block)
19
General Information
water output
water input water output water input
50°C
30°C
condensation partition
20
General Information
4.5 Delivery and Accessory
The VIADRUS K4 boiler is delivered as assembled on a pallet, packed in a carton cover. Flue gas ducting is
delivered in accordance with the customer requirements based on the actual connection of air inlet and flue gas
outlet (see chapter 11).
The installation shall comply with the regulations that are applicable for this equipment. The boiler shall be
compatible with the local connecting conditions (checking the parameters of the boiler with the information on the
name plate).
During the first start of operation of the boiler it is necessary to instruct the user in accordance with this
manual and to hand over this manual to the user.
Notice:
The ABS boiler cover is protected by a protection foil. This foil needs to be removed before commissioning of the
boiler or 1 month from unpacking the boiler from the packaging carton at the latest. Removing the foil after this
period may be more difficult.
21
User
5 Boiler Attendance by the User
Description of the control panel
In case of normal operation in DHW or CH mode and no error conditions it is always possible to enter the test
mode as the higher priority mode of operation. This implies that there are no error conditions present. If there was
an error condition, test mode can be entered after normal operating conditions are present again.
22
User
OFF mode
K5
This is mode is selected by mean of the push button.
When selected, LCD is indicating:
STAND-BY mode
K5
By mean of push button it possible to select boiler STAND-BY
modes selecting Winter (both DHW and CH modes are enable) or Summer
(only DHW mode is enable) working conditions.
When Winter is selected, an no head demand is present, LCD is indicating:
In case of water pressure switch usage, Supply temperature value is shown rather than water pressure
value/indication (scale).
In STAND-BY mode the fan is off, the gas valve is closed, Supply pump is switched off and the 3WV is in DHW
position.
Burner ignition
In case of valid heat demand request, ignition sequence will be started. In case of failed ignition, controller will try to
reignite for a defined number of times. At the first ignition trial, the burner will ignite with fan speed set by Ignition
fan speed value. As soon as the flame presence is validated, fan speed moves according to the heat demand type.
If no successful ignition after programmed number of retrials, flame lockout error will be indicated.
CH mode
Operation in the CH mode is possible only when Winter is enabled.
CH heat demand can be generated by Room Thermostat SELV input or by OpenTherm control unit. If remote
control is connected and communication is validated, room thermostat input is ignored.
23
User
ON/OFF control (no OTC – no OpenTherm room unit)
Closure of Room Thermostat contact generates an heat demand in CH mode.
Supply pump is switched on.
If a higher priority operating demand is received, the function in progress is stopped to meet this demand.
95
křivka
OTC 30 30
curve
90
85
80
OTC curve
křivka 25 25
teplota
75
point
70
Žádaná
křivka
OTC 20 20
curve
65
CH set
60
OTC curve
křivka 16 16
55
50
OTC curve
křivka 12 12
45
40
OTC curve
křivka 8 8
35
30
křivka
OTC 4 4
curve
25
20
20,0 15,0 10,0 5,0 0 -5,0 -10,0 -15,0 -20,0
Outside temperature [°С]
Fig. №. 9
i K3
By pressing pushbutton twice, it is possible to see following information:
1time PT1000 temperature (solar sensor temperature), if sensor is not connected,
LCD shows ---
2time OTC temperature, if sensor is not connected, LCD shows ---
i K3
Value stays on the LCD for 5 sec. (after releasing push button):
Frost protection
Frost protection is enabled in all the specified operating modes.
Legionella protection
The design of the boiler tank is activated protection against legionella.
24
User
5.2 Lockout condition codes
Lockout condition is given with the capital "E" (error) on the status display and error
code on the temperature display:
Symbols or are being shown only in case of lockout condition which
needs to be solved by Service people or pushing push button.
E01 Lockout signal after no flame and all ignition trials are expired.
This error condition is stopping the boiler and to get to the normal operation again, manual/remote reset is
required.
E02 If flame signal is measured with no heat demand currently present, error 2 is created. This error condition is
stopping the boiler and to get to the normal operation again, manual/remote reset is required.
E03 High limit temperature protection detected on supply or return sensor.
This error condition is stopping the boiler and to get to the normal operation again, manual/remote reset is
required.
E05 Fan driving problem – if the controller doesn’t detect the expected tacho signal from the fan for 1 minute
longer, error will be set. This error condition is stopping the boiler and to get to the normal operation again,
manual/remote reset is required.
E08 Flame circuit failure – The detected flame level is outside expected bounds, meaning a problem on
electronic components.
E09 Feedback error – The valve feedback doesn’t respect controller commands.
E12 The EEPROM check fails. The data in EEPROM are corrupted.
E15 Drift sensors check failed. Manual/remote reset is required.
E16 Stuck_at test on Supply sensor failed. Manual/remote reset is required.
E17 Stuck_at test on Return sensor failed. Manual/remote reset is required.
E18 Crack sensor test failed. Manual/remote reset is required.
E21 Adc failure. The adc test executed at runtime fail, that detect a major fault on electronic components.
