Professional Documents
Culture Documents
154 en Catalog0
154 en Catalog0
CATALOGUE
CONTENT
2
ABOUT US
5
DISMOD IN≤5000A LOW VOLTAGE
POWER DISTRIBUTION AND
MOTOR CONTROL SWITCHBOARD
21
400/230 VAC AND 48...220 DC
AUXILIARY SERVICES SUPPLY CABINETS
27
CONTROL, SIGNALLING AND
PROTECTION PANELS FOR
110/20(6) kV POWER STATIONS
1
About us
Evolving year by year as a team relied on
passion and trust as fundamental values, we
succeeded to show that, based on the high
technical level of our products, we can develop
the best solution to our customer’s requests.
Our constant focus for quality Electroalfa is a well known Electroalfa means today 10
made us keep in close plan first-class solutions provider divisions, 10 sales representatives,
for electrical power distribution 4 workshops, 3 modern factories
the improvement of facilities, with 20 years of experience and a strong brand based on solid
technical equipment and in field. experience, qualifications and
other specific endowments of enthusiasm of 350 specialists.
our activity. The company manufactures
low and medium voltage
distribution equipment for
electrical power systems, and also
steel manufacturing parts.
2 ABOUT US
We are not just quality equipment producer
and supplier, which offers safety, comfort and
ease in use, but we are long-term partners for
our clients.
The desire for producing high We also hold: • Romanian Railway authority
level products, in line with the (AFER), Romanian Civil
last technical improvements made • The National Commission for Aeronautical Autority (CAA) and
Electroalfa to implement and Nuclear Activities Control Romanian Naval Authority (ANR)
keep up to date an Integrated (CNCAN) authorization for authorized;
Management system, which manufacturing on the nuclear • authorized by Agriculture, Forests
meets SR EN ISO 9001:2008, SR field; and Rural Development Ministry
EN ISO 14001:2005, SR OHSAS • National Authority for Energy for land improvement activities
18001:2008, SR ISO/CEI Regulation (ANRE) A, B, C1B, (building and installation works);
27001:2006 and SA 8000:2008, C2B, E1, E2, F in energy field • approval from Constructions
standard requirements, system certification; Technical Council of the Transport,
which has been evaluated and • Accept as agreed supplier for Constructions and Tourism
certified by SRAC CERT Bucuresti, Transelectrica, Electrica and E-on Ministry.
respectively IQNet (SA 8000). Moldova;
Based on a strong research activity, we provide innovative, safety, high quality products and services
for our clients. Electroalfa spirit gives life to each product.
Product portfolio
Low voltage business unit
Low Voltage Business Unit We establish long-term action
provides for the customers plans with daring objectives, which
are carefully coordinated and
a full range of main and implemented by personnel with a
secondary distribution long experience in electrical field.
switchboards up to 5.000A
(Power Center and Motor The relationships with our partners
are the human expression of the
Control Center), DISMOD
technical solutions proposed.
type, auxiliary services AC
and DC cabinets, industrial For putting into work of our plans
automation and control we have developed partnerships
switchboards, protection, with the most important companies
working on the electrical
signalling, control and installations field.
automation panels for
110/20(6) kV power stations.
ABOUT US 3
DISMOD IN≤5000A LOW VOLTAGE
POWER DISTRIBUTION AND MOTOR
CONTROL SWITCHBOARD
• PCC&MCC, In≤5000A
Low voltage distribution
switchboard
5
DISMOD-T3 In≤5000A
Low voltage distribution board
DISMOD-T3 is the newest and most performing product of
DISMOD family; represents the optimal solution for a wide range
of low voltage applications in energy, infrastructure, industry and
buildings.
General presentation
DISMOD-T3 distribution board
generation represents a new
concept offering solutions in
power distribution, automation
and centralised motors control
for a wide range of application
within the following fields: energy,
infrastructure, industry, buildings.
Technical data
Installation indoor
Ambient temperature for operation −5°C...+40°C
Ambient humidity maximum 50% la +40°C
Ambient temperature during transport and storage –25°C...+55°C, maximum +70°C, for 24 h
Degree of pollution 3
Overvoltage category III
Operational altitude maximum 2000m above sea level
Electromagnetic environments Type A
Electric characteristics
Rated voltage (Ue) maximum 690V (*)
Rated insulation voltage (Ui) 1000V
Rated impulse withstand voltage (Uimp) 8kV
Rated frequency 50/60Hz (*)
Rated currents (In)
• main busbars 5000A
• distribution busbars 700/1000/1500A
Rated short-time withstand current (Icw/1s)
• main busbar 100kA
• distribution busbar 65kA
Peak current (Ipk)
• main busbars 220kA
• distribution busbars 143kA
Rated diversity factor 1
RInternal arc withstand current 80kA/0,3sec
(*)
conditioned values by the specific electric equipment for each application.
