Professional Documents
Culture Documents
Trademarks
ABB and Relion are registered trademarks of the ABB Group. All other brand or
product names mentioned in this document may be trademarks or registered
trademarks of their respective holders.
Warranty
Please inquire about the terms of warranty from your nearest ABB representative.
http://www.abb.com/substationautomation
Disclaimer
The data, examples and diagrams in this manual are included solely for the concept
or product description and are not to be deemed as a statement of guaranteed
properties. All persons responsible for applying the equipment addressed in this
manual must satisfy themselves that each intended application is suitable and
acceptable, including that any applicable safety or other operational requirements
are complied with. In particular, any risks in applications where a system failure and/
or product failure would create a risk for harm to property or persons (including but
not limited to personal injuries or death) shall be the sole responsibility of the
person or entity applying the equipment, and those so responsible are hereby
requested to ensure that all measures are taken to exclude or mitigate such risks.
This product has been designed to be connected and communicate data and
information via a network interface which should be connected to a secure
network. It is the sole responsibility of the person or entity responsible for network
administration to ensure a secure connection to the network and to take the
necessary measures (such as, but not limited to, installation of firewalls, application
of authentication measures, encryption of data, installation of anti virus programs,
etc.) to protect the product and the network, its system and interface included,
against any kind of security breaches, unauthorized access, interference, intrusion,
leakage and/or theft of data or information. ABB is not liable for any such damages
and/or losses.
This document has been carefully checked by ABB but deviations cannot be
completely ruled out. In case any errors are detected, the reader is kindly requested
to notify the manufacturer. Other than under explicit contractual commitments, in
no event shall ABB be responsible or liable for any loss or damage resulting from
the use of this manual or the application of the equipment.
Conformity
This product complies with the directive of the Council of the European
Communities on the approximation of the laws of the Member States relating to
electromagnetic compatibility (EMC Directive 2004/108/EC) and concerning
electrical equipment for use within specified voltage limits (Low-voltage directive
2006/95/EC). This conformity is the result of tests conducted by ABB in
accordance with the product standards EN 50263 and EN 60255-26 for the EMC
directive, and with the product standards EN 60255-1 and EN 60255-27 for the low
voltage directive. The product is designed in accordance with the international
standards of the IEC 60255 series.
Table of contents
Table of contents
Section 1 Introduction.......................................................................5
This manual........................................................................................5
Intended audience..............................................................................5
Product documentation.......................................................................6
Product documentation set............................................................6
Document revision history.............................................................6
Related documentation..................................................................7
Symbols and conventions...................................................................7
Symbols.........................................................................................7
Document conventions..................................................................8
Functions, codes and symbols......................................................8
REV615 1
Application Manual
Table of contents
2 REV615
Application Manual
Table of contents
Section 6 Glossary.........................................................................97
REV615 3
Application Manual
4
1MRS757946 A Section 1
Introduction
Section 1 Introduction
This manual addresses the protection and control engineer responsible for
planning, pre-engineering and engineering.
REV615 5
Application Manual
Section 1 1MRS757946 A
Introduction
Maintenance
Engineering
Planning &
Installation
Operation
Quick start guide purchase
Quick installation guide
Brochure
Product guide
Operation manual
Installation manual
Connection diagram
Engineering manual
Technical manual
Application manual c
Communication protocol manual c
IEC 61850 Engineering guide
Point list manual
GUID-12DC16B2-2DC1-48DF-8734-0C8B7116124C V1 EN
Figure 1: The intended use of documents during the product life cycle
6 REV615
Application Manual
1MRS757946 A Section 1
Introduction
1.4.1 Symbols
The tip icon indicates advice on, for example, how to design your
project or how to use a certain function.
REV615 7
Application Manual
Section 1 1MRS757946 A
Introduction
• Abbreviations and acronyms are spelled out in the glossary. The glossary also
contains definitions of important terms.
• Push button navigation in the LHMI menu structure is presented by using the
push button icons.
To navigate between the options, use and .
• Menu paths are presented in bold.
Select Main menu/Settings.
• LHMI messages are shown in Courier font.
To save the changes in non-volatile memory, select Yes and press .
