You are on page 1of 2

Anna-Merian-Straße 5

D-48599 Gronau-Epe
Tel:+49(0)2565/9346-0
Automatisierung Fax:+49(0)2565/7848
homepage:http://www.kima.de

Drive Check-List A ID: 1612BC01.MT01 Name: Belt conveyor 1 motor Page 1

drive type: FC

specials: PTC-Thermistor separately driven fan x current measurement


other: SIMOCODE

power: 3,7 kW

date of check: 29.08.2019 commissioning engineer: KIMA

functional test:

existing tested
control circuit fuse x x measured current input: 3,5 A
bimetal circ.breaker x x nominal current: 7,8 A
current range: VSD14-20A A
phase failure relay set current value: 7,8 A
repair switch
local control station x x
horn at manual time
fault warning
warning inactiv delay (s)
additional fault 1 x x type: belt off track 1 left DE x x x 10
additional fault 2 x x type: belt off track 1 right DE x x x 10
additional fault 3 x x type: belt off track 2 left NDE x x x 10
additional fault 4 x x type: belt off track 2 right NDE x x 10
additional fault 5 x x type: pull cord switch x 0
additional fault 6 x x type: speed monitoring x x 15

other el. Devices

drive rotation test x rotation: x clockwise counter clockwise

visual inspection x yes no remarks:

remarks: ISO Messung L1-PE / L2-PE / L3-PE / L1-L2 / L2-L3 / L3-L1 > 1000 MΩ

Customer: Project:
Loesche BIM SON CS Date, Signature customer
Projectnumber: Editor:
160223 SU Date, Signature KIMA
Anna-Merian-Straße 5
D-48599 Gronau-Epe
Tel:+49(0)2565/9346-0
Automatisierung Fax:+49(0)2565/7848
homepage:http://www.kima.de

Drive Check-List B ID: 1612BC01.MT01 Name: Belt conveyor 1 motor Page 2

manual operation:
x yes no x continuous running non maintained command mode

additional interlockings in manual mode start / type of type of


cont. external bus-
stop contact contact
x yes no condition
Signal system trans.
NC NO
Simocode Test Position x x

overall stop in manual mode


x yes no Quickstop / Quickstop from Group, MCC Phase/ Undervoltage protection

automatic mode:
x yes no Einschaltverzögerung 2 s Ausschaltverzögerung 30 s
group: 1612G01, 1612G11
additional selections: 1612R01/1612R11

additional interlockings in automatic mode start / type of type of


cont. external bus-
stop contact contact
x yes no condition
Signal system trans.
NC NO
Simocode Test Position x x
acc. VP 4E.12686 x x

overall stop in automatic mode


x yes no Quickstop Raw Material"

Customer: Project:
Loesche BIM SON CS Date, Signature customer
Projectnumber: Editor:
160223 SU Date, Signature KIMA