You are on page 1of 70

  Transmission System Analysis

  Capacity Building to Bangladesh Power


Sector
  Module A – Short Circuit Analysis
  07/09 February 2017
Short Circuit Analysis - Session 5

Table of Contents
Capacity Building to the
Bangladesh
Power Sector

 Short Circuit Analysis


 Fault Current Contribution
 Modelling of Transmission System
 Accurate Short Circuit Simulations
 IEC Short Circuit Calculations
 PSSE Short Circuit Analysis Examples

Project undertaken by a consortium led


2 by Ricardo Energy & Environment
2
Short Circuit Analysis - Session 5

Introduction to Short Circuit Analysis (1)


Capacity Building to the
Bangladesh
Power Sector

Short circuits incidents


- Power transmission system is composed of a wide range of equipment
- Failure of equipment due to a fault or short circuit on network elements is unavoidable
- Many factors can cause a short circuit fault, such as a lightning strike, a falling object on
equipment, or mal-operation, etc.

Effect of short circuit


- Undesirable large fault currents
- Voltage drops at the faulted point and around the faulted network
- Damage equipment due to large amount of fault current
- Excessive transient over-voltages during the period of fault clearance
- Hazardous to personnel nearby

Project undertaken by a consortium led


3 by Ricardo Energy & Environment
3
Short Circuit Analysis - Session 5

Introduction to Short Circuit Analysis (2)


Capacity Building to the
Bangladesh
Power Sector

Mitigation of short circuit current impact


- Designing and operating the system to reduce the likelihood of short circuit occurrence
- Detecting short circuit conditions as quick as possible by protection devices
- Managing the magnitude of the short circuit currents
- Isolating the portion of the system around the faulted area as small as possible

Short circuit analysis:


- As necessary for any power system as other fundamental power system analysis, such as
power flow and transient stability analysis, etc.
- A vital approach to understanding fault current patterns and designing mitigation
solutions to short circuit in the system
- Undertaken in system planning, design and operation

Project undertaken by a consortium led


4 by Ricardo Energy & Environment
4
Short Circuit Analysis - Session 5

Introduction to Short Circuit Analysis (3)


Capacity Building to the
Bangladesh
Power Sector

Purpose of short circuit analysis:


- Verification of the adequacy of interrupting equipment
o Checking adequacy of existing equipment
o Sizing adequacy of new equipment
- Determination of settings for protection devices
o Calculation of maximum fault currents
o Calculation of minimum fault currents
o Determination of settings for protection relays
- Determination of effects of fault currents on system components
o Fault ratings and fault withstand capability
- Assessment of the effect of various faults
o Retained voltage profiles for various faults
o Impact on system stability

Project undertaken by a consortium led


5 by Ricardo Energy & Environment
5
Short Circuit Analysis - Session 5

Requirements of Short Circuit Analysis


Capacity Building to the
Bangladesh
Power Sector

Short circuit analysis involves


- Application of faults at various points on the network
- Calculation of the resulting fault current flows.

Short circuit analysis in planning stage


- Help to finalize the transmission system layout
- Identify transmission system voltage levels, and
- Size cables, transformers and conductors

Short circuit analysis in operation stage


- Identify impact of adding new generators and large motors onto the system
- Verify adequacy of existing circuit breakers and other equipment
- Check impact of network reconfiguration
- Rearrange protection equipment
- Duplicate the reasons and system conditions leading to a system failure

Project undertaken by a consortium led


6 by Ricardo Energy & Environment
6
Short Circuit Analysis - Session 5

Types of Short Circuit Faults


Capacity Building to the
Bangladesh
Power Sector

Symmetrical faults
- Three phase fault (<5%)
o Solid three phase fault
o Fault via impedance

Asymmetrical faults
- Single phase to earth fault (up to 75%)
- Phase to phase fault
( 15~20%)
- Double phase to earth fault
- The fault could be solid or via a fault impedance

Project undertaken by a consortium led


7 by Ricardo Energy & Environment
7
Short Circuit Analysis - Session 5

Short Circuit Fault Level


Capacity Building to the
Bangladesh
Power Sector

Short circuit (SC) fault level:


- Shows severity of a potential fault in the system in terms of MVA rather than Amps
- Makes it easier to compare faults at different voltage levels
- Is normally represented in Amps, kA, kVA or MVA
- SC level is related to the fault location

SC level varies inversely with


- The Thevenin equivalent impedance seen at the fault point
- If SC is large, the network is ‘strong’, if SC is small, the network is ‘weak’

Factors influencing the fault level:


- Proximity to generators
- Number of generators connected to the system
- Network topology
- Transformer vector group

