Professional Documents
Culture Documents
soft starters
for single-phase and three-phase asynchronous motors
eCatalog
2014
Altistart 01 & U01 Contents
soft starters for
asynchronous motors
Ŷ Introduction...............................................................4
Ƒ Altistart 01 products...........................................4
Ƒ ATS01N1 soft starters .........................................6
Ƒ ATS01N2 & ATSU01N2 soft starters....................8
Ŷ Specifications .........................................................12
Ƒ Environmental...................................................12
Ƒ Electrical ..........................................................13
Ƒ I/O & Control......................................................14
Ƒ Connections .....................................................15
Ŷ Selection Tables & Dimensions..............................16
Ƒ ATS01N1 soft starters .......................................16
Ƒ ATS01N2 & ATSU01N2 soft starters..................18
Ŷ Accessories ............................................................22
Ŷ Wiring Diagrams.....................................................23
Ŷ Quality Assurance ..................................................44
Ŷ Services & Support.................................................46
3
Altistart 01 & U01 Contents
soft starters for
asynchronous motors
Ŷ Introduction...............................................................4
Ƒ Altistart 01 products...........................................4
Ƒ ATS01N1 soft starters .........................................6
Ƒ ATS01N2 & ATSU01N2 soft starters....................8
Ŷ Specifications .........................................................12
Ƒ Environmental...................................................12
Ƒ Electrical ..........................................................13
Ƒ I/O & Control......................................................14
Ƒ Connections .....................................................15
Ŷ Selection Tables & Dimensions..............................16
Ƒ ATS01N1 soft starters .......................................16
Ƒ ATS01N2 & ATSU01N2 soft starters..................18
Ŷ Accessories ............................................................22
Ŷ Wiring Diagrams.....................................................23
Ŷ Quality Assurance ..................................................44
Ŷ Services & Support.................................................46
3
Altistart 01 & U01 Introduction Altistart 01 & U01 Introduction
soft starters for Altistart 01 products soft starters for Altistart 01 products
asynchronous motors asynchronous motors
Introduction Product
The Altistart™ 01 soft starter offers enhanced starting and stopping performance for The Altistart 01 offer comprises 3 ranges:
single-phase and three-phase, low horsepower asynchronous motors in a compact Ŷ ATS01N1pppp for soft start operation
package. Ŷ ATS01N2pppp for soft start and stop operation
Ŷ ATSU01N2pppp for soft start and stop operation with TeSys U
This highly functional mini soft starter provides a controlled and smooth operation
while providing torque surge suppression during both starting and stopping of the
motor. It is ideal for applications that do not require high starting torque. By limiting the Motor starting performance easily adapted to the application
starting torque, the ATS01 reduces the current inrush experienced with other motor Ŷ Dials conveniently located on the front of the Altistart 01 soft starter allow
starting methods. This stepless starting method avoids the damaging torque surges adjustments for starting torque as well as starting and stopping ramp times
associated with other reduced voltage starting methods. Ŷ Handles both easy and hard to start load with a selectable kickstart feature
Ŷ Compatibility with motor starters such as TeSys U, GV2, GV3, and others
Altistart 01 soft starter helps decrease your maintenance work and production
downtime by helping prevent the mechanical shocks that create wear and tear on your
motor and machinery. Available in three different performance levels, Altistart 01 soft Simple setup and operation
starters meet the application needs of a wide range of fractional and low horsepower
Ŷ 3 logic inputs, 1 logic output, 1 relay output
single-phase and three-phase asynchronous motors. A feature-rich alternative to low
ATS01N109FT, Ŷ Adjustment dials and indicator lights
horsepower electromechanical reduced voltage starters, the Altistart 01 mini soft
ATS01N112FT
starters offer many options to fit your application.
Easy to install and start up
The Altistart 01 is compact, easy to install and can be mounted side-by-side. It
complies with standards IEC/EN 60947-4-2, carries UL, CSA, C-Tick, CCC Ŷ DIN rail or panel mounting options
certifications and e marking. Most Altistart 01 models are available in a 45 mm width Ŷ Removable control terminal for simple and easy wiring
to match the industry standard for IEC motor starters rated at or below 32 Amps. Ŷ Quick adjustments
Ŷ Eliminate power wiring by using custom power connector to TeSys U-line motor
starter
Starting time
Controlling the starting time means that the time of the voltage ramp applied to the
motor can be adjusted to obtain a gradual starting time, dependent on the motor
load.
ATS01N222LU/QN/RT...
ATS01N232LU/QN/RT, Voltage Boost
U
Applications 100%
Un
Altistart 01 soft starters are designed for use on simple applications such as:
Ŷ Conveyors
Voltage ramp
Ŷ Conveyor belts 50%
Ŷ Pumps Un
Ŷ Fans
Ŷ Compressors Initial voltage
Ŷ Automatic doors and gates
t
Ŷ Small cranes 200 ms
Ŷ Belt-driven machinery, etc.
Application of a voltage boost equal to 100% of the
nominal motor voltage
4 5
Altistart 01 & U01 Introduction Altistart 01 & U01 Introduction
soft starters for Altistart 01 products soft starters for Altistart 01 products
asynchronous motors asynchronous motors
Introduction Product
The Altistart™ 01 soft starter offers enhanced starting and stopping performance for The Altistart 01 offer comprises 3 ranges:
single-phase and three-phase, low horsepower asynchronous motors in a compact Ŷ ATS01N1pppp for soft start operation
package. Ŷ ATS01N2pppp for soft start and stop operation
Ŷ ATSU01N2pppp for soft start and stop operation with TeSys U
This highly functional mini soft starter provides a controlled and smooth operation
while providing torque surge suppression during both starting and stopping of the
motor. It is ideal for applications that do not require high starting torque. By limiting the Motor starting performance easily adapted to the application
starting torque, the ATS01 reduces the current inrush experienced with other motor Ŷ Dials conveniently located on the front of the Altistart 01 soft starter allow
starting methods. This stepless starting method avoids the damaging torque surges adjustments for starting torque as well as starting and stopping ramp times
associated with other reduced voltage starting methods. Ŷ Handles both easy and hard to start load with a selectable kickstart feature
Ŷ Compatibility with motor starters such as TeSys U, GV2, GV3, and others
Altistart 01 soft starter helps decrease your maintenance work and production
downtime by helping prevent the mechanical shocks that create wear and tear on your
motor and machinery. Available in three different performance levels, Altistart 01 soft Simple setup and operation
starters meet the application needs of a wide range of fractional and low horsepower
Ŷ 3 logic inputs, 1 logic output, 1 relay output
single-phase and three-phase asynchronous motors. A feature-rich alternative to low
ATS01N109FT, Ŷ Adjustment dials and indicator lights
horsepower electromechanical reduced voltage starters, the Altistart 01 mini soft
ATS01N112FT
starters offer many options to fit your application.
Easy to install and start up
The Altistart 01 is compact, easy to install and can be mounted side-by-side. It
complies with standards IEC/EN 60947-4-2, carries UL, CSA, C-Tick, CCC Ŷ DIN rail or panel mounting options
certifications and e marking. Most Altistart 01 models are available in a 45 mm width Ŷ Removable control terminal for simple and easy wiring
to match the industry standard for IEC motor starters rated at or below 32 Amps. Ŷ Quick adjustments
Ŷ Eliminate power wiring by using custom power connector to TeSys U-line motor
starter
Starting time
Controlling the starting time means that the time of the voltage ramp applied to the
motor can be adjusted to obtain a gradual starting time, dependent on the motor
load.
ATS01N222LU/QN/RT...
ATS01N232LU/QN/RT, Voltage Boost
U
Applications 100%
Un
Altistart 01 soft starters are designed for use on simple applications such as:
Ŷ Conveyors
Voltage ramp
Ŷ Conveyor belts 50%
Ŷ Pumps Un
Ŷ Fans
Ŷ Compressors Initial voltage
Ŷ Automatic doors and gates
t
Ŷ Small cranes 200 ms
Ŷ Belt-driven machinery, etc.
Application of a voltage boost equal to 100% of the
nominal motor voltage
4 5
Altistart 01 & U01 Introduction Altistart 01 & U01 Introduction
soft starters for ATS01N1 soft starters soft starters for ATS01N1 soft starters
asynchronous motors asynchronous motors
Functions
ATS01N1 soft starters Starting and stopping the ATS01N1 soft start:
ATS01N1 torque limiting mini soft starters extend the Altistart 01 product range down
The motor starts when both line and control power are supplied to the soft start. The
into the fractional horsepower arena (3 to 12 A, 1/2 to 3 HP at 208 V). They can control
soft start will not soft stop the motor. When the run command is removed, the motor will
the starting ramp of either a single-phase or a three-phase motor.
coast to a stop. If only line power is removed to stop the motor, reapplying line power
will not restart the motor. Soft start control power must also be cycled off and on to
By reducing the starting torque produced by an asynchronous motor, the ATS01N1
restart the motor. In a single-phase application, the soft start will allow the motor to stop
soft start extends the motor’s starting time. The ATS01N1 soft start ramps up the AC
when either line or control power is removed.
voltage applied to one of the motor terminals. The other motor terminal(s) are supplied
full motor starting voltage. Hence, starting current is not reduced.
Note: In a 3-phase application, connect line power to the soft start ONLY when
soft start control power is present and motor operation is needed. Applying line
power when no soft start control power is present will single-phase the connected
The ATS01N1 is ideal for the following applications: 3-phase motor.
Ŷ Small conveyors for fragile goods, such as bottle conveyors
Ŷ Constant power machines, such as drills, where the starting torque must be Control power
limited Control power can be either:
Ŷ 110 V to 220 Vac (± 10%): terminals CL1/0 and CL2
Ŷ 24 Vac/dc (± 10%): terminals CL1/0 (-) and 24 V (+)
The ATS01N1 is compatible with the following common motor voltages: Line power
Ŷ Single phase: 115 V and 230 V
Ŷ Three phase: 208 V, 230 V, and 460 V Line power must match the voltage rating of the motor and must not exceed
480 V (± 10%) .
The ATS01N1 soft start is compatible with most single-phase motor designs, including Ŷ Single-phase motors:
split phase induction, capacitor start, and shaded pole. Ƒ Power in: ATS01N1 terminals 1/L1 and 5/L3
Ƒ Power out: ATS01N1 terminals 2/T1 and 6/T3
Ŷ Three-phase motors:
Ƒ Power in: ATS01N1 terminals 1/L1, 3/L2, and 5/L3
The ATS01N1 series is one of the smallest soft starts on the market and is Ƒ Power out: ATS01N1 terminals 2/T1, 4/T2, and 6/T3
available in two frame sizes:
Ŷ 0.9 inch (22.5 mm) wide modules, rated for 3 and 6 A Starting times
Ŷ 1.77 inch (45 mm) wide modules, rated for 9 and 12 A The ATS01N1 soft start controls the starting time of the motor by ramping up the
ATS01N103FT, 06FT voltage applied to one phase of the motor. The starting voltage ramp time can be
Both can be DIN rail or panel mounted. They can be mounted side-by-side with no gap adjusted from 1 to 5 seconds by means of the potentiometer on the front of the soft
between soft starts required. start. Since the actual motor starting time is dependent on the level of the applied load,
the scale on the front of the soft start is calibrated from A to E rather than from 1 to 5
seconds, with A being the shortest time and E being the longest time. The starting
voltage ramp begins at the AC line voltage level set by the Initial Voltage adjustment.
The ATS01N109FT and ATS01N112FT models offer an internal shorting contactor to See the diagram below for more detail.
eliminate wasted energy and to reduce the heat that must be removed from the control
panel. They also offer removable control terminal plugs for ease of wiring and Note: The ATS01 soft start is internally bypassed at the end of the time set by the
installation. start time adjustment. If the motor is not up to speed by that time (due to a heavy
load), the internal contactor can be damaged, requiring replacement of the soft
start. SET THE START TIME AT A LEVEL ACHIEVABLE WITH THE MOTOR AT ITS
HIGHEST LOAD LEVEL.
The ATS01N1 is equipped with:
Ŷ One green LED 1 to indicate that soft start power is on V Up to speed
Ŷ One yellow LED 2 that illuminates 10 seconds after a start command is given, 100%
indicating that the soft starter’s voltage ramp is complete, the internal shorting
1
2 contactor (09FT & 12FT models only) is closed, and the motor is up to speed
3 Ŷ A potentiometer 3 for setting the starting time Start ramp
Ŷ A potentiometer 4 for adjusting the start voltage threshold according to the motor Coast to Stop
4
load
Ŷ Two inputs 5:
Ƒ One 24 V z input or one 110…240 V a for powering the control circuitry that Initial voltage
Adjustable
5 controls the motor 30-80%
t
The ATS01N1 is compatible with the following common motor voltages: Line power
Ŷ Single phase: 115 V and 230 V
Ŷ Three phase: 208 V, 230 V, and 460 V Line power must match the voltage rating of the motor and must not exceed
480 V (± 10%) .
The ATS01N1 soft start is compatible with most single-phase motor designs, including Ŷ Single-phase motors:
split phase induction, capacitor start, and shaded pole. Ƒ Power in: ATS01N1 terminals 1/L1 and 5/L3
Ƒ Power out: ATS01N1 terminals 2/T1 and 6/T3
Ŷ Three-phase motors:
Ƒ Power in: ATS01N1 terminals 1/L1, 3/L2, and 5/L3
The ATS01N1 series is one of the smallest soft starts on the market and is Ƒ Power out: ATS01N1 terminals 2/T1, 4/T2, and 6/T3
available in two frame sizes:
Ŷ 0.9 inch (22.5 mm) wide modules, rated for 3 and 6 A Starting times
Ŷ 1.77 inch (45 mm) wide modules, rated for 9 and 12 A The ATS01N1 soft start controls the starting time of the motor by ramping up the
ATS01N103FT, 06FT voltage applied to one phase of the motor. The starting voltage ramp time can be
Both can be DIN rail or panel mounted. They can be mounted side-by-side with no gap adjusted from 1 to 5 seconds by means of the potentiometer on the front of the soft
between soft starts required. start. Since the actual motor starting time is dependent on the level of the applied load,
the scale on the front of the soft start is calibrated from A to E rather than from 1 to 5
seconds, with A being the shortest time and E being the longest time. The starting
voltage ramp begins at the AC line voltage level set by the Initial Voltage adjustment.
