You are on page 1of 24

Magnetic Float Level Switch

www.fine-tek.com
INTRODUCTION

PRINCIPLE
The single unit or multiple reed switch units are When the float internal magnet approaches the
housed tightly in stainless steel or engineering reed switch, it will actuate the reed switch contact
plastic stem, and the permanent magnet is point to create an open or close circuit. We can
sealed into the middle of the specified float apply such on-off output signals to reach liquid
ball(s). You can mount the float ball to penetrating level controlling and monitoring purpose.
through the stem, then the liquid buoyancy will The figures below show the float orientations on
deliver the float ball up and down at the specified N.O. (Normal Open) and N.C. (Normal Close).
position by graduating rings.

Float ball

Reed switch

NO NO
NC NC
Permanent
magnet

Rising float ball to actuate Rising float ball to switch off.


the reed switch

FEATURES
Multiple points measuring, multiple level points The housing protection is at least IP65.
could be for custom-made.
Rugged construction and multiple options for
Employing the magnet to actuate the reed switch materials from engineering plastics as PVDF,
requires no power. PP, PVC, and stainless steels such as SUS304,
Life expectancy of each contact can reach up to 2 SUS316, float switches can be applied to
million times. versatile applications in chemical corrosion
of acidity and alkalinity liquid, solvents or oil
All output signal wiring are simplified in same fuels.
junction box (housing) to economize the external
wiring construction. The reed switch and lead wire are isolated
with liquids absolutely. All stainless steel
FC(D) type magnetic float level switches are more
switches are applicable to high pressure and
cost-effective than other level switches in terms of
high temperature environment.
multiple points.

1
FlneTek
APPLICATIONS
Shipbuilding Industry, Generator Facilities, Petrochemical Industry, Food/Beverage Industry,
Waste Water/Water Purified Facilities, Electronic Industry, Dyeing and Finishing Industry,
Chemical Industry, Rubber/ Plastic Industry, Hydraulic.

SPECIFICATION

Switching Switching Switching Switching Carry


Tube Type Material
Contact from Capacity Max. Voltage Max. Current Max. Current Max.

SUS SPST 50W 300Vac/350Vdc 0.5A 2.5A


OD8
PVC SPDT 20W 150Vac/200Vdc 1A 2A
SPST 50W 300Vac/350Vdc 0.5A 2.5A
OD9.5 SUS
SPDT 20W 150Vac/200Vdc 1A 2A
SPST 60W 220Vac/500Vdc 3A 4A
OD12.7 SUS
SPDT 60W 400Vac/1000Vdc 1A 2A
SPST 60W 220Vac/500Vdc 3A 4A
OD16 PVDF
SPDT 60W 400Vac/1000Vdc 1A 2A
SPST 60W 220Vac/500Vdc 3A 4A
OD17.2 PP
SPDT 60W 400Vac/1000Vdc 1A 2A
※Reed switches of UL approval are 240Vac/ 200Vdc, 50w,0.5A.

APPLICATION FIELDS OF FLOAT


Environments
Working Temp. Pressure Rating Acid Alkaline Oil Solvent
Float
- 20°C~120°C
SUS304 (200°C Max.) 10~ 30kg/cm2

- 20°C~120°C
SUS316 10~ 30kg/cm2
(200°C Max.)

Polypropylene -20°C~80°C 4kg/cm2

PVDF -20°C~120°C 3kg/cm2

Note: = Excellent = Good = Acceptable =Not good (S10 resistance:50 kg)

2
FlneTek
CHEMICAL RESISTANCE

Excellent Good Fair Corroded


Concentration Temp Plastic Rubber Stainless Concentration Temp Plastic Rubber Stainless
Chemical Chemical
% BC PVC PP PVDF PTFE NBR 304 316 % BC PVC PP PVDF PTFE NBR 304 316
Ammonia Water 10 40 104 Sodium 3 40 104
NH4OH 10 80 176 Hypochlorite 3 80 176
Aque Regia 10 40 104 NaCIO 5 40 104
3HCI+HNO3 10 80 176 5 80 176
Benzene 40 104 7 40 104
Pure
C6H6 80 176 7 80 176
Bleaching Liquor 5 40 104 10 40 104
Ca(CIO)2 5 80 176 10 80 176
20 40 104 13 40 104
20 80 176 13 80 176
Boric Acid 40 104 Sulfuric Acid 10 40 104
Satu
H3BO3 80 176 H2SO4 10 80 176
Brine 40 104 30 40 104
80 176 30 80 176
Butadiene 40 104 50 40 104
Gas
CH2=CH=CH=CH2 80 176 50 80 176
Butane 40 104 60 40 104
Gas
CH3(CH2)2CH3 80 176 60 80 176
Nitric Acid 10 40 104 70 40 104
HNO3 10 80 176 70 80 176
30 40 104 80 40 104
30 80 176 80 80 176
50 40 104 90 40 104
50 80 176 90 80 176
70 40 104 98 40 104
70 80 176 98 80 176
98 40 104 Toluene 40 104
98 80 176 C6H5CH3 80 176
Oxalic Acid 20 40 104 Chlorine Gas Wet 40 104
HOOCCOOH 20 80 176 CI2 Wet 80 176
50 40 104 Dry 40 104
50 80 176 Dry 80 176
Phosphoric Acid 10 40 104 Chromic Acid 10 40 104
H3PO4 10 80 176 H2CrO4 10 80 176
50 40 104 20 40 104
50 80 176 20 80 176
80 40 104 40 40 104
80 80 176 40 80 176
Butane 40 104 50 40 104
Gas
CH3(CH2)2CH3 80 176 50 80 176
Sodium 15 40 104 Hydrochloric 15 40 104
Hydroxide 15 80 176 Acid 15 80 176
NaOH 30 HCI 25
40 104 40 104
30 80 176 25 80 176
50 40 104 35 40 104
50 80 176 35 80 176
70 40 104 38 40 104
70 80 176 38 80 176