• Parameter names are shown in italics.
The function can be enabled and disabled with the Operation setting.
• Parameter values are indicated with quotation marks.
The corresponding parameter values are "On" and "Off".
• IED input/output messages and monitored data names are shown in Courier font.
When the function starts, the START output is set to TRUE.
• This document assumes that the parameter setting visibility is "Advanced".
8 REV615
Application Manual
1MRS757946 A Section 1
Introduction
REV615 9
Application Manual
Section 1 1MRS757946 A
Introduction
10 REV615
Application Manual
1MRS757946 A Section 1
Introduction
REV615 11
Application Manual
12
1MRS757946 A Section 2
REV615 overview
2.1 Overview
Re-engineered from the ground up, the 615 series has been designed to unleash the
full potential of the IEC 61850 standard for communication and interoperability
between substation automation devices.
The IED provides main protection for single Y, double Y, and H-bridge connected
capacitor banks and harmonic filters in distribution networks.
Depending on the chosen standard configuration, the IED is adapted for the
protection of H-bridge connected or double star connected shunt capacitor banks.
Once the standard configuration IED has been given the application-specific
settings, it can directly be put into service.
The 615 series IEDs support a range of communication protocols including IEC
61850 with GOOSE messaging, IEC 61850-9-2 LE (except in RED615), IEC
60870-5-103, Modbus® and DNP3. Profibus DPV1 communication protocol is
supported by using the protocol converter SPA-ZC 302.
• Application Configuration
• Signal Matrix
• Graphical Display Editor
• Communication Management
• IED User Management
• IED Compare
• Firmware Update
• Fault Record tool
• Load Record Profile
• Lifecycle Traceability
• Configuration Wizard
• AR Sequence Visualizer
• Label Printing
• IEC 61850 Configuration
The IED consists of two main parts: plug-in unit and case. The content depends on
the ordered functionality.
14 REV615
Application Manual
1MRS757946 A Section 2
REV615 overview
Rated values of the current and voltage inputs are basic setting parameters of the
IED. The binary input thresholds are selectable within the range 16…176 V DC by
adjusting the binary input setting parameters.
The connection diagrams of different hardware modules are presented in this manual.
See the installation manual for more information about the case and
the plug-in unit.
REV615 15
Application Manual
Section 2 1MRS757946 A
REV615 overview
BA FD 7 - 8 4 PO + 2 - -
SO + 3
HSO
A FF 7 - 14 4 PO + 5 - -
SO + 3
HSO
BA 7 - 8 4 PO + 6 6 2
SO
BG FD 7 - 8 4 PO + 2 6 2
SO + 3
HSO
AD 7 5 12 4 PO + 6 - -
SO
BC FE 7 5 12 4 PO + 2 - -
SO + 3
HSO
B
BA 7 5 8 4 PO + 6 2 1
SO
BE FD 7 5 8 4 PO + 2 2 1
SO + 3
HSO
The LHMI is used for setting, monitoring and controlling the IED. The LHMI
comprises the display, buttons, LED indicators and communication port.
16 REV615
Application Manual
1MRS757946 A Section 2
REV615 overview
REF615
Overcurrent
Dir. earth-fault
Voltage protection
Phase unbalance
Thermal overload
Breaker failure
Disturb. rec. Triggered
CB condition monitoring
Supervision
Arc detected
Autoreclose shot in progr.
A070704 V4 EN
2.4.1 Display
The LHMI includes a graphical display that supports two character sizes. The
character size depends on the selected language. The amount of characters and
rows fitting the view depends on the character size.
REV615 17
Application Manual
Section 2 1MRS757946 A
REV615 overview
3 4
A070705 V3 EN
1 Header
2 Icon
3 Content
4 Scroll bar (displayed when needed)
2.4.2 LEDs
The LHMI includes three protection indicators above the display: Ready, Start and
Trip.
There are 11 matrix programmable LEDs on front of the LHMI. The LEDs can be
configured with PCM600 and the operation mode can be selected with the LHMI,
WHMI or PCM600.