The ATS01N109FT and ATS01N112FT models offer an internal shorting contactor to See the diagram below for more detail.
eliminate wasted energy and to reduce the heat that must be removed from the control
panel. They also offer removable control terminal plugs for ease of wiring and Note: The ATS01 soft start is internally bypassed at the end of the time set by the
installation. start time adjustment. If the motor is not up to speed by that time (due to a heavy
load), the internal contactor can be damaged, requiring replacement of the soft
start. SET THE START TIME AT A LEVEL ACHIEVABLE WITH THE MOTOR AT ITS
HIGHEST LOAD LEVEL.
The ATS01N1 is equipped with:
Ŷ One green LED 1 to indicate that soft start power is on V Up to speed
Ŷ One yellow LED 2 that illuminates 10 seconds after a start command is given, 100%
indicating that the soft starter’s voltage ramp is complete, the internal shorting
1
2 contactor (09FT & 12FT models only) is closed, and the motor is up to speed
3 Ŷ A potentiometer 3 for setting the starting time Start ramp
Ŷ A potentiometer 4 for adjusting the start voltage threshold according to the motor Coast to Stop
4
load
Ŷ Two inputs 5:
Ƒ One 24 V z input or one 110…240 V a for powering the control circuitry that Initial voltage
Adjustable
5 controls the motor 30-80%
t
ATS01N2 & ATSU01N2 soft starters ATS01N2 for soft start and stop operation
Ŷ Control two phases of the motor power supply to limit the starting current and
The ATS01N2ppLU/QN/RT and ATSU01N2ppLT soft starters control the starting
deceleration
and stopping ramps of three-phase motors ranging from 0.5 to 20 HP (0.75 to 15 kW)
Ŷ Internal bypass relay
and have a motor voltage range of 208 V to 460 V.
Ŷ Motor power ratings ranging from 0.5 to 20 HP (0.75 to 15 kW) and 6 to 32 A
Ŷ The motor supply voltages range from 230 V - 460 V, 50/60 Hz. The use of a line
The ATS01N2ppLU/QN/RT soft start is self-powered from the AC line supply and is
contactor is not necessary on machines where electrical isolation is not required.
compatible with all other control power schemes.
4 These units are also compatible with motor starters such as TeSys U, GV2, GV3 and
The ATSU01N2ppLT soft start is optimized for installations offering 24 Vdc control 5
others.
power. 6
7
Equipped with:
These soft starters control two phases of the AC voltage supplied to the motor in 8 Ŷ 1 green LED 4 to indicate that the unit is switched on
order to limit starting torque and current. This is ideal for applications that do not
Ŷ 1 yellow LED 5 to indicate that the motor is powered at nominal voltage, if it is
require high starting torque. It limits starting torque and reduces the current inrush
connected to the starter
experienced with other motor starting methods. The stepless starting method of the
Ŷ A potentiometer 6 for setting the starting time
ATS01 soft start avoids the torque surges associated with other reduced voltage
9 Ŷ A potentiometer 7 for adjusting the start voltage threshold according to the motor
starting methods.
load
Ŷ A potentiometer 8 for setting the deceleration time
These two soft starters are ideal for any of the following applications:
Ŷ A connector 9:
Ŷ Material handling conveyors
Ƒ 2 logic inputs for Run/Stop commands
Ŷ Belt-driven machinery ATS01N206LU/QN/RT...
Ƒ 1 logic input for the BOOST function
Ŷ Fans and pumps ATS01N212LU/QN/RT,
Ƒ 1 logic output to indicate the end of starting
Ŷ Small compressors
Ƒ 1 relay output to indicate the motor has reached a standstill at the end of the
Ŷ Automatic doors and gates
deceleration stage
Ŷ Process machinery (such as grinders, mixers, and agitators)
Ŷ Filling lines
Ŷ People movers
Ŷ Any other application that can benefit from stepless reduced voltage starting
The ATS01N2 and ATSU01N2 are compatible with these common motor
ATSU01N206LT...ATSU01N212LT, ATSU01N2 for soft start and stop operation with TeSys U
voltages:
Ŷ 0.5 to 10 HP @ 200/208 V Designed specially for use with TeSys U
Ŷ 0.5 to 10 HP @ 230/240 V Ŷ When installed with TeSys U-Line family of motor starters, the Altistart 01 becomes
Ŷ 1.1 to 15 kW @ 400 V the smallest combination soft starter on the market with a full set of motor control
Ŷ 0.5 to 20 HP @ 460 V and machine protection features
While Altistart 01 soft starts can be used with almost any motor starter, they now add
The ATSU01N2pppp have the same specifications as the ATS01N2pppp units,
soft start and soft stop motor control to the TeSys™ U-Line family of motor starters.
with the added benefits of TeSys-U including but not limited to:
Ŷ Motor protection options
Ŷ Communication options
1 ATS01N2 or ATSU01N2 with TeSys U-Line motor starter Ŷ Load management
When an ATS01N2ppLU/QN/RT or an ATSU01N2ppLT model 3 is combined with the
Equipped with:
TeSys U-Line motor starter 1 by means of a power connector 2 (included with the
Ŷ 1 green LED 4 to indicate that the unit is switched on
ATSU01N2ppLT), the result is a unique, innovative motor starting solution. A low
Ŷ 1 yellow LED 5 to indicate that the motor is powered at nominal voltage, if it is
power soft start installation now has access to the benefits of the TeSys U-Line motor
connected to the starter
starter, including:
Ŷ A potentiometer 6 for setting the starting time
Ŷ Modular design with a standard 45 mm width
Ŷ A potentiometer 7 for adjusting the start voltage threshold according to the motor
Ŷ Short-circuit and multi-class overload protection
load
2 Ŷ Phase loss, phase imbalance, ground fault, jam, underload, and long-start
Ŷ A potentiometer 8 for setting the deceleration time
protection
Ŷ A connector 9:
Ŷ Fault history
Ƒ 2 logic inputs for Run/Stop commands
Ŷ PC based programming software 4
Ƒ 1 logic input for the BOOST function
Ŷ Optional LCD display 5
6 Ƒ 1 logic output to indicate the end of starting
Ŷ Networking capabilities: Modbus™, AS-I, DeviceNet™, Ethernet TCP/IP,
7 Ƒ 1 relay output to indicate the motor has reached a standstill at the end of the
Profibus® DP
3 8 deceleration stage
Ŷ Monitoring of motor status
Ŷ Remote starting and fault reset
Ŷ Electronic reversing
The panel space required to install the ATS01 soft start and the TeSys U-Line motor 9
starter is minimal, with a standard 45 mm product width and side-by-side mounting.
Please consult the TeSys U-Line motor starter catalog for TeSys U-Line mounting
information.
Example of motor starter/soft start combination
Example of motor starter/soft start combination
8 9
Altistart 01 & U01 Introduction Altistart 01 & U01 Introduction
soft starters for ATS01N2 & ATSU01N2 soft starters soft starters for ATS01N2 & ATSU01N2 soft starters
asynchronous motors asynchronous motors
ATS01N2 & ATSU01N2 soft starters ATS01N2 for soft start and stop operation
Ŷ Control two phases of the motor power supply to limit the starting current and
The ATS01N2ppLU/QN/RT and ATSU01N2ppLT soft starters control the starting
deceleration
and stopping ramps of three-phase motors ranging from 0.5 to 20 HP (0.75 to 15 kW)
Ŷ Internal bypass relay
and have a motor voltage range of 208 V to 460 V.
Ŷ Motor power ratings ranging from 0.5 to 20 HP (0.75 to 15 kW) and 6 to 32 A
Ŷ The motor supply voltages range from 230 V - 460 V, 50/60 Hz. The use of a line
The ATS01N2ppLU/QN/RT soft start is self-powered from the AC line supply and is
contactor is not necessary on machines where electrical isolation is not required.
compatible with all other control power schemes.
4 These units are also compatible with motor starters such as TeSys U, GV2, GV3 and
The ATSU01N2ppLT soft start is optimized for installations offering 24 Vdc control 5
others.
power. 6
7
Equipped with:
These soft starters control two phases of the AC voltage supplied to the motor in 8 Ŷ 1 green LED 4 to indicate that the unit is switched on
order to limit starting torque and current. This is ideal for applications that do not
Ŷ 1 yellow LED 5 to indicate that the motor is powered at nominal voltage, if it is
require high starting torque. It limits starting torque and reduces the current inrush
connected to the starter
experienced with other motor starting methods. The stepless starting method of the
Ŷ A potentiometer 6 for setting the starting time
ATS01 soft start avoids the torque surges associated with other reduced voltage
9 Ŷ A potentiometer 7 for adjusting the start voltage threshold according to the motor
starting methods.
load
Ŷ A potentiometer 8 for setting the deceleration time
These two soft starters are ideal for any of the following applications:
Ŷ A connector 9:
Ŷ Material handling conveyors
Ƒ 2 logic inputs for Run/Stop commands
Ŷ Belt-driven machinery ATS01N206LU/QN/RT...
Ƒ 1 logic input for the BOOST function
Ŷ Fans and pumps ATS01N212LU/QN/RT,
Ƒ 1 logic output to indicate the end of starting
Ŷ Small compressors
Ƒ 1 relay output to indicate the motor has reached a standstill at the end of the
Ŷ Automatic doors and gates
deceleration stage
Ŷ Process machinery (such as grinders, mixers, and agitators)
Ŷ Filling lines
Ŷ People movers
Ŷ Any other application that can benefit from stepless reduced voltage starting
The ATS01N2 and ATSU01N2 are compatible with these common motor
ATSU01N206LT...ATSU01N212LT, ATSU01N2 for soft start and stop operation with TeSys U
voltages:
Ŷ 0.5 to 10 HP @ 200/208 V Designed specially for use with TeSys U
Ŷ 0.5 to 10 HP @ 230/240 V Ŷ When installed with TeSys U-Line family of motor starters, the Altistart 01 becomes
Ŷ 1.1 to 15 kW @ 400 V the smallest combination soft starter on the market with a full set of motor control
Ŷ 0.5 to 20 HP @ 460 V and machine protection features
While Altistart 01 soft starts can be used with almost any motor starter, they now add
The ATSU01N2pppp have the same specifications as the ATS01N2pppp units,
soft start and soft stop motor control to the TeSys™ U-Line family of motor starters.
with the added benefits of TeSys-U including but not limited to:
Ŷ Motor protection options
Ŷ Communication options
1 ATS01N2 or ATSU01N2 with TeSys U-Line motor starter Ŷ Load management
When an ATS01N2ppLU/QN/RT or an ATSU01N2ppLT model 3 is combined with the
Equipped with:
TeSys U-Line motor starter 1 by means of a power connector 2 (included with the
Ŷ 1 green LED 4 to indicate that the unit is switched on
ATSU01N2ppLT), the result is a unique, innovative motor starting solution. A low
Ŷ 1 yellow LED 5 to indicate that the motor is powered at nominal voltage, if it is
power soft start installation now has access to the benefits of the TeSys U-Line motor
connected to the starter
starter, including:
Ŷ A potentiometer 6 for setting the starting time
Ŷ Modular design with a standard 45 mm width
Ŷ A potentiometer 7 for adjusting the start voltage threshold according to the motor
Ŷ Short-circuit and multi-class overload protection
load
2 Ŷ Phase loss, phase imbalance, ground fault, jam, underload, and long-start
Ŷ A potentiometer 8 for setting the deceleration time
protection
Ŷ A connector 9:
Ŷ Fault history
Ƒ 2 logic inputs for Run/Stop commands
Ŷ PC based programming software 4
Ƒ 1 logic input for the BOOST function
Ŷ Optional LCD display 5
6 Ƒ 1 logic output to indicate the end of starting
Ŷ Networking capabilities: Modbus™, AS-I, DeviceNet™, Ethernet TCP/IP,
7 Ƒ 1 relay output to indicate the motor has reached a standstill at the end of the
Profibus® DP
3 8 deceleration stage
Ŷ Monitoring of motor status
Ŷ Remote starting and fault reset
Ŷ Electronic reversing
The panel space required to install the ATS01 soft start and the TeSys U-Line motor 9
starter is minimal, with a standard 45 mm product width and side-by-side mounting.
Please consult the TeSys U-Line motor starter catalog for TeSys U-Line mounting
information.
Example of motor starter/soft start combination
Example of motor starter/soft start combination
8 9
Altistart 01 & U01 Introduction Altistart 01 & U01 Introduction
soft starters for ATS01N2 & ATSU01N2 soft starters soft starters for ATS01N2 & ATSU01N2 soft starters
asynchronous motors asynchronous motors
Note: The ATS01 soft start is internally bypassed at the end of the time set by the start 0 N/Ns
OR
time adjustment. If the motor is not up to speed by that time (due to a heavy load), the 0 0,25 0,5 0,75 1 External Power Supply
internal contactor can be damaged, requiring replacement of the soft start. SET THE (6 to 30 Vdc)
START TIME AT A LEVEL ACHIEVABLE WITH THE MOTOR AT ITS HIGHEST LOAD
LEVEL. This diagram shows the torque/speed characteristic 6 to 30 Vdc = motor up to speed
6 to 30 Vdc = motor up to speed
of a squirrel cage motor in relation to the applied Signal
ATS01 0 Vdc = motor stopped
voltage. The torque varies in proportion to the LO1
0 Vdc = motor stopped
squared ratio of the applied voltage to the motor’s Max
rated voltage at a fixed frequency. For example, 1/2 Current
200 mA
U voltage results in approximately 1/4 torque. The COM
100% Boost
gradual increase in the voltage helps prevent the
Un instantaneous current peak on startup.
External Power
Voltage ramp Supply Common
50%
Un
Fault/stop
Initial voltage
The ATS01 soft start provides a relay contact to indicate either that it has detected a
fault or that it has stopped running the motor. The normally-open contact between
t terminals R1A and R1C closes when a run command is provided at LI2. The relay
200 ms
contact opens under either one of the following two conditions:
Ŷ The contact opens instantly when the soft start detects a fault condition.