3
FlneTek
Excellent Good Fair Corroded
Concentration Temp Plastic Rubber Stainless
Chemical
% BC PVC PP PVDF PTFE NBR 304 316
Citric Acid 10 40 104
C6H8O7 10 80 176
Gasoline 10 40 104
10 80 176
Diesel Fuels 40 104
80 176
Ethyl Alchol 40 104
Pure
C2H5OH 80 176
Formic Acid 90 40 104
HCOOH 80 176
Hydrofluric Dilute 40 104
Acid Dilute 80 176
HF 30 40 104
30 80 176
40 40 104
40 80 176
50 40 104
50 80 176
Hydrogen 5 40 104
peroxide 5 80 176
H2O2 20 40 104
20 80 176
30 40 104
30 80 176
50 40 104
50 80 176
90 40 104
90 80 176
Isopropyl Alcohol 40 104
(CH3)CHOH
Pure
80 176
Kerosene 40 104
80 176
Methyl Alcohol 40 104
CH3OH 80 176
Methyl Ethyl Ketone 40 104
CH3COC2H5 80 176
Potassium Chromate 40 104
K2CrO4 80 176

4
FlneTek
CONTACT PROTECTION CIRCUITS

INDUCTIVE LOADS
When using a reed switch with inductive Such high induced voltage (transients) may
loads such as motors, relays, solenoids, etc., cause damages to the reed switch or
The contact will be subjected to a high significantly reduce its life.
induced voltage during opening of the Therefore, protective circuits such as: RC
contact (load circuit). (snubber), varistors or clamping diodes are
recommended.(refer to Fig.1)
(Fig.1)
Inductive load
H

DC
C R
N
(RC)

Inductive load Inductive load

DC DC

N
(Varistor) (Diode)

. It is prohibited to connect directly with any solenoid valve, motor or magnetic switch.

CAPACITIVE LOADS

When using a reed switch with capacitive Therefore, protective circuits such as:
loads such as capacitors, incandescent lamps surge suppressors or current limiting resistors
or long cables, the contact will be subjected to are recommended.(refer to Fig.2)
a high surge (inrush) current.

(Fig.2)
Capacitive load Bulb load

+
C R
AC AC
R
_

Parallel connection of RC circuit and switch will Series connection of resistance and switch limit
surge current bypass. surge current.

5
FlneTek
HOUSING SPECIFICATION

B 128
C 128 D
f118 f118 f113

1/2" NPT

108
107 107
1/2"PF 1/2"PF

Material : Aluminum Material : PP+Fiber Material : Aluminum


Enclosure : IP65 Enclosure : IP65 Enclosure : IP65
Terminals : 2~12 Terminals : 2~12 Terminals : 2~12
Max.Temp.: -20BC ~200BC Max.Temp.: -20BC ~80BC Max.Temp.: -20BC ~200BC

E G H
88 85x80 f70

55
84
70
PG16 1/2"PF
1/2"PF

Material : Aluminum Material : PC Material : Aluminum


Enclosure : IP65 Enclosure : IP65 Enclosure : IP65
Terminals : 2~6 Terminals : 2~6 Terminals : 2~12
Max.Temp.: -20BC ~200BC Max.Temp.: -20BC ~80BC Max.Temp.: -20BC ~100BC
*For side-mounting float series.

K Explosion-proof
100
L Explosion-proof M
80 f70
f90

80 1/2"NPT
100 1/2"NPT
3/4"NPT 80

3/4"NPT 1/2"NPT
Material : Aluminum Material : Aluminum
Enclosure : INERIS 09 ATEX 0049 Enclosure : INERIS 09 ATEX 0049 Material : SUS316
II 2GD Ex d IIC T4~T6 II 2GD Ex d IIC T4~T6 Enclosure : IP65
Terminals : 2~6 Terminals : 2~6 Terminals : 2~6
Max.Temp.: -20BC ~100BC Max.Temp.: -20BC ~90BC Max.Temp.: -20BC ~200BC
*For flow switch series. *For side-mounting float series.

