Professional Documents
Culture Documents
Technologic 500 Series PDF
Technologic 500 Series PDF
and
Technologic 500X Series TM
Pump Controller
! DANGER
DESCRIPTION: Microprocessor based dedicated pump controller for SAFETY
variable volume pumping systems. The controller consists of the following INSTRUCTIONS
components: microprocessor, operator interface with 4 line display and This safety alert symbol will be used in this manual and on the equipment
membrane key pad, and 24 VDC power supply. Safety Instructions decal to draw attention to safety related instructions.
When used, the safety symbol means ATTENTION! BECOME ALERT!
OPERATIONAL LIMITS: See the controller nameplate for operating YOUR SAFETY IS INVOLVED! FAILURE TO FOLLOW THE
voltage and current draw. INSTRUCTIONS MAY RESULT IN SAFETY HAZARD.
! DANGER
Touching electrical parts may be fatal, even after equipment has
been disconnected from AC line. To be sure that capacitors have
fully discharged, wait 14 minutes for 208 V and 460 V units and 30
minutes for 600 V units after power has been removed before
touching any internal component.
2
Table of Contents
3
Section 5 FEEDBACK TRANSMITTER WIRING .......................................................................................................... 26
5.1 Connecting Feedback Transmitters ................................................................................................................................................................. 26
5.2 Single 4 - 20 mA Flow Meter Connection ......................................................................................................................................................... 26
5.3 One or Two 4 - 20 mA Feedback Transmitters Connection .............................................................................................................................. 26
5.4 Two Feedback Signals and Two Setpoints Connection ................................................................................................................................... 27
4
Section 1 GENERAL
1.3 Clearances
NEMA 12
The controller is cooled by air circulation. For
Backplate Required
proper cooling, the minimum distances above X Controller Size Power
and below the unit must be maintained as
1 to 30 HP 200-240 V
shown in the table below. For units in an 1 to 75 HP 380-460 V
auxiliary enclosure with the controller
mounted on a backpanel, the required Backplate Requirements
clearances are measured from the top and
bottom of the controller, not the backpanel. X
Mounting Clearances
5
1.5 Grounding Plate 1.7 UL, C-UL, and CE Conformity
Controllers up to 3 HP, 200 to 240 V, up to 10 HP, 380 to 460 V and All Tech 500 and Tech 500X pump controllers are CE marked, and all
550 to 600 V with a NEMA 1 enclosure have a plastic bottom cover with controllers and option packages are UL and C-UL listed.
provision for conduit entry. To meet UL requirements, the metal
grounding plate must be in place above the plastic bottom cover. The 1.8 Model Numbers
plate must be grounded to the chassis, and the conduit grounded to the The specific installation instructions may vary depending upon the
plate. If the grounding plate is not factory installed, it must be installed in model of Technologic 500 or Technologic 500X series being installed.
the units that have a plastic bottom panel to ensure proper grounding of When this occurs, the model can be identified by a 6XXX number. This
the conduit to the enclosure. Connect the ground wire from the number can be found on the red nameplate on the outside left side of
grounding plate to the ground tab marked with the ground symbol. the controller enclosure, or the outside right side of a controller with an
auxiliary enclosure. A model identification description can be found on
This tab is located near the AC line terminal strip. Mount the bottom the next page.
cover on the control unit.
If unshielded control wires are used, control inputs are subject to signal
disturbances. Such disturbances may affect drive operation. Extreme
noise levels may disturb the microprocessor of the control card.
The shield of the control wires must be grounded at the cable clamp at
the bottom of the controller, but the shield must continue with the cable
all the way up to the control card. The shield is not to be connected to
any of the terminals on the control card. For safety reasons, the
insulation around the shield should only be removed where it is
connected to the cable clamp. The insulation should be left on the shield
between the clamp and the terminals.
6
1.9 Model Number Description 230 Volt Input
7
Section 2 ELECTRICAL CONNECTIONS
NEMA 1
2.1 Power Connections NEMA 1
1. Make all power connections with 75o C rated copper wiring.
2. Conduit entry must be from the bottom on all drives. Conduit
entries are provided on smaller drives. For drives with
auxiliary enclosures, refer to the dimensional drawings
provided for conduit entry locations.
3. To meet UL requirements, install the metal grounding plate in all
drives that have a plastic bottom. Install the grounding plate just
above the plastic bottom. Ground the metal plate to the chassis
and ground the conduit to the metal plate.
4. The conduit entries provide strain relief for the wires in drives
mounted in NEMA 1 or NEMA 12 enclosures. With chassis
mounted drives, the power and control wires must have strain
relief supplied by the installer. DO NOT rely on the terminal
blocks to provide strain relief.
8
2.3 Locations of Conduit Entry, Terminal Blocks NEMA 12
and Switches, NEMA 12
6002-6005, 200 to 240 V; 6002-6011, 380 to 460 V 6006-6032, 200 to 240 V; 6016-6075, 6102, 6122, 380 to 460 V
6042-6062, 200 to 240 V; 6100, 6125, 380 to 460 V 6150-6275, 380 to 460 V
9
2.4 Locations of Conduit Entry, Terminal Blocks NEMA 1 and NEMA 12
and Switches, Drives Over 300 HP
10
2.5 Input Power Connection Drive Input Maximum
Model
Current AWG
For drives with no auxiliary enclosure, connect input power to drive 2.2 10 6002
terminals L1, L2, and L3, (terminal numbers 91, 92, and 93). If an auxiliary 2.5 10 6003
enclosure is provided, input power connections are made in the auxiliary 3.6 10 6004
4.6 10 6005
enclosure. Refer to the connection diagrams shipped with the unit. 5.7 10 6006
8.4 10 6008
Size wiring to the input current as shown in the tables below. Maximum 10.3 10 6011
AWG wire size is also provided. 16.6 6 6016
20.5 6 6022
25.2 6 6027
! CAUTION 29.9
38.3
2
2
6032
6042
Incoming power, motor wiring and control 48.5 1/0 6052
wiring should be run in three separate conduits 57.9 1/0 6062
71.8 1/0 6072
or raceways. 92 4/0 6100
117 4/0 6125
Enclosures for larger drives and auxiliary 134 4/0 6150
enclosures are made of metal. To avoid getting 179 2 x 4/0 6175
226 2 x 4/0 6225
metal chips into electronics, do not drill any 270 2 x 4/0 6275
holes after unit has been installed in a vertical
position.
600 VAC Input Current/Wire Gage
Drive Input Maximum
Model
Current AWG
5.0 10 6002
7.0 10 6003 All current ratings are in amps.
