Professional Documents
Culture Documents
Uplift Resistance
3.1 Concept and function :
To provide a means to support vertical embedded walls through
anchorage in soil / rock mass outside the excavation area ,thus
enabling clear space for excavation and construction
• Anchors are normally stressed after grout has gained sufficient strength
(normally 1 week).
Anchor Installation
1. Drill the hole.
2. Place the anchor assembly (rod + sleeve+
grouting hoses).
3. Make primary grout injection around all
the length (under low grouting
pressure).
4. Wait a few hours, then make cracking
injection with water before mortar
stiffens up.
5. Make secondary grout injection (high
pressure)
6. Make post grout injection (if required)
7. Stress the anchor to required load level.
3.3 Types of
anchors
(as per BS 8081)
Anchor Installation
1. Drill the hole
2. Place the anchor assembly (rod + sleeve+
grouting hoses)
3. Make primary grouting around all the
length (low grouting pressure).
4. Wait a few hours, then make cracking
injection with water before mortar stiffen
up.
5. Make secondary grout injection (high
press)
6. Make post grouting injection ( if required)
7. Stress the anchor to required load level.
3.5 Anchor capacity (grout-ground bond)
(Canadian Foundations manual)
CHECK OUT CH 4
R πD Ls fmax Anchor Design Doc!!
Where fmax is the maximum friction between soil and grout
fmax σ’z Kf
σ’z = effective vertical stress at the midpoint of the load carrying length (Ls)
Ls = effective embedment length of the anchor
Kf = anchorage coefficient, dependent on the soil type and conditions as given in
table below
Allowable anchor load = , 3
b) Anchors in clay soils τ
fmax = ∝ ; therefore: φu = 0
cu=Su
R = ∝
∝ ; ϭ
0.35 0.75; qu
= average undrained shear strength of the clay over the length of
the anchor.
Allowable anchor load = , 3
Maximum fixed length
According to BS 8081: Ls ≤ 10 m (as no benefit is gained from longer
anchorage)
load
Displ
Empirical anchor capacity may be obtained from the following tables:
For high injection pressure anchors in Sand
- Type C- (based on field measurements)
Remarks on ground anchor capacity
Note:
• Final anchor location is to be
checked for overall stability as
shown later.
• Normally D 150 mm
• In sands, may take D ≃ 250 mm if
not otherwise stated (i.e. 1.67 dbh)
• According to BS 8081 anchor location is determined by the green
line in the figure below
Modes of failure of ground anchors
3
c
Summary of the modes of failure in ground anchors:
1. Tendon failure (Fdesign = (0.5-0.625) fpu )
2. Anchorage body failure:
a) Tendon / Grout bond failure ((fcu ≥ 400 kg/cm2)
>>> 10 kg/cm2 for plain bars; 20 kg/cm2 for
deformed bars)
b) Grout rupture/compression failure (fc’)
c) Grout / ground slippage (R = ?, FS = 3); FS may be
increased to 4 if excessive creep is expected.
3. Failure within ground mass ( watch out for rock
discontinuities or weak soil zones)
4. Anchor head failure
5. Long term deterioration (corrosion protection)
6. Excessive displacement (serviceability requirements)
3.7 Anchor testing and stressing (BS 8081)
• Testing covers:
a) Load-displacement behavior at 80% of tendon ultimate load
(design free length checked)
b) Time-dependent behavior (10-day observation at 110% of
design load Tw).
• Testing:
3 cycles, each taken up to proof load; with 15 min. observation
at Tp, then release and reload to 110% Tw, and lock-off to
start monitoring load-displacement behavior for 10 days.
• Acceptance criteria same as for Proving test
iii) On-site Acceptance Tests
b) Multi-stage anchors
c) Anchor removal !
d) Under-reamed anchors
Bond stress
distribution in
multiple anchor
systems
c) Anchor removal; why? how?
1) Mechanical Methods
a) Gripnut & plate method (USA)
2) Thermal Methods
a) Epoxy resin dissolution (Japan)
b) Oxygen-gas cutting to melt steel and grout locally (France)
3) Explosives Japan)
d) Under-reamed
anchors (Type D)
Best for cu ≥ 0.9 kg/cm2