N X Cable Conduit Ex d IIC


f70 Material: Washer ---NBR
f70
Body--- Aluminum (3/4" NPT)
Nickel plated (1/2" NPT)
1/2"NPT 1/2"PF 29-1104
3/4"NPT
80 70
40
fMax=9
fMin=6
36 68

Material : SUS316 Material : Aluminum 29-1108


1/2"NPT
Enclosure : IP65 Enclosure : IP65
Terminals : 2~6 Terminals : 2~6 35
Max.Temp.: -20BC ~200BC Max.Temp.: -20BC ~100BC fMax=12
32 55 fMin=9
Remark 1 : Cable conduit is optional. Contact us if needed.

6
FlneTek
FLOAT SPECIFICATIONS
Max. Pressure Weight Max. Temp.
MODEL TYPE fA xBxfC S.G. (kg/cm2) (g) Material/Color (LC)

A S1 28x28x9.5 E>0.7 10 8 SUS 316 / 316L 200

S3 45x55x15 E>0.65 12 37.6 SUS 316 200


B
S6 75x108x20 E>0.5 10 165 SUS 316 200

C
S13 38x50x15 E>0.62 12 22.9 SUS 316L 200

S2 41x38x11 E>0.7 35 19.5 SUS 316 200

S4 52x52x15 E>0.55 30 33.4 SUS 316 200

A S5 75x73x20 E>0.65 30 102.4 SUS 316 200

S7 30x28x9.5 E>0.82 25 8 SUS 316 / 316L 200


B
S8 100x100x20 E>0.5 15 249.7 SUS 304 200
C
S9 150x150x30 E>0.45 15 534 SUS 304 200

S10 30x32x9.5 E>0.82 50 8.6 SUS 316 200

S11 28x32x9.5 E>0.82 30 8.1 SUS 316 200

P1 25x15x10 E>0.65 4 3.5 white 80


PP /
black
A
white
P2 25x25x10 E>0.7 4 5 PP / 80
black
B
P3 48x45x18.5 E>0.6 5 35.5 PP / black 80

C P4 20x25x10 E>0.7 4 3.7 PP / black 80


(Hollow)
P5 20x20x8.1 E>0.75 4 4 PP / black 80

P8 18.2x15.3x7.2 E>0.8 4 1.82 PP / black 80

Q6 20x20x7.5 E>0.75 ATM 3.5 PP / white 80

Q7 25x25x8.8 E>0.7 ATM 6.7 PP / white 80


A
N1 25x15x10 E>0.5 ATM 2.7 NBR / black 100
B
N2 18.5x26x10 E>0.7 ATM 3.3 NBR / black 100

C N3 19x20x10 E>0.55 ATM 2.4 100


NBR / black
(Foam)
N4 17.5x25x10 E>0.65 ATM 2.5 NBR / black 100

N5 30x45x12.8 E>0.5 ATM 11.5 NBR / black 100

A
F2 42x44x14 E>0.63 5 18.5 PP 80

B F3 45x45x20 E>0.65 5 35.7 PP 80

F4 48x62x18 E>0.8 5 65.3 PVDF 120


C (Hollow)
※S5 float: E>0.65 for FC; E>0.61 for FG
※F4 float: E>0.8 for FC; E>0.75 for FG 7
FlneTek
ORDER SPECIFIED

THE PROPERTIES BETWEEN LIQUID AND FLOAT

Please choose the proper float subject to above independent specified terms and chemical characters.
1. Temperature: PVDF Max. 120BC, 4. Chemical: Please use plastic float for acid/
PP Max. 80BC, alkaline corrosion of chemical
SUS304/ 316 Max. 200BC applications. PVDF float is noted
2 for high temperature cases.
2. Pressure: SUS304/ 316 Float, Max. 35kg/cm
Engineering plastic, Max. 5kg/cm2 5. Benzine: Please choose stainless steel floats
(S10 float Max. 50kg) to apply in any gasoline, fuel oil,
3. Viscosity: Please choose smaller S.G. with petroleum application.
greater diameter floats to cope with
high viscosity liquid applications. 6. S.G.: The float S.G. Must be smaller than the
liquid, otherwise, the liquid buoyancy
can not deliver the float upword.
Buyer's guide :
The magnetic level switch can be done as per independent float actuating position, please
customer's specified technical data such as refer the order information to define the
the flange, thread, housing, float ball diameter, application specifications. A single ball driving
float ball number, the float traveling up or down multiple actuated points is available to apply
actuated position by N.C. or N.O. output, the on the order form.
total float working distance (L) or each

Example: FD B HM 7 S6 3 0405

Material Housing Type Connection Stem (Tube) Type Float Type Float Number Total Float Working Distance