300
7. Main busbar riser column – – – 700; 900
400
500
600
700
Various applications column
8. 800 700; 900
900
– 1000 1000 –
– 1200 1200 –
(*)
Depth D=700mm is valid for In≤2500A and depth D=900mm is valid for In>2500A.
Technical data
Installation indoor
Ambient air temperature • operation −5°C...+40°C
• storage –25°C...+55°C, maximum +70°C, for 24 h
Relative humidity maximum 50% up to +40°C, non condensing
Degree of pollution 3
Overvoltage category III
Altitude maxim 2000m
Electromagnetic environment Type A
Electric characteristics
Rated voltage (Ue) maximum 690V (*)
Rated insulation voltage (Ui) 1000V
TRated impulse withstand voltage (Uimp) 8kV
Rated frequency 50/60Hz (*)
Rated current (In)
• main busbars 3200A
• distribution busbars 630/1000/1500A
Rated peak current (Ipk)
• main busbars 176kA
• distribution busbars 105kA
Protection of persons against internal arcs 80kA/0,3sec
(*)
conditioned values by the specific electric equipment for each application.
Cubicle architecture
The column represents the basic unit of
any DISMOD switchboard. Regardless of
application, columns are divided into 4
fully partitioned zones:
Withdrawable drawer
• the device(devices) is mounted
on a mobile metallic frame called
“drawer”;
• the drawer has 4 functional
positions:
• working position “plug-in”;
• testing position “test”;
• cut-off position “draw-out”;
• “withdrawn” position;
• pre-triggering and blocking
procedures may be foreseen.
Drawer S2
• distribution (feeder): maximum
630A
• motor starters:
• direct-on-line (DOL): maximum
Fig. 1
Fig. 4 200 kW
“PLUG-IN” position • direct-on-line and reversing
• Power and auxiliary circuit are “WITHDRAWN” position (DOL-REV): maximum 90 kW
connected; This position can be reached • star-delta starter (SD): maximum
• Drawer is mechanically blocked. from ‘Test’ position by pressing 75 Kw
simultaneously the buttons on the • applications in special
Status indicator (2) is in ‘I’ position. drawer handles (position 4). configurations with In ≤ 630A
If required, the drawer may be
mechanically blocked in the Drawer S3
‘Withdrawn’ position, this option • distribution (feeder): maximum
providing the following advantages: 630A
• visible signalling of the drawers • motor starters
which are currently in this • direct-on-line (DOL): maximum
position; 250 kW
• avoiding possible accidents at • star-delta starter (SD): maximum
work due to incomplete 110 Kw
withdrawal of the drawer, • applications in special
Fig. 2 combined with its significant configurations with In ≤ 630A
“TEST” position weight;
• Power circuit is disconnected; • missing space for withdrawn
• Auxiliary circuit remains drawers storage. Note: Motor starters from above are for:
• utilization category AC-3;
connected; • rated voltage 400-415V/50 Hz;
• Drawer is mechanically blocked. • type 2 coordination.
L (mm)
Pos. Type H (mm) A (mm)
L1 L2
I. “Feeder”, “Busbar Coupler” Section
1. 600 –
2. B 700 –
3. 800 –
II. “Outgoing” Section 2.300 1.100
1. – 400
C
2. – 500
III. “Busbar Return” Section
1. A 300
21
400/230 VAC and 48...220 VDC auxiliary
services supply cabinets
DC own consumers:
• protection devices;
• automation units;
• interlocks;
• metering, measuring and
signalling devices;
• remote terminal units;
• emergency lighting.
22 AUXILIARY SERVICES SUPPLY CABINETS FOR 400/230 VAC AND 48...220 VDC
Functionalities Measured parameters can be Cabinet architecture
transmitted to other control centres,
AC/DC auxiliary services supply using convertors (transducers) with • usually, AC/DC auxiliary services
cabinet provides the following 4…20 mA unified signal or through supply cabinets are realized in
functions: communication network (Modbus, one or more associated steel
Profibus or other transmission enclosures with transparent doors,
• main busbar connection to protocols). allowing visual access of the
power suppllies (auxiliary service equipment without opening the
transformers, AC generators, door.
baterries and rectifiers); • equipments are mounted on
• loads connection to distribution a mounting plate located in the
busbar; backside of the enclosure, access
• overload and short-circuit being possible from the front side
protection for busbar and loads; of the cabinet.
• metering of electrical parameters • on request and according to the
(current, voltage) for incoming application type, equipments can
supply and busbar system; be mounted on both sides of the
• local and remote control for mounting panel. In these cases
connection; front/rear access is provided.