E33 Return sensor out of normal operating range (short circuit or open circuit). If NTC sensor goes outdoor the
range (00÷125 °C), error will be generated. In case sensor is back to the normal operating range, lockout
can be cleared by manual/remote reset. In error mode, heat demands will be disabled. In case 2 or more
sensors are broken, controller will pick up the first that was outside the operating range. Resolving situation
can be achieved only if the sensor is within operating range again. The lockout error on this sensor is
necessary because is it used for high limit protection.
E35 Supply sensor out of normal operating range (short circuit or open circuit). If NTC sensor goes outdoor the
range (00÷125 °C), error will be generated. In case sensor is back to the normal operating range, lockout
can be cleared by manual/remote reset. In error mode, heat demands will be disabled. In case 2 or more
sensors are broken, controller will pick up the first that was outside the operating range. Resolving situation
can be achieved only if the sensor is within operating range again. The lockout error on this sensor is
necessary because is it used for high limit protection.
E82 Flame loss. The loss of flame during actual HD is counted and if it reaches a defined number of losses (#3)
error is set. This error condition is stopping the boiler and to get to the normal operation again,
manual/remote reset is required. The counter is cleared if flame is not lost for a defined time (4 minutes) or
the HD is removed.
25
User
5.3 Blocking codes
Temporary blocking condition is given with the capital "F" on the status display and
error code on the temperature display:
The boiler controller recognizes also the fault situations that can block the heat
demands but do not lead to lockout condition. When the error condition becomes
resolved, error will disappear but will be also written into the history data.
Symbols is being shown only in case of lockout condition which needs to be
solved by Service people.
Blocking
Popis
code
F07 Exhaust gases temperature is too high
F13 Remote reset volatile lockout
F34 Low power supply from mains
F37 Water pressure is too low (blocking code is shown alternatively with WP value if WPS is used)
F39 Outdoor sensor error
F40 The water pressure in the CH installation is too high
F41 Water filling (auto) is running
F42 Water filling (auto) not completed
F43 Low water pressure after auto water filling attempts
F47 Water pressure sensor not connected
F50 DHW solar storage tank BOTTOM sensor error (only when DHW configuration is 2 or 4)
F51 PT1000 temperature sensor error (only when DHW configuration is 2 or 4)
F52 DHW water temperature sensor error
F53 Exhaust gases temperature sensor error
F81 Drift test waiting
F07 If the exhaust gases temperature becomes higher than Maximum exhaust gases temperature controller will
stop indicating F07. The blocking timer of 15 minutes is set. If the exhaust temperature is within normal
levels after this time expired, F07 will be resolved by itself. Error can be reset by switching off and on the
power supply if the temperature is back in range.
F13 All the attempts to reset the error remotely, either from OT unit or by button, are wasted. It is a volatile
lockout which disappears after removing supply.
F34 Low Mains voltage (less than 170 VAC) will trigger this error. In case of boiler running, burner is switched
off. When mains brought back (over 170 VAC), error is resolved.
F37 Low water pressure error can be caused by the low water pressure (water pressure lower than Water
pressure low limit or water pressure switch contact opens). In error mode, the heat demand and the supply
pump are switched off. Heat demands are ignored.
Diverting 3WV is moved in CH position (if it is not already there).
Water filling parameter 0 (disable)
Error is self resolved when water pressure value comes back over the Water pressure nominal or water
pressure switch contact is being closed.
Water filling parameter 1 (enable)
By pressing K4 push button, water filling valve is activated for a period of time equal to Water filling timeout.
If during, that period, water pressure value gets higher than the Water pressure nominal or water pressure
switch contact is being closed, error code is cancelled and the water filling valve is switched off.
Otherwise, if at the end of the Water filling timeout, water pressure value is still below the Water pressure
low limit value or water pressure switch contact is still open, error code becomes blinking.
Another manual water filling attempt, is allowed only after a power down (power up) of the main voltage.
F39 Outdoor sensor out of normal operating range (short circuit or open circuit). If NTC sensor goes in short
circuit and this condition lasts for more than 3 seconds, error is generated. In case sensor is back to the
normal operating range, error is gone. Normal operating range for the outdoor sensor is from -40°C till
+50°C. With sensor broken in a way that he makes an open circuit, error will be generated only if a curve is
selected: OTC will be disabled but heating mode will be possible. In case 2 or more sensors are broken,
controller will pick up the first that was outside the operating range. Resolving error situation can be
achieved only if the sensor is within operating range again.
F40 High water pressure error, caused by the water pressure sensor. Water pressure is higher than Water
pressure high limit. In error mode, the heat demand and the pumps are switched off.
F41 – F42 – F43 Water filling (automatic). Auto water filling functionality is disabled if boiler is set in OFF mode.
26
User
F47 Water pressure sensor not connected. In error mode, the heat demand and the pumps are switched off.
Resolving error situation can be achieved only if the sensor is connected again.
F50 DHW sensor out of normal operating range (short circuit or open circuit). If NTC sensor goes outside the
range (-5÷125 °C), error will be generated. In case sensor is back to the normal operating range, error is
gone. In error mode, heat demands will be disabled. In case 2 or more sensors are broken, controller will
pick up the first that was outside the operating range. Resolving situation can be achieved only if the
sensor is within operating range again.