Application of a voltage boost equal to 100% of the
nominal motor voltage Ŷ The contact opens when the motor voltage reaches zero after a stop command.
This information can be used to sequence a contactor if both line isolation and soft
stop are needed in the same application.
10 11
Altistart 01 & U01 Introduction Altistart 01 & U01 Introduction
soft starters for ATS01N2 & ATSU01N2 soft starters soft starters for ATS01N2 & ATSU01N2 soft starters
asynchronous motors asynchronous motors
Note: The ATS01 soft start is internally bypassed at the end of the time set by the start 0 N/Ns
OR
time adjustment. If the motor is not up to speed by that time (due to a heavy load), the 0 0,25 0,5 0,75 1 External Power Supply
internal contactor can be damaged, requiring replacement of the soft start. SET THE (6 to 30 Vdc)
START TIME AT A LEVEL ACHIEVABLE WITH THE MOTOR AT ITS HIGHEST LOAD
LEVEL. This diagram shows the torque/speed characteristic 6 to 30 Vdc = motor up to speed
6 to 30 Vdc = motor up to speed
of a squirrel cage motor in relation to the applied Signal
ATS01 0 Vdc = motor stopped
voltage. The torque varies in proportion to the LO1
0 Vdc = motor stopped
squared ratio of the applied voltage to the motor’s Max
rated voltage at a fixed frequency. For example, 1/2 Current
200 mA
U voltage results in approximately 1/4 torque. The COM
100% Boost
gradual increase in the voltage helps prevent the
Un instantaneous current peak on startup.
External Power
Voltage ramp Supply Common
50%
Un
Fault/stop
Initial voltage
The ATS01 soft start provides a relay contact to indicate either that it has detected a
fault or that it has stopped running the motor. The normally-open contact between
t terminals R1A and R1C closes when a run command is provided at LI2. The relay
200 ms
contact opens under either one of the following two conditions:
Ŷ The contact opens instantly when the soft start detects a fault condition.
Application of a voltage boost equal to 100% of the
nominal motor voltage Ŷ The contact opens when the motor voltage reaches zero after a stop command.
This information can be used to sequence a contactor if both line isolation and soft
stop are needed in the same application.
10 11
Altistart 01 & U01 Specifications Altistart 01 & U01 Specifications
soft starters for Environmental soft starters for Electrical
asynchronous motors asynchronous motors
t
Operating cycle
12 13
Altistart 01 & U01 Specifications Altistart 01 & U01 Specifications
soft starters for Environmental soft starters for Electrical
asynchronous motors asynchronous motors
t
Operating cycle
12 13
Altistart 01 & U01 Specifications Altistart 01 & U01 Specifications
soft starters for I/O & Control soft starters for Connections
asynchronous motors asynchronous motors
Contact reference table I/O & Control specifications Connections (maximum connection capacity and tightening torque)
Functions ATS01N1 ATS01N2 ATSU01N2
Relay outputs CL1/0 R1A R1A ATS01N1pppp Control Terminals ATS01N1pppp
CL/2 R1C R1C
Type of Soft Starter ATS01N1 03FT/06FT 09FT/112FT
External power - COM COM
supply 0 V CL1/0 CL2 24V Power circuit Cage type connector Connection onto Ø 4 mm screw terminals
Stranded wire without 1 conductor 2.5 mm2 (14 AWG) 1.5 - 10 mm2 (16 - 8 AWG)
Stop command - LI1 LI1 cable end
2 conductors 1 mm2 (18 AWG) 1.5 - 6 mm2 (16 - 10 AWG)
Control terminal description 110...230 Vac 24 Vac/dc
Run command - LI2 LI2 Stranded wire with 1 conductor 2.5 mm 2
(14 AWG) 1 - 6 mm 2
(18 - 10 AWG)
CL1/0 and CL2 or CL1/0 and 24V Connect line supply to CL2 Connect (+) to 24 V
Control power Connect neutral to CL1/0 Connect (-) to CL1/0 cable end
2 conductors 0.75 mm2 (18 AWG) 1 - 6 mm2 (18 - 10 AWG)
Control section 24V LI + 24V (electrical isolation between line power and
power supply (+24V positive control power) Solid wire 1 conductor 2.5 mm2 (14 AWG) 1 - 10 mm2 (18 - 8 AWG)
logic)
LED Signaling 2 conductors 1 mm 2
(18 AWG) 1 - 6 mm 2
(18 - 10 AWG)
Green LED Soft starter power on
BOOST - BOOST BOOST Tightening torque 0.8 Npm (7 in-lb) 1.9 - 2.5 Npm (16.9 - 22.1 in-lb)
Yellow LED Voltage ramp complete, motor up to speed
End of starting - LO1 LO1 Control circuit Cage type connector Screw connector
Stranded wire without 1 conductor 2.5 mm2 (14 AWG) 0.5 - 2.5 mm2 (20 - 14 AWG)
cable end
2 conductors 1 mm2 (18 AWG) 0.5 - 1.5 mm2 (20 - 16 AWG)
2 2
Stranded wire with 1 conductor 2.5 mm (14 AWG) 0.5 - 1.5 mm (20 - 16 AWG)
cable end
2 conductors 0.75 mm2 (18 AWG) 0.5 - 1.5 mm2 (20 - 16 AWG)
ATS01N2pppp and ATSU01N2pppp Control Terminals
2 2
Solid wire 1 conductor 2.5 mm (14 AWG) 0.5 - 2.5 mm (20 - 14 AWG)
For ATS01N2ppLU/QN/RT soft starters, the power connector is available as an option (VW3G4104).
Control terminal description ATS01N2pppLU/QN/RT ATSU01N2pppLT
24V and COM or LI+ and COM 24 V from ATS01 internal power 24 V ± 10% from ATS01 Power circuit Connection onto Ø 4 mm screw terminals
Control power supply external power supply
(electrical isolation between line Stranded wire without 1 conductor 1.5 - 10 mm2 (16 - 8 AWG)
power and control power) Connect to terminals: Connect to terminals: cable end
2 conductors 1.5 - 6 mm2 (16 - 10 AWG)
LI+ and COM +24V and COM
2
Stranded wire with 1 conductor 1 - 6 mm (16 - 10 AWG)
Max. available current: 10 mA Max. required current: cable end
100 mA 2 conductors 1 - 6 mm2 (16 - 10 AWG)
No short-circuit or overload Solid wire 1 conductor 1 - 10 mm 2
(16 - 8 AWG)
protection
2 conductors 1 - 6 mm2 (16 - 10 AWG)
LI1, LI2, Boost 27 kohms input impedance
Logic inputs 40 Vdc maximum input signal Tightening torque 1.9 - 2.5 Npm (16.9 - 22.1 in-lb)
Stop, Run, and Boost (Kickstart) Max. current: 8 mA
functions State 0 if signal < 5 V Control circuit Screw connector
State 1 if signal > 13 V Stranded wire without 1 conductor 0.5 - 2.5 mm2 (20 - 14 AWG)
LO1 Open collector logic output cable end 2
2 conductors 0.5 - 1.5 mm (20 - 16 AWG)
End of starting signal External power supply (minimum 6 Vdc, maximum 30 Vdc)
Max current: 200 mA Stranded wire with 1 conductor 0.5 - 1.5 mm2 (20 - 16 AWG)
cable end
2 conductors 0.5 - 1.5 mm2 (20 - 16 AWG)
R1A, R1C Normally-open (N.O.) contact
2
Relay output Solid wire 1 conductor 0.5 - 2.5 mm (20 - 14 AWG)
Fault signal and isolation Minimum switching capacity: 10 mA at 6 Vdc 2 conductors 0.5 - 1 mm2 (20 - 18 AWG)
contactor control
Max. switching capacity on inductive load 0 (cos = 0.5 and Ground connection Tinned connector.
Relay contact is open when soft L/R = 20 ms): 2 A at 250 V ac or 30 Vdc (AC-15) (ATSU01N2ppLT only) Fixed using Ø 6 screws
starter is not running or when it
has detected a fault. Max. operating voltage: 44 Vac Tightening torque 0.5 Npm (4.4 in-lb)
LED Signaling
Green LED Soft starter power on
Yellow LED Voltage ramp complete, motor up to speed
14 15
Altistart 01 & U01 Specifications Altistart 01 & U01 Specifications
soft starters for I/O & Control soft starters for Connections
asynchronous motors asynchronous motors
Contact reference table I/O & Control specifications Connections (maximum connection capacity and tightening torque)
Functions ATS01N1 ATS01N2 ATSU01N2
Relay outputs CL1/0 R1A R1A ATS01N1pppp Control Terminals ATS01N1pppp
CL/2 R1C R1C
Type of Soft Starter ATS01N1 03FT/06FT 09FT/112FT
External power - COM COM
supply 0 V CL1/0 CL2 24V Power circuit Cage type connector Connection onto Ø 4 mm screw terminals
Stranded wire without 1 conductor 2.5 mm2 (14 AWG) 1.5 - 10 mm2 (16 - 8 AWG)
Stop command - LI1 LI1 cable end
2 conductors 1 mm2 (18 AWG) 1.5 - 6 mm2 (16 - 10 AWG)
Control terminal description 110...230 Vac 24 Vac/dc
Run command - LI2 LI2 Stranded wire with 1 conductor 2.5 mm 2
(14 AWG) 1 - 6 mm 2
(18 - 10 AWG)
CL1/0 and CL2 or CL1/0 and 24V Connect line supply to CL2 Connect (+) to 24 V
Control power Connect neutral to CL1/0 Connect (-) to CL1/0 cable end
2 conductors 0.75 mm2 (18 AWG) 1 - 6 mm2 (18 - 10 AWG)
Control section 24V LI + 24V (electrical isolation between line power and
power supply (+24V positive control power) Solid wire 1 conductor 2.5 mm2 (14 AWG) 1 - 10 mm2 (18 - 8 AWG)
logic)
LED Signaling 2 conductors 1 mm 2
(18 AWG) 1 - 6 mm 2
(18 - 10 AWG)
Green LED Soft starter power on
BOOST - BOOST BOOST Tightening torque 0.8 Npm (7 in-lb) 1.9 - 2.5 Npm (16.9 - 22.1 in-lb)
Yellow LED Voltage ramp complete, motor up to speed
End of starting - LO1 LO1 Control circuit Cage type connector Screw connector
Stranded wire without 1 conductor 2.5 mm2 (14 AWG) 0.5 - 2.5 mm2 (20 - 14 AWG)
cable end
2 conductors 1 mm2 (18 AWG) 0.5 - 1.5 mm2 (20 - 16 AWG)
2 2
Stranded wire with 1 conductor 2.5 mm (14 AWG) 0.5 - 1.5 mm (20 - 16 AWG)
cable end
2 conductors 0.75 mm2 (18 AWG) 0.5 - 1.5 mm2 (20 - 16 AWG)
ATS01N2pppp and ATSU01N2pppp Control Terminals
2 2
Solid wire 1 conductor 2.5 mm (14 AWG) 0.5 - 2.5 mm (20 - 14 AWG)
For ATS01N2ppLU/QN/RT soft starters, the power connector is available as an option (VW3G4104).
Control terminal description ATS01N2pppLU/QN/RT ATSU01N2pppLT
24V and COM or LI+ and COM 24 V from ATS01 internal power 24 V ± 10% from ATS01 Power circuit Connection onto Ø 4 mm screw terminals
Control power supply external power supply
(electrical isolation between line Stranded wire without 1 conductor 1.5 - 10 mm2 (16 - 8 AWG)
power and control power) Connect to terminals: Connect to terminals: cable end
2 conductors 1.5 - 6 mm2 (16 - 10 AWG)
LI+ and COM +24V and COM
2
Stranded wire with 1 conductor 1 - 6 mm (16 - 10 AWG)
Max. available current: 10 mA Max. required current: cable end
100 mA 2 conductors 1 - 6 mm2 (16 - 10 AWG)
No short-circuit or overload Solid wire 1 conductor 1 - 10 mm 2
(16 - 8 AWG)
protection
2 conductors 1 - 6 mm2 (16 - 10 AWG)
LI1, LI2, Boost 27 kohms input impedance
Logic inputs 40 Vdc maximum input signal Tightening torque 1.9 - 2.5 Npm (16.9 - 22.1 in-lb)
Stop, Run, and Boost (Kickstart) Max. current: 8 mA
functions State 0 if signal < 5 V Control circuit Screw connector
State 1 if signal > 13 V Stranded wire without 1 conductor 0.5 - 2.5 mm2 (20 - 14 AWG)
LO1 Open collector logic output cable end 2
2 conductors 0.5 - 1.5 mm (20 - 16 AWG)
End of starting signal External power supply (minimum 6 Vdc, maximum 30 Vdc)
Max current: 200 mA Stranded wire with 1 conductor 0.5 - 1.5 mm2 (20 - 16 AWG)
cable end
2 conductors 0.5 - 1.5 mm2 (20 - 16 AWG)
R1A, R1C Normally-open (N.O.) contact
2
Relay output Solid wire 1 conductor 0.5 - 2.5 mm (20 - 14 AWG)
Fault signal and isolation Minimum switching capacity: 10 mA at 6 Vdc 2 conductors 0.5 - 1 mm2 (20 - 18 AWG)
contactor control
Max. switching capacity on inductive load 0 (cos = 0.5 and Ground connection Tinned connector.
