You are on page 1of 5

605

OEM Differential pressure switch


20 ... 400 Pa


Technical overview Medium Pressure connections
The differential pressure switches of Liquids and neutral gases Hose connector Ø 6.2 mm
type series 605 are specially designed for Orifice installed for damping pulsating
control and monitoring applications in pressure at P2 (option)
gasfired boilers. Pressure range
20 … 400 Pa
Higher pressures on request Installation arrangement
With turn-on point below 30 Pa, diaphragm
vertical or horizontal with electrical connec-
Tolerable overload on one side tions facing downward.
5000 Pa at -30 … +85 °C
1500 Pa at -30 … +110 °C Please indicate installation arrangement

Setting ranges / Switching difference Mounting


20 Pascal Several brackets
Smallest switching differential 8 Pa at a Fastening clip for quick mounting
turn-on pressure of 20 Pa (see accessories)
(See adjustable switching differences)
Switching differential is factory-set
Tests / Admissions
CE conformity
Reproducibility DVGW according to DIN EN 1854
Between ±1 Pa CE-0085AP0974

Legend to cross-section drawing


1 Diaphragm Switching load Weight
2 Contact system See Nominal loading limits Without accessories approx. 60 g
3 Combi-contact
4 Switching point setting
(only possible by the manufacturer) Contact system Packaging
5 Switching difference setting Changeover switch Multiple packaging
(only possible by the manufacturer) in cardboard (300 or 1200 pcs)
6 P1 Connection of higher pressure
7 P2 Connection of lower pressure Materials in contact with the medium
8 AMP Connectors Main case: fiberglass reinforced plastic
9 Contact safety guard Cover: PC Lexan 500R
Diaphragm: Silicon LSR

Temperature
The distinct advantages Medium and ambiance -30 … +110 °C
• Fitting of the switch Storage -30 … +110 °C
– Fast mounting with snapping bracket Higher temperature on request
system
• Adjusting security
– Switching point- and switching Service life
difference adjusting screw are secured Mechanical, > 106 switching cycles
after factory adjustment through
covering
– No false manipulation through Electrical connection
mounting or service personel AMP connector 6.3 mm or 4.8 mm
• High contact strength (10 cN typical) according to DIN 46244
– Essentially less susceptibility to
polution of contact
• Roll operation of contact surface Protection standard
– Less sensitive to contact polution Not mounted IP 00
through self cleaning effect With contact safety guard IP 30
• Form of diaphragm and material With cover, without seal IP 54
– Through use of 2-component silicon With cover and seal IP 65
longer long-time stability With DIN EN 175301-803-A connector IP 65
– Through new trapeoid diaphragm
enlargement exact transfer of contact
release and therefore exact switching
points

605 / EDITION 07/2009, Technical data subject to change.


Versions
A – with contact safety guard

B – with fastening clip

C – with bracket A

D – with bracket B
A B C D

Adjustable switching differences


20 - 220 Pa 220 - 400 Pa
min. max. min. max.
240
400

Switching point above (Pa)

Switching point above (Pa)


Switching difference adjustment only inside sha- 200
ded area: 360
160
Example: Upper switching point 220 pascal.
Switching difference between 14 and 36 pascal. 320
120
Example: Upper switching point 40 pascal.
Switching difference between 9 and 30 pascal. 280
80
Example: Upper switching point 20 pascal,
40 240
smallest switching difference 8 pascal.

0 200
0 10 20 30 40 50 0 20 40 60 80 100
Switching difference (Pa) Switching difference (Pa)

Tolerance of switching point The principle of high contact pressure

Kontaktkraft Simplified representation of the new DPS 605 contact system. The
Pa
high contact pressure results form the optimized length ratios of
Tolerance of switching point LC and LD.
▲ ▲ ▲ ▲ ▲ ▲

+/- 14 Contact pressure (CP)

Diaphragm pressure (DP)


+/- 10 CP = DP
( )
LD
LC
+/- 7

+/- 5
Pivot point

+/- 4
Switching
+/- 3 point
Pa
0 50 100 150 220 300 400

LC

LD

LC = Length of contact lever


LM = Length of diaphragm lever

Nominal loading limits


I (A) for DC I (A) for AC
0.9 1.4

0.8 1 = ohmic 1 = ohmic


2 = inductive 1.2 2 = inductive
0.7 (cos w 0.7)
1.0
0.6
1
0.5 0.8
I [A]

I [A]

0.4 0.6
2
0.3
0.4
1
0.2
2 0.2
0.1

0 0.0
Can also be operated with TTL-load
0 40 80 120 160 200 240 0 40 80 120 160 200 240
U [V] U (V) U [V] U (V)

605 / EDITION 07/2009, Technical data subject to change.


Dimensions in mm Electrical connections

Electrical connections

1 Feeder (COM)
2 NC contact
3 NO contact

Cover with seal Cover without seal Contact safety guard Contact safety guard
and PT screw with PT screw with PT screw with PT screw
100306 100307 Cable exit AMP2 Cable exit AMP1
100309 100308

Accessories

Fastening clip Fastening clip Bracket type A Bracket type


100294 S = 0.8 – 1.1 106790 100295 B
100293 S = 1.8 – 2.1 100296
(Dimensions in mounted state)

Thickness of sheet metal S


S

605 / EDITION 07/2009, Technical data subject to change.


505
Headquarters
Huba Control Schweiz
Industriestrasse 17
CH-5436 Würenlos
Telefon ++41 (0) 56 436 82 00
Telefax ++41 (0) 56 436 82 82
info.ch@hubacontrol.com

Huba Control Deutschland


Schlattgrabenstrasse 24
72141 Walddorfhäslach
Telefon (07127) 23 93-00
Telefax (07127) 23 93-20
info.de@hubacontrol.com

Huba Control France


Technopôle Forbach-Sud
57602 ForbachCedex
Téléphone 03 87 84 73 00
Télécopieur 03 87 84 73 01
info.fr@hubacontrol.com

Huba Control Nederland


Hamseweg 20A
3828 AD Hoogland
Telefoon 033 433 03 66
Telefax 033 433 03 77
info.nl@hubacontrol.com

Huba Control United Kingdom


Unit 3 Network Point, Range Road
Witney Oxfordshire OX29 0YD Sous réserve de modifications techniques.
Technische Änderungen vorbehalten.

Phone 01993 776667


Technical data subject to change.

Fax 01993 776671


info.uk@hubacontrol.com
605.Edition07/2009

www.hubacontrol.com

You might also like