F51 Solar panel sensor (PT1000) out of normal operating range (short circuit or open circuit). If NTC sensor
goes outside the range (-20÷150°C), error will be generated. In case sensor is back to the normal operating
range, error is gone. In error mode, heat demands are not disabled. In case 2 or more sensors are broken,
controller will pick up the first that was outside the operating range. Resolving situation can be achieved
only if the sensor is within operating range again.
F52 DHW sensor out of normal operating range (short circuit or open circuit). If NTC sensor goes outside the
range (-5÷125 °C), error will be generated. In case sensor is back to the normal operating range, error is
gone. In error mode, heat demands will be disabled. In case 2 or more sensors are broken, controller will
pick up the first that was outside the operating range. Resolving situation can be achieved only if the
sensor is within operating range again.
F53 Exhaust sensor out of normal operating range (short circuit or open circuit). If NTC sensor goes outside the
range (-5÷125 °C) and this condition lasts for more than 3 seconds, error will be generated. In case sensor
is back to the normal operating range, error is gone. In error mode, heat demands will be disabled. In case
2 or more sensors are broken, controller will pick up the first that was outside the operating range.
Resolving situation can be achieved only if the sensor is within operating range again.
F81 Drift test waiting. System is waiting for sensor drift test.
27
User
5.5 OpenTherm communication
The OpenTherm remote control is acting as a master and boiler controller is acting as a slave.
means “Inquiry”
means “History”
means “Reset”
28
User
5.6.2 “In” as Inquiry mode
Selecting “In” the display starts with showing i00.
K6 K7
By means of the and push buttons is possible to select the parameters.
K1 K2
Selecting one of these parameters, by means of the and push buttons is possible to see his value (not
flashing; only in case of negative outdoor temperature the value is flashing).
In case of sensors in short circuit or open circuit, the display visualizes: “—“.
Actual Fan Speed is showed always in terms rpm x 10.
Actual Flame Current is showed always in terms of uA/10.
K4
reset reset K4
By pressing push button for 1 second is possible to come back to the “In” list, then by pressing
once again, escape from the Inquiry mode.
K5
By pressing push buttton for 1 second is possible to leave the Installer mode.
If no action has been taken, the display automatically leaves this mode after 2 minutes.
i K3
Inquiry mode can be activated also by mean of push button for 10 sec.
K4
reset reset K4
By pressing push button for 1 second, is possible to come back to the “Hi” list, then by pressing
once again, escape from the History Mode.
K5
By pressing push buttton for 1 second is possible to leave the Installer mode.
If no action has been taken, the display automatically leaves this mode after 2 minutes.
K5
By pressing the push button for 5 seconds longer, is possible to reset all the History information; to
confirm that, the system automatically leave the Installer mode.
29
User
6 Maintenance
Before cleaning always turn off the equipment.
The plastic cover of the product does not require any extensive maintenance. The cover of the boiler can be wiped
off by a dry cloth or by a cloth dipped in a detergent lotion. Never use solvents or abrasive agents for cleaning of
the boiler surface.
While checking the tightness of the gas distribution and the valve connection, it is necessary to be careful
not to wet the coil of the gas valve!
All maintenance can be performed only by the contracted servicing organization trained by the
manufacturer.
The user is obliged to ensure regular inspection of the gas boiler once a year. When these conditions are
not observed, the user cannot claim warranty repairs.
Burner sealing shall be replaced approximately every 2 years of operation or when damaged.
Use only original spare parts approved by the manufacturer in order to ensure safety and long service life
of the boiler.
30
User
7 IMPORTANT NOTICES
Boiler installation and setting can be performed only by a servicing organization trained by the
manufacturer.
The boiler can be used only for the purpose for which it has been designed.
Only adult persons are allowed to operate the boiler in compliance with this manual.
The boiler is not designed for the use by persons (incl. children) whose physical, sensual or mental
disability or lack of experience and knowledge prevent them from a safe use of the appliance unless
they are supervised or if they were not instructed on the use of appliance by a person responsible for
their safety.
Children should be supervised in order to ensure that they do not play with the appliance.
The boiler is fully automatic therefore we do not recommend disconnecting it from electric power.
The boiler is equipped with automatic anti-freezing protection (if electric power is supplied).
It is forbidden to intervene with any secured parts.
No flammable objects can be placed, built or suspended near the boiler and flue gas ducting (a safe
distance of the appliance from flammable materials in the main radiation direction is 50 mm and 10 mm
in other directions).
If any building reconstructions are performed in the close vicinity of the boiler, turn off the boiler with a
sufficient lead time and protect it from polluting.
Avoid cleaning of the boiler by flammable or explosive agents.
In winter (if leaving for a holiday, for instance) it is necessary to ensure the necessary inspection of
functionality of the boiler and the entire heating system in order to avoid possible water freezing
resulting in equipment damage due to some external reasons (such as electricity or heating gas supply
outage, and so on).
The manufacturer recommends the use of antifreeze Alphi 11 manufactured by Fernox or X500
manufactured by Sentinel approved for the Sermeta heat exchangers.
In case of boilers with flue gas exhaust into the surrounding environment through the peripheral
external wall of the building it is necessary to check whether the condensed water from flue gas in the
exhaust basket does not freeze in a frosty weather.
The boiler is fed with 230 V/50 Hz electric power supply.
While checking the tightness of the gas distribution and the valve connection, it is necessary to be
careful not to wet the coil of the gas valve!