Project undertaken by a consortium led


8 by Ricardo Energy & Environment
8
Short Circuit Analysis - Session 5

Impact of Topology on SC Fault Current


Capacity Building to the
Bangladesh
Power Sector

jX’’d jX’’d

Z TH  ( X / / X )  X d''
X
jX jX   X d'' jX jX
2

Z TH  ( X / /3 X )  X d''
jX jX jX jX
3
 X  X d''
4

Project undertaken by a consortium led


9 by Ricardo Energy & Environment
9
Short Circuit Analysis - Session 5

Extent of Short Circuit Analysis


Capacity Building to the
Bangladesh
Power Sector

3-phase symmetrical short circuit


- Usually the most onerous fault current case
- Balanced RMS fault currents
- Necessary to calculate the make current (IEC 10ms) and break current (CB
operating time values)
- Make current needs to include the decayed DC current component
- Positive phase sequence network data used for the fault current calculation

1-phase or two phase asymmetrical short circuits


- Phase to earth and line to line with and without earth
- Positive, negative and zero sequence network data used for the fault current
calculation

Project undertaken by a consortium led


10 by Ricardo Energy & Environment
10
Short Circuit Analysis - Session 5

Maximum System Fault Levels


Capacity Building to the
Bangladesh
Power Sector

Maximum system fault level calculation


- To size equipment
- To verify fault withstand capability of existing switchgear and equipment

Assumptions made to calculate maximum system fault level


- Intact network topology
- Interconnection with the neighbouring AC system
- Maximum demand scenario
- All generating units and motors in the system potentially switched on
- Solid fault without fault impedance

Project undertaken by a consortium led


11 by Ricardo Energy & Environment
11
Short Circuit Analysis - Session 5

Minimum System Fault Levels


Capacity Building to the
Bangladesh
Power Sector

Minimum system fault level calculation


- To meet protection setting requirement
- To confirm connection compliance of new generators and loads onto the system

Assumptions made to calculate minimum system fault level


- Network may not have the intact topology
- Interconnection with the neighbouring AC system may be switched off
- Minimum load demand scenario
- The number of generators switched onto the system is minimum
- An actual operational scenario, in which the fault level could be the minimum case

Project undertaken by a consortium led


12 by Ricardo Energy & Environment
12
Short Circuit Analysis - Session 5

Fault Level Terms


Capacity Building to the
Bangladesh
Power Sector

Peak fault current


- Maximum instant current value normally at 10ms after the fault

Symmetric fault current


- Fault current AC RMS component (excluding DC component)

DC fault current
- DC fault current component only

Asymmetric fault current


- Instant DC + symmetric fault currents

Project undertaken by a consortium led


13 by Ricardo Energy & Environment
13
Short Circuit Analysis - Session 5

Fault Current Component Calculation


Capacity Building to the
Bangladesh
Power Sector

Initial peak fault current

I peak  2 I sym  I DC

Asymmetric fault current

I Asym  I DC
2
 I sym
2

Worst case asymmetric fault current

I Asym  2 2  I sym

Project undertaken by a consortium led


14 by Ricardo Energy & Environment
14
Short Circuit Analysis - Session 5

DC Current Component vs XR Ratio


Capacity Building to the
Bangladesh
Power Sector

These graphs are the


exponential decay, or DC
decay

These assume that R and


X are constant

Project undertaken by a consortium led


15 by Ricardo Energy & Environment
15
Short Circuit Analysis - Session 5

AC Components of Fault Current


Capacity Building to the
Bangladesh
Power Sector

The ac component consists of:


- Sub-transient ac component (around
1~2 cycles) characterised by sub-
transient reactance Xd” and short
circuit sub-transient time constant Td”
- Transient ac component (around 5~6
cycles after the sub-transient)
characterised by transient reactance
Xd’ and short circuit transient time
constant Td’
- Steady state ac component (after
completion of the transient decay
(characterised by synchronous
reactance Xd)

Project undertaken by a consortium led


16 by Ricardo Energy & Environment
16
Short Circuit Analysis - Session 5

DC Component of Fault Current


Capacity Building to the
Bangladesh
Power Sector

The dc current component decays


exponentially according to:

- Where:
- Ik’’ = initial symmetrical short circuit
current (RMS) (kA)
- τ = decay time constant (s)
- t = time since fault inception (s)
- The time constant τ, is dependant on the
system reactance, X and resistance, R and
at frequency f is given by:

Project undertaken by a consortium led


17 by Ricardo Energy & Environment
17
Short Circuit Analysis - Session 5

Fault Current Waveforms


Capacity Building to the
Bangladesh
Power Sector

For a fault, the abc three phase fault current waveforms differ due to phase
angle at the fault instant

Project undertaken by a consortium led


18 by Ricardo Energy & Environment
18
Short Circuit Analysis - Session 5

Table of Contents
Capacity Building to the
Bangladesh
Power Sector

 Short Circuit Analysis


 Fault Current Contribution
 Modelling of Transmission System
 Accurate Short Circuit Simulations
 IEC Short Circuit Calculations
 PSSE Short Circuit Analysis Examples

Project undertaken by a consortium led


19 by Ricardo Energy & Environment
19
Short Circuit Analysis - Session 5

Fault Contribution
Capacity Building to the
Bangladesh
Power Sector

Fault contribution sources


- Only components or devices with energy storage contribute to fault current
- Generators (and other rotating machines) contribute bulk of fault current
- Induction motors contribute small amount of fault current
- Grid infeed contribution fault current without considering ac component decay,
representing an equivalent system far away to the fault point