10.0 10 6004
16.0 10 6006
23.0 6 6008
30.0 6 6011 2.6 Motor Wiring Connection
46.0 6 6016
! WARNING
59.2 2 6022
74.8 2 6027
88.0 0 6032 Connecting input power to motor terminals will
101.3 1/0 6042
126.6 3/0 6052 result in drive failure when power is applied.
149.9 4/0 6062 Output motor cables from multiple drives must
be run in separate conduits or raceways.
208 VAC Input Current/Wire Gage
For drives with no auxiliary enclosure, connect the motor to drive
Drive Input Maximum
Current AWG
Model terminals U, V, and W (terminal numbers 96, 97, and 98). Terminal 99
2.5 10 6002 is earth ground. If an auxiliary enclosure is provided, refer to the
3.4 10 6003
connection diagrams shipped with the unit. Ground the shield on the
4.8 10 6004
8.3 10 6006 motor wire, if used, at both the drive and the motor.
10.6 10 6008
14 10 6011 2.7 Grounding
21 6 6016
! DANGER
27.6 6 6022
34 6 6027
41 6 6032 For operator safety, it is important to ground
53 2 6042
64 2 6052
drive properly.
77 2 6062
103 1/0 6075 Ground the drive properly. Use a ground wire at least 7 AWG (10mm2).
145 2/0 6100
174 3/0 6125 Connect the ground wire directly to a reliable earth ground. Do not use
206 2x1/0 6150 the conduit connecting to the drive as a replacement for a ground wire. Do
256 2x1/0 6175
317 2x3/0 6225
not ground one drive to another in a daisy chain fashion.
366 2x4/0 6275
443 3x1/0 6350
540 3x3/0 6400
590 3x3/0 6500
678 3x4/0 6550
11
2.8 Location of Input Power (Mains) and Output
Power (Motor Terminal Blocks)
Connect input power to the terminals identified as L1, L2 and L3.
Connect the motor leads to the terminals identified as U, V and W.
! WARNING
Connecting input power to motor terminals will
result in drive failure when the power is applied.
NEMA 1
6042-6062, 200-240 V
6100, 6125, 380-460 V
6100-6150, 550-600 V
NEMA 1
6006-6032, 200-240 V NEMA 1
6016-6075, 6102, 6122, 380-460 V 6150-6275, 380-460 V
6016-6072, 550-600 V 6175-6275, 550-600 V
12
2.8 Location of Input Power (Mains) and Output
Power (Motor Terminal Blocks), continued
Connect input power to the terminals identified as L1, L2 and L3.
NEMA 12
6006-6032, 200-240 V
6016-6062, 380-460 V
NEMA 12
6150-6275, 380-460 V
NEMA 12
6042-6062, 200-240 V
6075-6125, 380-460 V
13
2.8 Location of Input Power (Mains) and Output
Power (Motor Terminal Blocks), continued
Connect input power to the terminals
identified as L1, L2 and L3.
14
2.9 Electrical Installation, Control Wiring 2.12 Digital Input 33
A spare digital input terminal number 33 is available and programmed
! CAUTION through parameter 307, Digital Input 33. Thirteen preset functions are
Incoming power, motor wiring and control available including reset, freeze reference, hand start, auto start and
wiring should be run in three separate conduits others.
or raceways.
2.13 DIP Switches 1 through 4
Torque: 5 - 6 in-lbs (0.6 - 0.7 Nm) DIP switches are located on the control card.
Screw size: M3
They are used for serial communication and the common of digital
Shielded control wires are recommended. To reduce interference from inputs 16 through 33. The switch positions shown are the factory
electrical noise, ground the cable shield at a cable clamp, as shown settings.
below, at both ends. Connect the shield to the grounded clamp. Very
long control wires may create 60 Hz interference. To resolve this,
connect one end of the shield to earth with a 0.1 µF capacitor, keeping
the leads as short as possible. If interference persists, disconnect the
grounded shield connection at the end opposite to the drive.
Switch 1 is not used.
2.10 Electronic Thermal Protection Switch 4 separates the common for the internal 24 VDC supply from the
The electronic thermal relay is UL approved for single motor thermal common of the external 24 VDC supply. Normally this switch is ON and
protection as long as the following is complied with: the power supply is present at terminals 12 and 13. Set Switch 4 to the
OFF position when an external 24 VDC supply is used.
1. Parameter 117, Thermal Protection, is set to ETR TRIP.
2. Parameter 105, Motor Current, is set for the full-load nameplate
motor current.
15
2.14 Ground Leakage Current 2.16 Electrical Noise
It is normal for there to be some leakage current from the drive to earth In general, electrical noise can be divided into two forms: wire-borne
ground. Paths of current leakage are shown on the drawing below. electromagnetic interference (EMI), and radiating radio frequency
The leakage current will exceed 3.5 mA. interference (RFI).
2.15 Galvanic Isolation Using shielded motor cables reduces RFI but increases EMI. This is
Galvanic isolation offers protection from electric shock. All control because shielded wires have a greater capacitance than unshielded
terminals of all Tech 500 pump controllers, and terminals 1 through 3 of wires. Unshielded input power connections to the drive generate more
the relay output, offer galvanic isolation as long as the RFI switch (if noise in the radio frequency range on the AC line. The shield reduces
provided) is in the ON position. The galvanic isolation in the Tech 500 the radiated noise, but increases the low-frequency electromagnetic
conforms to the European standard EN 50178. noise on the AC line. But, since the noise current is taken back to the
unit through the shield, only a small electromagnetic field is generated
The components that make up the galvanic isolation are: from shielded motor wires.
1. Power supply, including signal isolation.
With an EMI filter, the noise level on the AC line will be reduced to about
2. Gate drive for IGBTs, trigger transformers and optocouplers.
the same level for shielded and unshielded wires alike.
3. Output current Hall effect transducers.
Connect the motor wiring shield, if used, in the enclosure of the drive as
well as at the motor. Use shield brackets to avoid pigtail shield ends.
Even short pigtails increase the shields impedance at higher
frequencies, which reduces the shields effect and increases the noise
produced.
16
2.17 Terminal Tightening Torque
Tighten terminals connecting the controller input power, output to the 380 to 460 VAC Terminal Tightening Torque
motor(s) and ground to the values shown in the tables below. Units with
200 to 240 volts of 88 amps and less, and units with 380 to 600 volts of 90
Max. Drive Torque Max. Drive Torque
amps and less, have removable terminal blocks with screws. Larger units
Output Current in-lbs (Nm) Output Current in-lbs (Nm)
have fixed bolts. (See the controller nameplate for maximum drive output
to 10 5 (0.6) 147 100 (11.3)
current.)