Relay contact is open when soft L/R = 20 ms): 2 A at 250 V ac or 30 Vdc (AC-15) (ATSU01N2ppLT only) Fixed using Ø 6 screws
starter is not running or when it
has detected a fault. Max. operating voltage: 44 Vac Tightening torque 0.5 Npm (4.4 in-lb)
LED Signaling
Green LED Soft starter power on
Yellow LED Voltage ramp complete, motor up to speed
14 15
Altistart 01 & U01 Selection Table Altistart 01 & U01 Dimensions
soft starters for ATS01N1 soft starters soft starters for ATS01N1 soft starters
asynchronous motors asynchronous motors
1.97
Motor Power Isolation Isolation Fast Acting
50
ATS01 GV Manual
Contactor Contactor Class J Overload Relay(2)
Voltage HP kW Soft Starter Starter
with AC Coil with DC Coil Fuses(1)
3.94
100
0.5 - ATS01N103FT GV2ME07 LC1D09 or LC1K06 LC1D09 or LP1K06 10 A LRD07 or LR2K0308
0.75 - ATS01N106FT GV2ME08 LC1D09 or LC1K06 LC1D09 or LP1K06 15 A LRD08 or LR2K0310
200/
1 - ATS01N106FT GV2ME10 LC1D09 or LC1K06 LC1D09 or LP1K06 15 A LRD10 or LR2K0312
208 V
1.5 - 2 - ATS01N109FT GV2ME14 LC1D09 or LC1K09 LC1D09 or LP1K09 25 A LRD12 or LR2K0314
3 - ATS01N112FT GV2ME16 LC1D12 or LC1K12 LC1D12 or LP1K12 35 A LRD16 or LR2K0316
0.5 - ATS01N103FT GV2ME07 LC1D09 or LC1K06 LC1D09 or LP1K06 10 A LRD07 or LR2K0308
0.75 - ATS01N106FT GV2ME08 LC1D09 or LC1K06 LC1D09 or LP1K06 10 A LRD08 or LR2K0310
ATS01N109FT, 12FT
230/ 1 - ATS01N106FT GV2ME10 LC1D09 or LC1K06 LC1D09 or LP1K06 15 A LRD10 or LR2K0312
240 V 1.5 - ATS01N106FT GV2ME10 LC1D09 or LC1K06 LC1D09 or LP1K06 20 A LRD12 or LR2K0314
Mounting on 5 (35 mm) DIN rail Panel Mounting
2 - ATS01N109FT GV2ME14 LC1D09 or LC1K09 LC1D09 or LP1K09 20 A LRD12 or LR2K0314
5.15
3 - ATS01N112FT GV2ME16 LC1D12 or LC1K12 LC1D12 or LP1K12 30 A LRD16 or LR2K0316 1.19 (1)
4.44 130.7 1.77
0.5 - ATS01N103FT GV2ME06 LC1D09 or LC1K06 LC1D09 or LP1K06 3A LRD06 or LR2K0306 30.2
0.75 - ATS01N103FT GV2ME06 LC1D09 or LC1K06 LC1D09 or LP1K06 6A LRD06 or LR2K0307 112.8 45
1 - ATS01N103FT GV2ME07 LC1D09 or LC1K06 LC1D09 or LP1K06 6A LRD07 or LR2K0308
132.5
460/ 1.5 - ATS01N103FT GV2ME08 LC1D09 or LC1K06 LC1D09 or LP1K06 10 A LRD08 or LR2K0310
5.22
2.07
52.7
480 V 2 - ATS01N106FT GV2ME08 LC1D09 or LC1K06 LC1D09 or LP1K06 10 A LRD08 or LR2K0310
3 - ATS01N106FT GV2ME10 LC1D09 or LC1K06 LC1D09 or LP1K06 15 A LRD10 or LR2K0312
5 - ATS01N109FT GV2ME14 LC1D09 or LC1K09 LC1D09 or LP1K09 25 A LRD12 or LR2K0314
5.71
4.88
145
124
7.5 - ATS01N112FT GV2ME16 LC1D12 or LC1K12 LC1D12 or LP1K12 35 A LRD16 or LR2K0316
- 0.37 ATS01N103FT GV2ME05 LC1D09 or LC1K06 LC1D09 or LP1K06 3A LRD05 or LR2K0306
- 0.55 ATS01N103FT GV2ME06 LC1D09 or LC1K06 LC1D09 or LP1K06 6A LRD06 or LR2K0307
- 0.75 ATS01N103FT GV2ME07 LC1D09 or LC1K06 LC1D09 or LP1K06 6A LRD07 or LR2K0308
- 1.1 ATS01N103FT GV2ME07 LC1D09 or LC1K06 LC1D09 or LP1K06 10 A LRD07 or LR2K0308
400 V - 1.5 ATS01N106FT GV2ME08 LC1D09 or LC1K06 LC1D09 or LP1K06 15 A LRD08 or LR2K0310
- 2.2 ATS01N106FT GV2ME10 LC1D09 or LC1K06 LC1D09 or LP1K06 15 A LRD10 or LR2K0312 (1)
- 3 ATS01N109FT GV2ME14 LC1D09 or LC1K09 LC1D09 or LP1K09 20 A LRD12 or LR2K0314
- 4 ATS01N109FT GV2ME14 LC1D09 or LC1K09 LC1D09 or LP1K09 25 A LRD14 or LR2K0316 (1) Retractable screws
16 17
Altistart 01 & U01 Selection Table Altistart 01 & U01 Dimensions
soft starters for ATS01N1 soft starters soft starters for ATS01N1 soft starters
asynchronous motors asynchronous motors
1.97
Motor Power Isolation Isolation Fast Acting
50
ATS01 GV Manual
Contactor Contactor Class J Overload Relay(2)
Voltage HP kW Soft Starter Starter
with AC Coil with DC Coil Fuses(1)
3.94
100
0.5 - ATS01N103FT GV2ME07 LC1D09 or LC1K06 LC1D09 or LP1K06 10 A LRD07 or LR2K0308
0.75 - ATS01N106FT GV2ME08 LC1D09 or LC1K06 LC1D09 or LP1K06 15 A LRD08 or LR2K0310
200/
1 - ATS01N106FT GV2ME10 LC1D09 or LC1K06 LC1D09 or LP1K06 15 A LRD10 or LR2K0312
208 V
1.5 - 2 - ATS01N109FT GV2ME14 LC1D09 or LC1K09 LC1D09 or LP1K09 25 A LRD12 or LR2K0314
3 - ATS01N112FT GV2ME16 LC1D12 or LC1K12 LC1D12 or LP1K12 35 A LRD16 or LR2K0316
0.5 - ATS01N103FT GV2ME07 LC1D09 or LC1K06 LC1D09 or LP1K06 10 A LRD07 or LR2K0308
0.75 - ATS01N106FT GV2ME08 LC1D09 or LC1K06 LC1D09 or LP1K06 10 A LRD08 or LR2K0310
ATS01N109FT, 12FT
230/ 1 - ATS01N106FT GV2ME10 LC1D09 or LC1K06 LC1D09 or LP1K06 15 A LRD10 or LR2K0312
240 V 1.5 - ATS01N106FT GV2ME10 LC1D09 or LC1K06 LC1D09 or LP1K06 20 A LRD12 or LR2K0314
Mounting on 5 (35 mm) DIN rail Panel Mounting
2 - ATS01N109FT GV2ME14 LC1D09 or LC1K09 LC1D09 or LP1K09 20 A LRD12 or LR2K0314
5.15
3 - ATS01N112FT GV2ME16 LC1D12 or LC1K12 LC1D12 or LP1K12 30 A LRD16 or LR2K0316 1.19 (1)
4.44 130.7 1.77
0.5 - ATS01N103FT GV2ME06 LC1D09 or LC1K06 LC1D09 or LP1K06 3A LRD06 or LR2K0306 30.2
0.75 - ATS01N103FT GV2ME06 LC1D09 or LC1K06 LC1D09 or LP1K06 6A LRD06 or LR2K0307 112.8 45
1 - ATS01N103FT GV2ME07 LC1D09 or LC1K06 LC1D09 or LP1K06 6A LRD07 or LR2K0308
132.5
460/ 1.5 - ATS01N103FT GV2ME08 LC1D09 or LC1K06 LC1D09 or LP1K06 10 A LRD08 or LR2K0310
5.22
2.07
52.7
480 V 2 - ATS01N106FT GV2ME08 LC1D09 or LC1K06 LC1D09 or LP1K06 10 A LRD08 or LR2K0310
3 - ATS01N106FT GV2ME10 LC1D09 or LC1K06 LC1D09 or LP1K06 15 A LRD10 or LR2K0312
5 - ATS01N109FT GV2ME14 LC1D09 or LC1K09 LC1D09 or LP1K09 25 A LRD12 or LR2K0314
5.71
4.88
145
124
7.5 - ATS01N112FT GV2ME16 LC1D12 or LC1K12 LC1D12 or LP1K12 35 A LRD16 or LR2K0316
- 0.37 ATS01N103FT GV2ME05 LC1D09 or LC1K06 LC1D09 or LP1K06 3A LRD05 or LR2K0306
- 0.55 ATS01N103FT GV2ME06 LC1D09 or LC1K06 LC1D09 or LP1K06 6A LRD06 or LR2K0307
- 0.75 ATS01N103FT GV2ME07 LC1D09 or LC1K06 LC1D09 or LP1K06 6A LRD07 or LR2K0308
- 1.1 ATS01N103FT GV2ME07 LC1D09 or LC1K06 LC1D09 or LP1K06 10 A LRD07 or LR2K0308
400 V - 1.5 ATS01N106FT GV2ME08 LC1D09 or LC1K06 LC1D09 or LP1K06 15 A LRD08 or LR2K0310
- 2.2 ATS01N106FT GV2ME10 LC1D09 or LC1K06 LC1D09 or LP1K06 15 A LRD10 or LR2K0312 (1)
- 3 ATS01N109FT GV2ME14 LC1D09 or LC1K09 LC1D09 or LP1K09 20 A LRD12 or LR2K0314
- 4 ATS01N109FT GV2ME14 LC1D09 or LC1K09 LC1D09 or LP1K09 25 A LRD14 or LR2K0316 (1) Retractable screws
16 17
Altistart 01 & U01 Selection Table Altistart 01 & U01 Selection Table
soft starters for ATS01N2 & ATSU01N2 soft starters soft starters for Tesys U-Line motor starter combinations
asynchronous motors asynchronous motors
Part Number Explanation ATS01N2 & ATSU01N2 soft starters ATS01 and TeSys U-Line motor starter combinations
LUBp2p
Supply Voltage The ATS01N2ppLU/QN/RT and ATSU01N2ppLT soft starters control the starting and Numerous combination possibilities exist. Consult the TeSys U-Line motor starter
FT = 115 - 480 V QN = 400 V stopping ramps of three-phase motors ranging from 0.5 to 20 HP (0.75 to 15 kW), and catalog for more information.
Product Family
LU = 200 - 240 V RT = 460 V have a motor voltage range of 208 V to 460 V.
Altistart 01
LT = 200 - 460 V
Motor Power(1) ATS01 Rated
1 24 Vdc Control Power
ATS01N1 pp FT The ATSU01N2ppLT soft starter features the same specifications as the Current
ATS01N2 pp LU/QN/RT ATS01N2ppLU/QN/RT, with the added benefits of the Tesys U-Line motor starter. Voltage kW HP A TeSys U-Line
ATSU01N2 pp LT ATS01 Soft Starter
Power Base Control Module(2)
The ATS01N2 and ATSU01N2 are compatible with these common motor voltages: 0.75 1 6 ATS01N206LU LUB12 LUCp05FU
Power Range (Amps) 2
ATS01N1: 03, 06, 09, or 12 Ŷ 0.5 to 10 HP @ 200/208 V
1.1 1.5 6 ATS01N206LU LUB12 LUCp12FU
ATS01N2: 06, 09, 12, 22, or 32 Ŷ 0.5 to 10 HP @ 230/240 V
ATSU01N2: 06, 09, 12, 22, or 32 Ŷ 1.1 to 15 kW @ 400 V 1.5 2 9 ATS01N209LU LUB12 LUCp12FU
Ŷ 0.5 to 20 HP @ 460 V 2.2 3 12 ATS01N212LU LUB12 LUCp12FU
230 V
3 - 12 ATS01N212LU LUB32 LUCp18FU
4 5 22 ATS01N222LU LUB32 LUCp18FU
5.5 7.5 22 ATS01N222LU LUB32 LUCp32FU
7.5 10 32 ATS01N232LU LUB32 LUCp32FU
18 19
Altistart 01 & U01 Selection Table Altistart 01 & U01 Selection Table
soft starters for ATS01N2 & ATSU01N2 soft starters soft starters for Tesys U-Line motor starter combinations
asynchronous motors asynchronous motors
Part Number Explanation ATS01N2 & ATSU01N2 soft starters ATS01 and TeSys U-Line motor starter combinations
LUBp2p
Supply Voltage The ATS01N2ppLU/QN/RT and ATSU01N2ppLT soft starters control the starting and Numerous combination possibilities exist. Consult the TeSys U-Line motor starter
FT = 115 - 480 V QN = 400 V stopping ramps of three-phase motors ranging from 0.5 to 20 HP (0.75 to 15 kW), and catalog for more information.
Product Family
LU = 200 - 240 V RT = 460 V have a motor voltage range of 208 V to 460 V.
Altistart 01
LT = 200 - 460 V
Motor Power(1) ATS01 Rated
1 24 Vdc Control Power
ATS01N1 pp FT The ATSU01N2ppLT soft starter features the same specifications as the Current
ATS01N2 pp LU/QN/RT ATS01N2ppLU/QN/RT, with the added benefits of the Tesys U-Line motor starter. Voltage kW HP A TeSys U-Line
ATSU01N2 pp LT ATS01 Soft Starter
Power Base Control Module(2)
The ATS01N2 and ATSU01N2 are compatible with these common motor voltages: 0.75 1 6 ATS01N206LU LUB12 LUCp05FU
Power Range (Amps) 2
ATS01N1: 03, 06, 09, or 12 Ŷ 0.5 to 10 HP @ 200/208 V
1.1 1.5 6 ATS01N206LU LUB12 LUCp12FU
ATS01N2: 06, 09, 12, 22, or 32 Ŷ 0.5 to 10 HP @ 230/240 V
ATSU01N2: 06, 09, 12, 22, or 32 Ŷ 1.1 to 15 kW @ 400 V 1.5 2 9 ATS01N209LU LUB12 LUCp12FU
Ŷ 0.5 to 20 HP @ 460 V 2.2 3 12 ATS01N212LU LUB12 LUCp12FU
230 V
3 - 12 ATS01N212LU LUB32 LUCp18FU
4 5 22 ATS01N222LU LUB32 LUCp18FU
5.5 7.5 22 ATS01N222LU LUB32 LUCp32FU
7.5 10 32 ATS01N232LU LUB32 LUCp32FU
18 19
Altistart 01 & U01 Dimensions Altistart 01 & U01 Dimensions
soft starters for ATS01N206pp to ATS01N212pp soft starters for ATS01N222pp, ATS01N232pp
asynchronous motors ATSU01N206LT to ATSU01N212LT asynchronous motors ATSU01N222LT, ATSU01N232LT
Dimensions Dimensions
WxHxD WxHxD
Soft Starter Soft Starter
inches mm inches mm
ATS01N206LU/QN/RT...ATS01N212LU/QN/RT, ATS01N222LU/QN/RT...ATS01N232LU/QN/RT,
1.77 x 4.88 x 5.15 45 x 124 x 130.7 1.77 x 6.06 x 5.16 45 x 154 x 131
ATSU01N206LT...ATSU01N212LT ATSU01N222LT...ATSU01N232LT
U U U
U U U
11.18
5.91
284
150
12.36
6.69
170
314
A A A
A A A
ATSU01N206LU/QN/RT... ATS01N222LU/QN/RT...
