19-23” Rack Mountable FDU


(Fiber Distribution Unit)
SC Compatible

Product Specification

`
`

CONTENTS

A. Features………………………………………….…………… 1
B. Dimensions……………..…………………………..…...... 1
C. Pictures……………………………………………………….. 3
D. Wiring Diagram.…………………………………...…..... 5
E. Installation Manual……..………………………………. 6

`
`

FEATURES

• 19-23” Width Standard Size


• Light weight
• Swing/Swivel Type
• FC/SC/ST/LC Compatible
• White/Black Color

DIMENSIONS

12C 144C

Metal Cold-roll steel sheet


Splice Tray Plastic
Splice Capacity Splice Tray Dimension (L*W*H)mm
12 1pc – 12/24 Fiber Tray 485*310*44.5 (1U)
24 1pc – 24 Fiber Tray 485*310*44.5 (1U)
48 2pcs – 24 Fiber Tray 485*310*89 (2U)
72 3pcs – 24 Fiber Tray 485*310*89 (2U)
96 4pcs – 24 Fiber Tray 485*310*89 (2U)
144 6pcs – 24 Fiber Tray 485*310*178 (4U)
` 288 12pcs – 24 Fiber Tray 485*310*267 (6U)

1 of 9
`

PICTURES

12C- 1U 24C- 1U 48C- 2U

72C- 2U 96C- 2U 144C- 4U

1U 2U 4U

178cm
89
44.5

485cm 485cm 485cm


12/24C 48/72/96C 144C
`

2 of 9
`

WIRING DIAGRAM

3 of 9
`

INSTALLATION PROCEDURE

1. Fixing Ground Terminal

Place two plastic washers on each side


and attach the grounding terminal on
the rear panel

2. Mounting

Mount Swing-out Modules on an


open rack or a cabinet using an
approved installation method

3. Cable Preparation

Cut off about 1m from the end and


mark the stripping point using a tape at
a 150cm point from the cut end

4 of 9
`

INSTALLATION PROCEDURE

Remove the sheath from the


marked point using a sheath
stripper

Remove plastic tape and dummy


fillers. Clean the loose tube using
jelly cleaner

Leave 7cm from the Cable Sheath


end and cut off the Tension
Member. Leave 5cm from the
Cable Sheath end and remove
loose tubes using a loose tube
cutter

Insert fibers into the colored


Protection tubes. Push the
protection tube up to the loose
tube end

5 of 9
`

4. Cable Clamping

Secure the cable to the


rear side of the shelf with
a provided steel band

5. Ground Terminal Fixing

If the OSP cable has a metallic sheath


and tension member, insert the
tension member into the ground
terminal and tighten it using a screw
driver

Connect Grounding wire to


Ground terminal

Connect on the side of Grounding


wire to Rack earth bar

6 of 9
`

6. Fixing Splice Tray

Fixed splice tray to the rear


door with bolt

7. Cable Routing

After the cable termination,


protection tubes are routed into the
swing-out module

8. Pigtail Insertion

Insert each 6pigtail cords into a


provided protection tubes to make a
cord unit for easy identification

Place the loose tubes containing


optical fibers on the splice tray inlet,
and fasten them tightly using cable
ties

7 of 9
`

9. Optical Fiber Splicing


Check the color of fibers and
remove coatings. Cut the fiber
using an approved fiber
cutting method. Splice fibers
using an approved fiber
splicing method

10. Splice Storage

When the splicing is completed,


insert sleeves into slits accordingly

11. Record index card

After record the contents of works


on the cover of splice tray, close the
cover of splice tray

12. Patchcord Connection

Connect patchcords on the opposite


side of adapters

8 of 9
`

13. Completion of work

Pull out the patch cords toward the


system through the reserved holes

After the completion, push the


module back into the main body

Record the splicing list on the card


attached on the front door. Check
splicing, routing, storage and
system status before starting the
operation

9 of 9
China Telecommunication Technology Labs

Report code: F16X76622

TEST REPORT

Product Name: Optical Distribution Frame


Model : GPX167
Manufacturer: Nanjing Huamai technology Co.,Ltd
Test type : First inspection of product certification

China Telecommunication Technology Labs


China Telecommunication Technology Labs

China Telecommunication Technology Labs

TEST REPORT

Product name ODF Model GPX167

Nanjing Huamai Technology


Applicant Production Date 2016.08.30
Co., Ltd.
Nanjing Huamai Technology
Manufacturer Test type First inspection
Co., Ltd.
No.66, Fengze Road, Industrial Zone, Dongshan Street, Jiangning District,
Production
Nanjing, Jiangsu Province
Address
12

