Design calculation sheet

Project no: Q07019 Date: 6/6/2007 Sheet no.: 1 of 1 Computed by: A.B
3
Checked by: A.K
Subject: Transformer room forced ventilation
Approved by: T.Z

Heat dissepation in the transformer room = 10 Kw

= 34121.4 BTH

Qs = 1.08 x CFM x ∆T

Design temperature @ Transformer room =38 Degree C

= 100.4 Degree F

and ambient temperature = 32 Degree C


= 89.6 Degree F

Then ∆T = 10.8 Degree F

Then forced ventilation rate ( CFM ) =2925.36

= 1379.89 L/s

an exhaust fan will be provided with the above rate & fresh air intake louver will be provided for air make up