Professional Documents
Culture Documents
Table of Contents
Capacity Building to the
Bangladesh
Power Sector
Symmetrical faults
- Three phase fault (<5%)
o Solid three phase fault
o Fault via impedance
Asymmetrical faults
- Single phase to earth fault (up to 75%)
- Phase to phase fault
( 15~20%)
- Double phase to earth fault
- The fault could be solid or via a fault impedance
jX’’d jX’’d
Z TH ( X / / X ) X d''
X
jX jX X d'' jX jX
2
Z TH ( X / /3 X ) X d''
jX jX jX jX
3
X X d''
4
DC fault current
- DC fault current component only
I peak 2 I sym I DC
I Asym I DC
2
I sym
2
I Asym 2 2 I sym
- Where:
- Ik’’ = initial symmetrical short circuit
current (RMS) (kA)
- τ = decay time constant (s)
- t = time since fault inception (s)
- The time constant τ, is dependant on the
system reactance, X and resistance, R and
at frequency f is given by:
For a fault, the abc three phase fault current waveforms differ due to phase
angle at the fault instant
Table of Contents
Capacity Building to the
Bangladesh
Power Sector
Fault Contribution
Capacity Building to the
Bangladesh
Power Sector
Fault Current:
- Sub-transient component Sub-transient
E q"
i
"
X d"
E q'
i'
X d'
Eq
i steady _ state
Xd
( X d" X q" )
Ta - E is the terminal no-load voltage
ra
- Td”,Td’, short circuit time constants
- Ta, dc component decay time constants
Project undertaken by a consortium led
22 by Ricardo Energy & Environment
22
Short Circuit Analysis - Session 5
- The saturated values of Xd”, Xd’ and Xd used for fault calculation
- X2 and X0 used for unsymmetrical fault current calculation
o X2 XdX
" "
q applicable to sub-transient, transient and steady state unsymmetrical fault
calculation
o X0 normally provided by generator manufacturer
Motor FL Contribution
Capacity Building to the
Bangladesh
Power Sector
R X’
Isc
E’
Fault Current:
- No sub-transient and transient
components
- Steady state component equals
to initial AC component
- DC component decay in
accordance with time constant
calculated based on X and R
- Applicable to a fault far away
from the equivalent Grid Infeed
Table of Contents
Capacity Building to the
Bangladesh
Power Sector
- Induction motors
o R+jX”
- Transformers
o R1+jX1 with off-nominal tap ratio
- Induction motors
o The equivalent X”
- Transformers
o R0+jX0 with off-nominal tap ratio
o Winding group
Z0
I0
E1
If
Z1
Z1
I1
E1 Key Note:
- Only positive sequence current
- No negative and zero sequence currents
Z-2
I2
Z0
I0 3E1
If
Z 0 Z1 Z 2
Z1
Key Note:
I1 - Equal positive, negative and zero sequence
E1
currents
- Equivalent to connecting the three sequence
circuits in series
Z2
I2
Z0
E1
I0 If
Z1 Z 2
Z1
1
Key Note:
I
E1 - Equal positive and negative sequence currents
- No zero sequence current available
Z2
I2
Z1
I1
E1
E1
If
Z1 Z 2 // Z 0
Key Note:
Z0 Z2
- Negative sequence and zero sequence circuits
I0 I2
are connected in parallel
Table of Contents
Capacity Building to the
Bangladesh
Power Sector
- Conversion of load flow case may be necessary depending upon fault calculation
requirements
Applying a fault
- Based on the constructed sequence network, apply a fault at the concerned bus
- Fault type could be three phase, single phase to earth, or phase fault, etc.
Table of Contents
Capacity Building to the
Bangladesh
Power Sector
Pre-fault Voltage
Capacity Building to the
Bangladesh
Power Sector
- IEC 60909 short circuit calculation is based on generic factors and worst-case
parameters
- It provides greater degree of safety when level of data is limited
- Generally IEC60909 produces more pessimistic fault current results than other
commercial short-circuit calculation software packages
Table of Contents
Capacity Building to the
Bangladesh
Power Sector
X0
R0
Bus From, Bus To, Ckt ID, Ro, Xo, Bo, ZeroSeq G From, Zero Seq B From, Zero Seq G To, Zero Seq B To
where:
- Ro, Xo and Bo: Zero sequence resistance, reactance and susceptance of the branch
- Zero Seq G and B From: Zero sequence admittance of the line connected shunt at From end
- Zero Seq G and B To: Zero sequence admittance of the line connected shunt at To end
Bus From, Bus To, Ckt ID, Ro, Xo, Bo, ZeroSeq G From, Zero Seq B From, Zero Seq G To, Zero Seq B To
where:
- Ro, Xo and Bo: Zero sequence resistance, reactance and susceptance of the branch
- Zero Seq G and B From: Zero sequence admittance of the line connected shunt at From end
- Zero Seq G and B To: Zero sequence admittance of the line connected shunt at To end
YNy
where:
- CC: Winding Connection Code (1- Ynyn, 2-Ynd, 3-Dyn, 4, Yy or Dd)
- RG and XG: Zero sequence
Yyn grounding impedance for an impedance grounded transformer
- R1 and X1: Impedance connected to Winding 1 side OR total series impedance, depending on the CC
- R2 and X2: Zero sequence grounding impedance OR series impedance at the Winding 2 side,
YNyn
depending on the CC
Ydyn
Bus I, Bus J, Bus K, Branch ID, CC, RG, XG, R1, X1, R2, X2, R3, X3
Not
considered
in PSSE,
YNdyn so set to 0
where:
- CC: Winding Connection Code. (1- Ynynyn, 2-Ynynd, 3-Dynd)
- RG and XG: Zero sequence grounding impedance for an impedance grounded transformer
- R1 and X1: Impedance connected to Winding 1 side OR total series impedance, depending on the CC
- R2 and X2: Zero sequence grounding impedance OR series impedance at the Winding 2 side,
depending on the CC
- R3 and X3: Winding 3 zero sequence star circuit equivalent impedance of the 3-winding transformer
Key notes
- Automatic sequencing fault calculation
- Total fault currents at faulted bus
- Fault contribution from branches related to the faulted bus
- Retained voltages at buses in the surrounding network
Key notes
- Fault type: three phase and single phase to ground
- Short circuit capacity in MVA
- Short current in kA
- Equivalent sequence impedance Z and angle in ohm and degree
Key notes
- Fault contribution from other buses connected to the faulted bus
- Sequence fault current and phase fault current contribution
Key notes
- Load flow case needs to be converted
- Preparation of bkdy data file for synchronous
machines including sub-transient and transient
data
- Interpreting simulation results
Bkdy file:
1000, 1, 6.6, 0.07, 1.1, 0.1, 1.93, 1.79, 0.24, 0.27, 0.14
1010, 1, 6.6, 0.07, 1.1, 0.1, 1.93, 1.79, 0.24, 0.27, 0.14
1020, 1, 6.6, 0.07, 1.1, 0.1, 1.93, 1.79, 0.24, 0.27, 0.14
1070, 1, 4.7, 0.04, 0.82, 0.06, 1.76, 1.63, 0.31, 0.35, 0.22
1080, 1, 4.7, 0.04, 0.82, 0.06, 1.76, 1.63, 0.31, 0.35, 0.22
0/
Key Notes:
- Z-source for generator
- Loads converted to constant impedance
Key notes
- Fault calculation in accordance with IEC 60909
- Additional data, such as transformer name plate
data required to enable the calculation
End of Module B
Thank You !