Date 2016.10.29 sample sender Zhumengtong

Sample Qty ODF *1 , Patchcord 10 pcs , splicing tray and distribution tray 2 pcs

Sample Status The sample is in good condition,Comply with the inspection requirements

Test standard YD/T 778-2011《ODF》

The GPX167 ODF of this company , after testing , conclusion as follow :


Test Item : 44
Measured project:44
Inspection
Unrelated item:0
Conclusion
Unqualified item:0 ( B 0 , C0 )
This prduct is qualified. Match the standard.
Signed date : 2016.12.13

Test according to China Telecommunication Technology Labs engagement letter


Remarks
1609056 . TLC<ODF>

Approve : review: Principal inspector:


China Telecommunication Technology Labs

Inspection List

Unqulified Classfies
NO. TEST ITEM Conclusions
CLASS B CLASS C
Ⅰ.Frame

1 Appearence & Structure 〇 Qualified

2 Fucntion Requirement 〇 Qualified

3 Coating adhesion 〇 Qualified

4 Voltage tolerance level 〇 Qualified

5 Insulation resistance 〇 Qualified

6 Combustion experiment 〇 Qualified

7 Appearence 〇 Qualified

8 High Temperature Dielectric strength 〇 Qualified

9 Insulation resistance 〇 Qualified

10 Appearence 〇 Qualified

11 Low Temperature Dielectric strength 〇 Qualified

12 Insulation resistance 〇 Qualified

13 Appearence 〇 Qualified

14 Damp heat test Dielectric strength 〇 Qualified

15 Insulation resistance 〇 Qualified


16 Salt spray test Appearence 〇 Qualified
Ⅱ. Fiber optical connetcor

1 Insertion Loss 〇 Qualified

2 Ruturn Loss 〇

3 radius of curvature 〇
End Face
4 Apex Offset 〇
Size
5 Fiber Sunken (Bulge) 〇
China Telecommunication Technology Labs

Inspection List

Unqulified Classfies
NO. TEST ITEM Conclusions
CLASS B CLASS C

6 Insertion Loss 〇 Qualified


Interchangeability
7 Return Loss 〇 Qualified

8 Appearence 〇 Qualified
Mechanical
9 Additional losses 〇 Qualified
durability test
10 Return Loss Variation 〇 Qualified

11 Appearence 〇 Qualified

12 Tensile Test Additional losses 〇 Qualified

13 Return Loss Variation 〇 Qualified

14 Appearence 〇 Qualified

15 High Temperature Additional losses 〇 Qualified

16 Return Loss Variation 〇 Qualified

17 Appearence 〇 Qualified

18 Low Temperature Additional losses 〇 Qualified

19 Return Loss Variation 〇 Qualified

20 Appearence 〇 Qualified

21 Damp heat test Additional losses 〇 Qualified

22 Return Loss Variation 〇 Qualified


23 Appearence 〇 Qualified
24 Salt spray test Additional losses 〇 Qualified

25 Return Loss Variation 〇 Qualified

26 Appearence 〇 Qualified

27 Shaking Test Additional losses 〇 Qualified

28 Return Loss Variation 〇 Qualified


China Telecommunication Technology Labs

Test Report
Ⅰ. Test Conclusion
1. GPX167 Frame

NO. TEST ITEM Unit Technical Requirement Test result Conclusions

mm Size: Height have 2600mm ,2200mm Height x Width


and 2000mm three type . Width better to x depth
choose integer multiples of 120mm , 2200*840*300
1 depth better to choose 300mm ,
Appearence 450mm,600mm . Size tolerance should
& Structure less than ±2mm, Vertical tolerance
should not over 3mm. Qualified
--- Mechanical activity:The mechanical part Compliant
should be rotated flexibly , The opening
angle of the door should not be less
than 110°, The gap should not be
greater than 3mm.
--- Frame structure: The structure should Compliant
be firm,No loosening of fastener
--- Optical cable bending radius: When the Compliant
optical cable enters the frame, the
allowable bending radius should be no
less than 15 times of the diameter of the
optical cable.
--- Protection tube , fiber and pigtail Compliant
bending radius : When optical cable
through the hole of steel panel,should
have protection tube and gasket .Fiber
and pigtail allowable benidng radius
cannot less than 30mm , Non-sensitive
optical fiber, allowable bending radius
not less than 15mm
--- Appearence : ODF coating surface Compliant
should smooth , Color uniformity, No
rust of metal.Plastic parts have no
deformation .
--- Logo should clear ,complete and no Compliant
error.
China Telecommunication Technology Labs