16 5 (0.6) 177 100 (11.3)
24 17 (1.8) 212 100 (11.3)
32 17 (1.8) 260 100 (11.3)
37.5 17 (1.8) 315 100 (11.3)
44 28 (3.0) 368 100 (11.3)
61 28 (3.0) 487 372 (42.0)
200 to 240 VAC Terminal Tightening Torque 73 28 (3.0) 594 372 (42.0)
90 28 (3.0) 649 372 (42.0)
Max. Drive Torque 106 100 (11.3) 746 372 (42.0)
Output Current in-lbs (Nm )
6.6 5 (0.6)
7.5 5 (0.6)
10.6 5 (0.6)
16.7 5 (0.6)
550 to 600 VAC Terminal Tightening Torque
24.2 17 (1.8)
30.8 17 (1.8) Max. Drive Torque
46.2 28 (3.0) Output Current in-lbs (Nm)
59.4 28 (3.0)
74.8 28 (3.0) to 11 5 (0.6)
88 35 (4.0) 27 17 (1.8)
114 100 (11.3) 41 28 (3.0)
143 100 (11.3) 77 35 (4.0)
169 100 (11.3) 144 100 (11.3)
289 100 (11.3)
All current ratings are in amps.
200-208 V Max Overload In/Out Power Main Disco Drive Disco MN/BYP Fuse Drive Fuse Ground
CTK Breaker
Output Relay Terminal Switch Switch BLK BLK Terminal
59.4 A 40 (4.5) 175 (19.8) 44 (5) 18 (2) 18 (2) 120 (13.6) 120 (13.6) 50 (5.6)
74.8 A 40 (4.5) 175 (19.8) 44 (5) 55 (6.2) 55 (6.2) 120 (13.6) 275 (30.1) 50 (5.6)
88 A 40 (4.5) 175 (19.8) 44 (5) 70 (7.9) 70 (7.9) 120 (13.6) 275 (30.1) 50 (5.6)
114 A 200 (22.6) 275 (30.1) 275 (30.1) 375 (42.4) 375 (42.4) 275 (31.1) N/A 50 (5.6)
143 A 200 (22.6) 275 (30.1) 275 (30.1) 375 (42.4) 375 (42.4) 275 (31.1) N/A 50 (5.6)
169 A 200 (22.6) 275 (30.1) 275 (30.1) 375 (42.4) 375 (42.4) 450 (50.8) N/A 275 (30.1)
All current ratings are in amps. All torques are in in-lbs (Nm). All TB1 connections must be torqued to 8 in-lbs (0.9 Nm).
17
2.17 Terminal Tightening Torque (continued)
230-240 V Max Overload In/Out Pow er Main Disco Drive Disco MN/BYP Fuse Drive Fuse Ground
CTK Breaker
Output Relay Term inal Sw itch Sw itch BLK BLK Term inal
46.2 A 40 (4.5) 175 (19.8) 44 (5) 18 (2) 18 (2) 45 (5.1) 45 (5.1) 50 (5.6)
59.4 A 40 (4.5) 175 (19.8) 44 (5) 18 (2) 18 (2) 120 (13.6) 120 (13.6) 50 (5.6)
74.8 A 40 (4.5) 175 (19.8) 44 (5) 55 (6.2) 18 (2) 120 (13.6) 275 (30.1) 50 (5.6)
88 A 40 (4.5) 175 (19.8) 275 (30.1) 70 (7.9) 55 (6.2) 275 (31.1) 275 (30.1) 50 (5.6)
104 A 40 (4.5) 175 (19.8) 275 (30.1) 375 (42.4) 70 (7.9) 275 (31.1) N/A 50 (5.6)
130 A 200 (22.6) 275 (30.1) 275 (30.1) 375 (42.4) 375 (42.4) 275 (31.1) N/A 50 (5.6)
154 A 200 (22.6) 275 (30.1) 275 (30.1) 375 (42.4) 375 (42.4) 450 (50.8) N/A 275 (30.1)
380-460 V Max Overload In/Out Power Main Disco Drive Disco MN/BYP Fuse Drive Fuse Ground
CTK Breaker
Output Relay Terminal Switch Switch BLK BLK Terminal
61 A 40 (4.5) 175 (19.8) 44 (5) 18 (2) 18 (2) 45 (5.1) 120 (13.6) 50 (5.6)
73 A 40 (4.5) 175 (19.8) 44 (5) 55 (6.2) 18 (2) 120 (13.6) 120 (13.6) 50 (5.6)
90 A 40 (4.5) 175 (19.8) 44 (5) 70 (7.9) 55 (6.2) 120 (13.6) 275 (30.1) 50 (5.6)
106 A 40 (4.5) 175 (19.8) 275 (30.1) 375 (42.4) 70 (7.9) 275 (31.1) N/A 50 (5.6)
147 A 200 (22.6) 275 (30.1) 275 (30.1) 375 (42.4) 375 (42.4) 275 (31.1) N/A 50 (5.6)
177 A 200 (22.6) 275 (30.1) 275 (30.1) 375 (42.4) 375 (42.4) 275 (31.1) N/A 275 (30.1)
212 A 200 (22.6) 275 (30.1) 275 (30.1) 375 (42.4) 375 (42.4) 450 (50.8) 500 (56.5) 275 (30.1)
260 A 200 (22.6) 375 (42.4) 275 (30.1) 500 (56.8) 500 (56.8) 450 (50.8) 500 (56.5) 275 (30.1)
315 A 375 (42.4) 375 (42.4) 275 (30.1) 500 (56.8) 500 (56.8) 450 (50.8) 275 (30.1) 275 (30.1)
368 A 375 (42.4) 375 (42.4) 275 (30.1) 500 (56.8) 500 (56.8) 375 (42.4) 375 (42.4) 275 (30.1)
Current ratings are in amps. Torques are in in-lbs (Nm). All TB1 connections must be torqued to 8 in-lbs (0.9 Nm).