2.4.3 Keypad
The LHMI keypad contains push-buttons which are used to navigate in different
views or menus. With the push-buttons you can give open or close commands to
objects in the primary circuit, for example, a circuit breaker, a contactor or a
disconnector. The push-buttons are also used to acknowledge alarms, reset
indications, provide help and switch between local and remote control mode.
18 REV615
Application Manual
1MRS757946 A Section 2
REV615 overview
A071176 V1 EN
Figure 4: LHMI keypad with object control, navigation and command push-
buttons and RJ-45 communication port
The WHMI allows secure access to the IED via a Web browser. The supported
Web browser versions are Internet Explorer 8.0, 9.0 and 10.0. When the Secure
Communication parameter in the IED is activated, the Web server is forced to take
a secured (HTTPS) connection to WHMI using TLS encryption.
The menu tree structure on the WHMI is almost identical to the one on the LHMI.
REV615 19
Application Manual
Section 2 1MRS757946 A
REV615 overview
A070754 V5 EN
• Locally by connecting the laptop to the IED via the front communication port.
• Remotely over LAN/WAN.
2.6 Authorization
The user categories have been predefined for the LHMI and the WHMI, each with
different rights and default passwords.
20 REV615
Application Manual
1MRS757946 A Section 2
REV615 overview
User audit trail is defined according to the selected set of requirements from IEEE
1686. The logging is based on predefined usernames or user categories. The user
audit trail events are accessible with IEC 61850-8-1, PCM600, LHMI and WHMI.
REV615 21
Application Manual
Section 2 1MRS757946 A
REV615 overview
PCM600 Event Viewer can be used to view the audit trail events together with
normal events. Since only the administrator has the right to read audit trail,
authorization must be properly configured in PCM600. The audit trail cannot be
reset but PCM600 Event Viewer can filter data. Some of the audit trail events are
interesting also as normal process events.
22 REV615
Application Manual
1MRS757946 A Section 2
REV615 overview
2.7 Communication
The IED supports a range of communication protocols including IEC 61850, IEC
61850-9-2 LE, IEC 60870-5-103, Modbus® and DNP3. Profibus DPV1
communication protocol is supported by using the protocol converter SPA-ZC 302.
Operational information and controls are available through these protocols.
However, some communication functionality, for example, horizontal
communication between the IEDs, is only enabled by the IEC 61850
communication protocol.
REV615 23
Application Manual
Section 2 1MRS757946 A
REV615 overview
The IED can support five simultaneous clients. If PCM600 reserves one client
connection, only four client connections are left, for example, for IEC 61850 and
Modbus.
All communication connectors, except for the front port connector, are placed on
integrated optional communication modules.
Client A Client B
Network A
Network B
GUID-283597AF-9F38-4FC7-B87A-73BFDA272D0F V3 EN
24 REV615
Application Manual
1MRS757946 A Section 2
REV615 overview
PRP specifies that each device is connected in parallel to two local area networks.
HSR applies the PRP principle to rings and to the rings of rings to achieve cost-
effective redundancy. Thus, each device incorporates a switch element that
forwards frames from port to port. The HSR/PRP option is available for REF615,
REM615, RET615, REU615 and REV615.
PRP
Each PRP node, called a doubly attached node with PRP (DAN), is attached to two
independent LANs operated in parallel. These parallel networks in PRP are called
LAN A and LAN B. The networks are completely separated to ensure failure
independence, and they can have different topologies. Both networks operate in
parallel, thus providing zero-time recovery and continuous checking of redundancy
to avoid communication failures. Non-PRP nodes, called singly attached nodes
(SANs), are either attached to one network only (and can therefore communicate
only with DANs and SANs attached to the same network), or are attached through
a redundancy box, a device that behaves like a DAN.
REV615 25
Application Manual
Section 2 1MRS757946 A
REV615 overview
COM600
SCADA
HSR
HSR applies the PRP principle of parallel operation to a single ring, treating the
two directions as two virtual LANs. For each frame sent, a node, DAN, sends two
frames, one over each port. Both frames circulate in opposite directions over the
ring and each node forwards the frames it receives, from one port to the other.