In case of fire, extinguish the boilers as electric equipment.
Pay attention to any gas leakage (in case of any suspicion of gas leakage, shut off the gas intake and
ventilate the area - call a service firm). The gas valve under the boiler must always be kept freely
accessible.
It is necessary to avoid combustion air pollution with halogen hydrocarbons (contained, for example,
in sprays, solvents, paints, glues) and with dust.
During assembly, installation and operation of the appliance it is necessary to comply with the
standards that apply in the relevant country of destination.
If you fail to meet these conditions you cannot require guarantee repairs.
31
User
The manufacturer reserves the right for changes performed within the product innovation process which
are not necessarily contained in this manual.
32
Servicing
10 Placement and Installation
10.1 Standards and regulations
The heating system shall be filled with water meeting the requirements of ČSN 07 7401 and especially the
water hardness shall not exceed the required parameters.
Tab. №. 5
Recommended values
Hardness mmol/l 1
2+
Ca mmol/l 0,3
Concentration of total Fe + Mn mg/l (0.3)*
*) recommended value
a) to the heating system
ČSN 06 0310 Heating systems in buildings – Designing and installation
ČSN 06 0830 Heating systems in buildings – protecting device
ČSN 07 7401 Water and steam for thermal energy equipments with working pressure up to 8 MPa.
EN 15502-2-1 Gas-fired central heating boilers. Specific standard for type C appliances and type B2,
B3 and B5 appliances of a nominal heat input not exceeding 1 000 kW
EN 677 Gas – fired central heating boilers – Specific requirements for condensing boilers with
a nominal heat input not exceeding 70 kW
b) to the chimney
ČSN 73 4201 Chimneys and flue gas ducting– designing, implementation and connection of fuel
consumers.
c) regarding the fire regulations
ČSN 06 1008 Fire safety of heat installations.
EN 13501-1 +A1 Fire classification of construction products and building elements – Part 1:
Classification using test data from reaction to fire tests
d) to the system of HWS heating
ČSN 06 0320 Heating systems in buildings – Hot water preparation – Designing and planning
ČSN 06 0830 Heating systems in buildings – Safety devices.
ČSN 75 5409 Water installations inside buildings.
e) regarding the electric network
CSN 33 0165 Electrical regulations. Identification of conductors by colours or numerals. Procedure
provisions
ČSN 33 1500 Electrical regulations; revision of electrical equipments
ČSN 33 2000-1 ed. 2 Low-voltage electrical installations – Part 1: Fundamental principles, assessment of
general characteristics, definitions.
ČSN 33 2000-4-41 ed. 2 Low voltage electrical installations - Part 4- 41: Protection for safety - Protection
against electric shock
ČSN 33 2000-5-51 ed. 3 Electrical installations of buildings – Part 5-51: Selection and erection of electrical
equipment – Common rules
ČSN 33 2000-7-703 ed.2 Electrical installations in buildings - Part 7-703: Single-purpose equipment and
equipment in special buildings - Rooms and cabins with sauna stoves.
ČSN 33 2130 ed. 2 Low-voltage electrical installations – Internal electric distribution lines
ČSN 33 2180 Electrical regulations: Connection of electric instruments and appliances
ČSN 34 0350 ed. 2 Safety requirements for flexibile cords and cables
EN 60079-10-1 Explosive atmospheres — Part 10-1: Classification of areas — Explosive gas
atmospheres
EN 60079-14 ed.3 Explosive atmospheres - Part 14: Electrical installations design, selection and erection
EN 60252-1 ed. 2 Capacitors for AC motors – Part 1: In general – Design, testing, dimensioning – Safety
requirements – Instructions for installation and operation.
EN 60 335-1 ed.2 Electric appliances for household and similar purposes – Safety – Part 1: General
requirements
EN 60 335-2-102 Electric appliances for household and similar purposes – Safety – Part 2-102: Special
demands on appliances containing the electric connections and burning the gas, oil
and solid fuels
EN 60445 ed. 4 Basic and safety principles for man-machine interface, marking and identification –
Identification of equipment terminals, conductor terminations and conductors
f) to the gas distribution
33
Servicing
EN 1775 Gas supply. Gas pipework for buildings. Maximum operating pressure less than or
equal to 5 bar. Functional recommendations
EN 12007-1 Gas supply systems - Pipelines for maximum operating pressure up to and including
16 bar - Part 1: General functional recommendations
EN 12007-2 Gas supply systems - Pipelines for maximum operating pressure up to and including
16 bar - Part 2: Specific functional recommendations for polyethylene (MOP up to and
including 10 bar)
EN 12007-3 Pipelines for maximum operating pressure up to and including 16 bar - Part 3: Specific
functional recommendations for steel
EN 12007-4 Gas supply systems - Pipelines for maximum operating pressure up to and including
16 bar - Part 4: Specific functional recommendations for renovation
ČSN 07 0703 Boiler room with gas fuel –operated equipments
ČSN 38 6405 Gas equipments. Operating principles
EN 15001-1 Gas supply systems Pipelines for operating pressure greater than 0,5 bar for industrial
use and pipelines for operating pressure greater than 5 bar for industrial and non-
industrial use - Part 1: Detailed functional requirements for design, materials,
construction, inspection and testing
Act No. 458/2000 Coll. on Business Conditions and Public Administration in the Energy Sectors and on
amending certain acts (the Energy Act)
34
Servicing
Placement of the boiler with respect to fire regulations:
A safe distance from flammable materials:
− when installing and operating the boiler it is necessary to keep a safe distance of 200 mm from the materials
of combustibility grade A1, A2, B and C (D);
− for easily combustible materials of combustibility grade E (F), which quickly burn and burn themselves even
after removal of ignition source (such as paper, cardboard, asphalt and tar paper, wood and woodfiber boards,
plastics, floor coverings) the safe distance has to be doubled, i.e. to 400 mm;
− safe distance should be doubled also where the grade of reaction to fire has not been proved.
