Professional Documents
Culture Documents
Abstract— Extra-high voltage underground power cables partial discharge signals within the kit. The sensitivity of
are adopted as the major transmission cable system in most measuring partial discharge over ground such as in a
metropolitan cities of Korea. As a result, any operational termination kit tends to drop compared to the kit
malfunctioning thereof may cause social and economic damage underground or in a manhole. [1-3]
and the ripple effects as well as enormous time and financial
costs. Moreover, as the EHV underground power cables in
Korea have operated for a prolonged time, the necessity for
regular check-ups and other preventive diagnostics becomes
more critical. One of the preventive diagnostic methods is to
detect the VHF partial discharge that could occur inside
terminations or the cables, and this method has been
conducted to decide the current states of underground power
lines. Conventional detection methods for the partial discharge
of the underground cables utilized the detection of the high- Fig. 1. Diagnosing partial discharge and measuring external noise within a
frequency ranges. Contrary to them, this paper described the termination kit
method of detecting and analyzing the partial discharge for the
underground transmission cable terminations at the VHF Figure 1 is an example diagnosing partial discharge and
ranges, and this method can minimize the extraneous noise measuring external noise within a termination kit. The
effect. Also, on-site application of the method is conducted in following research paper provides a method of detecting
this paper in order to test reliability. signals in the VHF/UHF wideband used in the GIS (Gas
Insulated Switchgear) as a measuring technology for EHV
Keywords— Partial Discharge, PD, VHF, UHF underground power cables. It gives a review of the applied
sensor for the measurement of partial discharge within a
I. INTRODUCTION EHV underground power cable termination kit, and an
organization of the research of a partial discharge
The most important characteristic of a partial discharge measurement system using a spectrum analyzer. [4-6]
sensor created in extra-high voltage underground power
cables is that the generation and extinction of partial
II. DEVELOPMENT AND APPLICATION OF A VHF
discharge is very frequent, occurs intermittently in initial
MEASUREMENT SYSTEM
stages of deterioration, and the ampere-hour is very small.
Therefore, it is highly possible that a flaw cannot be detected
in a cable as the measuring time of partial discharge lasts for A. VHF wideband measurement sensor
only a couple of minutes. A suitable measuring technology The sensor developed by the company through mutual
had to be applied and a superior measuring sensitivity and development was used, with the specifications listed below
noise reduction function was required after the testing on Table 1. The sensor measures frequencies ranging from
involving various partial discharge sensors and measuring 2~400MHz and were used for performance testing in
technology in order to extract the miniscule partial discharge construct systems and in spot adoption.
occurring in actual path deficiencies. The reality is that
underground cables’ measured frequency range for partial TABLE I. SPECIFICATIONS OF THE APPLIED SENSOR
discharge is HF(1~50MHz) because the signal reduction
characteristics are very large in high frequencies due to the Model HFCT-400M-40D
high capacitance of the internal insulator within the XLPE
underground transmission cables. External noise and partial
discharge signals are mixed due to the operation conditions Image
of the sealing end of the underground transmission cable,
while the current measuring device for partial discharge
cannot differentiate the noise and partial discharge signals,
which is a broad range mixing external noises and the innate Frequency 2MHz ~ 400MHz
Fig. 11. Zero Span mode classification results per frequency band