Project undertaken by a consortium led


20 by Ricardo Energy & Environment
20
Short Circuit Analysis - Session 5

Synchronous Machine Fault Contribution (1)


Capacity Building to the
Bangladesh
Power Sector

Symmetrical three phase fault


- A fault occurs near generator terminal
- Fault currents have both AC and DC components.
- Fault currents could be divided into three periods:
o The sub-transient period
o The transient period
o The steady state fault current, i.e. the transient is largely over.
- The initial total fault current is dominated by Xd”
- The initial total fault current ac component will decay in accordance with the short circuit
time constant Td” and Td’
- The dc component will be determined by Xd” as well, but decay with a time constant Ta.
- X/R ratio of the generator plays an important role to the dc component decay.

Project undertaken by a consortium led


21 by Ricardo Energy & Environment
21
Short Circuit Analysis - Session 5

Synchronous Machine Fault Contribution (2)


Capacity Building to the
Bangladesh
Power Sector

Fault Current:
- Sub-transient component Sub-transient

- Transient component Transient

- Steady state component Steady-state

E q"
i 
"

X d"
E q'
i' 
X d'
Eq
i steady _ state 
Xd

Simplified Fault Current Calculation


1 1 1 −t 1 1 −t 1 −𝑡
ia = 2E sin ωt + θ + ′ − e T ′d sin ωt + θ + − e T "d sin ωt + θ − 𝑒 𝑇𝑎 sin 𝜃 − 𝜑
Xd Xd Xd Xd" Xd′ 𝑋𝑑"

( X d"  X q" )
Ta  - E is the terminal no-load voltage
ra
- Td”,Td’, short circuit time constants
- Ta, dc component decay time constants
Project undertaken by a consortium led
22 by Ricardo Energy & Environment
22
Short Circuit Analysis - Session 5

Synchronous Machine Parameters


Capacity Building to the
Bangladesh
Power Sector

Key machine parameters in fault calculation


- Sub-transient reactance Xd’’ and short circuit time constant Td”
- Transient reactance Xd’ and short circuit time constant Td’
- Synchronous reactance Xd
- Time varying reactance values used to represent fault at different time periods
o Xd’’ and Td” for sub-transient AC component immediately following the fault
o Xd’ and Td’ for transient AC component, a few cycles (10-20ms) following the fault
o Xd for steady state AC component, approximately 100-200ms following the fault

- The saturated values of Xd”, Xd’ and Xd used for fault calculation
- X2 and X0 used for unsymmetrical fault current calculation
o X2  XdX
" "
q applicable to sub-transient, transient and steady state unsymmetrical fault
calculation
o X0 normally provided by generator manufacturer

Project undertaken by a consortium led


23 by Ricardo Energy & Environment
23
Short Circuit Analysis - Session 5

Motor FL Contribution
Capacity Building to the
Bangladesh
Power Sector

Fault contribution composition: R  Rs


XmXr
X'  Xs 
- AC component with a decay time constant T’ Xm  Xr
(Xr  Xm) X' X'
T 
'
  ,
- DC component with a decay constant Tdc Rr ( X S  X m ) Rr
X'
Tdc 
E ' t / T ' E '  t / Tdc Rs
iac  ' e , idc  2 'e ,
X X

Fault equivalent circuit:

R X’

Isc
E’

Project undertaken by a consortium led


24 by Ricardo Energy & Environment
24
Short Circuit Analysis - Session 5

Grid Infeed FL Contribution


Capacity Building to the
Bangladesh
Power Sector

Fault Current:
- No sub-transient and transient
components
- Steady state component equals
to initial AC component
- DC component decay in
accordance with time constant
calculated based on X and R
- Applicable to a fault far away
from the equivalent Grid Infeed

Project undertaken by a consortium led


25 by Ricardo Energy & Environment
25
Short Circuit Analysis - Session 5

Table of Contents
Capacity Building to the
Bangladesh
Power Sector

 Short Circuit Analysis


 Fault Current Contribution
 Modelling of Transmission System
 Accurate Short Circuit Simulations
 IEC Short Circuit Calculations
 PSSE Short Circuit Analysis Examples

Project undertaken by a consortium led


26 by Ricardo Energy & Environment
26
Short Circuit Analysis - Session 5

Positive Sequence Network


Capacity Building to the
Bangladesh
Power Sector

All elements are represented by positive sequence impedance


- Synchronous machines
o Ra+ jXd” for sub-transient period
o Ra +jXd’ for transient period
o Ra+jXd for steady state

- Induction motors
o R+jX”

- OHL and cable circuits


o R1 + jX1, jB1

- Transformers
o R1+jX1 with off-nominal tap ratio

- Shunt capacitor banks and shunt reactors


o The equivalent R1, X1 based on the given MVAr capacity and shunt losses.