ATSU01N212LU/QN/RT, ATS01N232LU/QN/RT,
(1)
(1)
TeSys U-Line combination (non-reversing or reversing power base) and ATS01N206pp..ATS01N212pp or ATSU01N206LT...ATSU01N212LT TeSys U-Line combination (non-reversing or reversing power base) and ATS01N222pp...ATS01N232pp or ATSU01N222LT...ATSU01N232LT
Side-by-side mounting Panel mounting Side-by-side mounting Panel mounting
1.19 (1)
5.31 1.19 (2) 30.2
5.31 3.90
135 3.90 30.2 135 99
99
2.84
72.2
2.84
72.2
162.5 6.89
175
5.71 132.5
5.22
A
4.88
124
U A
6.06
A U A
154
6.40
6.06
154
145
(1) Gap only required when using a TeSys-U type LUCM multifunction control unit in an ambient temperature above 113 °F (45 °C). See TeSys U-Line motor starter catalog for more information (1) Gap only required when using a TeSys-U type LUCM multifunction control unit in an ambient temperature above 113 °F (45 °C). See TeSys U-Line motor starter catalog for more information
(2) Retractable screw tabs (2) Retractable screw tabs
20 21
Altistart 01 & U01 Dimensions Altistart 01 & U01 Dimensions
soft starters for ATS01N206pp to ATS01N212pp soft starters for ATS01N222pp, ATS01N232pp
asynchronous motors ATSU01N206LT to ATSU01N212LT asynchronous motors ATSU01N222LT, ATSU01N232LT
Dimensions Dimensions
WxHxD WxHxD
Soft Starter Soft Starter
inches mm inches mm
ATS01N206LU/QN/RT...ATS01N212LU/QN/RT, ATS01N222LU/QN/RT...ATS01N232LU/QN/RT,
1.77 x 4.88 x 5.15 45 x 124 x 130.7 1.77 x 6.06 x 5.16 45 x 154 x 131
ATSU01N206LT...ATSU01N212LT ATSU01N222LT...ATSU01N232LT
U U U
U U U
11.18
5.91
284
150
12.36
6.69
170
314
A A A
A A A
ATSU01N206LU/QN/RT... ATS01N222LU/QN/RT...
ATSU01N212LU/QN/RT, ATS01N232LU/QN/RT,
(1)
(1)
TeSys U-Line combination (non-reversing or reversing power base) and ATS01N206pp..ATS01N212pp or ATSU01N206LT...ATSU01N212LT TeSys U-Line combination (non-reversing or reversing power base) and ATS01N222pp...ATS01N232pp or ATSU01N222LT...ATSU01N232LT
Side-by-side mounting Panel mounting Side-by-side mounting Panel mounting
1.19 (1)
5.31 1.19 (2) 30.2
5.31 3.90
135 3.90 30.2 135 99
99
2.84
72.2
2.84
72.2
162.5 6.89
175
5.71 132.5
5.22
A
4.88
124
U A
6.06
A U A
154
6.40
6.06
154
145
(1) Gap only required when using a TeSys-U type LUCM multifunction control unit in an ambient temperature above 113 °F (45 °C). See TeSys U-Line motor starter catalog for more information (1) Gap only required when using a TeSys-U type LUCM multifunction control unit in an ambient temperature above 113 °F (45 °C). See TeSys U-Line motor starter catalog for more information
(2) Retractable screw tabs (2) Retractable screw tabs
20 21
Altistart 01 & U01 Accessories Altistart 01 & U01 Wiring Diagrams
soft starters for Power connector soft starters for Motor Installation
asynchronous motors asynchronous motors
The power connector is included with the ATSU01N2ppLT soft starter offer. Overload
KM1 (1) Fuses Relay KM1 (1) Fuses
VW3G4104
Dimensions
(1): Optional contactor for line isolation and remote control.
WxHxD
Part number (2): Other motor starters must provide motor overload protection.
inches mm
VW3G4104 1.76 x 1.10 x 1.83 44.8 x 28 x 46.6 Note: Observe national and local electrical codes when selecting
the circuit breaker and other motor starters. See the selection table
on page 18 for recommendations on the following components:
Ŷ ATS01 soft start
Ŷ GV manual starter
Ŷ KM1 isolation contactor
1.83
46.6
Ŷ Fuses
ATSp01N2pppp
Ŷ Overload relay
in.
1.10
Dimensions: mm
28
0.24
6
22 23
Altistart 01 & U01 Accessories Altistart 01 & U01 Wiring Diagrams
soft starters for Power connector soft starters for Motor Installation
asynchronous motors asynchronous motors
The power connector is included with the ATSU01N2ppLT soft starter offer. Overload
KM1 (1) Fuses Relay KM1 (1) Fuses
VW3G4104
Dimensions
(1): Optional contactor for line isolation and remote control.
WxHxD
Part number (2): Other motor starters must provide motor overload protection.
inches mm
VW3G4104 1.76 x 1.10 x 1.83 44.8 x 28 x 46.6 Note: Observe national and local electrical codes when selecting
the circuit breaker and other motor starters. See the selection table
on page 18 for recommendations on the following components:
Ŷ ATS01 soft start
Ŷ GV manual starter
Ŷ KM1 isolation contactor
1.83
46.6
Ŷ Fuses
ATSp01N2pppp
Ŷ Overload relay
in.
1.10
Dimensions: mm
28
0.24
6
22 23
Altistart 01 & U01 Wiring Diagrams Altistart 01 & U01 Wiring Diagrams
soft starters for ATS01N1pppp soft starters for ATS01N1pppp
asynchronous motors asynchronous motors
110-240 V 208-480 V
L1
L2
L1
L2
L3
Q1 Q1
Manual Starter Manual Starter
or Disconnect or Disconnect
+ L - N KM1 + L - N KM1
OL (2) OL (2)
(3)
FU1 FU1
S1 S2 S1 S2
STOP START STOP START
Q1 OL OL
1/L1 Q1
3/L2
5/L3
1/L1
3/L2
5/L3
KM1 A1 A1
KM1
TS CL1/0 CL1/0
TS
KM1
120 V KM1
ATS01N1--FT 120 V
CL2 CL2 ..
24 Vdc 24 Vdc
24 V 24 V
2/T1
4/T2
6/T3
2/T1
4/T2
6/T3
M1 M1
1~ 3~
Notes:
Notes:
Line voltage/ A1: ATS01 soft starter Line voltage/ A1: ATS01 soft starter
Green LED FU1: Control circuit fuse - 120 Vac control power only Green LED
FU1: Control circuit fuse - 120 Vac control power only
Start FU3: Fast-acting UL Listed Class J fuse Start
Stop Stop FU3: Fast-acting UL Listed Class J fuse
KM1: Isolation contactor
KM1: Isolation contactor
TS: Transient suppressor
Yellow LED Yellow LED TS: Transient suppressor
OL: Overload relay
OL: Overload relay
Q1: Manual motor starter or disconnect switch
V1
V1
S1, S2: Momentary pushbuttons
Motor voltage Motor voltage S1, S2: Momentary pushbuttons
t1: 1 - 5 second adjustable starting time
t1 t t1 t t1: 1 - 5 second adjustable starting time
V1: Initial motor voltage - adjustable from 30 to 80% of the
motor’s rated voltage (1) Fuses FU3 are not required if device Q1 is a TeSys U-Line or GV manual
starter. Motor starter installed per local and national electrical codes. Fuse is
(1) Fuses FU3 are not required if device Q1 is a TeSys U-Line or GV manual not required on neutral log.
starter. Motor starter installed per local and national electrical codes. (2) Overload protection is required if not included on device Q1.
(2) Overload protection is required if not included on device Q1. (3) Wait 5 seconds after switching off the soft start before switching it on again.
24 25
Altistart 01 & U01 Wiring Diagrams Altistart 01 & U01 Wiring Diagrams
soft starters for ATS01N1pppp soft starters for ATS01N1pppp
asynchronous motors asynchronous motors
110-240 V 208-480 V
L1
L2
L1
L2
L3
Q1 Q1
Manual Starter Manual Starter
or Disconnect or Disconnect
+ L - N KM1 + L - N KM1
OL (2) OL (2)
(3)
FU1 FU1
S1 S2 S1 S2
STOP START STOP START
Q1 OL OL
1/L1 Q1
3/L2
5/L3
1/L1
3/L2
5/L3
KM1 A1 A1
KM1
TS CL1/0 CL1/0
TS
KM1
120 V KM1
ATS01N1--FT 120 V
CL2 CL2 ..
24 Vdc 24 Vdc
24 V 24 V
2/T1
4/T2
6/T3
2/T1
4/T2
6/T3
M1 M1
1~ 3~
Notes:
Notes:
Line voltage/ A1: ATS01 soft starter Line voltage/ A1: ATS01 soft starter
Green LED FU1: Control circuit fuse - 120 Vac control power only Green LED
FU1: Control circuit fuse - 120 Vac control power only
Start FU3: Fast-acting UL Listed Class J fuse Start
Stop Stop FU3: Fast-acting UL Listed Class J fuse
KM1: Isolation contactor
KM1: Isolation contactor
TS: Transient suppressor
Yellow LED Yellow LED TS: Transient suppressor
OL: Overload relay
OL: Overload relay
Q1: Manual motor starter or disconnect switch
V1
V1
S1, S2: Momentary pushbuttons
Motor voltage Motor voltage S1, S2: Momentary pushbuttons
t1: 1 - 5 second adjustable starting time
t1 t t1 t t1: 1 - 5 second adjustable starting time
V1: Initial motor voltage - adjustable from 30 to 80% of the
motor’s rated voltage (1) Fuses FU3 are not required if device Q1 is a TeSys U-Line or GV manual
starter. Motor starter installed per local and national electrical codes. Fuse is
(1) Fuses FU3 are not required if device Q1 is a TeSys U-Line or GV manual not required on neutral log.
starter. Motor starter installed per local and national electrical codes. (2) Overload protection is required if not included on device Q1.
(2) Overload protection is required if not included on device Q1. (3) Wait 5 seconds after switching off the soft start before switching it on again.