18
2.17 Terminal Tightening Torque (continued)
550-600 V Max Overload In/Out Power Main Disco Drive Disco MN/BYP Fuse Drive Fuse Ground
CTK Breaker
Output Relay Terminal Switch Switch BLK BLK Terminal
52 A 40 (4.5) 175 (19.8) 50 (5.6) 70 (7.9) 55 (6.2) 120 (13.6) 120 (13.6) 50 (5.6)
62 A 40 (4.5) 175 (19.8) 50 (5.6) 70 (7.9) 55 (6.2) 120 (13.6) 120 (13.6) 50 (5.6)
77 A 40 (4.5) 175 (19.8) 275 (30.1) 70 (7.9) 55 (6.2) 120 (13.6) 120 (13.6) 50 (5.6)
99 A 40 (4.5) 175 (19.8) 275 (30.1) 375 (42.4) 70 (7.9) 275 (31.1) 275 (30.1) 50 (5.6)
125 A 200 (22.6) 275 (30.1) 275 (30.1) 375 (42.4) 375 (42.4) 275 (31.1) N/A 50 (5.6)
144 A 200 (22.6) 275 (30.1) 275 (30.1) 375 (42.4) 375 (42.4) 275 (31.1) N/A 275 (30.1)
192 A 200 (22.6) 275 (30.1) 275 (30.1) 375 (42.4) 375 (42.4) 450 (50.8) N/A 275 (30.1)
242 A 375 (42.4) 375 (42.4) 275 (30.1) 500 (56.8) 500 (56.8) 450 (50.8) 500 (56.5) 275 (30.1)
289 A 375 (42.4) 375 (42.4) 275 (30.1) 500 (56.8) 500 (56.8) 375 (42.4) 275 (30.1) 275 (30.1)
Current ratings are in amps. Torques are in in-lbs (Nm). All TB1 connections must be torqued to 8 in-lbs (0.9 Nm).
19
Section 3 USER INTERFACE
3.1 Programming through the LCP [CHANGE DATA] is used for changing a parameter
The combined display and keypad on the front of the Tech 500 is called setting selected in either the Extend Menu or the Quick
the Local Control Panel (LCP). The LCP is the user interface to the Menu mode.
pump controller.
[CANCEL] is used if a change to a selected parameter
The LCP has several user functions: programming the controller; is not to be carried out.
displaying operational data, along with warnings and cautions; to reset
the controller after a fault; to manually alternate pump selection; and, in [OK] is used for confirming a change to a selected
local control, to start/stop and control the speed of the Tech 500. parameter.
20
3.5 Tech 500/500X Control RESET is used for manually resetting the drive after a
The keys below the indicator lamps are used for Start/Stop control fault trip (alarm) or pump/AFD fail. In this case, the top
and selection of the operating site. Keys for control of the drive are line of the display will show TRIP (RESET). If the top
described below. line of the display shows TRIP (AUTO START), the
drive will automatically restart. If the top line of the
display shows TRIPLOCK (DISC. MAINS), input power
to the drive must be removed before the trip can be
reset.
[OFF/STOP] is used for stopping the connected Line 4 (bottom line) automatically displays the operating status of the
motor in Hand or Auto mode. If the stop function is drive (see 6.5 Status Messages).
activated, the main display will flash. This key can
be disabled in parameter 013. The active setup number and an arrow indicating the direction of motor
rotation is shown. Clockwise indicates forward and counterclockwise
[AUTO START] is used if the Tech 500/500X is to indicates reverse. The arrow body is removed if a stop command is
be controlled through the control terminals. When a given or if the output frequency falls below 0.01 Hz.
start signal is active on the control terminals and/or
Warnings and alarms (fault trips) will also be displayed. During an
serial bus, the unit will start.
alarm, ALARM and the alarm number is shown on the large display. An
explanation is given in line 3 or in lines 3 and 4. For a warning,
! WARNING WARN. and the warning number is shown with an explanation in line 1.
Tech 500/500X can start at anytime with a start Both alarms and warnings cause the display to flash.
signal through digital inputs. Digital inputs have
higher priority than control keys [HAND START]
and [AUTO START]. VAR1.1 VAR1.2 VAR1.3
P1
VAR 2
P2 P3
SETUP
STATUS
21
Operating data options for the first and second line of the LCP display: 3.6.2 Display Mode II
This display mode shows three operating data values in the top line
Data Item: Unit:
Resulting reference, % %
programmed via parameters 007, 008, and 009. Pressing the
Resulting reference, unit [unit] [DISPLAY MODE] key toggles between Display Modes I and II.
Frequency Hz
% of maximum output frequency %
Motor current A
Power kW
Power HP 10.0U 10.0U 500U
Output energy kWh
Hours run
Used-defined readout
Setpoint 1
hours
[unit]
[unit]
50.0Hz SETUP
1
Setpoint 2 [unit] P2:R P3:R P1:O
Feedback 1 [unit]
Feedback 2 [unit] AUTO REMOTE RUNNING
Feedback [unit]
Motor voltage V
DC-link voltage V
Thermal load on motor %
Thermal load on drive % 3.6.3 Display Mode III
Input status, digital input [binary code] Press and hold the [DISPLAY MODE] key while in Mode II. Mode III is
Input status, analog terminal 53 V
Input status, analog terminal 54 V visible as long as the key is depressed. The top line changes to identify
Input status, analog terminal 60 mA the data names and units displayed. Lines 2 and 4 are unchanged.
Output status, relay status [binary code]
Pulse reference Hz When the key is released, the display returns to Mode II.
External reference %
Heat sink temperature °C
User-defined text [-]
PID output [unit]
FB analog input 60 [mA] FEED 1 FEED 2 FLOW
Three operating data values can be shown in the first display line and
one in the large display line, programmed via parameters 007, 008,
009, and 010.
60.0Hz SETUP
1
P1:R P2:R P3:O
3.6.1 Display Mode I AUTO REMOTE RUNNING
In Display mode I, the drive is in Auto mode with reference and control
determined via the control terminals. Below is an example in which the
drive is running in setup 1, in Auto mode, with a remote reference, and
at an output frequency of 40 Hz. Pump 2 is currently the lead pump 3.6.4 Display Mode IV
with Pump 3 running and Pump 1 off. This display mode is used for local operation, where the local speed
reference is given from the keypad. In this display mode, the reference
The text in line 1, FREQUENCY, describes the meter shown in the is determined via the [+] and [-] keys. Control is carried out through the
large display. Line 2 (large display) shows the current output bottom keys on the keypad. The first line indicates the required
frequency (40.0 Hz), direction of rotation (reverse arrow), and active reference. The third line gives the relative value of the output
setup (1). Line 3 reports pump status. Line 4 is the status line and the frequency in the form of a bar graph in relation to the maximum
information is automatically generated for display by the drive in frequency.
response to its operation. It shows that the drive is in auto mode, with a
remote reference, and that the motor is running. See Status Messages
section for a detailed description of line 4 data.
USE +/- 40Hz
P2:R
40.0Hz
P3:R P1:O
SETUP
22
3.7 Changing Data 3.7.3 Changing Listed Numeric Values
Regardless of whether a parameter has been selected under the Quick A few parameters offer numeric lists of values that can be selected from
Menu or the Extend Menu, the procedure for changing data is the or changed. This means that if the numeric value is not listed, a value
same. Pressing the [CHANGE DATA] key gives access to changing the may be entered using the procedure for changing numeric values. This
selected parameter. Line 3 displays the parameter number and title. applies to parameter 102, Motor power; parameter 103, Motor voltage;
The underlined function or number flashing in line 4 on the display is and parameter 104, Motor frequency.
subject to change.