A safe distance from surfaces of materials with individual degrees of flammability and information of the
flammability degree of common building materials, if necessary, for appliances which can be operated in the
immediate vicinity of walls made of flammable materials will be defined with the maximum permissible
temperatures of surface or wall temperature increase according to ČSN EN 13 501 – 1 + A1.
35
Servicing
NOTICE: The manufacturer recommends installing water filter to the heating system.
Fig. №. 13 VIADRUS K4G1HXXXX –Connections of the boiler with a flow type heater, bottom view of the
boiler
Fig. №. 14 VIADRUS K4G1HXXXX – Connections of the boiler with a reservoir type heater, bottom view of
the boiler
36
Servicing
10.4 Connecting to the Heating System and Water Filling
Water for filling the boiler and the heating system must be clear and colorless, with no suspended substances, oil
and chemically aggressive substances. The parameters of circulation and refilling water shall meet tab. no. 3.
When the water hardness does not meet the required parameters, it shall be treated accordingly. Several times
reheated water with a higher hardness does not prevent precipitation of salts on the walls of the boiler body. The
precipitation of limestone decreases the heat transfer from metal to water at the particular point by 10 %.
During the heating season it is necessary to keep a constant volume of heating water in the heating system and be
particular about bleeding the heating system. The water from the boiler and the heating system shall never be
discharged or taken for some other use except in cases of emergency like repairs etc. Draining of the heating water
and filling new water increases the danger of corrosion and scaling. If it is necessary to refill water into the
heating system, then add water only when the boiler is cold.
When adding water to the boiler, the system shall be disconnected from electric power supply. The bleeding valve
on the boiler and on the heating system shall be functional and open. Adjust the expansion reservoir to a pressure
which is higher by 10 kPa than the required pressure in the heating system. The system will be pressurized to the
required pressure of approx. 100 kPa and it will be vented again. We recommend using the filter on the inlet to the
heating system for water filling.
The heating system shall have a sufficient number of venting points. The lowest point of the heating system shall
be equipped with a drain valve.
37
Servicing
10.9 Boiler Electrical Wiring
10.9.1 Main components of boiler electrical equipment exchanger ISOTHERMIC
3+1 - K4GXH24XX
Outside sensor 10 kΩ 4+1 - K4GXH33XX
flue gas
THERMOSTAT temperature sensor
Opentherm
thermostat exchanger sensor
NEXSYS S4962V3224
sensor TV 10 kΩ emergency
(option K4G 3) thermostat
combination
electrode
Venturi tube
45900444B - 003B - K4GXH24XX
45900444B - 002B - K4GXH33XX
Fig. №. 15
38
Servicing
10.9.3 Connecting terminal
VIADRUS K4G1HXXXX with heating of water for the system only
Connection of the connection terminal of the boiler without a parent control (boiler standard supply):
X201.2
B9 Outdoor sensor
X201.2
Fig. №. 17
39
Servicing
VIADRUS K4G2HXXXX with through-flow heater
Connection of the connection terminal of the boiler without a parent control (boiler standard supply):
X201.2
X201.2
Fig. №. 18
40
Servicing
VIADRUS K4G3HXXXX in the boiler option
Connection of the connection terminal of the boiler without a parent control (boiler standard supply):
X201.2
X201.2
X201.2
Fig. №. 19
41
Servicing
42
LEGEND:
A1 CONTROL BOARD WITH LCD SCREEN BT SAFETY THERMOSTAT
A6 ROOM INSTRUMENT OPENTHERM BT1 EXCHANGER THERMAL FUSE
B2 HEATING WATER SENSOR BTr ROOM THERMOSTAT
B3 HOT WATER SENSOR MV1 FAN
B7 RETURN WATER SENSOR PS1 WATER PRESSURE SENSOR
B8 FLUE GAS SENSOR P2 HW FLOW SENSOR
B9 EXTERNAL SENSOR Q1 PUMP
Y100 GAS VALVE
Servicing
bk black
bu blue
bn brown
rd red
wh white
vt purple
og orange
ye yellow
gn green
gnye green-yellow
43
Servicing
LEGEND:
44
Q1 PUMP
Y100 GAS VALVE
gnye green-yellow
Y3 THREE-WAY VALVE
X60 MV1 fan power connector
X61 Q1 pump power connector
X101 Euro connector – the boiler power supply
X110 bonding connector
Servicing
45
Servicing
11 Flue Gas Ducting
According to the means of flue gas removal and combustion air inlet the boiler version is classified as C. this
means a close appliance that takes the combustion air from the outside space or from a joint shaft and from which
the flue gases are removed into the outside space or to a joint shaft. The shaft is represented by a structural part of
the building, e.g., a chimney, a duct, etc. The combustion area and the flue gas ducts of the appliance are
separated in a gas-tight way from the area in which the appliance is located.