Project undertaken by a consortium led


27 by Ricardo Energy & Environment
27
Short Circuit Analysis - Session 5

Negative Sequence Network


Capacity Building to the
Bangladesh
Power Sector

All elements are represented by negative sequence impedance


- Synchronous machines
o Ra+jX2, X2  X d" X q"

- Induction motors
o The equivalent X”

- OHL and cable circuits, equal to their positive sequence impedance


o R1 + jX1, jB1

- Transformers, equal to their positive sequence impedance


o R1+jX1 with off-nominal tap ratio

- Shunt capacitor banks and shunt reactors


o The equivalent R1, X1 based on the given MVAr capacity and shunt losses.

Project undertaken by a consortium led


28 by Ricardo Energy & Environment
28
Short Circuit Analysis - Session 5

Zero Sequence Network


Capacity Building to the
Bangladesh
Power Sector

All elements are represented by zero sequence impedance


- Synchronous machines
o Ra +jX0, X0: zero sequence reactance provided by machine manuifacturer

- OHL and cable circuits


o R0 + jX0, jB0
o Rm0+jXm0 mutual impedance between two or more circuits

- Transformers
o R0+jX0 with off-nominal tap ratio
o Winding group

- Shunt capacitor banks and shunt reactors


o The equivalent R0, X0 based on the given MVAr capacity and shunt losses
o Phase connection type and neural earthing conditions

Project undertaken by a consortium led


29 by Ricardo Energy & Environment
29
Short Circuit Analysis - Session 5

Transmission System Sequence Network


Capacity Building to the
Bangladesh
Power Sector

Project undertaken by a consortium led


30 by Ricardo Energy & Environment
30
Short Circuit Analysis - Session 5

Three Phase Fault Current


Capacity Building to the
Bangladesh
Power Sector

Z0
I0
E1
If 
Z1
Z1

I1
E1 Key Note:
- Only positive sequence current
- No negative and zero sequence currents
Z-2
I2

Project undertaken by a consortium led


31 by Ricardo Energy & Environment
31
Short Circuit Analysis - Session 5

Single Phase to Earth Fault Current


Capacity Building to the
Bangladesh
Power Sector

Z0
I0 3E1
If 
Z 0  Z1  Z 2

Z1
Key Note:
I1 - Equal positive, negative and zero sequence
E1
currents
- Equivalent to connecting the three sequence
circuits in series
Z2
I2

Project undertaken by a consortium led


32 by Ricardo Energy & Environment
32
Short Circuit Analysis - Session 5

Two Phase Fault Current


Capacity Building to the
Bangladesh
Power Sector

Z0
E1
I0 If 
Z1  Z 2

Z1
1
Key Note:
I
E1 - Equal positive and negative sequence currents
- No zero sequence current available

Z2
I2

Project undertaken by a consortium led


33 by Ricardo Energy & Environment
33
Short Circuit Analysis - Session 5

Two Phase to Earth Fault Current


Capacity Building to the
Bangladesh
Power Sector

Z1

I1
E1
E1
If 
Z1  Z 2 // Z 0

Key Note:
Z0 Z2
- Negative sequence and zero sequence circuits
I0 I2
are connected in parallel

Project undertaken by a consortium led


34 by Ricardo Energy & Environment
34
Short Circuit Analysis - Session 5

Table of Contents
Capacity Building to the
Bangladesh
Power Sector

 Short Circuit Analysis


 Fault Current Contribution
 Modelling of Transmission System
 Accurate Short Circuit Simulations
 IEC Short Circuit Calculations
 PSSE Short Circuit Analysis Examples

Project undertaken by a consortium led


35 by Ricardo Energy & Environment
35
Short Circuit Analysis - Session 5

Accurate Short Circuit Calculation


Capacity Building to the
Bangladesh
Power Sector

Detailed model of the transmission system


- Detailed modeling of all network components in the system
o Network topology for positive, negative and zero sequence current paths
o Sequence impedance of generators, motors, transmission circuits and transformers
o Transformer winding connection and phase angle difference between HV, LV and TV windings
o Neutral earthing point and impedance
o Neutral connections of generators, transformers, and shunts

- Pre-fault network operating condition


o Pre-fault load flows
o Loading currents in network components
o Pre-fault voltage at a faulted point

- Conversion of load flow case may be necessary depending upon fault calculation
requirements

Project undertaken by a consortium led


36 by Ricardo Energy & Environment
36
Short Circuit Analysis - Session 5

Short Circuit Simulations (1)


Capacity Building to the
Bangladesh
Power Sector

Applying a fault
- Based on the constructed sequence network, apply a fault at the concerned bus
- Fault type could be three phase, single phase to earth, or phase fault, etc.