3.8 Enter/Change Quick Menu Parameter Data
The procedure for changing data depends on whether the selected Enter or change parameter data or settings in accordance with the
parameter represents a numerical data value or a function. following procedure.
24.2Hz SETUP
1
205 MAX.REFERENCE
000060.000 Hz
MOTOR CURRENT
3.90 A SETUP
1
210 REFERENCE TYPE
SUM
The functional value flashes until signing off by pressing the [OK]
button. The functional value has then been selected. Use [CANCEL] to
ignore the change.
23
3.9 Example of Changing Parameter Data 3.12 Uploading/Downloading Parameters
Assume Parameter 206, Ramp Up Time, is set at 60 seconds. Change The local control panel (LCP) has the capability to store and transfer all
the ramp up time to 100 seconds in accordance with the following the parameters programmed into the Tech 500/500X controller. Setup
procedure. data stored in the LCP is useful as a backup for preserving initial
setting. This data can be downloaded from the LCP to the drive to
1. Press [QUICK MENU] key.
reestablish initial parameter settings, if so desired.
2. Press [+] key until you reach Parameter 206, Ramp Up Time.
3. Press [CHANGE DATA] key. This feature is also useful when setting up multiple drives. LCPs are
4. Press t key twice hundreds digit will flash. removable and interchangeable. Once setup information has been
5. Press [+] key once to change hundreds digit from 0 to 1. uploaded from the drive, the LCP may be connected to another drive
6. Press u key to move cursor to tens digit.
and all parameter setting downloaded to quickly program additional
7. Press [-] key until 6 counts down to 0 and setting for Ramp Up
drives with identical settings.
Time reads 100 s.
8. Press [OK] key to enter new value into drive controller. To upload data, use the Extended Menu to find parameter 004, LCP
Copy. Select Upload All Parameters to store parameter settings
NOTE (including motor data) into the LCP. LCP Copy will be displayed while
Programming parameter functions available data is uploading. This may take a minute or two. To download data,
through Extended Menu key is done in select either Download All Parameters or Download
accordance with same procedure described for
Power-independent Parameters (to exclude motor data entered in
Quick Menu functions.
parameters 102 through 106).
3.10 Extended Menu Manually initializing the drive using parameter 620, Operating Mode,
In some applications, the Quick Menu will not access additional does not change the values stored in the LCP.
parameters necessary to set up the drive. To access all parameters,
including Quick Menu items, use the Extended Menu. The Extended
Menu is enabled by pressing the [EXTEND. MENU] key.
! CAUTION
Initialization using parameter 620, Operating
Mode, will reset drive to default parameters. Any
special application programming performed at
factory, during start-up or thereafter, will be lost.
24
Section 4 START UP
4.1 Pre-installation Checks Protect signal wires from noise.
1. Compare drive model number to what was ordered. Ground each controller and drive individually.
2. Ensure each of following are rated for same voltage: Double check input and output power wiring for correct location.
Controller
Power line ! WARNING
Motor Ensure that all safety instructions in this manual
3. Record following motor data: as well as all local safety requirements have
Voltage been satisfied prior to applying power to unit.
Frequency 4.3 Apply Power to Controller
Full load current Installation, start-up and maintenance should only be performed by
Full load speed qualified personnel.
Power convert HP to kW (See conversion table in this
4.4 Setting Up Controller for Motor Start
manual.)
Enter motor nameplate data into controller parameters in the following
4. Ensure that rated controller current is equal to or greater than total
sequence:
full load current.
For multiple motor operations, add up full load current ratings of 08 MOTOR POWER, parameter 102 (in kW) (See conversion table in
all motors. this manual.)
Controller can be at most one size smaller than motor. 09 MOTOR VOLTAGE, parameter 103
If rating is less than motor, full motor output cannot be achieved. 10 MOTOR FREQUENCY, parameter 104
5. Check motor wiring: 11 MOTOR CURRENT, parameter 105
Any disconnect between controller and motor should be 12 MOTOR SPEED, parameter 106
interlocked to safety interlock circuit to avoid unwanted trips. Press HAND START key to initiate operation in local control.
No power factor correction capacitors can be connected between
4.5 Operational Tests, HAND
controller and motor.
1. Check motor rotation from drive. If incorrect, disconnect input
Two speed motors must be wired permanently for full speed.
power from drive and reverse two leads between drive and motor.
Y-start, r-run motors must be wired permanently for run. 2. If a bypass is provided, check motor rotation in bypass mode. If
4.2 Installation Checks incorrect, disconnect input power from drive and reverse two input
1. Input fusing in power supply for all controllers must be provided. power leads.
2. Environmental concerns for standard NEMA 1 drive: 3. Accelerate motor quickly to full speed and verify operation.
4. Decelerate motor quickly to stop and verify operation.
Clean air supply
5. Operate motor over entire speed range while closely checking for
Dry air (max 95% relative humidity, non-condensing)
resonance.
14oF to 104oF ambient temperature operating range, or as rated
3,300 foot maximum elevation with no derating 4.6 Operational Tests, AUTO
3. Mounting 1. Ensure that controller follows run/stop and safety interlock
Vertical commands from system.
Controllers with heat sink fins exposed in back of unit must be 2. Ensure controller follows speed reference or feedback from system.
mounted against a solid surface (see Clearances section in this
4.7 General Troubleshooting
manual).
1. Display Messages:
Keep any construction dirt out of controller.
AUTO STARTController has tripped off and is in process of
4. Wiring
automatically restarting.
Wire controller in accordance with instructions and diagrams TRIPController has tripped off. Press RESET to start.
received with unit.
TRIP LOCKEDController has tripped off. Remove and apply
Separate conduits must be provided to controller for input power, power before restarting with RESET.
output power, and control wiring. 2. Refer to Warnings and Alarms section in this manual.
Note that safety interlock and remote run/stop circuitry is 115 VAC 3. Check tightness of all connections and wires for proper location.
for controllers with bypasses. 4. Measure input signals.
Use knockouts or conduit entry plates. Avoid metal shavings in cabinet. 5. Check controller input and output for balanced voltage and current.
25
Section 5 FEEDBACK TRANSMITTER WIRING
The input scaling of the Tech 500 analog inputs in this case would have
to be 2 - 10 Volt.