24 25
Altistart 01 & U01 Wiring Diagrams Altistart 01 & U01 Wiring Diagrams
soft starters for ATS01N2pppp & ATSU01N2pppp soft starters for ATS01N2pppp & ATSU01N2pppp
asynchronous motors asynchronous motors
ATS01N2ppLU/QN/RT ATS01N2ppLU/QN/RT
208-480 V 208-480 V
L1
L2
L3
120 Vac Supply
L1
L2
L3
120 Vac Supply
L N L N
LUB LUB
TeSys U-line S1 TeSys U-line
Fuse S1 Fuse EMERG S2
LUB STOP/RUN LUB STOP STOP/RUN LUB
LUB
LUA1C20 LUA1C20
M M
17 18 A1 A2
1/L1
3/L2
5/L3
17 18 A1 A2 A1
1/L1
3/L2
5/L3
A1
R1A R1A
R1C R1C
COM COM
**** ATS01N2,,,,
LI1 (3) LI1
LI2 LI2
Line voltage LI+ Line voltage LI+
(1) BOOST Logic input LI2 (1) BOOST
2/T1
4/T2
6/T3
2/T1
4/T2
6/T3
(2) LO1 Pushbutton S2 (2) LO1
Green LED
Pushbutton S1
Logic input LI2
Pushbutton S1
Yellow LED
10 s
Yellow LED M1 M1
Logic output LO1 3~
10 s 3~
V1
Logic output LO1
Motor voltage
V1
t1 t2
Motor voltage
t1
ATSU01N2ppLT Notes: ATSU01N2ppLT
Notes: 208-480 V 208-480 V
A1: ATS01 soft starter
LUB: TeSys U-Line motor starter
L1
L2
L3
24 Vdc Supply
L1
L2
L3
A1: ATS01 soft starter 24 Vdc Supply
LUA1C20: Control circuit contact block for TeSys
LUB: TeSys U-Line motor starter
U-Line motor starter + -
LUA1C20: Control circuit contact block for TeSys + -
S1, S2: Selector switches or maintained pushbuttons
U-Line motor starter
t1: 1 - 10 second adjustable starting time LUB
S1: Selector switch or maintained pushbutton LUB
t2: 1 - 10 second adjustable stopping time S1 TeSys U-line
t1: 1 - 10 second adjustable starting time TeSys U-line
S1
V1: Initial motor voltage - adjustable from 30 to 80% EMERG S2
V1: Initial motor voltage - adjustable from 30 to 80% STOP STOP/RUN
LUB STOP/RUN LUB of the motor’s rated voltage LUB LUB
of the motor’s rated voltage LUA1C20
LUA1C20
(1) Optional jumper to select boost M
(1) Optional jumper to select boost M (2) See page 11 for L01 wiring recommendations 17 18 A1 A2
1/L1
3/L2
5/L3
(2) See page 11 for L01 wiring recommendations 17 18 A1 A2 A1
1/L1
3/L2
5/L3
R1A
R1A
R1C
R1C
COM
COM ++
)) LI1
LI1
LI2
LI2
+24 V
+24 V
(1) BOOST
2/T1
4/T2
6/T3
(1) BOOST
(2) LO1
2/T1
4/T2
6/T3
(2) LO1
M1
M1 3~
3~
26 27
Altistart 01 & U01 Wiring Diagrams Altistart 01 & U01 Wiring Diagrams
soft starters for ATS01N2pppp & ATSU01N2pppp soft starters for ATS01N2pppp & ATSU01N2pppp
asynchronous motors asynchronous motors
ATS01N2ppLU/QN/RT ATS01N2ppLU/QN/RT
208-480 V 208-480 V
L1
L2
L3
120 Vac Supply
L1
L2
L3
120 Vac Supply
L N L N
LUB LUB
TeSys U-line S1 TeSys U-line
Fuse S1 Fuse EMERG S2
LUB STOP/RUN LUB STOP STOP/RUN LUB
LUB
LUA1C20 LUA1C20
M M
17 18 A1 A2
1/L1
3/L2
5/L3
17 18 A1 A2 A1
1/L1
3/L2
5/L3
A1
R1A R1A
R1C R1C
COM COM
**** ATS01N2,,,,
LI1 (3) LI1
LI2 LI2
Line voltage LI+ Line voltage LI+
(1) BOOST Logic input LI2 (1) BOOST
2/T1
4/T2
6/T3
2/T1
4/T2
6/T3
(2) LO1 Pushbutton S2 (2) LO1
Green LED
Pushbutton S1
Logic input LI2
Pushbutton S1
Yellow LED
10 s
Yellow LED M1 M1
Logic output LO1 3~
10 s 3~
V1
Logic output LO1
Motor voltage
V1
t1 t2
Motor voltage
t1
ATSU01N2ppLT Notes: ATSU01N2ppLT
Notes: 208-480 V 208-480 V
A1: ATS01 soft starter
LUB: TeSys U-Line motor starter
L1
L2
L3
24 Vdc Supply
L1
L2
L3
A1: ATS01 soft starter 24 Vdc Supply
LUA1C20: Control circuit contact block for TeSys
LUB: TeSys U-Line motor starter
U-Line motor starter + -
LUA1C20: Control circuit contact block for TeSys + -
S1, S2: Selector switches or maintained pushbuttons
U-Line motor starter
t1: 1 - 10 second adjustable starting time LUB
S1: Selector switch or maintained pushbutton LUB
t2: 1 - 10 second adjustable stopping time S1 TeSys U-line
t1: 1 - 10 second adjustable starting time TeSys U-line
S1
V1: Initial motor voltage - adjustable from 30 to 80% EMERG S2
V1: Initial motor voltage - adjustable from 30 to 80% STOP STOP/RUN
LUB STOP/RUN LUB of the motor’s rated voltage LUB LUB
of the motor’s rated voltage LUA1C20
LUA1C20
(1) Optional jumper to select boost M
(1) Optional jumper to select boost M (2) See page 11 for L01 wiring recommendations 17 18 A1 A2
1/L1
3/L2
5/L3
(2) See page 11 for L01 wiring recommendations 17 18 A1 A2 A1
1/L1
3/L2
5/L3
R1A
R1A
R1C
R1C
COM
COM ++
)) LI1
LI1
LI2
LI2
+24 V
+24 V
(1) BOOST
2/T1
4/T2
6/T3
(1) BOOST
(2) LO1
2/T1
4/T2
6/T3
(2) LO1
M1
M1 3~
3~
26 27
Altistart 01 & U01 Wiring Diagrams Altistart 01 & U01 Wiring Diagrams
soft starters for ATS01N2pppp & ATSU01N2pppp soft starters for ATS01N2pppp & ATSU01N2pppp
asynchronous motors asynchronous motors
ATS01N2ppLU/QN/RT ATS01N2ppLU/QN/RT
208-480 V
208-480 V
L1
L2
L3
120 Vac Supply
L1
L2
L3
120 Vac Supply
L N L N
LUB LUB
TeSys U-line TeSys U-line
Fuse Fuse
S1 S2 S2
LUB LUB START LUB
STOP START LUB LUA1C20
LUA1C20
M
M
17 18 A1 A2
3/L2
5/L3
1/L1
17 18 A1 A2 A1
1/L1
3/L2
5/L3
A1
LUB LUB
R1A R1A
R1C R1C
S1 14 13
14 13 COM STOP COM
(3) ****
**** LI1
LI1
LI2 LI2
LI+ LI+
Line voltage (1) BOOST (1) BOOST
Line voltage
2/T1
4/T2
6/T3
2/T1
4/T2
6/T3
500 ms (2) LO1 (2) LO1
Pushbutton S1 Logic input LI2
Pushbutton S2
Pushbutton S2 Logic input LI1
Pushbutton S1
Logic output LI2
M1 Yellow LED M1
Yellow LED 10 s 3~
10 s 3~
Logic output LO1 Logic output LO1
V1
V1
ATSU01N2ppLT ATSU01N2ppLT
208-480 V Notes: 208-480 V
Notes:
A1: ATS01 soft starter
L1
L2
L3
L1
L2
L3
24 Vdc Supply 24 Vdc Supply
A1: ATS01 soft starter LUB: TeSys U-Line motor starter
LUB: TeSys U-Line motor starter + - LUA1C20: Control circuit contact block for TeSys + -
LUA1C20: Control circuit contact block for TeSys U-Line motor starter
U-Line motor starter LUB S1, S2: Momentary pushbuttons LUB
S1, S2: Momentary pushbuttons TeSys U-line t1: 1 - 10 second adjustable starting time TeSys U-line
t1: 1 - 10 second adjustable starting time S1 S2
t2: 1 - 10 second adjustable stopping time S2
V1: Initial motor voltage - adjustable from 30 to 80% LUB LUB V1: Initial motor voltage - adjustable from 30 to 80% LUB LUB
STOP START START
LUA1C20 LUA1C20
of the motor’s rated voltage of the motor’s rated voltage
M M
17 18 A1 A2 17 18 A1 A2
1/L1
3/L2
5/L3
1/L1
A1 A1
3/L2
5/L3
(1) Optional jumper to select boost (1) Optional jumper to select boost
(2) See page 11 for L01 wiring recommendations (2) See page 11 for L01 wiring recommendations LUB
R1A (3) Use shielded cable if control wiring is longer than 3 feet R1A
R1C R1C
LUB S1 14 13
COM STOP COM
)) ))
LI1 LI1
14 13 LI2 LI2
+24 V +24 V
(1) BOOST (1) BOOST
2/T1
4/T2
6/T3
2/T1
4/T2
6/T3
(2) LO1 (2) LO1
M1 M1
3~ 3~
28 29
Altistart 01 & U01 Wiring Diagrams Altistart 01 & U01 Wiring Diagrams
soft starters for ATS01N2pppp & ATSU01N2pppp soft starters for ATS01N2pppp & ATSU01N2pppp
asynchronous motors asynchronous motors
ATS01N2ppLU/QN/RT ATS01N2ppLU/QN/RT
208-480 V
208-480 V
L1
L2
L3
120 Vac Supply
L1
L2
L3
120 Vac Supply
L N L N
LUB LUB
TeSys U-line TeSys U-line
Fuse Fuse
S1 S2 S2
LUB LUB START LUB
STOP START LUB LUA1C20
LUA1C20
M
M
17 18 A1 A2
3/L2
5/L3
1/L1
17 18 A1 A2 A1
1/L1
3/L2
5/L3
A1
LUB LUB
R1A R1A
R1C R1C
S1 14 13
14 13 COM STOP COM
(3) ****
**** LI1
LI1
LI2 LI2
LI+ LI+
Line voltage (1) BOOST (1) BOOST
Line voltage
2/T1
4/T2
6/T3
2/T1
4/T2
6/T3
500 ms (2) LO1 (2) LO1
Pushbutton S1 Logic input LI2
Pushbutton S2
Pushbutton S2 Logic input LI1
Pushbutton S1
Logic output LI2
M1 Yellow LED M1
Yellow LED 10 s 3~
10 s 3~
Logic output LO1 Logic output LO1
V1
V1
ATSU01N2ppLT ATSU01N2ppLT
208-480 V Notes: 208-480 V
Notes:
A1: ATS01 soft starter
L1
L2
L3
L1
L2
L3
24 Vdc Supply 24 Vdc Supply
A1: ATS01 soft starter LUB: TeSys U-Line motor starter
LUB: TeSys U-Line motor starter + - LUA1C20: Control circuit contact block for TeSys + -
LUA1C20: Control circuit contact block for TeSys U-Line motor starter
U-Line motor starter LUB S1, S2: Momentary pushbuttons LUB
S1, S2: Momentary pushbuttons TeSys U-line t1: 1 - 10 second adjustable starting time TeSys U-line
t1: 1 - 10 second adjustable starting time S1 S2
t2: 1 - 10 second adjustable stopping time S2
V1: Initial motor voltage - adjustable from 30 to 80% LUB LUB V1: Initial motor voltage - adjustable from 30 to 80% LUB LUB
STOP START START
LUA1C20 LUA1C20
of the motor’s rated voltage of the motor’s rated voltage
M M
17 18 A1 A2 17 18 A1 A2
1/L1
3/L2
5/L3
1/L1
A1 A1
3/L2
5/L3
(1) Optional jumper to select boost (1) Optional jumper to select boost
(2) See page 11 for L01 wiring recommendations (2) See page 11 for L01 wiring recommendations LUB
R1A (3) Use shielded cable if control wiring is longer than 3 feet R1A
R1C R1C
LUB S1 14 13
COM STOP COM
)) ))
LI1 LI1
14 13 LI2 LI2
+24 V +24 V
(1) BOOST (1) BOOST
2/T1
4/T2
6/T3
2/T1
4/T2
6/T3
(2) LO1 (2) LO1
M1 M1
3~ 3~
28 29
Altistart 01 & U01 Wiring Diagrams Altistart 01 & U01 Wiring Diagrams
soft starters for ATS01N2pppp & ATSU01N2pppp soft starters for ATS01N2pppp & ATSU01N2pppp
asynchronous motors asynchronous motors
L1
L2
L3
L1
L2
L3
L1
L2
L3
120 Vac Supply 24 Vdc Supply
1/L1
3/L2
5/L3
17 18 A1 A2 A1
R1A
1/L1
3/L2
5/L3
1/L1
3/L2
5/L3
R1C A1 A1
COM ,,,,
LI1 R1A R1A
LI2 R1C R1C
(1) LI+
Line voltage COM COM
BOOST 6666 ATSU01N255LT
2/T1
4/T2
6/T3
(3) LI1 LI1
S1 Hand LO1
AUTO (4) LI2 LI2
Off
Auto RUN/STOP LI+ +24 V
(1) BOOST (1) BOOST
2/T1
4/T2
6/T3
2/T1
4/T2
6/T3
Auto Run/Stop (2) LO1 (2) LO1
(2) M1
3~
Yellow LED
10 s
Motor voltage
t1 t2 t
ATSU01N2ppLT
Notes: 208-480 V
L1
L2
L3
A1: ATS01 soft starter
LUB: TeSys U-Line motor starter 24 Vdc Supply
LUA1C20: Control circuit contact block for TeSys Notes:
+ - Line voltage
U-Line motor starter S1 LUB
S1, S2: Momentary pushbuttons HAND - OFF - AUTO TeSys U-Line A1: ATS01 soft starter
S1 - Start forward
t1: 1 - 10 second adjustable starting time LUB: TeSys U-Line motor starter
S2 - Start reverse LUA1C20: Control circuit contact block
t2: 1 - 10 second adjustable stopping time See note.
V1: Initial motor voltage - adjustable from 30 to 80% LUB LUB S3 - Stop for TeSys U-Line motor starter
of the motor’s rated voltage LUA1C20 S1, S2: Momentary pushbuttons
M
S3: Momentary pushbutton - must be held
1/L1
3/L2
5/L3
17 18 A1 A2 A1 Yellow LED
(1) Use shielded cable if control wiring is longer than 3 feet 10 s for a minimum of 1/2 second
(2) From automated control system
(3) Optional jumper to select boost R1A t1: 1 - 10 second adjustable starting time
Logic output LO1
(4) See page 11 for L01 wiring recommendations R1C V1: Initial motor voltage - adjustable from
V1
COM ,,
30 to 80% of the motor’s rated voltage
LI1 Motor voltage
LI2
+24 V t1 t (1) Optional jumper to select boost
motor reverses (2) See page 11 for L01 wiring recommendations
BOOST
2/T1
4/T2
6/T3
(3) LO1
AUTO (4)
RUN/STOP
(2) M1
3~
30 31
Altistart 01 & U01 Wiring Diagrams Altistart 01 & U01 Wiring Diagrams
soft starters for ATS01N2pppp & ATSU01N2pppp soft starters for ATS01N2pppp & ATSU01N2pppp
asynchronous motors asynchronous motors
L1
L2
L3
L1
L2
L3
L1
L2
L3
120 Vac Supply 24 Vdc Supply
1/L1
3/L2
5/L3
17 18 A1 A2 A1
R1A
1/L1
3/L2
5/L3
1/L1
3/L2
5/L3
R1C A1 A1
COM ,,,,
LI1 R1A R1A
LI2 R1C R1C
(1) LI+
Line voltage COM COM
BOOST 6666 ATSU01N255LT
2/T1
4/T2
6/T3
(3) LI1 LI1
S1 Hand LO1
AUTO (4) LI2 LI2
Off
Auto RUN/STOP LI+ +24 V
(1) BOOST (1) BOOST
2/T1
4/T2
6/T3
2/T1
4/T2
6/T3
Auto Run/Stop (2) LO1 (2) LO1
(2) M1
3~
Yellow LED
10 s
Motor voltage
t1 t2 t
ATSU01N2ppLT
Notes: 208-480 V
L1
L2
L3
A1: ATS01 soft starter
LUB: TeSys U-Line motor starter 24 Vdc Supply
LUA1C20: Control circuit contact block for TeSys Notes:
+ - Line voltage
U-Line motor starter S1 LUB
S1, S2: Momentary pushbuttons HAND - OFF - AUTO TeSys U-Line A1: ATS01 soft starter
S1 - Start forward
t1: 1 - 10 second adjustable starting time LUB: TeSys U-Line motor starter
S2 - Start reverse LUA1C20: Control circuit contact block
t2: 1 - 10 second adjustable stopping time See note.