It is requested the minimum interval for a single A= Minimum distance from the mounting
ball driving dual actuated positions (D) or position to the highest actuation level.
neighboring two balls (B), or from the bottom to B= Minimum distance between any two
the lowest ball interval (C) or from the mounting actuation levels.
position to the first ball (A), otherwise, there will
be some magnetic mutually interference involved C= Minimum distance from end of the lowest level.
by insufficient interval. To ensure the defined D= Minimum distance between two actuation levels
distance, please see the data below: by one float.
E= Screw length

FLOAT
TYPE S1 S2 S3 S4 S5 S6 P1 P2 P3 F4

A(mm) 25 32 40 39 50 70 23 27 47 55
B(mm) 50 64 82 78 99 136 44 55 85 98
C(mm) 25 32 40 39 50 70 23 31 43 50
D(mm) 30 40 55 50 65 70 30 30 45 65

SCREW 1/2" 3/4" 1" 1-1/4" 1-1/2" 2" 2-1/2" 3"

(E) (mm) 14 16 19 22 22 25 28 32

8
FlneTek
HOW TO MAKE YOUR ORDER

F D B HM 7 S 6 3 05 00 A T
P: Pipe Shield
R: Sensor
T: Test Rod
Contact Form
A: SPST C: SPDT F: 1 float 2 points
G: 1 float 3 points : No contact
Length:(L) Unit=mm
0500: below 500mm
1000: 501~1000mm
1500: 1001~1500mm ※ 500mm/per unit
Quantity of float (1~4)
Float Type (Please refer page 7)
F2, F3, F4
P1,P2, P3, P4
S1, S2, S3, S4, S5, S6, S7, RO
Q7, N1, N2, N3, N4, N5
Stem
Code size Material Code size Material Code size Material
0: f8 PP 6: f16 PVDF A: f8 SUS316
1: f8 SUS304 7: f17.2 SUS304 B: f9.5 SUS316
2: f8 PVC 8: f12.7 P.P. C: f12.7 SUS316
3: f9.5 SUS304 9: f12.7 PVC D: f17.2 SUS316
4: f12.7 SUS304 E: f8 PFA
5: f17.2 P.P. S: special
Connection Type
Housing Type
B: AL. (Big space) Size for flange or screw Pressure range or other
C: PP (Anti-acidity) M: 5kg/cm2 JIS
A: 3/8" (10A) I: 4"(100A) N: 10kg/cm2 JIS
D: Aluminum B: 1/2" (15A) J: 5"(125A)
E: AL. (Small space) O: 150Lbs ANSI
C: 3/4" (20A) K: 6"(150A) P : 300Lbs ANSI
G: PC (Anti-acidity) D: 1" (25A) S: Others Q: PT (Male)
H: Aluminum E: 1-1/2"(40A) 1: 1/8" R: PF(G) (Male)
K: AL. F: 2" (50A) 2: 1/4" T: BSP (Male)
G: 2-1/2"(65A) 3: 1-1/4"(32A) U : NPT (Male)
N: SUS304 or SUS316 H: 3" (80A) S : Others
P: Plastic IP65 W: PN10 (10Bar)
-: Without housing X: PN16 (16Bar)
2: Without housing Y: PN25 (25Bar)
(Side Mounting) Z: PN40 (40Bar)
J :Adjustment screw
K:Adjustment flange
A: PT (Female)
B: PF (Female)
FC: Plastic (Stem) C: BSP (Female)
U: NPT (Female)
FD: Metal (Stem)
* Special term for LR Marine approval: "Environmental test has been carried out but it is not applicable
to use in the ship and offshore that type of screw fittings is used for pipe exceeding 51mm outer
diameter".
9
FlneTek
ANTI-CORROSION SCREW TYPE / FLANGE TYPE

Housing material apply by PP, wet portion material


options in PP, PVDF, specially applicable for chemical
applications against corrosive environments.

Type FC C (FQ) 6 F4 4 Type FC C (FQ) 5 P3 4


128 128

1/2"PFx1 1/2"PFx1

130 130

2"PT 2"PT

NO 1 NO 1
NC mm NC mm

2
2 NO
NO
NC mm
NC mm

L=
mm NO 3
L= 3 NC mm
mm NO
NC mm

NO 4
NC mm
NO 4
NC mm 45

60
f17.2
Wetted Parts:PVDF f 48 Wetted Parts:PP

f16
f 48

Type FC C (FN) 6 F4 4 Type FC C (FN) 5 P3 4


Order information 128 128

1/2"PFx1 1/2"PFx1
Type
Housing Type 145 145
Flange Flange
2"x10kg/cm2 2"x10kg/cm2
FC C (FQ) 6 F1 4
NO 1
NO 1
NC mm
NC mm

2
NO
2 NC mm
NO
NC mm
Connection Pipe Float Float
Flanges Diameter Type Quantity
L= mm NO 3

FQ=2" F4=PVDF L= 3
NC mm
6= f16 1~ 4 mm NO
PT f48x60 NC mm

FQ=2" P3=PP NO 4
5= f17.2 1~ 4
PT f48x45 NC mm
NO 4
FN=2" F4=PVDF NC mm 45
6= f16 1~ 4
10kg/cm 2 f48x62
60 f17.2
FN=2" P3=PP
10kg/cm 2 5= f17.2 1~ 4 f 48
f48x45 Wetted Parts:PVDF Wetted Parts:PP
f16
※FCC(FQ) & (FN)2" flange/thread f 48
are available,too.