Calculating equivalent sequence impedance at the fault point


- Equivalent positive sequence impedance
- Equivalent negative sequence impedance
- Equivalent zero sequence impedance

Project undertaken by a consortium led


37 by Ricardo Energy & Environment
37
Short Circuit Analysis - Session 5

Short Circuit Simulations (2)


Capacity Building to the
Bangladesh
Power Sector

Calculating fault currents across the network


- Total fault current flowing through the fault point
- Sequence fault current on network components
- Phase fault current on network components

Calculating retained voltages across the network


- Retained sequence voltage at buses across the network including at the neutral of
transformers and generators
- Retained phase voltage at buses across the network

Project undertaken by a consortium led


38 by Ricardo Energy & Environment
38
Short Circuit Analysis - Session 5

Table of Contents
Capacity Building to the
Bangladesh
Power Sector

 Short Circuit Analysis


 Fault Current Contribution
 Modelling of Transmission System
 Accurate Short Circuit Simulations
 IEC Short Circuit Calculations
 PSSE Short Circuit Analysis Examples

Project undertaken by a consortium led


39 by Ricardo Energy & Environment
39
Short Circuit Analysis - Session 5

IEC 60909 Fault Current Calculation (1)


Capacity Building to the
Bangladesh
Power Sector

IEC 60909 short circuit calculation


- Applicable to low voltage three phase AC system
- Applicable to high voltage three phase AC system below 550 kV
- Applicable to both balanced and unbalanced short circuit cases

Assumptions made for IEC 60909 short circuit calculation


- Only an equivalent voltage source is introduced at the faulted point
- The impedance of the transformer is referred to the tap-changer in main position.
- All line capacitances and shunt admittances and non-rotating loads, except those of the
zero-sequence system, are neglected

Project undertaken by a consortium led


40 by Ricardo Energy & Environment
40
Short Circuit Analysis - Session 5

IEC 60909 Fault Current Calculation (2)


Capacity Building to the
Bangladesh
Power Sector

Initial symmetrical short-circuit current


- Defined as the AC symmetrical component of a prospective (available) short-circuit
current applicable at the instant of short-circuit.

Peak short-circuit current


- Defined as the maximum possible instantaneous value of fault current reached in a
phase following the short –circuit, including the dc component.

Project undertaken by a consortium led


41 by Ricardo Energy & Environment
41
Short Circuit Analysis - Session 5

IEC 60909 Fault Current Calculation (3)


Capacity Building to the
Bangladesh
Power Sector

Symmetrical short-circuit breaking current


- Defined as the r.m.s. value of an integral cycle of the symmetrical ac component of the
prospective short-circuit current at the instant of contact separation of the first pole to
open of a switching device.

Steady state short-circuit current


- Defined as the r.m.s. value of the short-circuit current which remains after the decay of
the transient phenomena

Project undertaken by a consortium led


42 by Ricardo Energy & Environment
42
Short Circuit Analysis - Session 5

Pre-fault Voltage
Capacity Building to the
Bangladesh
Power Sector

- IEC defines a voltage factor to be


used as the pre-fault voltage for the
voltage source in fault current
calculation.
- The voltage source is the only active
voltage in the system.
- All network feeders and synchronous
and asynchronous machines are
replaced by their internal
impedances

Project undertaken by a consortium led


43 by Ricardo Energy & Environment
43
Short Circuit Analysis - Session 5

Far-from-generator Short Circuit


Capacity Building to the
Bangladesh
Power Sector

- A “ far-from-generator” short-circuit is defined as a short-circuit during which the


magnitude of the symmetrical ac component of the prospective current remain
essentially constant
- No ac component decay

Project undertaken by a consortium led


44 by Ricardo Energy & Environment
44
Short Circuit Analysis - Session 5

Near-to-generator Short Circuit


Capacity Building to the
Bangladesh
Power Sector

- A “ Near-to-generator” short-circuit is defined as a short-circuit to which at least one


synchronous machine contributes a prospective initial symmetrical short-circuit current
which is more than twice the machine's rated current, or a short circuit to which
asynchronous motors contribute more than 5 % of the initial symmetrical short circuit
current without motors
- ac component decaying

Project undertaken by a consortium led


45 by Ricardo Energy & Environment
45
Short Circuit Analysis - Session 5

Motor Fault Contribution


Capacity Building to the
Bangladesh
Power Sector

- Synchronous motors and synchronous compensators contribute to initial symmetrical,


peak make, rms break, and steady state fault currents.
- asynchronous motors contribute only to initial symmetrical, peak make, and rms break
fault currents.
- Low-voltage public motors in public supply systems would not contribute any fault
currents and can be neglected.
- Some low-voltage motors which are connected through a two winding transformer can be
neglected as well if their capacity is relatively small
- Low voltage motors, if their fault contribution considered, can be grouped together as
an equivalent motor

Project undertaken by a consortium led


46 by Ricardo Energy & Environment
46
Short Circuit Analysis - Session 5

Comparison with other Approaches


Capacity Building to the
Bangladesh
Power Sector

- IEC 60909 short circuit calculation is based on generic factors and worst-case
parameters
- It provides greater degree of safety when level of data is limited
- Generally IEC60909 produces more pessimistic fault current results than other
commercial short-circuit calculation software packages

Project undertaken by a consortium led


47 by Ricardo Energy & Environment
47
Short Circuit Analysis Examples - Session 6

Table of Contents
Capacity Building to the
Bangladesh
Power Sector

 Short Circuit Analysis


 Fault Current Contribution
 Modelling of Transmission System
 Accurate Short Circuit Simulations
 IEC Short Circuit Calculations
 PSSE Short Circuit Analysis Examples