V1: Initial motor voltage - adjustable from 30 to 80% LUB LUB S3 - Stop for TeSys U-Line motor starter
of the motor’s rated voltage LUA1C20 S1, S2: Momentary pushbuttons
M
S3: Momentary pushbutton - must be held
1/L1
3/L2
5/L3
17 18 A1 A2 A1 Yellow LED
(1) Use shielded cable if control wiring is longer than 3 feet 10 s for a minimum of 1/2 second
(2) From automated control system
(3) Optional jumper to select boost R1A t1: 1 - 10 second adjustable starting time
Logic output LO1
(4) See page 11 for L01 wiring recommendations R1C V1: Initial motor voltage - adjustable from
V1
COM ,,
30 to 80% of the motor’s rated voltage
LI1 Motor voltage
LI2
+24 V t1 t (1) Optional jumper to select boost
motor reverses (2) See page 11 for L01 wiring recommendations
BOOST
2/T1
4/T2
6/T3
(3) LO1
AUTO (4)
RUN/STOP
(2) M1
3~
30 31
Altistart 01 & U01 Wiring Diagrams Altistart 01 & U01 Wiring Diagrams
soft starters for ATS01N2pppp & ATSU01N2pppp soft starters for ATS01N2pppp & ATSU01N2pppp
asynchronous motors asynchronous motors
L1
L2
L3
L1
L2
L3
24 Vdc Supply 24 Vdc Supply
L1
L2
L3
L1
L2
L3
120 Vac Supply 24 Vdc Supply
L N + - + - + -
S2 S2
START START LUB LUB
Fuse LUB LUB LUB LUB TeSys U-line TeSys U-line
REVERSE REVERSE
LUA1C20 LUA1C20
TeSys U-Line TeSys U-Line
A3 with reversing A3 with reversing
17 18 B3 17 18 B3 LO1 LO1
module module Modbus Modbus
S1 S1 COM COM
A1 LU2B62FU A1 5 module module
START START
FORWARD B1 FORWARD B1 +24 V LULC031 +24 V LULC031
A2 A2 -24 V -24 V
+24 V Aux +24 V Aux
-24 V Aux -24 V Aux
1/L1
3/L2
5/L3
1/L1
3/L2
5/L3
A1 A1
LU9BN11C LU9BN11C
R1A R1A
Pre-wired coil Pre-wired coil
S3 R1C S3 R1C
STOP COM STOP COM
(3) 6666 ATSU01N255LT
LI1 LI1
1/L1
3/L2
5/L3
1/L1
3/L2
5/L3
LI2 LI2 A1 A1
LI+ +24 V
(1) BOOST (1) BOOST R1A R1A
2/T1
4/T2
6/T3
2/T1
4/T2
6/T3
(2) LO1 (2) LO1 R1C R1C
COM COM
//// 11
LI1 LI1
LI2 QF1 LI2
M1 M1 LI+ +24 V
3~ 3~ 14 13
(1) BOOST (1) BOOST
2/T1
4/T2
6/T3
2/T1
4/T2
6/T3
(2) LO1 (2) LO1
M1 M1
3~ 3~
Notes:
Line voltage
Run 700 0 1
Soft stop 700 0 0
32 33
Altistart 01 & U01 Wiring Diagrams Altistart 01 & U01 Wiring Diagrams
soft starters for ATS01N2pppp & ATSU01N2pppp soft starters for ATS01N2pppp & ATSU01N2pppp
asynchronous motors asynchronous motors
L1
L2
L3
L1
L2
L3
24 Vdc Supply 24 Vdc Supply
L1
L2
L3
L1
L2
L3
120 Vac Supply 24 Vdc Supply
L N + - + - + -
S2 S2
START START LUB LUB
Fuse LUB LUB LUB LUB TeSys U-line TeSys U-line
REVERSE REVERSE
LUA1C20 LUA1C20
TeSys U-Line TeSys U-Line
A3 with reversing A3 with reversing
17 18 B3 17 18 B3 LO1 LO1
module module Modbus Modbus
S1 S1 COM COM
A1 LU2B62FU A1 5 module module
START START
FORWARD B1 FORWARD B1 +24 V LULC031 +24 V LULC031
A2 A2 -24 V -24 V
+24 V Aux +24 V Aux
-24 V Aux -24 V Aux
1/L1
3/L2
5/L3
1/L1
3/L2
5/L3
A1 A1
LU9BN11C LU9BN11C
R1A R1A
Pre-wired coil Pre-wired coil
S3 R1C S3 R1C
STOP COM STOP COM
(3) 6666 ATSU01N255LT
LI1 LI1
1/L1
3/L2
5/L3
1/L1
3/L2
5/L3
LI2 LI2 A1 A1
LI+ +24 V
(1) BOOST (1) BOOST R1A R1A
2/T1
4/T2
6/T3
2/T1
4/T2
6/T3
(2) LO1 (2) LO1 R1C R1C
COM COM
//// 11
LI1 LI1
LI2 QF1 LI2
M1 M1 LI+ +24 V
3~ 3~ 14 13
(1) BOOST (1) BOOST
2/T1
4/T2
6/T3
2/T1
4/T2
6/T3
(2) LO1 (2) LO1
M1 M1
3~ 3~
Notes:
Line voltage
Run 700 0 1
Soft stop 700 0 0
32 33
Altistart 01 & U01 Wiring Diagrams Altistart 01 & U01 Wiring Diagrams
soft starters for ATS01N2pppp & ATSU01N2pppp soft starters for ATS01N2pppp & ATSU01N2pppp
asynchronous motors asynchronous motors
L1
L2
L3
L1
L2
L3
L1
L2
L3
+ - + - + - + -
LUB
TeSys U-line "/+%$'"
LUB LUB
TeSys U-line TeSys U-line
A3 with reversing A3 with reversing AS-i AS-i
B3 unit B3 unit module module
A1 1 A1 1 +24 V ASILUFC5 +24 V
B1 B1 -24 V -24 V
A2 A2 + AS-Interface ',"*# "
- AS-Interface ',"*# "
COM COM
OA1 OA1 LU9BN11C C
OA3 Modbus OA3 Modbus
Pre-wired coil Pre-wired coil
module module
LO1 LULC031 LO1 LULC031
COM COM
+24 V +24 V
1/L1
3/L2
5/L3
-24 V -24 V A1 A1
+24 V Aux +24 V Aux
-24 V Aux -24 V Aux R1A R1A
R1C R1C
COM COM
1111 B 11
LI1
1/L1
3/L2
5/L3
1/L1
3/L2
5/L3
A1 A1 LI2
LI+ 14 13 +24 V
R1A R1A (1) BOOST (1) BOOST
2/T1
4/T2
6/T3
2/T1
4/T2
6/T3
R1C R1C (2) LO1 (2)
COM COM
ATS01N21111 ATSU01N211LT
LI1 LI1
LI2 LI2
LI+ +24 V
M1 M1
(1) BOOST (1) BOOST
2/T1
4/T2
6/T3
2/T1
4/T2
6/T3
3~ 3~
(2) LO1 (2) LO1
M1 M1
3~ 3~
Run 700 0 1
Soft stop 700 0 0
34 35
Altistart 01 & U01 Wiring Diagrams Altistart 01 & U01 Wiring Diagrams
soft starters for ATS01N2pppp & ATSU01N2pppp soft starters for ATS01N2pppp & ATSU01N2pppp
asynchronous motors asynchronous motors
L1
L2
L3
L1
L2
L3
L1
L2
L3
+ - + - + - + -
LUB
TeSys U-line "/+%$'"
LUB LUB
TeSys U-line TeSys U-line
A3 with reversing A3 with reversing AS-i AS-i
B3 unit B3 unit module module
A1 1 A1 1 +24 V ASILUFC5 +24 V
B1 B1 -24 V -24 V
A2 A2 + AS-Interface ',"*# "
- AS-Interface ',"*# "
COM COM
OA1 OA1 LU9BN11C C
OA3 Modbus OA3 Modbus
Pre-wired coil Pre-wired coil
module module
LO1 LULC031 LO1 LULC031
COM COM
+24 V +24 V
1/L1
3/L2
5/L3
-24 V -24 V A1 A1
+24 V Aux +24 V Aux
-24 V Aux -24 V Aux R1A R1A
R1C R1C
COM COM
1111 B 11
LI1
1/L1
3/L2
5/L3
1/L1
3/L2
5/L3
A1 A1 LI2
LI+ 14 13 +24 V
R1A R1A (1) BOOST (1) BOOST
2/T1
4/T2
6/T3
2/T1
4/T2
6/T3
R1C R1C (2) LO1 (2)
COM COM
ATS01N21111 ATSU01N211LT
LI1 LI1
LI2 LI2
LI+ +24 V
M1 M1
(1) BOOST (1) BOOST
2/T1
4/T2
6/T3
2/T1
4/T2
6/T3
3~ 3~
(2) LO1 (2) LO1
M1 M1
3~ 3~
Run 700 0 1
Soft stop 700 0 0
34 35
Altistart 01 & U01 Wiring Diagrams Altistart 01 & U01 Wiring Diagrams
soft starters for ATS01N2pppp & ATSU01N2pppp soft starters for ATS01N2pppp & ATSU01N2pppp
asynchronous motors asynchronous motors
ATS01N2ppLU/QN/RT ATSU01N2ppLT
208-480 V
230-460 V 208-480 V
L1
L2
L3
L1
L2
L3
24 Vdc Supply
L1
L2
L3
24 Vdc Supply
+ - + -
LUB LUB Q1
TeSys U-line TeSys U-line Starter (2)
A3 A3 with reversing
with reversing
B3 unit B3 unit
A1 1 A1 2
B1 B1
A2 A2
FU3 (1)
COM COM
OA1 OA1
AS-i OA3 AS-i
OA3 module
module
1/L1
3/L2
5/L3
ASILUFC5 ASILUFC5 A1
+24V +24 V
R1A
-24V -24 V
+ AS-Interface R1C
+ AS-Interface
- AS-Interface COM
- AS-Interface ####
LI1
LI2
LI+
1/L1
3/L2
5/L3
1/L1
3/L2
5/L3
A1 A1 (3) BOOST
2/T1
4/T2
6/T3
(4) LO1
R1A R1A
R1C R1C
COM COM
ATS01N21111 ATSU01N222LT
LI1 LI1
LI2 LI2 M1
LI+ +24 V 3~
(1) BOOST (1) BOOST
2/T1
4/T2
6/T3
2/T1
4/T2
6/T3
M1 M1
3~ 3~
Notes:
V1
Run forward D0 1 LUB: TeSys U-Line motor starter motor’s rated voltage
Motor voltage
Stop D0 0 (1) Optional jumper to select boost t1 (1) Fuses are not required if device Q1 is a GV manual motor starter installed per
t
(2) See page 11 for L01 wiring recommendations local and national electrical codes.
Run reverse D1 1 (2) Overload protection is required if not included on device Q1.
(3) Optional jumper to select boost.
Stop D1 0 (4) See page 11 for L01 wiring recommendations
36 37
Altistart 01 & U01 Wiring Diagrams Altistart 01 & U01 Wiring Diagrams
soft starters for ATS01N2pppp & ATSU01N2pppp soft starters for ATS01N2pppp & ATSU01N2pppp
asynchronous motors asynchronous motors
ATS01N2ppLU/QN/RT ATSU01N2ppLT
208-480 V
230-460 V 208-480 V
L1
L2
L3
L1
L2
L3
24 Vdc Supply
L1
L2
L3
24 Vdc Supply
+ - + -
LUB LUB Q1
TeSys U-line TeSys U-line Starter (2)
A3 A3 with reversing
with reversing
B3 unit B3 unit
A1 1 A1 2
B1 B1
A2 A2
FU3 (1)
COM COM
OA1 OA1
AS-i OA3 AS-i
OA3 module
module
1/L1
3/L2
5/L3
ASILUFC5 ASILUFC5 A1
+24V +24 V
R1A
-24V -24 V
+ AS-Interface R1C
+ AS-Interface
- AS-Interface COM
- AS-Interface ####
LI1
LI2
LI+
1/L1
3/L2
5/L3
1/L1
3/L2
5/L3
A1 A1 (3) BOOST
2/T1
4/T2
6/T3
(4) LO1
R1A R1A
R1C R1C
COM COM
ATS01N21111 ATSU01N222LT
LI1 LI1
LI2 LI2 M1
LI+ +24 V 3~
(1) BOOST (1) BOOST
2/T1
4/T2
6/T3
2/T1
4/T2
6/T3
M1 M1
3~ 3~
Notes:
V1
Run forward D0 1 LUB: TeSys U-Line motor starter motor’s rated voltage
Motor voltage
Stop D0 0 (1) Optional jumper to select boost t1 (1) Fuses are not required if device Q1 is a GV manual motor starter installed per
t
(2) See page 11 for L01 wiring recommendations local and national electrical codes.
Run reverse D1 1 (2) Overload protection is required if not included on device Q1.
(3) Optional jumper to select boost.
Stop D1 0 (4) See page 11 for L01 wiring recommendations
36 37
Altistart 01 & U01 Wiring Diagrams Altistart 01 & U01 Wiring Diagrams
soft starters for ATS01N2pppp & ATSU01N2pppp soft starters for ATS01N2pppp & ATSU01N2pppp
asynchronous motors asynchronous motors
208-480 V 208-480 V
OL
KM1
1/L1
3/L2
5/L3
S1
1/L1
3/L2
5/L3
A1 HAND-OFF-AUTO A1
OL
R1A R1A
R1C (6) R1C
(5)
COM AUTO COM
ATS01N20000 RUN/STOP ATS01N2----
LI1 LI1
(5)
LI2 LI2
LI+ LI+
BOOST (3) BOOST
2/T1
4/T2
6/T3
2/T1
4/T2
6/T3
M1 M1
3~ 3~
-
Notes: Notes:
V1
Motor voltage (1) Fuses FU3 are not required if device Q1 is a GV manual motor starter installed
Logic output LO1 motor’s rated voltage per local and national electrical codes.
t1 t2 t (2) Overload protection is required if not included on device Q1.