When the originating node receives a frame sent to itself, it discards that to avoid
loops; therefore, no ring protocol is needed. Individually attached nodes, SANs,
such as laptops and printers, must be attached through a “redundancy box” that acts
as a ring element. For example, a 615 or 620 series IED with HSR support can be
used as a redundancy box.
26 REV615
Application Manual
1MRS757946 A Section 2
REV615 overview
GUID-207430A7-3AEC-42B2-BC4D-3083B3225990 V1 EN
UniGear Digital switchgear concept relies on the process bus together with current
and voltage sensors. The process bus enables several advantages for the UniGear
Digital like simplicity with reduced wiring, flexibility with data availability to all
IEDs, improved diagnostics and longer maintenance cycles.
With process bus the galvanic interpanel wiring for sharing busbar voltage value
can be replaced with Ethernet communication. Transmitting measurement samples
over process bus brings also higher error detection because the signal transmission
is automatically supervised. Additional contribution to the higher availability is the
possibility to use redundant Ethernet network for transmitting SMV signals.
REV615 27
Application Manual
Section 2 1MRS757946 A
REV615 overview
GUID-2371EFA7-4369-4F1A-A23F-CF0CE2D474D3 V1 EN
The 615 series supports IEC 61850 process bus with sampled values of analog
phase voltages. The measured values are transferred as sampled values using the
IEC 61850-9-2 LE protocol which uses the same physical Ethernet network as the
IEC 61850-8-1 station bus. The intended application for sampled values is sharing
the measured phase voltages from one 615 series IED to other IEDs with phase
voltage based functions and 9-2 support.
The 615 series IEDs with process bus based applications use IEEE 1588 v2
Precision Time Protocol (PTP) according to IEEE C37.238-2011 Power Profile for
high accuracy time synchronization. With IEEE 1588 v2, the cabling infrastructure
requirement is reduced by allowing time synchronization information to be
transported over the same Ethernet network as the data communications.
28 REV615
Application Manual
1MRS757946 A Section 2
REV615 overview
GUID-7C56BC1F-F1B2-4E74-AB8E-05001A88D53D V2 EN
Figure 10: Example network topology with process bus, redundancy and IEEE
1588 v2 time synchronization
The process bus option is available for REF615, REM615, RET615, REU615 and
REV615. See the IEC 61850 engineering guide for detailed system requirements
and configuration details.
REV615 29
Application Manual
30
1MRS757946 A Section 3
REV615 standard configurations
The IED is delivered from the factory with default connections described in the
functional diagrams for binary inputs, binary outputs, function-to-function
connections and alarm LEDs. The positive measuring direction of directional
protection functions is towards the outgoing feeder.
REV615 31
Application Manual
Section 3 1MRS757946 A
REV615 standard configurations
1) The instances of a protection function represent the number of identical protection function blocks available in the standard configuration.
2) Io selectable by parameter, "Io measured" as default
3) Uo selectable by parameter, "Uo measured" as default
4) Must be added with Application Configuration to be available in Signal Matrix and in IED
5) "Uob measured" is always used for unbalance protection with unearthed single Y-connected capacitor bank.
6) Master trip included and connected to the corresponding HSO in the configuration only when the BIO0007 module is used. If the ARC
option is selected additionally, ARCSARC is connected to the corresponding master trip input in the configuration.
7) Multi-purpose protection is used, for example, for RTD/mA-based protection or analog GOOSE.
8) The Iunb measurement values are taken from this block and put in the Measurement view.
9) Power quality option includes only current total demand distortion.
10) Power quality option includes current total demand distortion, voltage total harmonic distortion and voltage variation.
11) Unbalance voltage measurement for capacitor bank
12) Only available with COM0031-COM0034
32 REV615
Application Manual
1MRS757946 A Section 3
REV615 standard configurations
The external I/O module’s binary inputs and outputs can be used for the less time-
critical binary signals of the application. The integration enables releasing some
initially reserved binary inputs and outputs of the IED’s standard configuration.
The suitability of the IED’s binary outputs which have been selected for primary
device control should be carefully verified, for example make and carry and
breaking capacity. If the requirements for the primary device control circuit are not
met, using external auxiliary relays should be considered.