Project undertaken by a consortium led


48 by Ricardo Energy & Environment
48
Short Circuit Analysis Examples - Session 6

Sequence Network and Data in PSSE (1)


Capacity Building to the
Bangladesh
Power Sector

Positive sequence network data


- Established in the load flow study
- Generator X-source data should use Xd” with saturated value
- Positive sequence resistance and reactance equal to R-source and X-source

Negative sequence network data


- OHL circuits, cables, transformers and other static equipment use the corresponding
positive sequence data as negative sequence data
- Generator use the specified negative sequence data
- Generator negative sequence resistance may differ from its positive sequence resistance

Project undertaken by a consortium led


49 by Ricardo Energy & Environment
49
Short Circuit Analysis Examples - Session 6

Sequence Network and Data in PSSE


Capacity Building to the
Bangladesh
Power Sector

Zero sequence network data


- OHL circuits, cables, shunts use the calculated or given zero sequence data
- Mutual zero sequence impedance between neighbouring circuits need to be considered
- Transformers use the calculated or given zero sequence data including winding group
- Generators use the specified zero sequence data

Sequence data structure


- Strictly follow the order or sequence specified in PSSE user manual
- Creation of the xxx.seq file

Sequence data appended to the power flow case


- Open xxx.raw or xxx.sav case file
- Append xxx.seq file to the power flow case
- Review sequence network model and data

Project undertaken by a consortium led


50 by Ricardo Energy & Environment
50
Short Circuit Analysis Examples - Session 6

Network Sequence Data in PSSE


Capacity Building to the
Bangladesh
Power Sector
0, 32 / PSS®E-32.0 THU, FEB 02 2017 13:10
1,'1 ', 2.96000E-03, 1.10000E-01
2,'2 ', 2.96000E-03, 1.10000E-01
......
0 / END OF POSITIVE SEQ. MACHINE IMPEDANCE DATA, BEGIN NEGATIVE SEQ. MACHINE DATA
1,'1 ', 2.96000E-03, 1.10000E-01
2,'2 ', 2.96000E-03, 1.10000E-01
......
0 / END OF NEGATIVE SEQ. MACHINE IMPEDANCE DATA, BEGIN ZERO SEQ. MACHINE DATA
1,'1 ', 2.96000E-03, 1.10000E-01
2,'2 ', 2.96000E-03, 1.10000E-01
.....
0 / END OF ZERO SEQ. MACHINE IMPEDANCE DATA, BEGIN NEGATIVE SEQ. SHUNT DATA
0 / END OF NEGATIVE SEQ. SHUNT DATA, BEGIN ZERO SEQ. SHUNT DATA
5200, 0.00000E+00, 5.00000E-05
0 / END OF ZERO SEQ. SHUNT DATA, BEGIN ZERO SEQ. NON-TRANSFORMER BRANCH DATA
100, 387,'1 ', 1.35000E-3, 7.40000E-4, 0.07088, 0.00000E+0, 0.00000E+0, 0.00000E+0, 0.00000E+0
100, 700,'1 ', 1.07700E-2, 8.68600E-2, 0.00742, 0.00000E+0, 0.00000E+0, 0.00000E+0, 0.00000E+0
......
0 / END OF ZERO SEQ. NON-TRANSFORMER BRANCH DATA, BEGIN ZERO SEQ. MUTUAL DATA
0 / END OF ZERO SEQ. MUTUAL DATA, BEGIN ZERO SEQ. TRANSFORMER DATA
1, 100, 0,'1 ', 2, 0.00000E+0, 0.00000E+0, 4.60000E-3, 1.34590E-1
2, 100, 0,'1 ', 2, 0.00000E+0, 0.00000E+0, 4.60000E-3, 1.34590E-1
......
0 / END OF ZERO SEQ. TRANSFORMER DATA, BEGIN ZERO SEQ. SWITCHED SHUNT DATA
0 / END OF ZERO SEQ. SWITCHED SHUNT DATA, BEGIN ZERO SEQ. FIXED SHUNT DATA
100,'1 ', 0.00000E+00, 0.00000E+00
......
0 / END OF ZERO SEQ. FIXED SHUNT DATA
Project undertaken by a consortium led
51 by Ricardo Energy & Environment
51
Short Circuit Analysis Examples - Session 6

Study Case – Synchronous Machine


Capacity Building to the
Bangladesh
Power Sector

Generator sequence data


R1 X1

0, 32 / PSS®E-32.0 THU, FEB 02 2017 13:10


1,'1 ', 2.96000E-03, 1.10000E-01
2,'2 ', 2.96000E-03, 1.10000E-01 R2
......
0 / END OF POSITIVE SEQ. MACHINE IMPEDANCE DATA, BEGIN NEGATIVE SEQ. MACHINE DATA
1,'1 ', 2.96000E-03, 1.10000E-01
2,'2 ', 2.96000E-03, 1.10000E-01
X2
Gen Bus ......
0 / END OF NEGATIVE SEQ. MACHINE IMPEDANCE DATA, BEGIN ZERO SEQ. MACHINE DATA
1,'1 ', 2.96000E-03, 1.10000E-01
Gen Bus ID 2,'2 ', 2.96000E-03, 1.10000E-01
.....
0 / END OF ZERO SEQ. MACHINE IMPEDANCE DATA, BEGIN NEGATIVE SEQ. SHUNT DATA