V1
Motor voltage (1) Fuses FU3 are not required if device Q1 is a GV manual motor starter installed (3) Optional jumper to select boost.
per local and national electrical codes. (4) See page 11 for L01 wiring recommendations
t1 t2 t (2) Overload protection is required if not included on device Q1. (5) Use shielded cable if control wiring is longer than 3 feet.
(3) Optional jumper to select boost. (6) From automated control system.
(4) See page 11 for L01 wiring recommendations
(5) Use shielded cable if control wiring is longer than 3 feet.
(6) From automated control system.
38 39
Altistart 01 & U01 Wiring Diagrams Altistart 01 & U01 Wiring Diagrams
soft starters for ATS01N2pppp & ATSU01N2pppp soft starters for ATS01N2pppp & ATSU01N2pppp
asynchronous motors asynchronous motors
208-480 V 208-480 V
OL
KM1
1/L1
3/L2
5/L3
S1
1/L1
3/L2
5/L3
A1 HAND-OFF-AUTO A1
OL
R1A R1A
R1C (6) R1C
(5)
COM AUTO COM
ATS01N20000 RUN/STOP ATS01N2----
LI1 LI1
(5)
LI2 LI2
LI+ LI+
BOOST (3) BOOST
2/T1
4/T2
6/T3
2/T1
4/T2
6/T3
M1 M1
3~ 3~
-
Notes: Notes:
V1
Motor voltage (1) Fuses FU3 are not required if device Q1 is a GV manual motor starter installed
Logic output LO1 motor’s rated voltage per local and national electrical codes.
t1 t2 t (2) Overload protection is required if not included on device Q1.
V1
Motor voltage (1) Fuses FU3 are not required if device Q1 is a GV manual motor starter installed (3) Optional jumper to select boost.
per local and national electrical codes. (4) See page 11 for L01 wiring recommendations
t1 t2 t (2) Overload protection is required if not included on device Q1. (5) Use shielded cable if control wiring is longer than 3 feet.
(3) Optional jumper to select boost. (6) From automated control system.
(4) See page 11 for L01 wiring recommendations
(5) Use shielded cable if control wiring is longer than 3 feet.
(6) From automated control system.
38 39
Altistart 01 & U01 Wiring Diagrams Altistart 01 & U01 Wiring Diagrams
soft starters for ATS01N2pppp & ATSU01N2pppp soft starters for ATS01N2pppp & ATSU01N2pppp
asynchronous motors asynchronous motors
208-480 V 208-480 V
L1
L2
L3
L1
L2
L3
Q1 Q1
Manual Starter Manual Starter
or Disconnect or Disconnect
KM1
OL (2)
FU1
S1 S2
STOP START OL (2)
OL
1/L1
3/L2
5/L3
A1 KM1
1/L1
3/L2
5/L3
R1A A1
S1 S2 R1C KM1
STOP START COM R1A
(5) ----
3-wire LI1 R1C
control LI2 COM
////
LI+ LI1
S3 OL (3) BOOST LI2
2/T1
4/T2
6/T3
2/T1
4/T2
6/T3
2-wire
(4) LO1
control
M1
3~
M1
3~
Notes: Notes:
V1
V1
(1) Fuses FU3 are not required if device Q1 is a GV manual motor starter installed Motor voltage 1) Fuses FU3 are not required if device Q1 is a GV manual motor starter installed
Motor voltage per local and national electrical codes. per local and national electrical codes.
t1 t
t1 t2 t (2) Overload protection is required if not included on device Q1. (2) Overload protection is required if not included on device Q1.
(3) Optional jumper to select boost. (3) Optional jumper to select boost.
(4) See page 11 for L01 wiring recommendations (4) See page 11 for L01 wiring recommendations
(5) Use shielded cable if control wiring is longer than 3 feet.
40 41
Altistart 01 & U01 Wiring Diagrams Altistart 01 & U01 Wiring Diagrams
soft starters for ATS01N2pppp & ATSU01N2pppp soft starters for ATS01N2pppp & ATSU01N2pppp
asynchronous motors asynchronous motors
208-480 V 208-480 V
L1
L2
L3
L1
L2
L3
Q1 Q1
Manual Starter Manual Starter
or Disconnect or Disconnect
KM1
OL (2)
FU1
S1 S2
STOP START OL (2)
OL
1/L1
3/L2
5/L3
A1 KM1
1/L1
3/L2
5/L3
R1A A1
S1 S2 R1C KM1
STOP START COM R1A
(5) ----
3-wire LI1 R1C
control LI2 COM
////
LI+ LI1
S3 OL (3) BOOST LI2
2/T1
4/T2
6/T3
2/T1
4/T2
6/T3
2-wire
(4) LO1
control
M1
3~
M1
3~
Notes: Notes:
V1
V1
(1) Fuses FU3 are not required if device Q1 is a GV manual motor starter installed Motor voltage 1) Fuses FU3 are not required if device Q1 is a GV manual motor starter installed
Motor voltage per local and national electrical codes. per local and national electrical codes.
t1 t
t1 t2 t (2) Overload protection is required if not included on device Q1. (2) Overload protection is required if not included on device Q1.
(3) Optional jumper to select boost. (3) Optional jumper to select boost.
(4) See page 11 for L01 wiring recommendations (4) See page 11 for L01 wiring recommendations
(5) Use shielded cable if control wiring is longer than 3 feet.
40 41
Altistart 01 & U01 Wiring Diagrams Altistart 01 & U01 Wiring Diagrams
soft starters for ATS01N2pppp & ATSU01N2pppp soft starters for ATS01N2pppp & ATSU01N2pppp
asynchronous motors asynchronous motors
L1
L2
L3
208-480 V
L1
L2
L3
Q1
Manual Starter
or Disconnect
Q1
Manual Starter
or Disconnect
120 Vac Supply
FU3 (1)
L N
120 Vac Supply
S1 S2
FU3 (1) FU1
L N EMERG START
STOP FORWARD
OL KM3
KM2
KM1 KM2 M/I KM3
S1
FU1 KM2
EMERG S2
STOP START OL (2)
S3
OL
START
KM1 REVERSE
KM2
KM3 OL (2)
1/L1
3/L2
5/L3
A1
KM1
R1A KM3
R1C
1/L1
3/L2
5/L3
S3 A1
(5) COM
SOFT STOP 1111
LI1 R1A
LI2 S4 R1C
LI+ SOFT STOP COM
(3) (5) 2222
BOOST LI1
2/T1
4/T2
6/T3
2/T1
4/T2
6/T3
(4) LO1
M1
3~
M1
3~
Notes: Notes:
A1: ATS01 soft starter A1: ATS01 soft starter
FU1: Control circuit fuse Line voltage/
Line voltage/ FU1: Control circuit fuse
Green LED
Green LED FU3: Fast-acting UL Listed Class J fuse FU3: Fast-acting UL Listed Class J fuse
Start
KM1: Isolation contactor Start FW
KM2, KM3: Reversing contactor
OL: Overload relay See note. OL: Overload relay
Start RV
Soft Stop Q1: Manual motor starter or disconnect switch Q1: Manual motor starter or disconnect switch
E Stop Soft Stop
S1, S2, S3: Momentary pushbuttons S1, S2, S3, S4: Momentary pushbuttons
10 s 10 s t1: 1 - 10 second adjustable starting time E Stop
t1: 1 - 10 second adjustable starting time
Yellow LED t2: 1 - 10 second adjustable stopping time 10 s 10 s
Yellow LED
t2: 1 - 10 second adjustable stopping time
LO1 V1: Initial motor voltage - adjustable from 30 to 80% of the V1: Initial motor voltage - adjustable from 30 to 80% of the
motor’s rated voltage LO1 motor’s rated voltage
V1
Motor voltage (1) Fuses FU3 are not required if device Q1 is a GV manual motor starter installed
V1
(1) Fuses FU3 are not required if device Q1 is a GV manual motor starter installed
per local and national electrical codes.
t1 t2 t Motor voltage per local and national electrical codes.
(2) Overload protection is required if not included on device Q1.
(2) Overload protection is required if not included on device Q1.
(3) Optional jumper to select boost. t1 t2 t
motor reverses (3) Optional jumper to select boost.
(4) See page 11 for L01 wiring recommendations
(4) See page 11 for L01 wiring recommendations
(5) Use shielded cable if control wiring is longer than 3 feet.
(5) Use shielded cable if control wiring is longer than 3 feet.
42 43
Altistart 01 & U01 Wiring Diagrams Altistart 01 & U01 Wiring Diagrams
soft starters for ATS01N2pppp & ATSU01N2pppp soft starters for ATS01N2pppp & ATSU01N2pppp
asynchronous motors asynchronous motors
L1
L2
L3
208-480 V
L1
L2
L3
Q1
Manual Starter
or Disconnect
Q1
Manual Starter
or Disconnect
120 Vac Supply
FU3 (1)
L N
120 Vac Supply
S1 S2
FU3 (1) FU1
L N EMERG START
STOP FORWARD
OL KM3
KM2
KM1 KM2 M/I KM3
S1
FU1 KM2
EMERG S2
STOP START OL (2)
S3
OL
START
KM1 REVERSE
KM2
KM3 OL (2)
1/L1
3/L2
5/L3
A1
KM1
R1A KM3
R1C
1/L1
3/L2
5/L3
S3 A1
(5) COM
SOFT STOP 1111
LI1 R1A
LI2 S4 R1C
LI+ SOFT STOP COM
(3) (5) 2222
BOOST LI1
2/T1
4/T2
6/T3
2/T1
4/T2
6/T3
(4) LO1
M1
3~
M1
3~
Notes: Notes:
A1: ATS01 soft starter A1: ATS01 soft starter
FU1: Control circuit fuse Line voltage/
Line voltage/ FU1: Control circuit fuse
Green LED
Green LED FU3: Fast-acting UL Listed Class J fuse FU3: Fast-acting UL Listed Class J fuse
Start
KM1: Isolation contactor Start FW
KM2, KM3: Reversing contactor
OL: Overload relay See note. OL: Overload relay
Start RV
Soft Stop Q1: Manual motor starter or disconnect switch Q1: Manual motor starter or disconnect switch
E Stop Soft Stop
S1, S2, S3: Momentary pushbuttons S1, S2, S3, S4: Momentary pushbuttons
10 s 10 s t1: 1 - 10 second adjustable starting time E Stop
t1: 1 - 10 second adjustable starting time
Yellow LED t2: 1 - 10 second adjustable stopping time 10 s 10 s
Yellow LED
t2: 1 - 10 second adjustable stopping time
LO1 V1: Initial motor voltage - adjustable from 30 to 80% of the V1: Initial motor voltage - adjustable from 30 to 80% of the
motor’s rated voltage LO1 motor’s rated voltage
V1
Motor voltage (1) Fuses FU3 are not required if device Q1 is a GV manual motor starter installed
V1
(1) Fuses FU3 are not required if device Q1 is a GV manual motor starter installed
per local and national electrical codes.
t1 t2 t Motor voltage per local and national electrical codes.
(2) Overload protection is required if not included on device Q1.
(2) Overload protection is required if not included on device Q1.
(3) Optional jumper to select boost. t1 t2 t
motor reverses (3) Optional jumper to select boost.
(4) See page 11 for L01 wiring recommendations
(4) See page 11 for L01 wiring recommendations
(5) Use shielded cable if control wiring is longer than 3 feet.
(5) Use shielded cable if control wiring is longer than 3 feet.
42 43
Altistart 01 & U01 Quality Assurance Procedures
soft starters for
asynchronous motors
In addition to the processes and procedures detailed above, the ISO certified manufacturing facility test stations
have instructions for visual quality checks and electrical inspection. The visual quality check list includes a physical
inspection for proper connections, proper assembly torques, mechanical integrity and proper documentation.
The quality assurance procedures detailed above are in place for the manufacturing of Altistart 01. These
procedures are established to monitor and confirm the quality of the product line that has been designed in from the
outset.
Software parameters
44
Altistart 01 & U01 Quality Assurance Procedures
soft starters for
asynchronous motors
In addition to the processes and procedures detailed above, the ISO certified manufacturing facility test stations
have instructions for visual quality checks and electrical inspection. The visual quality check list includes a physical
inspection for proper connections, proper assembly torques, mechanical integrity and proper documentation.
The quality assurance procedures detailed above are in place for the manufacturing of Altistart 01. These
procedures are established to monitor and confirm the quality of the product line that has been designed in from the
outset.
Software parameters
44
Solutions for every stage of your
equipment’s life cycle Talk to someone you can trust
The Altivar family of variable speed AC drives and the Altistart family of soft starts presents the most advanced and user-friendly solutions in the
marketplace. Featuring proprietary motor control algorithms to achieve optimal reaction times and complete scalability to match your application
Schneider Electric™ provides services far beyond meeting your immediate needs for requirements for speed, size, and protection, the complete line of Altivar and Altistart products provides the flexibility and performance to:
application or equipment repair. We take a long-term, holistic approach to determine
your facility and operational needs and develop a strategy for improving the Ŷ Meet the needs of a broad range of industries, including HVAC, pump, material handling, hoisting, packaging and many more.
performance of your people, systems, and processes. Ŷ Reduce your energy costs using proprietary energy-saving technologies available only from Schneider Electric.
Ŷ Improve your up-time by simplifying installation, commissioning and maintenance by providing advanced diagnostics, industry-leading
Schneider Electric provides services from system design and consulting, to voltage ride thru capability and seismic qualified products.
maintenance support, modernization of your installation, and project delivery.
Schneider Electric provides the people, tools, and processes to help maximize your We also work with you to deliver the benefits of a global service and support of a global service and support organization to further increase the
business’s infrastructure. value of working with Schneider Electric. Our product specialists, industry experts, distributors, partners, and the countless other members of the
Schneider Electric family are dedicated to helping you make the most of your energy everyday. Contact your local sales representative today to
Our expertise enables you to cut costs, reduce energy consumption, and keep your learn how Schneider Electric can improve operational performance and help your business to achieve a competitive advantage. Or visit www.
systems up and running through routine maintenance, added enhancements, and schneider-electric.com
migrations to new state-of-the-art functionality.