1. GPX167 Frame

NO
TEST ITEM Unit Technical Requirement Test result Conclusions
.
mm Optical entry , fasten and protect Height x Width Qualified
function : Should have optical entry and x depth
ground wire unit . a.) Entry optical cable 2200*840*300
and fasten it on the frame , protect the
fiber and confirm do not damage fiber. b.)
After stripe cable,should have device to
protect them . c.)Partial insulation of
metal. d.) The fixed metal cable
sheath should be able to connect to the
Function high voltage grounding device.
2 Requirement --- Fiber end connect : Should have end Compliant Qualified
connector unit . This unit should easier
for pigtail connect ,fiber splicing ,protect
the pigtail .
--- Line function : There should be set a Compliant Qualified
vertical line channel .Quick and
convenient scheduling fiebr number
--- Capacity : Every ODF capacity and unit Compliant Qualified
capacity should describe in the manual ,
It should be configured in a complete set
--- Marking Function : Frame and unti should Compliant Qualified
have complete record part , for easier to
recognize the fiber number.
--- Fiber storage function : Fame and Unti Compliant Qualified
should have enough space to storage
redundant fiber cable .
--- PLC Splitter installation and connect Compliant Qualified
(optional) :Should have space for PLC
splitter use
China Telecommunication Technology Labs

1. GPX167 Frame

NO Conclusio
TEST ITEM Unit Technical Requirement Test result
. n
Use metal parts with coating Compliant Qualified
treatment,The coating should have
good adhesion Adhesion
3 Coating adhesion mm cannot lower than GB/T
9286-1998 requirement .
4 Voltage tolerance level -- Frame High pressure protection No Qualified
grounding with frame ≥ 3000V , breakdown,
No breakdown, no flying arc no flying arc
5 Insulation resistance MΩ Frame High pressure protection >1x105 Qualified
grounding with frame ≥ 1000MΩ
6 Burning test s Match standard below : a. The test Burning time Qualified
sample is not burning b.The after leaving
combustion time does not exceed fire:
10s after leaving the flame. First : 2 s
Second: 3s
No falme
7 High -- ODF surface should clear and Compliant Qualified
Temp smooth and clear , The color is
test Appearence uniform and without coating
leak .No rust of metal.Plastic parts
have no deformation .
8 Voltage -- Frame High pressure protection Compliant
tolerance grounding with frame ≥ 3000V ,
level No breakdown, no flying arc
9 Insulation MΩ Frame High pressure protection Compliant
resistance grounding with frame ≥ 1000MΩ
10 Low ODF surface should clear and Compliant Qualified
Temp smooth and clear , The color is
test Appearence uniform and without coating
leak .No rust of metal.Plastic parts
have no deformation .
11 Voltage Frame High pressure protection No
tolerance grounding with frame ≥ 3000V , breakdown,
level No breakdown, no flying arc no flying arc
12 Insulation MΩ Frame High pressure protection >1x105
resistance grounding with frame ≥ 1000MΩ
China Telecommunication Technology Labs

13 Damp -- ODF surface should clear and Compliant Qualified


heat smooth and clear , The color is
test uniform and without coating
Appearence
leak .No rust of metal.Plastic parts
have no deformation .

14 Voltage -- Frame High pressure protection No


tolerance grounding with frame ≥ 3000V , breakdown,
level No breakdown, no flying arc no flying arc

15 Insulation MΩ Frame High pressure protection >1x105


resistance grounding with frame ≥ 1000MΩ

16 salt Appearence - ODF surface should clear and Compliant Qualified


spray smooth and clear , The color is
test uniform and without coating
leak .No rust of metal.Plastic parts
have no deformation .

No content
China Telecommunication Technology Labs

Ⅱ FC/UPC Fiber optical connector


NO Technical
TEST ITEM Unit Test Conclusions Conclusions
. Requirement
1 Insertion Loss dB ≤0.35 1310nm : 0.05~0.13 Qualified

2 Return Loss dB UPC ≥50 1310nm : 52~54 Qualified

code End face Value

1# A 14.54

B 14.29
2# A 13.24
B 13.64
3# A 11.83

3 End radius of mm PC R= 7~25 B 14.31


Face curvature APC R=5~12 4# A 13.23
Size
B 10.78
Qualified
5# A 16.32
B 15.02
6# A 11.37
B 12.82
7# A 13.94
B 13.60
8# A 14.54
B 14.20
9# A 13.78
B 13.80
10# A 13.67
B 13.30
China Telecommunication Technology Labs