X0
R0

Project undertaken by a consortium led


52 by Ricardo Energy & Environment
52
Short Circuit Analysis Examples - Session 6

Branch Zero Sequence Data


Capacity Building to the
Bangladesh
Power Sector

ZERO SEQ. BRANCH DATA


1030, 1050, '1 ', 4.61493E-2, 1.93924E-1, 0.13684, 0.00000E+0, 0.00000E+0, 0.00000E+0, 0.00000E+0

Bus From, Bus To, Ckt ID, Ro, Xo, Bo, ZeroSeq G From, Zero Seq B From, Zero Seq G To, Zero Seq B To

where:
- Ro, Xo and Bo: Zero sequence resistance, reactance and susceptance of the branch
- Zero Seq G and B From: Zero sequence admittance of the line connected shunt at From end
- Zero Seq G and B To: Zero sequence admittance of the line connected shunt at To end

Project undertaken by a consortium led


53 by Ricardo Energy & Environment
53
Short Circuit Analysis Examples - Session 6

Branch Zero Sequence Data


Capacity Building to the
Bangladesh
Power Sector

ZERO SEQ. BRANCH DATA


1030, 1050, '1 ', 4.61493E-2, 1.93924E-1, 0.13684, 0.00000E+0, 0.00000E+0, 0.00000E+0, 0.00000E+0

Bus From, Bus To, Ckt ID, Ro, Xo, Bo, ZeroSeq G From, Zero Seq B From, Zero Seq G To, Zero Seq B To

where:
- Ro, Xo and Bo: Zero sequence resistance, reactance and susceptance of the branch
- Zero Seq G and B From: Zero sequence admittance of the line connected shunt at From end
- Zero Seq G and B To: Zero sequence admittance of the line connected shunt at To end

Project undertaken by a consortium led


54 by Ricardo Energy & Environment
54
Short Circuit Analysis Examples - Session 6

2-W Transformer Zero Sequence Data


Capacity Building to the
Bangladesh
Power Sector

ZERO SEQ. 2-WINDING TRANSFORMER DATA


1000, 1030, 0, '1 ', 2, 1.78559E-3, 6.57938E-2, 1.79000E-3, 7.31000E-2

Bus I, Bus J, Bus K, Transformer ID, CC, RG, XG, R1, X1


Total series
Yy impedance

YNy
where:
- CC: Winding Connection Code (1- Ynyn, 2-Ynd, 3-Dyn, 4, Yy or Dd)
- RG and XG: Zero sequence
Yyn grounding impedance for an impedance grounded transformer

- R1 and X1: Impedance connected to Winding 1 side OR total series impedance, depending on the CC
- R2 and X2: Zero sequence grounding impedance OR series impedance at the Winding 2 side,
YNyn
depending on the CC

Project undertaken by a consortium led


55 by Ricardo Energy & Environment
Dy
55
Short Circuit Analysis Examples - Session 6
YNynyn
3-W Transformer Zero Sequence Data
Capacity Building to the
Bangladesh
Power Sector

ZERO SEQ. 3-WINDING TRANSFORMER DATA


1040, 1030, 1045,'1 ', 2, 0.0E+0, 0.0E+0, -4.37E-3, -3.97E-3, 7.86E-3, 1.54760E-1, 2.627E-2, 3.293E-1
Ydy

Ydyn
Bus I, Bus J, Bus K, Branch ID, CC, RG, XG, R1, X1, R2, X2, R3, X3

Not
considered
in PSSE,
YNdyn so set to 0

where:
- CC: Winding Connection Code. (1- Ynynyn, 2-Ynynd, 3-Dynd)
- RG and XG: Zero sequence grounding impedance for an impedance grounded transformer
- R1 and X1: Impedance connected to Winding 1 side OR total series impedance, depending on the CC
- R2 and X2: Zero sequence grounding impedance OR series impedance at the Winding 2 side,
depending on the CC
- R3 and X3: Winding 3 zero sequence star circuit equivalent impedance of the 3-winding transformer

Project undertaken by a consortium led


56 by Ricardo Energy & Environment
56
Short Circuit Analysis Examples - Session 6

PSSE Fault Calculation Interface


Capacity Building to the
Bangladesh
Power Sector

Fault calculation function

Project undertaken by a consortium led


57 by Ricardo Energy & Environment
57
Short Circuit Analysis Examples - Session 6

PSSE Fault Calculation Models (1)


Capacity Building to the
Bangladesh
Power Sector

Detailed fault calculation model


- Full sequence network model
- Initial operating condition considered

Simplified fault calculation model


- No MW out put from generators
- Loads and fixed shunts neglected in the positive and negative sequence network
- Line charging and line shunts neglected
- Zero sequence shunts and ground transformer winding considered
- All transformers set at nominal tap position