10
FlneTek
STANDARD FLANGE TYPE

The housing complies with the IP65 rating and can


therefore be used in outdoor environment.

Type
FD B (EM) 3 S2 4 Type
FD B (FM) 4 S3 4
128 128

1/2"PFx2 1/2"PFx2

107 107
Flange Flange
1-1/2"x 5kg/cm2 2"x 5kg/cm2

NO 1 NO 1
NC mm NC mm

2
NO 2
NC mm NO
NC mm

3
L= NO
mm NC mm
NO 3
L=
mm NC mm
NO 4
NC mm

38 NO 4
NC mm

f9.5 55
f 41

f12.7
f 45

Type FD B (FM) 4 S4 4 Type FD B (HM) 7 S6 4


Order information 128 128

1/2"PFx2 1/2"PFx2
Type
107 107
Housing Type
Flange Flange
2"x 5kg/cm2 3"x 5kg/cm2
FD B (HM) 7 S6 4
NO 1
NC mm
NO 1
NC mm
2
NO
NC mm

2
Connection Pipe Float Float NO
3 NC mm
Flanges Diameter Type Quantity L=
mm
NO
NC mm

EM=1-1/2" S2=
3= f9.5 f41x38 1~ 4
5kg/cm 2 NO 4
NC mm
FM=2" S3= 3
4= f12.7 1~ 4 52 L= NO
5kg/cm 2 f45x55 mm NC mm

FM=2" S4=
4= f12.7 1~ 4 f12.7
5kg/cm 2 f52x52 f 52
HM=3" S6=
5kg/cm 2 7= f17.2 f75x108
1~ 4 4
NO
NC mm

108

f17.2
f 75
11
FlneTek
STANDARD SCREW TYPE

The housing complies with the IP65 rating and can


therefore be used in outdoor environment.

Type
FD B (EQ) 3 S2 4 Type FD B (FQ) 4 S3 4
128 128

1/2"PFx2 1/2"PFx2

107 107

1-1/2"PT 2"PT

NO 1
NO 1
NC mm NC mm

2
NO
NC mm 2
NO
NC mm
3
L= NO
mm NC mm
L= NO 3
mm
NO 4 NC mm
NC mm

38
NO 4
NC mm
f9.5
f 41 55

f12.7
f 45

Type
FD B (FQ) 4 S4 4 Type
FD B (HQ) 7 S6 4
Order information 128 128

1/2"PFx2 1/2"PFx2
Type
Housing Type 107 107

2"PT 3"PT
FD B (HQ) 7 S6 4 NO 1
NC mm
NO 1
NC mm
2
NO
NC mm

Connection Pipe Float Float 3 NO


2
L= NO
Flanges Diameter Type Quantity mm NC mm
NC mm

EQ=1-1/2" S2=
3= f9.5 f41x38 1~ 4 4
PT NO
NC mm
FQ=2" S3=
4= f12.7 1~ 4 52 NO 3
PT f45x55 L=
mm NC mm

FQ=2" S4= f12.7


4= f12.7 1~ 4
PT f52x52 f 52

HQ=3" S6=
PT 7= f17.2 f75x108
1~ 4
NO 4
NC mm

108

f17.2
12 f 75
FlneTek
SCREW TYPE / FLANGE TYPE

The housing complies with the IP65 rating and can


therefore be used in outdoor environment.

Type FD E (EM) 3 S2 3 Type FD E (3M) 1 S1 3

88 88

1/2"PFx1 1/2"PFx1
Flange Flange
84 84
1-1/2"x5kg/cm2 1-1/4"x5kg/cm2

NO 1
NO 1
NC mm
NC mm
2
NO
L= NC mm
mm
2
L= NO
3
mm NC mm NO
NC mm

NO 3 28
NC mm
f8
38
f28

f9.5
f 41

Type
FD E (EQ) 3 S2 3 Type
FD E (DQ) 1 S1 3
Order information
Type 88 88
Housing Type
1/2"PFx1 1/2"PFx1
84 84
FD E (3Q) 1 S1 3 1-1/2"PT 1"PT

NO 1
NO 1
NC mm
NC mm
2
NO
L= NC mm
2 mm
Connection Float NO
Pipe Float L=
mm NC mm NO 3
Flanges Diameter Type Quantity NC mm

NO 3 28
EM=1-1/2" S2= NC mm
3= f9.5 f41x38 1~ 3 f8
5kg/cm 2 38 f28
3M=1-1/4" S1=
1= f8 1~ 3 f9.5
5kg/cm 2 f28x28
f 41
EQ=1-1/2" S2=
3= f9.5 1~ 3
PT f41x38
S1=
DQ=1"PT 1= f8 f28x28
1~ 3