26
5.4 Two Feedback Signals and Two Setpoints Parameter Description Factory Setting
Connection
415 REF./FDBK UNIT PSI
Similar to two feedback signals and one setpoint, the need for two
413 MIN. FEEDBACK 0
feedback signals with two setpoints is frequently encountered. 414 MAX. FEEDBACK 100
Whenever two critical zones do not have the same setpoint value, two 417 2 FEEDBACK CALC. 2 ZONE MIN.
feedback with two setpoint control is required. Many pumping systems 308 AI [V] 53 FUNCT. FEEDBACK
require the monitoring and control of two loads that differ in size and 309 AI 53 SCALE LOW 2V
310 AI 53 SCALE HIGH 10 V
pressure drop.
311 AI [54] 54 FUNCT. NO OPERATION
312 AI 54 SCALE LOW 2V
To enable this setup, the feedback function in parameter 417, Feedback
313 AI 54 SCALE HIGH 10 V
Function, is selected. When selecting 2-zone Minimum in parameter
417, the drive will regulate the system so the feedbacks are equal to or
greater than their associated setpoints. If 2-zone Maximum is selected,
the feedbacks will be equal to or less than their associated setpoints.
The transmitters are connected to the Tech 500 in the same way as
shown in 5.3 Two 4 - 20 mA Feedback Transmitters Connection with
1 setpoint and 2 feedbacks. The feedback connected to terminal 53 is
assigned to setpoint 1 and the one connected to terminal 54 to setpoint
2. Both transmitters must have the same output signal and range.
27
Section 6 TECH 500 CONTROLLER SETUP
6.1 Introduction The quick menu items for programming the Tech 500 are arranged in
A quick menu list is activated by pressing the Quick Menu key on the the following sequence (see block diagram):
controller keypad. The 29 item quick menu allows programming the
01 07, 13 and 14 setup basic controller options for Tech 500
Tech 500 controller, basic pump functions, and fine tuning the internal
operation.
PID controller. For programming a Tech 500X pump controller, see
08 12 establish basic motor settings.
Section 7.
15 - 25 set pump parameters for system control.
The items on the quick menu are arranged in order for sequencial 26 - 29 provide instructions for fine tuning the PID controller for
programming. Review the factory settings prior to programming since operation after system start.
these settings frequently meet operational requirements. Many of the The remaining drives are programmed by entering data for quick menu
Tech 500 programming features may already be set. items 08 - 14 in sequence into each drive.
To program the Tech 500 for typical operation, scroll through the quick The Tech 500 has four independent setups that can be programmed.
menu items and enter the appropriate data required. Additional The initial programming in this chapter is stored as Setup 1.
parameter settings are available which can be selected through the
extended menu. The quick menu is designed to provide access to The Tech 500 has been programmed with factory settings typical for
those items most commonly used in setup and system operation. See operation. These settings may be satisfactory for initial start up of the
Section 3 User Interface for procedures on accessing and setting drive system.
parameters.
MOTOR
08 Motor Power
09 Motor Voltage
10 Motor Frequency
11 Motor Current
12 Motor Rated Speed
MICROPROCESSOR
28
6.2 Quick Menu Setup Instructions for Tech 500
See 3.7 Enter/Change Quick Menu Parameter Data for instructions on
entering and changing parameter data.
Quick Para. Name Units Range Factory Setting
Menu Number
Number
01 418 Setpoint 1 PSI Min. Ref. to Max. Ref. 0
Set the desired setpoint 1 value within the range of Min. Reference to Max. Reference.
11 105 Motor Current Amps 0.01 to VLT rating Depends on drive and
motor settings.
Set the motor current value in amps that equals the nameplate value of the motor.
12 106 Motor Nominal Speed RPM 100 to 60,000 Depends on drive and
motor settings.
Set the rated motor speed value in RPM that equals the nameplate value of the motor.
29
Quick Para. Name Units Range Factory Setting
Menu Number
Number
20 774 High System Pressure Units 0 to 999,999.999 Disable
Set the value when High System Pressure Alarm will be activated. A value of 0 will disable the high
system pressure function.
21 775 High System Proof Timer Sec. 0 to 999 0
Set the proof time prior to high system pressure shutdown.
6.3 Setup Instructions for AFD 2 and AFD 3 6.4 HP to kW Convertion Table
AFD 2 and AFD 3 drives run in open loop mode and receive stop/start
and speed reference commands from the Tech 500 controller. Each )1 L8 )1 L8
drive must be programmed with the nameplate data from the motor it 0.4 0.25 50 37
controls. For normal operation, all other parameter settings must remain 0.5 0.37 60 45
at factory default settings or match the settings in the Tech 500. 0.75 0.55 75 55
1.0 0.75 100 75
1. Program AFD 2 and AFD 3 drives for operation by entering motor 1.5 1.10 125 90
data for parameters 102 through 106, in sequence. 2 1.50 150 110
2. Ensure that parameter 100, Configuration, is set for Open Loop. 3 2.20 200 132
3. Ensure that the setting for Min. Frequency (parameter 201) and
4 3.00 250 160
Max. Frequency (parameter 202) match those of the Tech 500
5 4.00 300 200
pump controller Min. Frequency and Max. Frequency.
7.5 5.50 350 250
4. Ensure that terminal 17 (parameter 301) is set for Pulse Output.
10 7.50 400 300
15 11 420 315
20 15 450 355
25 18.5 500 400
30 22 540 450
40 30 600 500
30
Section 7 TECH 500X CONTROLLER SETUP
MOTOR
102 Motor Power
103 Motor Voltage
104 Motor Frequency
105 Motor Current
106 Motor Rated Speed
CONTROLLER
CONTROLLER SETTINGS
418 Setpoint 1
PUMP 419 Setpoint 2
417 Feedback Calculation
712 Pump Combination 414 Max. Feedback
713 Staging Bandwidth 201 Min. Frequency
714 SBW Stage OFF Delay Timer 202 Max. Frequency
715 SBW Stage ON Delay Timer 205 Max. Reference
716 Override Bandwidth 723 Mode Select
717 OBW Timer
718 Transition Frequency
721 Destage Timer
762 Max. Feedback 60
776 NFSD Proof Timer
777 Min. Speed Proof Timer
778 Restart PV Drop
779 Min. Run Timer PID CONTROLLER TUNING
780 Pump Min. Frequency for NFSD
781 Pump Max. Frequency for NFSD 422 PID Start-up Frequency
782 NF Power at Min. Frequency 423 PID Proportional Gain
783 NF Power at Max. Frequency 424 PID Integrator Time
784 Multiplier for NF Detection 427 PID Lowpass Filter Time
31
7.2 Setup Instructions for Tech 500X
Set parameter data in the order listed since some selections entered
change options available for items later in the list. See 3.7
Enter/Change Quick Menu Parameter Data for instructions on entering
and changing parameter data.