Project undertaken by a consortium led


58 by Ricardo Energy & Environment
58
Short Circuit Analysis Examples - Session 6

PSSE Fault Calculation Models (2)


Capacity Building to the
Bangladesh
Power Sector

Special conditions for fault calculation models


- Flat start mode
- Setting special fault voltage case
- Setting classic fault calculation mode
- Setting up IEC60909 fault calculation mode

Project undertaken by a consortium led


59 by Ricardo Energy & Environment
59
Short Circuit Analysis Examples - Session 6

PSSE Short Circuit Calculation Interface


Capacity Building to the
Bangladesh
Power Sector

Project undertaken by a consortium led


60 by Ricardo Energy & Environment
60
Short Circuit Analysis Examples - Session 6

PSSE ASCC Fault Calculation


Capacity Building to the
Bangladesh
Power Sector

Key notes
- Automatic sequencing fault calculation
- Total fault currents at faulted bus
- Fault contribution from branches related to the faulted bus
- Retained voltages at buses in the surrounding network

Project undertaken by a consortium led


61 by Ricardo Energy & Environment
61
Short Circuit Analysis Examples - Session 6

PSSE ASCC Fault Calculation Results (1)


Capacity Building to the
Bangladesh
Power Sector

Short circuit result summary

Key notes
- Fault type: three phase and single phase to ground
- Short circuit capacity in MVA
- Short current in kA
- Equivalent sequence impedance Z and angle in ohm and degree

Project undertaken by a consortium led


62 by Ricardo Energy & Environment
62
Short Circuit Analysis Examples - Session 6

PSSE ASCC Fault Calculation Results (2)


Capacity Building to the
Bangladesh
Power Sector

Fault current contribution summary

Key notes
- Fault contribution from other buses connected to the faulted bus
- Sequence fault current and phase fault current contribution

Project undertaken by a consortium led


63 by Ricardo Energy & Environment
63
Short Circuit Analysis Examples - Session 6

PSSE Circuit Breaker Duty Calculation (1)


Capacity Building to the
Bangladesh
Power Sector

Key notes
- Load flow case needs to be converted
- Preparation of bkdy data file for synchronous
machines including sub-transient and transient
data
- Interpreting simulation results

Project undertaken by a consortium led


64 by Ricardo Energy & Environment
64
Short Circuit Analysis Examples - Session 6

PSSE Circuit Breaker Duty Calculation (2)


Capacity Building to the
Bangladesh
Power Sector

Bkdy file:

1000, 1, 6.6, 0.07, 1.1, 0.1, 1.93, 1.79, 0.24, 0.27, 0.14
1010, 1, 6.6, 0.07, 1.1, 0.1, 1.93, 1.79, 0.24, 0.27, 0.14
1020, 1, 6.6, 0.07, 1.1, 0.1, 1.93, 1.79, 0.24, 0.27, 0.14
1070, 1, 4.7, 0.04, 0.82, 0.06, 1.76, 1.63, 0.31, 0.35, 0.22
1080, 1, 4.7, 0.04, 0.82, 0.06, 1.76, 1.63, 0.31, 0.35, 0.22
0/

Project undertaken by a consortium led


65 by Ricardo Energy & Environment
65
Short Circuit Analysis Examples - Session 6

PSSE Circuit Breaker Duty Calculation (3)


Capacity Building to the
Bangladesh
Power Sector

Key Notes:
- Z-source for generator
- Loads converted to constant impedance

Project undertaken by a consortium led


66 by Ricardo Energy & Environment
66
Short Circuit Analysis Examples - Session 6

PSSE Circuit Breaker Duty Calculation (4)


Capacity Building to the
Bangladesh
Power Sector

Immediately after the fault: t=0 seconds

Circuit breaker duty time: t=0.05 seconds

Project undertaken by a consortium led


67 by Ricardo Energy & Environment
67
Short Circuit Analysis Examples - Session 6

PSSE IEC60909 Fault Calculation (1)


Capacity Building to the
Bangladesh
Power Sector

Key notes
- Fault calculation in accordance with IEC 60909
- Additional data, such as transformer name plate
data required to enable the calculation

Project undertaken by a consortium led


68 by Ricardo Energy & Environment
68
Short Circuit Analysis Examples - Session 6

PSSE IEC60909 Fault Calculation (2)


Capacity Building to the
Bangladesh
Power Sector

IEC 60909 fault current results

Fault current calculation comparison


rms break DC current
SC Calculation
Ik" (amps) ip (amps) (amps (amps
Methods
@0.05s) @0.05s)
IEC60909 22098.7 57545.9 21929.4 13725
BKDY 18085.4 49792.6 17137.8 10141.3
Difference (%) 18.16 13.47 21.85 26.11

Project undertaken by a consortium led


69 by Ricardo Energy & Environment
69
Short Circuit Analysis Examples - Session 6
Capacity Building to the
Bangladesh
Power Sector

End of Module B

Thank You !

Project undertaken by a consortium led


70 by Ricardo Energy & Environment
70

You might also like