In the standard version the boiler is supplied with an air flange. The boiler flue gas exhaust is not a part of the boiler
delivery. It is necessary to maintain a 3 % inclination to the boiler. The pressure loss for the flue gas exhaust shall
not exceed 150 Pa. The total pressure loss is the sum total of individual losses of the parts described in this
chapter.
The boiler shall only be installed together with wind protective equipment which meets the requirements of EN
1856-1 (See Annex N). For removal of flue gases through the roof it is necessary to use a concentric chimney
piece.
The boiler shall be installed together with the necessary accessories (pipeline for the combustion air supply and
flue gas exhaust).
The approved and recommended flue ducting versions for the VIADRUS K4 boiler made by ALMEVA are as
follows:
• Star D80mm
• Flex D80 mm
• LIK 60/100 mm
• LIK 80/125 mm
The recommended flue ducting can be ordered together with the boiler.
46
Servicing
The boiler in version C is specified in more detail by a two digit number:
- The first digit in the index refers to the possible boiler installation with regard to the way of combustion air inlet
and flue gas removal,
- The second digit in the index refers to the application and positioning of the built-in fan in the boiler. VIADRUS
K4 is a boiler with a fan that is built-in before the combustion chamber/heat exchanger (boiler body) and is
marked with „3“, the second digit in the index
Version C1
A boiler in version C whose ducting is connected to the protection inlet installed horizontally either on the outside
peripheral wall or on the roof of the building. Terminal outlets of these ducts are either concentric or they are
located so close one to the other that they are subject to the same climatic conditions.
Outlet openings of the terminated separate ducts for supply of the combustion air and for removal of flue gases
shall be located inside a square with a side of 50 cm.
The wind protection equipment can be placed on the wall and/or the roof depending on the installation.
Version C3
A boiler in version C whose ducting is connected to the protection inlet installed vertically. Terminal outlets of these
ducts are either concentric or they are located so close one to the other that they are subject to the same climatic
conditions.
Outlet openings of the terminated separate ducts for supply of the combustion air and for removal of flue gases
shall be located inside a square with a side of 50 cm and the distance between the planes of two openings shall be
lower than 50 cm.
Version C4
A boiler in version C whose ducting or adapter is connected to the joint shaft. Terminal outlets of these ducts are
either concentric or they are located so close one to the other that they are subject to the same climatic conditions.
The boiler shall be installed with the shortest possible length of the ducts for supply of the combustion air and for
removal of flue gases. By its suction effect used for ducting for removal of flue gases the boiler shall not create
negative pressure of 50 Pa. This connection can be implemented using the systems made by ALMEVA.
Version C5
The wind protection equipment on ducts for supply of the combustion air and for removal of flue gases shall not be
placed on the opposite walls of building.
Version C8
A boiler in version C whose ducting or adapter is connected on the air supply side to the protection inlet and on the
flue gas removal side to a separate or joint chimney.
The chimney shall be equipped with a special lining designed for the condensing boilers and a condensate outlet
from the chimney.
For the VIADRUS K4 boiler it is possible to use a plastic lining with temperature resistance 120 °C made e.g. by
ALMEVA.
The boiler shall only be installed together with wind protective equipment which meets the requirements of EN
1856-1 (See Annex N).
In case of using of the fuming system consisted of a small vertical chimney, going through the cold roof, it
is necessary to buy additionally LIK condensate diverter (60/100 - LPKFK5, code for ordering 20 175 or
80/125 - LPKFK8, code for ordering 20 176), which collects condensed water incurred on the surface of the
small vertical chimney.
Design of flue gas ducting and air supply ducts, including their lengths, shall be made by the designer in
the technical documentation on the basis of design documentation provided by VIADRUS.
Note: The quantity of the components for the individual version types depends on the placement of the
boiler.
47
Servicing
11.1 Flue gas ducting – examples of correct connection of flue duct and air supply
Fig. №. 25
11.2 Flue gas ducting – examples of incorrect connection of flue duct and air supply
Fig. №. 26
1 reducing insert
2 transition piece
3 flue gas exhaust, measuring piece
4 air intake pipe
In case of using the flue gas exhaust with the diameter of 60/100 mm it is
necessary to use reducing insert of the exchanger. In case of using the flue
gas exhaust with the diameter of 80/125 mm, this insert must be removed
from the exchanger.
Fig. №. 27
48
Servicing
11.3.1 STARR, 2 x D 80 mm flue ducting diagram
Rain-protection collar
Inspection T-piece
Inspection door
Inspection T-piece
Elbow 45°
Fig. №. 28
49
Servicing
11.3.2 FLEX, 2 x D 80 mm flue ducting diagram
Rain-protection collar
Inspection T-piece
flex/starr
Adapter starr/flex
Adaptor
starr/flex 87°
Inspection
T-piece with
drainage and
change of
direction - flex
Long John
siphon (for
overpressure)
Fig. №. 29
50
Servicing
11.4 LIK 60/100, 80/125 system connection
4 measuring piece
5 blinding plug D80
8 exchanger reducer piece
51
Servicing
11.4.1 Diagram for flue gas ducting of the LIK type, version 60/100 mm (max. length 5 m),
or 80/125
Fig. №. 30
Design of flue gas ducting and air supply ducts, including their lengths, shall be made by the designer in
the technical documentation.