32
7.2 Setup Instructions for Tech 500X (continued)
33
7.2 Setup Instructions for Tech 500X (continued)
PID Tuning
34
Section 8 STATUS MESSAGES
A. The first part of the status line indicates the CONTROL POINT of P1:R
40.0 Hz P2:R P3:0
SETUP
The energy saving function in parameter 403, Sleep Mode Timer, is enabled.
This status message shows that at present the motor has been stopped by
sleep mode. It can restart automatically.
START DEL
! DANGER
When in Start Delay mode, motor may restart at any time
without warning.
A start delay time has been programmed in parameter 111, Start Delay.
When the delay has passed, the drive will start and ramp up to the reference
frequency.
35
8.2 Table of Status Messages (continued)
DISPLAY DESRIPTION
WORD
RUN REQ.
! DANGER
When in Run Request mode, motor may restart at any time
without warning.
A start command has been given, but the motor will not be started until a
Run Permission signal is received via a digital input.
JOG Jog has been enabled via a digital input or via serial communication.
JOG REQ.
! DANGER
When in Jog Request mode, motor may restart at any time
without warning.
A start command has been given, but the motor will remain stopped until a
Run Permission signal is received via a digital input.
FRZ.OUT The output frequency has been frozen.
FRZ.REQ
! DANGER
When in Freeze Request mode, motor may restart at any time
without warning.
A start command has been given, but the motor will remain stopped until a
Run Permission signal is received via a digital input.
START F/R Reversing and start on terminal 19, parameter 303, Digital Inputs, and Start
on terminal 18, parameter 302, Digital Inputs, are enabled at the same time.
The motor will remain stopped until one of the signals becomes a logic ‘0.’
AMA RUN Automatic motor adaptation has been enabled in parameter 107, Automatic
Motor Adaptation, AMA.
AMA STOP Automatic motor adaptation has been completed. The drive is now ready for
operation after the Reset signal has been given. Note that the motor will start
after the drive has received the Reset signal.
STANDBY The drive is able to start the motor when a start command is received.
STOP The motor has been stopped via a stop signal from serial communication.
DC STOP The DC brake has been enabled in parameters 114 through 116.
UN.READY The drive is ready for operation, but terminal 27 is a logic ‘0’ and/or a
Coasting Command has been received via the serial communication.
CTR.READY This status is only active when a Profibus option card is installed.
NOT READY The drive is not ready for operation, because of a trip or because OFF1,
OFF2 or OFF3 is a logic ‘0.’
START IN. This status will only be displayed if, in parameter 599, Profidrive [1] has been
selected and OFF2 or OFF3 is a logic ‘0.’
XXXX The microprocessor of the control has stopped and the drive is not
operating. The cause may be noise on the power line, motor leads or control
wires.
36
8.3 Table of Additional B&G Parameters
No. N am e U n its L o w L im it H ig h L im it F a c to ry D e fa u lt
Parameter
No. Title Changes
111 Start Delay Changed default value from 0 to 20 sec.
301 Terminal 17 Digital Input System Start/Stop: removing control voltage
initiates a sequenced stop. The PID controller
is stopped and reinitializes.
302 Terminal 18 Digital Input Programming Lock: applying control voltage
prevents programming the drive from the
keypad. Data Change Locked is displayed
when the [CHANGE DATA] key is pressed.
303 Terminal 19 Digital Input AFD-1 Input: receiving control voltage confirms
the AFD is running for drive failure detection.
304 Terminal 27 Digital Input Add Low Suction Cut Out: a normally closed
pressure switch opens when pressure is
available; a timer issues a warning and trips
the drive at time out expiration.
305 Terminal 29 Digital Input AFD-2 Input: receiving control voltage confirms
the AFD is running for drive failure detection.
306 Terminal 32 Digital Input AFD-3 Input: receiving control voltage confirms
the AFD is running for drive failure detection.
317 All Zone Fail Proof Time All Zone Failure Timeout: low feedback signals
on terminals 53 and 54 issues an alarm and
the drives ramp to a preset user-defined speed.
One low signal causes a warning to be issued
with continued system operation.
319 Terminal 42 Output PID Pulse Output: the PID controller exports a
0 - 5000 Hz pulse for speed reference. The
reference output continues in drive stop mode.
37
Section 9 AUTOMATIC BYPASS
9.1 Mode of Operation 9.1.1 Setup A1
The automatic bypass option allows for bypassing the Tech 500 TECH 500 controller One 100% A1 constant speed Three-contactor
controller to run directly from input line power. The Tech 500 has three pump bypass drive bypass
available configurations as standard. In the event of drive failure detection, the pump controller can
automatically start the pump across the line. For a motor or pump
Setup A1
failure, the controller can automatically shut down the system. Reset the
Setup B3
controller manually after the fault has been cleared. The
Setup C4/D4
Drive/Off/Bypass/Test switch can be used to manually select system
The active setup is displayed on the keypad display under the word operation in bypass from line power (bypass), from the controller
setup. Setup is selected in parameter 002, Active Setup. The following (drive), or to shut the system off.
parameters must be programmed for automatic bypass operation.
9A
9B
NO contact
8A
Bypass
8B
7A
7B
6A
6B
U/V/W
A1 Bypass
"PUMP 1"
38
9.1.2 Setup B3
9A
9B
NO contact
8A
Bypass
8B
7A
Select pump 2
7B
6A
Select pump 1
6B
U/V/W
B3 Bypass unit
DIGITAL INPUT
"Pump 1"
16: (RESET)
Motor/Pump/
17: (SYSTEM START)
DP-switch
18: (PROGRAMMING LOCK)
29: ()
NO
32: (PUMP 1 INPUT) switch
"Pump 2"
Motor/Pump/
DP-switch
+24V
NO
switch
39
9.1.3 Setup C4/D4
9A
Bypass pump2
9B
NO contact
8A
Bypass pump1
8B
7A
7B
6A
Start slave 1
6B
D4 Bypass unit
NO NO
switch switch
40
9.2 Options Single-point Power Connection
The bypass architecture for the Tech 500 controller allows for a variety A single incoming power connection supplies power for all drives and
of optional control, indicator, and protective features. bypasses, when supplied. The terminals mount in the Tech 500 fused-
disconnect or bypass enclosure.
Local/Off/Remote Switch Master Drive Failure Protection (Optional)
The Local/Off/Remote switch controls power to the Tech 500 system. In This option monitors the Tech 500 for functionality. If the
the Local position, the system will be ON (connected to terminal 17 on Drive/Off/Bypass switch is in the Drive position and voltage is not being
the Tech 500 controller). In the OFF position, the system will be OFF. supplied to the drive (two or three drive fuses are cleared), the unit is
In Remote, the Tech 500 system is ON or OFF based on a contact hardwired to JOG all available drives. The component(s) for this
closure, such as from a building management system. In the single- function are mounted in the Tech 500 fused-disconnect or bypass
drive configuration this switch is mounted on the fused-disconnect enclosure option.
enclosure door.