NO Technical
TEST ITEM Unit Test Conclusions Conclusions
. Requirement
code End face Value

1# A 35.37

B 22.78
2# A 27.31
B 36.89
3# A 42.31

4 End Apex μm PC APC B 29.54


Face offset 0~50 4# A 13.47
Size
B 39.20
5# A 19.76
B 36.75 Qualified

6# A 38.02
B 40.04
7# A 27.86
B 19.11
8# A 36.05
B 42.34
9# A 29.51
B 40.74
10# A 25.76
B 41.44
China Telecommunication Technology Labs

NO Technical
TEST ITEM Unit Test Conclusions Conclusions
. Requirement
code End face Value

1# A 21

B 23
2# A 30
B 9
3# A 30

5 End Fiber nm PC sunken≤125 B 24


Face Sunken (radius of 4# A 5
Size (Bulge) curvature about
B 15
7~10mm)
5# A 16
PC sunken≤ B 20
-0.02R3+1.3R3-31R
6# A -5
+325
B 36 Qualified
PC Bulge≤50 7# A 24
APC±100
B 2
8# A 13
B 15
9# A 15
B 19
10# A 17
B 27
China Telecommunication Technology Labs

Test Report
NO Conclusi
TEST ITEM Unit Technical Requirement Test result
. ons

6 interchang Insertion Loss dB ≤ 0.5 1310nm: 0.12~0.16


7 eability Return Loss dB UPC≥48 1310nm:51~52
8 - No mechanical Compliant
damage, shedding or
Appearence
Mechanical deformation will be
durability allowed after the test.
9 test Additional losses dB ≤0.2 1310nm: 0.02

10 Return Loss dB ≤5 1310nm:1


Variation
11 - No mechanical Compliant
damage, shedding or
Appearence
deformation will be
Tensile Test allowed after the test.
12 Additional losses dB ≤0.2 1310nm: 0.01~0.07
13 Return Loss dB ≤5 1310nm:1~1
Variation Qualified
14 - No mechanical Compliant
damage, shedding or
Appearence
deformation will be
High
allowed after the test.
Temperatur
15 e Additional losses
dB ≤0.2 1310nm: 0.00~0.13

16 Return Loss dB ≤5 1310nm:0~1


Variation
17 - No mechanical Compliant
damage, shedding or
Appearence
deformation will be
Low
allowed after the test.
Temperatur
18 dB ≤0.2 1310nm: 0.01~0.02
e Additional losses

19 Return Loss dB ≤5 1310nm:0~1


Variation
20 - No mechanical Compliant
damage, shedding or
Appearence
deformation will be
Damp heat allowed after the test.
21 test dB ≤0.2 1310nm: 0.02~0.07
Additional losses
22 Return Loss dB ≤5 1310nm:0~1
Variation
China Telecommunication Technology Labs

23 - No mechanical Compliant
damage, shedding or Conclusi
Appearence
deformation will be ons
allowed after the test.
24 dB ≤0.2 1310nm: 0.00~0.08
Salt spray
test Additional losses

25 dB ≤5 1310nm:0~0
Return Loss Qualified
Variation

26 - No mechanical Compliant
damage, shedding or
Appearence
deformation will be
allowed after the test.
27 dB ≤0.2 1310nm: 0.01~0.02
Shaking
Test Additional losses

28 dB ≤5 1310nm:1 ~ 1
Return Loss
Variation

No Content
China Telecommunication Technology Labs

Testing conditions for environmental and mechanical


properties
Test Item Condition
Test temperature: 55℃±2℃
High temperature
Test Time: 2h
Test temperature: -25℃ ± 3℃
Low temperature
Test Time: 2h
Test temperature: 40℃±2℃
Damp heat test
Relative humidity: 93% ± 3%
Test Time: 48h
Frequency range: 10Hz ~ 55Hz
Shaking
sweep frequency : every min each octave
Tolerance : ±10%
Swing: 0.75 single shaking
Last time: 30min
Test temperature: 35℃ ± 2℃
Salt spray test
Test Time:48h
Brine strength : 5%
Loading : 50N
Tensile
Loading time:10min
Load rating :50N/min ~250N/min
Distance:22~28cm
Insert and pulling : 500 times
Mechanical durability
Height : (20±2)mm , blue flame , time : 30s
Burning
China Telecommunication Technology Labs

GPX 167 ODF