REV615 33
Application Manual
Section 3 1MRS757946 A
REV615 standard configurations
REV615
X120 X100
Positive +
Current 1 1/5A 1
IL1unb 2) U aux
Direction 2 N 2
-
3 1/5A
IL2unb 3
4 N IRF
P1 5 1/5A 4
S1 IL3unb
6 N
5
S2
P2 7 1/5A
IL1 PO1
8 N
9 1/5A 6
IL2 7
10 N
11 1/5A
PO2
IL3
12 N
8
13 1/5A
Io 9
P1 S1 10
14 N
SO1
P2 S2 11
12
13
SO2
14
16
PO3
X110 17
15
1 19
BI 1 3) TCS1
2 18
20
3 22
BI 2 PO4
4
21
5 23
BI 3
6 TCS2 24
BI 4
7 X110
8 14
BI 5 3)
9 SO1
16
BI 6 15
10 17
SO2
11
BI 7 19
12 18
20
BI 8 SO3
13
22
21
23
X130 SO4
1 4) 24
BI 1
2
X130
BI 2
3 4) 10
4 SO1
BI 3
5 12
11
13
BI 4
6 SO2
15
7 14
BI 5
8 16
SO3
BI 6 18
9 17
X13
1)
Light sensor input 1 1) Optional
2) The IED features an automatic short-circuit
X14 mechanism in the CT connector when plug-in
1) unit is detached
Light sensor input 2
3) BIO0005 Module (8BI+4BO)
X15 Alternative Module BIO0007 (8BI+3HSO)
1) 4) BIO0006 Module (6BI+3BO)
Light sensor input 3 Alternative Module RTD0001 (6RTD+2mA)
GUID-6E21CF35-D1AC-484F-99C0-830FA9F70960 V1 EN
34 REV615
Application Manual
1MRS757946 A Section 3
REV615 standard configurations
L1
L2
L3
A
n
N REV615
X130 X100
1 + 1
a BI 1 4) U aux
2
-
2
da dn
3 3
BI 2
4 IRF
4
5
BI 3 5
6
PO1
7
BI 4
8 6
60 - 7
9 210V
UoB
10 N PO2
60 -
11 210V
U1 8
12 N 9
60 -
13 210V
10
U2 SO1
14 N
60 -
15 210V
11
U3 12
16 N 13
60 -
17 210V SO2
Uo
18 N
14
16
PO3
X120
Positive 17
Current 1 1/5A
15
IL1unb 2)
Direction 19
2 N TCS1 18
3 1/5A
IL2unb 20
4 N 22
P1 5 1/5A PO4
S1 IL3unb
6 N 21
P2
S2
7 1/5A 23
IL1 TCS2 24
8 N
9 1/5A
IL2
10 N
11 1/5A
IL3
12 N
13 1/5A
P1 S1
Io
14 N
P2 S2
X110
1
BI 1 3)
2
3
BI 2
4
5
BI 3 X110
6
14
3)
BI 4 SO1
7
16
8 15
BI 5 17
9
SO2
19
BI 6 18
10
20
11 SO3
BI 7
12 22
21
23
BI 8
13 SO4
24
X13
1)
Light sensor input 1 1) Optional
2) The IED features an automatic short-circuit
X14 mechanism in the CT connector when plug-in
1) unit is detached
Light sensor input 2
3) BIO0005 Module (8BI+4BO)
X15 Alternative Module BIO0007 (8BI+3HSO)
1) 4) AIM0006 Module (5U+4BI)
Light sensor input 3
Alternative Module AIM0003 (5U+2RTD+1mA)
GUID-2750EADB-83D4-4222-A759-12432FD8D118 V1 EN
3.3.1 Applications
The standard configuration offer three-phase overload protection, unbalance
protection with compensation for natural unbalance and switching resonance
protection for capacitor banks. An integrated undercurrent function in the overload
REV615 35
Application Manual
Section 3 1MRS757946 A
REV615 standard configurations
protection function block detects the disconnection of a capacitor bank and inhibits
the closing of the circuit breaker as long as the capacitor bank is still partially
discharged. A three-phase thermal overload protection is available and can be used
for the thermal protection of the reactors and resistors in the harmonic filter circuits.