13
FlneTek
INERIS 09 ATEX 0049 II 2GD Exd IIC T4~T6
IM2 ExdI ExtD A21
ENCLOSURE EXPLOSION PROOF IP66 T85~135BC

FLANGE TYPE
Type
FD K (FM) 4 S4 4 Type FD K (HM) 7 S6 4
Order information 100 100
f90 f90

3/4"NPTx1 3/4"NPTx1
Type
Housing Type 120 120 Flange
Flange
2"x5kg/cm2 3"x 5kg/cm2

FD - K - HM - 7 - S6 - 4 1
NO
NC mm
NO 1
NC mm
2
NO
NC mm

2
NO
Connection Pipe Float Float L= NO 3 NC mm
Flanges Diameter Type Quantity mm NC mm

EM=1-1/2" S2=
3= f9.5 f41x38 1~ 4
5kg/cm 2 NO 4
NC mm
3
FM=2" S3= 52 L= NO
4= f12.7 1~ 4 mm NC mm
5kg/cm 2 f45x55
FM=2" S4= f12.7
4= f12.7 1~ 4
5kg/cm 2 f52x52 f52

HM=3" S6=
5kg/cm 2 7= f17.2 f75x108
1~ 4 NO 4
NC mm

108

f17.2
f 75
SCREW TYPE Type FD K (FQ) 4 S4 4 Type FD K (HQ) 7 S6 4
100 100
Order information f90 f90
3/4"NPTx1 3/4"NPTx1
Type
Housing Type 120 120

2"PT
3"PT
FD - K - HQ - 7 - S6 - 4 NO 1
NC mm
NO 1
NC mm
2
NO
NC mm

Connection Pipe Float Float L= NO 3 2


Flanges Diameter Type Quantity mm NC
NO
mm NC mm

EQ=1-1/2" S2=
3= f9.5 f41x38 1~ 4
PT NO 4
NC mm
FQ=2" S3=
4= f12.7 1~ 4 52
PT f45x55 L= NO 3
mm NC mm
FQ=2" S4= f12.7
4= f12.7 1~ 4
PT f52x52 f 52

HQ=3" S6=
PT 7= f17.2 f75x108
1~ 4
NO 4
NC mm

108

f17.2
14 f 75
FlneTek
VERTICAL ADJUSTMENT TYPE

This is a special design for some liquid Applicable at tank interior pressure under
applications requiring monitoring different 5 kg/cm2.
actuation levels frequently. The user needs only to Standard specification 80BC, special order
loose the hexagon nut, then remove the mounted of max. 200BC available.
screw/ flange up or down to achieve the Switch contact: 20W/150Vac /250Vdc SPDT
actuated level position adjustment.
50W/300Vac /350Vdc SPST
60W/220Vac /500Vdc SPST
60W/400Vac /1000Vdc SPDT
Customer specified flange/ screw
acceptable.

FD E (EJ) 4 S4 1 FD E (EK) 3 S2 1
93
93
1/2"PFx1
84 1/2"PFx1
84
6
6

L= NO L1
mm NC mm L= NO L1
mm NC mm
2"PT

8 1-1/2"x5kg/cm2
105 8
52 90
38

f12.7
f 52 f 9.5
f41

Order information
Pipe Float
Type Connection Diameter Type
Housing Type
EJ=1-1/2" S2=
3=f9.5
PT f41x38
FD E (EJ) 4 S4 1 FJ=2" 4=f12.7
S4=
PT f52x52
Float quantity
Connection Float Type EK=1-1/2" S2=
3=f9.5
Pipe diameter 5kg/cm2 f41x38

Please specify the while placing an order.


(Length from lower end of housing to center line
of float ball)

15
FlneTek
TEST ROD GL Marine Approval 50885-04HH

FUNCTION: MATERIAL:
When the Test Rod is attached to a magnetic float 1. Rod Connection: Bronze
level switch, user could test the performance of 2. Compressed Spring: Stainless Steel
the magnetic switch directly by pulling the handle 3. Positioning Clip: Stainless Steel
of the test rod on the top of the switch. 4. Test Rod Stem: Stainless Steel

FD......T

FDB-4000

HEX27 45
Connecting flange 1
Min. 3"x5kg/cm 2
2

f8

88

16
FlneTek
MARINE GRADE APPROVAL

TYPE APPROVAL PROGRAM

FH DM 4 S3 1 FM FM 4 S3 1
f70 f70

1/2"NPTx1 1/2"NPTx1
70 70

200

2"x5kg/c㎡

L(Max. 2M)
L(Max. 2M)
C-C

1"x5kg/cm2 f 60.5 f 60.5

FH DM 4 S3 1 0500 A FM DM 4 S3 1 0500 A
Contact Form Contact Form
A: SPST, C: SPDT A: SPST, C: SPDT
Length: mm Length: mm
0500: below 500mm 0500: below 500mm
1000: 501~1000mm 1000: 501~1000mm
1500: 1001~1500mm 1500: 1001~1500mm
Float quantity Float quantity
Float Type Float Type
Pipe diameter Pipe diameter
Connection Connection

* Please specify the , 2 , C-C and L while placing an order.