Motor 1/Auto/Motor 2 Switch (B3 bypass only)
Drive/Off/Bypass Switch (Two-contactor bypass) A manual three-position Motor 1/Auto/Motor 2 selector switch mounted
A manual three-position Drive/Off/Bypass switch for each two-contactor on the option enclosure door electrically selects which motor is
bypass is mounted on the bypass enclosure door to electrically select operated. In the Auto mode, the Tech 500 pump controller determines
whether a motor is powered from the Tech 500 controller (Drive), the which motor is operated via two of its Form C relays. The Motor 1 or
AC line (Bypass), or is disconnected from both (Off). Motor 2 positions of the manual switch determine which respective
motor is operated.
Drive/Off/Bypass/Test Switch (Three-contactor bypass)
A manual four-position switch mounted on the bypass enclosure door Drive Input Fuses
electrically selects whether the motor is powered by the drive, the AC Fast-acting, semiconductor input drive fuses provide short-circuit
line or is disconnected from both. In the Test mode, the motor is protection to the drive.
disconnected from the controller and powered by the line, but power is
also applied to the controller for test purposes. Bypass Fuses
Dual-element, time-delay fuses provide short-circuit protection to the
Fused Drive Disconnect Switch motor while running in bypass. These fuses mount in the bypass
A drive disconnect with drive input fuses allows manual switching of enclosure.
input power to the Tech 500 controller and provides the controller with
short-circuit protection. The switch and fuses are mounted below the Motor Overload
controller in a separate fused-disconnect enclosure. The drive itself offers overload protection for one motor. A separate
overload must be used with the bypass and is mounted in the bypass
Main Panel Disconnect Switch enclosure. The overloads normally open auxiliary contact is
A main ON/OFF disconnect switch for switching input power for the factory-wired to the pump 1 digital input of the controller.
entire panel is mounted on the bypass enclosure.
41
Section 10 PUMP ALTERNATION AND RELAY STATUS
1
P1:R P2:R P3:O
the failed pump until manual reset of the system. The standby pump
complies with the pump alternation characteristics described in 10.1, AUTO REMOTE RUNNING
with or without automatic bypass. Standby applies to the last pump in
the current alternation sequence.
Relay open: 0
10.1.3 Pump On Time Relay closed: 1
Parameter 724: Pump 1 NOTE
Parameter 725: Pump 2 For readout via serial communication, parameter
Parameter 726: Pump 3 537 must be used.
A timer accumulates hours the pump has run. The counter is updated Bit 7 = Relay 01
10 times per hour which means that cycles less than 6 minutes are not Bit 6 = Relay 02
registered. The hours can be reset to zero when a pump is replaced. Bits 5 - 4 = Relays 06 - 07
42
Section 11 WARNINGS AND ALARMS
11.1 Warning and Alarm Displays 11.2 Description and Remedy
A warning will flash on the large display line along with the warning The table in 8.3 Table of Alarms and Warnings gives Tech 500/500X
number. The explanation is displayed on the top (line 1). warnings and alarms and indicates whether the fault trip-locks the
drive. An alarm is issued when the drive is tripped (discontinues
operation). A warning is issued when an alarm condition is impending.
LOW SUCTION CUT OUT After a trip-lock fault, the input power must be removed, the cause of the
fault corrected, and input power restored to reset the drive. Table 8.3
WARN.72
P1:R P2:R P3:R
SETUP
1
also describes the common remedies for the fault condition.
If the Tech 500/500X trips, the controller will continue to operate and
will not perform a sequenced stop providing power is supplied to the
AUTO REMOTE RUNNING
Tech 500/500X card.
Where an X is placed under both warning and alarm in the table in
TRIP (RESET)
8.3, this means that a warning precedes the alarm. After a trip, the
ALARM 72
LOW SUCTION CUT OUT
SETUP
1
motor will be coasting and the drive warning and alarm indications will
flash. If the fault is removed, only the alarm will flash. After a reset, the
drive will be ready to start operation again.
43
11.3 Table of Alarms and Warnings
4 MAINS PHASE LOSS X X X Phase missing on the input power. Check the
supply voltage to the drive.
44
11.3 Table of Alarms and Warnings (continued)
45
11.3 Table of Alarms and Warnings (continued)
15 SWITCH MODE FAULT X X Fault in the switch mode power supply (internal
±15 V supply).
46
11.3 Table of Alarms and Warnings (continued)
29 HEAT SINK OVERTEMP. X X The heatsink temperature became too high. For
NEMA 1 drives, the limit is 90°C. For NEMA 12
drives, the limit is 80°C. The tolerance is ±5°C.
The fault cannot be reset until the temperature of
the heatsink has fallen below 60°C.
35 OUT FREQ RNG/ROT LIM X This warning will occur if the output frequency
has reached its Output Frequency Low Limit ,
parameter 201, or Output Frequency High Limit,
parameter 202. If the drive is in Closed Loop,
parameter 100, the warning will show in the
display.
47
11.3 Table of Alarms and Warnings (continued)
40 CHECK P.103 & P.106 X Parameter 103, Motor Voltage, or 105, Motor
Current, has not been set correctly. Correct the
setting and run AMA again.
41 MOTOR TOO BIG X The motor used is probably too large for AMA to
be carried out. The setting in parameter 102,
Motor Power, may not match the motor. Check
the motor and select Continue or press [STOP]
key.
42 MOTOR TOO SMALL X The motor used is probably too small for AMA to
be carried out. The setting in parameter 102
Motor Power, may not match the motor. Check
the motor and select Continue or press [STOP]
key.
63 I MOTOR <I LOW X X The output current is lower than parameter 221,
Warning: Low Current. Select the required
function in parameter 409, Function in Case of
No Load.
64 I MOTOR >I HIGH X The output current is higher than parameter 222,
Warning: High Current.
48
11.3 Table of Alarms and Warnings (continued)
72 LOW SUCTION CUT OUT X X Low suction pressure has been detected. Check
the suction pressure and suction pressure switch
setting.
73 ALL ZONE FAILURE X The controller is not receiving any zone sensor
signal(s). Check wiring, polarity, piping and
continuity.
Drive 208 to 230 volt 380 to 460 volt 550 to 600 volt
VDC VAC VDC VAC VDC VAC
Undervoltage alarm 211 151 402 289 557 413
Voltage warning, low 222 159 423 304 613 443
Voltage warning, high 384 276 777 530 943 667
Overvoltage alarm 425 305 798 550 975 689
49