The IED with a standard configuration is delivered from the factory with default
settings and parameters. The end user flexibility for incoming, outgoing and
internal signal designation within the IED enables this configuration to be further
adapted to different primary circuit layouts and the related functionality needs by
modifying the internal functionality using PCM600.
36 REV615
Application Manual
1MRS757946 A Section 3
REV615 standard configurations
3.3.2 Functions
94/86
U12 0. 0 kV
P 0.00 kW
IL2 0 A
- User management
I ESC Clear
- Web HMI
2×
3I AND
I2> 3Ith>T 3I>>> O R
46 49T 50P/51P
L
OR
3× 3×
ARC 3I>/Io>BF
50L/50NL CONDITION MONITORING COMMUNICATION
51BF/51NBF
AND SUPERVISION
Protocols:
IEC 61850-8-1 1 0 1 0 0 0 1 1 0 0 1 1 0 0
3I>3I< dI>C 3dI>C 3I> CBCM MCS 3I OPTS Modbus® 1 0 1 1 0 0 1 0 1 1 1 0 0 1 0
51C 51NC-1 51NC-2 51P-1 CBCM MCS 3I OPTM IEC 60870-5-103 1 1 0 0 1 1 1 0 1 1 0 1 0
DNP3 1 0 1 1 0 1 1 0 1 1 0 1 0 0
1 0 1 0 0 0 1 1 0 0 1 1 0 0 1 0 1 0 0
2× 1 0 1 1 0 0 1 0 1 1 1 0 0 1 0
2× Interfaces:
3I>> TD> 1 1 0 0 1 1 1 0 1 1 0 1 0
TCS Ethernet: TX (RJ45),
1 0FX1(LC)
1 0 1 1 0 1 1 0 1 0 0
51P-2 55TD Io TCM Serial: Serial glass fiber (ST),
RS-485, RS-232/485
D-sub 9, IRIG-B
Redundant protocols:
Io HSR
PRP
RSTP
2×
Io Io>>> Io> Io>>
CONTROL AND INDICATION 1) MEASUREMENT
50N/51N 51N-1 51N-2
- I, Io
Object Ctrl 2)
Ind 3)
- Limit value supervision
CB 1 - - Load profile record
2 3 - RTD/mA measurement (optional)
DC
- Symmetrical components
ES 1 2
1)
Check availability of binary inputs/outputs Analog interface types 1)
PQM3I
PQM3I
REMARKS
18× Optional 3× No. of Calculated OR Alternative
MAP function instances value function to be
MAP Io/Uo defined when
6xRTD ordering
2xmA
3Iunb
GUID-DFC320F5-AD45-4D28-8632-C3FB2CFDCB06 V2 EN
Connector pins for each input and output are presented in the IED physical
connections section.
REV615 37
Application Manual
Section 3 1MRS757946 A
REV615 standard configurations
38 REV615
Application Manual
1MRS757946 A Section 3
REV615 standard configurations
REV615 39
Application Manual
Section 3 1MRS757946 A
REV615 standard configurations
The analog channels have fixed connections to the different function blocks inside
the IED’s standard configuration. However, the 12 analog channels available for
the disturbance recorder function are freely selectable as a part of the disturbance
recorder’s parameter settings.
The capacitor phase currents as well as capacitor unbalance current to the IED are
fed from a current transformer. The residual current to the IED is fed either from
residually connected current transformers, an external core balance CT, neutral CT
or internally calculated.
40 REV615
Application Manual
1MRS757946 A Section 3
REV615 standard configurations
The IED offers six different settings group which can be set based on the individual
needs. Each group can be activated or deactivated using the setting group settings
available in the IED.
The functional diagrams describe the IEDs protection functionality in detail and
according to the factory set default connections.
Four non-directional overcurrent stages are offered for capacitor overcurrent and
short-circuit protection.