• automatic source changeover for • metering devices, control and
AC auxiliary services supply signalling equipments are
cabinets; Cabinet presentation mounted on dedicated hinged
• working status signalization; front plates located in the upper
• safety of operators; • one or more steel enclosures part of the cabinet.
• circuits testing. with transparent doors, with • the cable entry is done through
front or front/rear access (by the lower side of the cabinet,
For AC services cabinets, the request). through dedicated gland plates.
following measurements and • distribution system made with On request, the cable access is
signalling can be provided: copper bars and fixed busbar possible through the top part of
supports, located in the top part the cabinet.
• busbar voltage; of the cabinet, protected against • switchboard lighting, opening,
• frequency and power factor direct contact. 16A/230V a.c. outlet, heating
metering; • withdrawable circuit breakers element with thermal control are
• measurement of active/reactive for incoming feeders (from provided as standard.
energy of incoming supply; transformers or rectifiers/ • the cabinets are floor mounting
• current/ voltage measurements on batteries), with auxiliary contact type; 100mm or 200mm high
loads circuits; for open/close/tripped signalling, plinths are available.
• automatic source changeover of with manual or remote control. • Romanian language labelling
power supplies; • circuit breakers for outgoings (other languages on request) is
• circuit breakers status signalling fixed or withdrawable (most provided.
(position, fault) for incoming and common case), with auxiliary • RAL 7035 powder paint colour
outgoing circuits. contacts. finishing.
• metering devices: ammeter,
For DC services cabinets, the voltmeter, power factor meter,
following measurements and frequency meter, etc.
signalling can be provided: • insulation fault detectors.
• local control and signalling
• busbar voltage metering; equipment’s: pushbuttons,
• battery (or rectifiers) currents lamps, position indicators.
measuring; • connection terminals for
• busbar insulation fault detection; power and control and signalling
• no voltage, undervoltage and circuits.
overvoltage signalling;
• battery status (insulation, voltage
level, charging current, capacity);
• circuit breakers status signalling
(position, fault) for incoming and
outgoing circuits.
AUXILIARY SERVICES SUPPLY CABINETS FOR 400/230 VAC AND 48...220 VDC 23
Technical Data
AC services supply cabinets
Rated voltage (Ue) 400/230V
Rated insulation voltage (Ui) 690V
Rated frequency (fn) 50Hz
Rated impulse voltage (Uimp) 8kV
Rated current (In) maximum 630A
Rated short-time withstand current (Icw/1s) 25kA
Rated peak withstand current (Ipk) 52,5kA
Operating conditions
Environment type WDr/CT (moderate climate: dry hot/ cold temperate)
Installation indoor
Operating temperature -10°C…+40°C
Transport, storage temperature -40°C…+55°C
Humidity 50% la +40°C, 90% la +20°C
Maximum operating altitude 2000m
Degree of pollution 3
Overvoltage category III
Electromagnetic environments Type A
Protection degree IP43
24 AUXILIARY SERVICES SUPPLY CABINETS FOR 400/230 VAC AND 48...220 VDC
400/230 V a.c. own services customers 400/230 V a.c. own services customers
SECTION OF BUS BAR 1 SECTION OF BUS BAR 2
220 V d.c. own services customers 220 V d.c. own services customers
SECTION OF BUS BAR 1 SECTION OF BUS BAR 2
AUXILIARY SERVICES SUPPLY CABINETS FOR 400/230 VAC AND 48...220 VDC 25
CONTROL, SIGNALLING AND PROTECTION
PANELS FOR 110/20(6)Kv
POWER STATIONS
27
Control, signalling and protection panels
for 110/20(6)kv power stations
Mounting conditions
Installation indoor
Ambient temperature during operation -5÷40°C
Ambient temperature during transport,
-25÷50°C
storage
Average operation ambient temperature within 24h 35°C
Relative humidity maximum 50% la 40°C without condensation
Maximum operating altitude 2000m
Degree of pollution 3
Vibrations, shocks resistance class 1
Overvoltage category III
Electromagnetic environments Type A
Lifetime service 25 years
REMOTE CONTROL
REMOTE MEASURING
MAIN NUMERIC
REMOTE SIGNALING
PROTECTION COMMAND
DISPATCHING
CONTROL UNIT
EVENTS LOG
PARAMETERIZATION
WORK STATION
REMOTE CONTROL
NUMERIC PROTECTION UNIT REMOTE MEASURING
REMOTE SIGNALING
EVENTS LOG
PARAMETERIZATION
Manolesti Deal 33
Botosani 710003, Romania
T +40 231 532186 (87,88,89)
F +40 231 532185
office@electroalfa.ro
www.electroalfa.ro
Sales Representatives