Note: The quantity of the components for the individual version types depends on the placement of the
boiler.
52
Servicing
11.5 Pressure Losses of Chimney Flue Elements in Case of VIADRUS K4 Boiler Usage
53
Servicing
12 Commissioning
The entire installation shall comply with the regulations that are applicable for this equipment. The boiler shall be
compatible with the local connecting conditions (checking the parameters of the boiler with the information on the
name plate). The boiler can only be commissioned by organizations that are authorized and trained for this
purpose by the manufacturer. The minimum pressure in the heating system is 0,8 bar. It is necessary to open all
closing valves and make sure that no gas is leaking. Connect the boiler to the electric power mains. Check the gas
distribution line after the gas valve. Check the safety valve function. Then check the pump operation. During the
operation of the boiler it is necessary to check removal of the condensate from the boiler and also from the
chimney lining, if applicable.
During the first start of operation of the boiler it is necessary to train the user in accordance with this
manual and to hand over this manual to the user.
Then it is necessary to perform:
- inspection revision before commissioning,
- inspection for any water leakages,
- inspection of instrumentation and safety controls.
54
Servicing
12.1 Instructions before Putting into Operation
Expansion tank filling valve. Pressure in the expansion tank shall be set
according to the heating system designing documentation. Pressure in the
expansion tank shall be checked during the regular annual servicing
inspection.
The minimum water pressure in the heating system is 0.8 bar, max.
operating pressure is 2,5 bar. When filling and bleeding the system the
pressure in the heating system needs to be adjusted according to the
designing documentation.
55
Servicing
12.2 Boiler Setting
Boiler emissions:
Natural gas: Propane:
CO2 – minimum boiler output CO2 value – 8,5 % CO2 – minimum boiler output CO2 value – 9,5 %
– nominal boiler output CO2 value – 8,5 % – nominal boiler output CO2 value – 9,5 %
When the set parameters do not correspond with the values shown above follow the instructions in the
Servicing Manual.
K1 K2
By pressing and push button for 10 seconds, is possible
to enter the chimney-sweeper function.
K2
By long pressing push button the fan speed slows down to a
minimum (x10).
Can adjust burning at minimum performance.
K2 K1
Operate (decrease) and (increase) pushbuttons to
adjust fan speed.
reset K4
By pressing push button to exit the chimney-sweeper
function.
56
Servicing
1. Venturi tube
2. Clamp
3. Diaphragm
4. Ring
5. Gas supply
6. Gas valve
Note 3: Sealing
Note 5: Gas valve
57
Servicing
12.4 Boiler Electronics Setting
Setting parameters
The product meets the values for “Environment Friendly Product”.
Note: The actual values measured depend on the type of connection of the combustion air supply and flue gas
removal for the given appliance.
Setting Setting
Parameter
K4G2H24P.
K4G3H24P.
K4G1H24Z.
K4G2H24Z.
K4G3H24Z.
K4G1H24P
Renge
Name
Unit
P00 DHW configuration 1= Instantaneous
2= Instantaneous + Solar
3= Storage tank num. 5 1 3 5 1 3
4= Solar storage tank
5= CH only
P01 Gas type 0=Natural
num. 0 0 0 1 1 1
1=LPG
P02 Ignition fan speed
175-675 rpm/min x 10 400 400 400 400 400 400
P03 Water filling 0= Enable
1= Disable num. 0 0 0 0 0 0
2=Auto
P04 DHW user set point max. 30-65 °C x 65 65 x 65 65
P05 DHW maximum fan speed 175-675 rpm/min x 10 x 675 675 x 675 675
P06 DHW minimum fan speed 175-675 rpm/min x 10 x 175 175 x 175 175
P07 DHW pump overrun time 0 - 255 min. x 1 1 x 1 1
P08 DHW frost protection ON 0 - 50 °C x 8 8 x 8 8
P09 DHW frost protection OFF 0 - 50 °C x 35 35 x 35 35
P10 DHW heat demand type 0=sensor
num. x x 0 x 0 x
1=thermostat
P11 DHW antilegionella set
0 - 70 °C x x 70 x 70 x
point
P12 DHW antilegionella timeout 1-7 day x x 7 x x 7
P13 Supply temperature delta 0 - 20 °C x x 5 x x 5
P14 Maximum supply
0 - 90 °C x x 85 x x 85
temperature
P15 Solar enable temperature 5 - 20 °C x x x x x x
P16 Solar disable temperature 5 - 20 °C x x x x x x
P17 Solar pump min. running
0 - 120 sec. x x x x x x
time
P18 Solar limit temperature 100 - 150 °C x x x x x x
P19 Solar storage tank limit
50 - 100 °C x x x x x x
temperature
P20 Solar mode functionality 0= 0=solar priority
num. x x x x x x
1= parallel
P21 Heat demand delay after
0 - 60 sec. x x x x x x
Solar pump activation
P22 Delta for virtual DHW user
0 - 30 °C x x x x x x
set point
P23 CH user set point
20 - 90 °C 80 80 80 80 80 80
maximum
P24 CH maximum fan speed 175 - 675 rpm/min x 10 675 675 675 675 675 675
P25 CH minimum fan speed 175 - 675 rpm/min x 10 175 175 175 175 175 175
58
Servicing
Setting Setting
Parameter
K4G2H24P.