PHIPTOC1
BLOCK OPERATE PHIPTOC1_OPERATE
ENA_MULT START PHIPTOC1_START
PHHPTOC1
BLOCK OPERATE PHHPTOC1_OPERATE
ENA_MULT START PHHPTOC1_START
PHHPTOC2
BLOCK OPERATE PHHPTOC2_OPERATE
ENA_MULT START PHHPTOC2_START
PHLPTOC1
BLOCK OPERATE PHLPTOC1_OPERATE
ENA_MULT START PHLPTOC1_START
OR6
PHIPTOC1_OPERATE B1 O OC_OPERATE
PHLPTOC1_OPERATE B2
PHHPTOC1_OPERATE B3
PHHPTOC2_OPERATE B4
B5
B6
GUID-F44AEFA0-6C24-41B7-B73B-AABC9E9A5AEE V1 EN
Two negative sequence overcurrent stages NSPTOC1 and NSPTOC2 are provided
for phase unbalance protection. These functions are used to protect the capacitor
against unbalance conditions. The negative sequence overcurrent protections are
blocked in case of detection in failure in secondary circuit of current transformer.
REV615 41
Application Manual
Section 3 1MRS757946 A
REV615 standard configurations
NSPTOC1
CCRDIF1_FAIL BLOCK OPERATE NSPTOC1_OPERATE
ENA_MULT START NSPTOC1_START
NSPTOC2
CCRDIF1_FAIL BLOCK OPERATE NSPTOC2_OPERATE
ENA_MULT START NSPTOC2_START
OR
NSPTOC1_OPERATE B1 O NSPTOC_OPERATE
NSPTOC2_OPERATE B2
GUID-17616E9D-2491-400F-922F-CA3C44B1835B V1 EN
EFIPTOC1
BLOCK OPERATE EFIPTOC1_OPERATE
ENA_MULT START EFIPTOC1_START
EFHPTOC1
BLOCK OPERATE EFHPTOC1_OPERATE
ENA_MULT START EFHPTOC1_START
EFLPTOC1
BLOCK OPERATE EFLPTOC1_OPERATE
ENA_MULT START EFLPTOC1_START
EFLPTOC2
BLOCK OPERATE EFLPTOC2_OPERATE
ENA_MULT START EFLPTOC2_START
OR6
EFIPTOC1_OPERATE B1 O EF_OPERATE
EFLPTOC1_OPERATE B2
EFLPTOC2_OPERATE B3
EFHPTOC1_OPERATE B4
B5
B6
GUID-B0744352-B69D-4A7A-ADA4-DB96C09ABD2B V1 EN
42 REV615
Application Manual
1MRS757946 A Section 3
REV615 standard configurations
The thermal overload protection T2PTTR1 with two time constants detects
overload under varying load conditions. The BLK_CLOSE output of the function is
used to block the closing operation of circuit breaker.
T2PTTR1
BLOCK OPERATE T2PTTR1_OPERATE
TEMP_AMB START T2PTTR1_START
ALARM T2PTTR1_ALARM
BLK_CLOSE T2PTTR1_BLK_CLOSE
GUID-DD6AEBAD-E5BA-4D62-9733-394B195E4F1B V1 EN
The breaker failure protection CCBRBRF1 is initiated via the START input by
number of different protection functions available in the IED. The breaker failure
protection function offers different operating modes associated with the circuit
breaker position and the measured phase and residual currents.
The breaker failure protection function has two operating outputs: TRRET and
TRBU. The TRRET operate output is used for retripping its own breaker through
TRPPTRC2_TRIP. The TRBU output is used to give a backup trip to the breaker
feeding upstream. For this purpose, the TRBU operate output signal is connected to
the binary output X100:PO2.
