INSPECTION REPORT
To : Mr. BLN
Bed super heater coil: Leakage observed on RHS bed super heater coils#24, 25 & due to
leakage erosion noticed on adjacent bed super heater coils#22, 23 & 26. Same coils are
recommended for replacement.
Also reduction in thickness observed on coils#02 & 09. These two coils to be planned for
replacement during next suitable opportunity after rechecking for further reduction in
thickness.
Thickness of LHS bed super heater coil was checked & found satisfactory in general.
Bed Coil: Due to leakages on RHS bed super heater coils, RHS bed coils#66, 67, 68, 69
found eroded. Same coils are recommended for replacement.
LHS bed coils condition found satisfactory in general.
Thanks,
To : Mr. BLN
Equipment Name : Boiler-II (MR-14448) Date of Inspection : 11/12/2018
Specified Thk : OD 44.5 mm & 5.0 mm Thk MOC : SA 213 T91
Corrosion Allowance : Nil (As per IBR) Inspected By : Mr. SCK, VAR
We have carried out thickness survey of bed super heater coils as per requirement.
Details of the survey are given below.
To : Mr. BLN
Equipment Name : Boiler-II (MR-14448) Date of Inspection : 11/12/2018
Specified Thk : OD 44.5 mm & 5.0 mm Thk MOC : SA 213 T91
Corrosion Allowance : Nil (As per IBR) Inspected By : Mr. SCK, VAR
We have carried out thickness survey of bed super heater coils as per requirement.
Details of the survey are given below.