calculo demanda apto 201

AREA VA/M^2 VA P ARTEFACTOS PLANCHA St Sr I (Amp) proteccion


70 32 2240 1500 1500 5240 3784 31.5333333 1 x 40
calculo de la bodega
AREA VA/M^2 VA P ARTEFACTOS St Sr I (Amp) proteccion
120 2.5 300 1500 1800 2580 12.4038462 2 x 40
local comercial 1
AREA VA/M^2 VA AVISO LUMINOSO L VITRINA St
60 32 1920 1200 400 3520
tomas
5 900 900 I (Amp) proteccion
4.42 21.25 2 x 30
local comercial 2 y 3
AREA VA/M^2 VA AVISO LUMINOSO L VITRINA St
60 32 1920 1200 400 3520
tomas
5 900 900 I (Amp) proteccion
4.42 21.25 2 x 30

RESIDENCIAL COMERCIAL BODEGA


N 2 N 3 N 1
SR 7.568 SR 13.26 SR 2.58
F.D 1.14000988 F.D 1.33542 F.D 1
DMAX 6.638538955 DMAX 9.92944 DMAX 2.58

ST 19.14797532
REGULACION ACOMETIDA CASA
Tramo Long Carga Corriente Momento F.P. CONDUCTOR DE COBRE 90° THHN
KVA Calibre Kg Kc
0 - TG 15 19 53.14946493 287.21963 0.95 4 92.4032 0.004805547
REGULACION CONDUCTOR
Parcial Total NEUTRO
1.38024753 1.38024753 4