K4G3H24P.
K4G1H24Z.
K4G2H24Z.
K4G3H24Z.
K4G1H24P
Renge
Name
Unit
P26 CH OFF time 0 - 10 min. 1 1 1 1 1 1
P27 CH pump overrun timer 0 - 255 min. 3 3 3 3 3 3
P28 CH pump 0= Continuous
num. 0 0 0 0 0 0
1= Overrun
P29 CH minimum time 0-5 min. 1 1 1 1 1 1
P30 CH slope rate 0-60 °C/min. 4 4 4 4 4 4
P31 CH frost protection ON 0 - 10 °C 5 5 5 5 5 5
P32 CH frost protection OFF 0 - 10 °C 10 10 10 10 10 10
P33 OTC curve selection 0 - 30 num. 0 0 0 0 0 0
P34 Supply for CH thermostatic
0 - 100 °C 80 80 80 80 80 80
pump overrun OFF
P35 Supply for CH thermostatic
0 - 100 °C 85 85 85 85 85 85
pump overrun ON
P36 System configuration Bit x: cleared / set
num. 4 4 4 4 4 4
Bit 2: WP switch / sensor
P37 DHW request type 0= Fugas Flow sensor
1= Bitron Flow sensor
2= Kramer Flow sensor
num. x 3 x x 3 x
3= Flow switch
2= Honeywell Flow
sensor
Setting Setting
Parameter
K4G2H33P.
K4G3H33P.
K4G1H33Z.
K4G2H33Z.
K4G3H33Z.
K4G1H33P
Renge
Name
Unit
K4G2H33P.
K4G3H33P.
K4G1H33Z.
K4G2H33Z.
K4G3H33Z.
K4G1H33P
Renge
Name
Unit
P16 Solar disable temperature 5 - 20 °C x x x x x x
P17 Solar pump min. running
0 - 120 sec. x x x x x x
time
P18 Solar limit temperature 100 - 150 °C x x x x x x
P19 Solar storage tank limit
50 - 100 °C x x x x x x
temperature
P20 Solar mode functionality 0= 0=solar priority
num. x x x x x x
1= parallel
P21 Heat demand delay after
0 - 60 sec. x x x x x x
Solar pump activation
P22 Delta for virtual DHW user
0 - 30 °C x x x x x x
set point
P23 CH user set point
20 - 90 °C 80 80 80 80 80 80
maximum
P24 CH maximum fan speed 150-635 rpm/min x 10 635 635 635 635 635 635
P25 CH minimum fan speed 150-635 rpm/min x 10 150 150 150 150 150 150
P26 CH OFF time 0 - 10 min. 1 1 1 1 1 1
P27 CH pump overrun timer 0 - 255 min. 3 3 3 3 3 3
P28 CH pump 0= Continuous
num. 0 0 0 0 0 0
1= Overrun
P29 CH minimum time 0-5 min. 1 1 1 1 1 1
P30 CH slope rate 0-60 °C/min. 4 4 4 4 4 4
P31 CH frost protection ON 0 - 10 °C 5 5 5 5 5 5
P32 CH frost protection OFF 0 - 10 °C 10 10 10 10 10 10
P33 OTC curve selection 0 - 30 num. 0 0 0 0 0 0
P34 Supply for CH thermostatic
0 - 100 °C 80 80 80 80 80 80
pump overrun OFF
P35 Supply for CH thermostatic
0 - 100 °C 85 85 85 85 85 85
pump overrun ON
P36 System configuration Bit x: cleared / set
num. 4 4 4 4 4 4
Bit 2: WP switch / sensor
P37 DHW request type 0= Fugas Flow sensor
1= Bitron Flow sensor
2= Kramer Flow sensor
num. x 3 x x 3 x
3= Flow switch
2= Honeywell Flow
sensor
60
Servicing
The instructions for the servicing inspection procedure is available for servicing organizations.
Attention: Before you remove the boiler casing, disconnect the boiler from the electric supply.
61
Servicing
Information for customer
Packaging identification Assessment reference
NOTE Conformity with EN 13427 requires affirmative responses to sections 1.1; 1.2; 1.3 and to at
least one of 3.1; 3.2; 3.3. In addition, where a claim of reuse is made section 2 should also
record affirmative responses.
62
Servicing
RECORD OF THE BOILER COMMISSIONING
This side is used to confirm the inspection service and is kept by the customer!!!
63
Annex to the Warranty Certificate for the Customer – User
A record of warranty and after-warranty repairs and regular annual product inspections performed
Contracted service
Date of Customer’s
Activity performed organization
entry signature
(signature, stamp)
64
VIADRUS K4
VIADRUS a.s.
Bezručova 300 | CZ - 735 81 Bohumín
E-mail: info@viadrus.cz | www.viadrus.cz