(Length from lower end of housing to center line of float ball) DM=1"x 5kg/cm2 4= f12.7 S3= f45x55

FM=2"x 5kg/cm2 4= f 12.7 S4= f52x52

* Special term for LR Marine approval: "Environmental test has been carried out but it is not applicable to use in the ship
and offshore that type of screw fittings is used for pipe exceeding 51mm outer diameter".

17
FlneTek
NEPSI PROOF No.GYJ111215 Ex d IIC T3~T6
PTB PROOF No. 05 ATEX 1027 II 2G Ex d IIB T6~T3 GB
II 2D Ex tb IIIC
EXPLOSION PROOF TYPE T85BC~T200BC Db IP65

FLANGE TYPE
Type
FD7 D FM 4 S4 4 Type FD7 D HM 7 S6 4 Type FD7 N HM 7 S6 4
f113 f113 f70

1/2"NPTx2 1/2"NPTx2
1/2"NPTx2
108 108
80
Flange Flange
3"x 5kg/cm2 Flange
2"x 5kg/cm2 3"x 5kg/cm
2

NO 1
NC mm
NO 1
NO 1
NC mm NC mm
2
NO
NC mm

2
NO 2
mm NO
3 NC
L= NO NC mm
mm NC mm

NO 4
NC mm
NO 3
L= NO 3
52 mm NC mm L=
mm NC mm

f12.7
f 45

NO 4
NO 4
NC mm
NC mm

108 108
f75 f75

SCREW TYPE f17.2 f17.2


f 75 f 75

Type FD7 D FQ 4 S4 4 Type FD7 D HQ 7 S6 4 Type FD7 N HQ 7 S6 4


f113 f113 f70

1/2"NPTx2 1/2"NPTx2
1/2"NPTx2
108 108
80
2"PT 3"PT
3"PT

NO 1
NC mm
NO 1
NO 1
NC mm NC mm
2
NO
NC mm

2
3 NO 2
L= NO mm NO
mm NC mm
NC
NC mm

NO 4
NC mm

52 NO 3
3
L= NC L= NO
mm mm
mm NC mm

f12.7
f 45

NO 4
NO 4
NC mm
NC mm

108 108

f17.2 f17.2
f 75 f 75
18
FlneTek
HOW TO MAKE YOUR ORDER

F D 7 D HM 7 S 6 3 0 5 0 0 A (L T )

T: Test Rog
Tag
Contact Form
A: SPST C: SPDT
F: 1 float 2 points G:1 float 3 points

Length: mm
0500: below 500mm
1000: 501~1000mm
1500: 1001~1500mm ※ 500mm/per unit

Quantity of float
Float Type (see page 7)
P1,P2, P3, P4
F2, F3, F4
S1, S2, S3, S4, S5, S6, S7
Stem
Code size Material Code size Material Code size Material
0: f8 PP 6: f16 PVDF A: f8 SUS316
1: f8 SUS304 7: f17.2 SUS304 B: f9.5 SUS316
2: f8 PVC 8: f12.7 P.P. C: f12.7 SUS316
3: f9.5 SUS304 9: f12.7 PVC D: f17.2 SUS316
4: f12.7 SUS304
5: f17.2 P.P.
Connection Type
Housing Type
D: Aluminum Size for flange or screw Pressure range or other
N: SUS304 or SUS316 M: 5kg/cm2 JIS
A: 3/8" (10A) I: 4"(100A) N: 10kg/cm2 JIS
B: 1/2" (15A) J: 5"(125A) O: 150Lbs ANSI
C: 3/4" (20A) K: 6"(150A) P : 300Lbs ANSI
D: 1" (25A) S: Others Q: PT
E: 1-1/2"(40A) 1: 1/8" R: PF (G)
F: 2" (50A) 2: 1/4" T: BSP
G: 2-1/2"(65A) 3: 1-1/4"(32A) U : NPT
H: 3" (80A) S : Others
W: PN10 (10Bar)
X: PN16 (16Bar)
Y: PN25 (25Bar)
Z: PN40 (40Bar)
J : Adjustment screw
K: Adjustment flange
Explosion proof

* Certified by GL, ABS Marine grade are available. (Please see page 17)
* Special term for LR Marine approval: "Environmental test has been carried out but it is not
applicable to use in the ship and offshore that type of screw fittings is used for pipe exceeding
51mm outer diameter".

19
FlneTek
TYPICAL WIRING DIAGRAMS

N.O. N.C. R2 R2
Supply
water HI LOW
N.O. LEVEL LEVEL
N.C.
AUTO SUPPLY CASE: R1
SINGLE FLOAT
DUAL SWITCHES R1 R2
N.O.
N.C. Relay Relay Solenoid
1 2 valve

R2 R2
N.C. N.O.
LOW HI
LEVEL LEVEL
N.O.
AUTO DRAIN CASE: N.C. R1
SINGLE FLOAT
DUAL SWITCHES R1 R2

Drain N.O.
water N.C. Relay Relay Solenoid
1 2 valve

Supply HI N.C. R1
water N.O. LEVEL
AUTO SUPPLY CASE: N.C.
DUAL FLOATS LOW N.C. R1
DUAL SWITCHES LEVEL

N.O. R1
N.C.
Relay Solenoid
1 valve

HI N.O. R1 R1
LEVEL
N.O.
AUTO DRAIN CASE: N.C. LOW N.O.
DUAL FLOATS LEVEL
DUAL SWITCHES
N.O.
Drain
water N.C.

Relay Solenoid
1 valve

The "N.O." Means normally opened circuit of the reed switch (off) in lower liquid
level. As the float moves up to the specified higher level, the circuit closed (on).
The "N.C." Means normally closed circuit of the reed switch (on) in lower liquid
level. As the float moves up to the specified higher level, the circuit open (off).

20
FlneTek
INSTALLATION

The float level switch should be It is advised to place a pipe shield or


mounted far away from liquid inlet. equivalent device to normalize the
Any strong liquid fluctuation will switch actuation if the switch is used
produce error output signals. near agitator.

It had better require an L type It is recommended to select the


supporter, when the switch is standpipe with diameter larger than
mounted in concrete wall tank as the float ball for installation process.
figure below.

21
FlneTek
CONNECTION DIAGRAMS

1NO 1C 1NC 1NO 1C 1NC 1NO 1C 1NC

2NO 2C 2NC 2NO 2C 2NC 2NO 2C 2NC

3NO 3C 3NC 3NO 3C 3NC 3NO 3C 3NC

4NO 4C 4NC 4NO 4C 4NC 4NO 4C 4NC

5NO 5C 5NC 5NO 5C 5NC 5NO 5C 5NC

NO C NC
Means that the NC-C circuit will be close while liquid level lower than the float ball,
by mark of "?ON".
NO C NC
Means that the NO-C circuit will be close while liquid level higher than the float ball,
by mark of "?ON".
NO C NC
Means that the NO-C circuit will be close while liquid level higher than the float ball,
and NC-C circuit will be close while liquid level lower than the float ball.

Please screw the housing cap tightly and fix the conduit outlet, it will reinforce the housing
performance against the moisture and direct water. (f8mm multiple cord is recommended
for wiring)

If the end user is intended to adjust the actuation level position independently, please move
the float ball(s) position as well as the interior reed switches, otherwise, it will appear an
error or no signal.

22
FlneTek
Global Network
Germany
China

U.S.
Taiwan U.S.

Singapore

Asia North America Europe


Taiwan California, U.S. Germany
FINETEK CO., LTD. - Taipei Head Quarter APLUS FINETEK SENSOR INC. - US Office FineTeK GmbH - Germany Office
No.16, Tzuchiang St., Tucheng Industrial Park 355 S. Lemon Ave, Suite D, Walnut, Frankfurter Str. 62, OG D-65428
New Taipei City 236, Taiwan CA 91789 Ruesselsheim, Germany
TEL: 886-2-2269-6789 TEL: 1 909 598 2488 TEL: +49-(0)6142-17608-0
FAX: 886-2-2268-6682 FAX: 1 909 598 3188 FAX: +49-(0)6142-17608-20
EMAIL: info@fine-tek.com EMAIL: info@aplusfine.com EMAIL: info@fine-tek.de

FINETEK CO., LTD. - I-Lan Factory Illinois, U.S.


TEL: 886-3-990-9669 APLUS FINETEK SENSOR INC.
FAX: 886-3-9909659 TEL: 1 815 632-3132
FAX: 1 815 716 8464
FINETEK CO., LTD. - Taichung Brance EMAIL: info@aplusfine.com
TEL: 886-4-2337-0825
FAX: 886-4-2337-0836

FINETEK CO., LTD. - Kaohsiung Branch


TEL: 886-7-333-6968
FAX: 886-7-536-8758

China
FINE AUTOMATION CO., LTD. - Shanghai Factory
No.451 DuHui Rd, MinHang District, Shanghai,
China 201109
TEL: 86-21-6490-7260
FAX: 86-21-6490-7276
EMAIL: info.sh@fine-tek.com Distributor:

Singapore
FINETEK PTE LTD. - Singapore Office
No. 60 Kaki Bukit Place, #07-06 Eunos
Techpark 2 Lobby B, Singapore 415979
TEL: 65-6452-6340
FAX: 65-6734-1878
EMAIL: info.sg@fine-tek.com

08-FD-B0-EP, 08/24/2015