CCBRBRF1
OR6 OR6
BLOCK CB_FAULT_AL
PHIPTOC1_OPERATE B1 O B1 O START TRBU CCBRBRF1_TRBU
PHHPTOC1_OPERATE B2 B2 POSCLOSE TRRET CCBRBRF1_TRRET
PHHPTOC2_OPERATE B3 B3 CB_FAULT
PHLPTOC1_OPERATE B4 B4
NSPTOC1_OPERATE B5 B5
NSPTOC2_OPERATE B6 B6
OR6
COLPTOC1_OPR_OVLOD B1 O
COLPTOC1_OPR_UN_I B2
EFIPTOC1_OPERATE B3
EFLPTOC1_OPERATE B4
EFLPTOC2_OPERATE B5
EFHPTOC1_OPERATE B6
OR6
T2PTTR1_OPERATE B1 O
SRCPTOC1_OPERATE B2
HCUBPTOC1_OPERATE B3
ARCSARC1_OPERATE B4
ARCSARC2_OPERATE B5
ARCSARC3_OPERATE B6
X110_BI4_CB_CLOSED
GUID-633258B3-D89D-418F-ABFA-B27C2DD77778 V1 EN
The operate signals from ARCSARC1...3 are connected to both trip logic
TRPPTRC1 and TRPPTRC2. If the IED has been ordered with high speed binary
outputs, the individual operate signals from ARCSARC1...3 are connected to
dedicated trip logic TRPPTRC3...5. The outputs of TRPPTRC3...5 are available at
high speed outputs X110:HSO1, X110:HSO2 and X110:HSO3.
REV615 43
Application Manual
Section 3 1MRS757946 A
REV615 standard configurations
ARCSARC1
BLOCK OPERATE ARCSARC1_OPERATE
REM_FLT_ARC ARC_FLT_DET ARCSARC1_ARC_FLT_DET
OPR_MODE
ARCSARC2
BLOCK OPERATE ARCSARC2_OPERATE
REM_FLT_ARC ARC_FLT_DET ARCSARC2_ARC_FLT_DET
OPR_MODE
ARCSARC3
BLOCK OPERATE ARCSARC3_OPERATE
REM_FLT_ARC ARC_FLT_DET ARCSARC3_ARC_FLT_DET
OPR_MODE
OR6
ARCSARC1_OPERATE B1 O ARCSARC_OPERATE
ARCSARC2_OPERATE B2
ARCSARC3_OPERATE B3
B4
B5
B6
GUID-AD0475AD-B69E-4EAE-AAAE-470275749B45 V1 EN
TRPPTRC3
BLOCK TRIP TRPPTRC3_TRIP
ARCSARC1_OPERATE OPERATE CL_LKOUT
RST_LKOUT
TRPPTRC4
BLOCK TRIP TRPPTRC4_TRIP
ARCSARC2_OPERATE OPERATE CL_LKOUT
RST_LKOUT
TRPPTRC5
BLOCK TRIP TRPPTRC5_TRIP
ARCSARC3_OPERATE OPERATE CL_LKOUT
RST_LKOUT
GUID-6120D810-63F0-4D7B-BA6F-DD519D6343AC V1 EN
44 REV615
Application Manual
1MRS757946 A Section 3
REV615 standard configurations
COLPTOC1
BLOCK OPR_OVLOD COLPTOC1_OPR_OVLOD
X110_BI4_CB_CLOSED CB_CLOSED OPR_UN_I COLPTOC1_OPR_UN_I
ST_OVLOD COLPTOC1_ST_OVLOD
ST_UN_I COLPTOC1_ST_UN_I
ALARM COLPTOC1_ALARM
BLK_CLOSE COLPTOC1_BLK_CLOSE
GUID-13EE20DE-CBD6-475C-A4A8-2B13760055DC V1 EN
HCUBPTOC1
BLOCK OPERATE HCUBPTOC1_OPERATE
START HCUBPTOC1_START
ALARM
GUID-12E4FC9C-4F80-475C-98F0-BCEC1F5914E5 V1 EN
SRCPTOC1
BLOCK ALARM SRCPTOC1_ALARM
RESO_IN OPERATE SRCPTOC1_OPERATE
GUID-C417AE30-0923-45CA-910C-39836780A12E V
General start and operate from all the functions are connected to pulse timer
TPGAPC1 for setting the minimum pulse length for the outputs. The output from
TPGAPC1 is connected to binary outputs.
REV615 45
Application Manual
Section 3 1MRS757946 A
REV615 standard configurations
OR6 OR6
PHLPTOC1_START B1 O B1 O
PHHPTOC1_START B2 B2
PHHPTOC2_START B3 B3
PHIPTOC1_START B4 B4
EFLPTOC1_START B5 B5
EFLPTOC2_START B6 B6
TPGAPC1
IN1 OUT1 GENERATE_START_PULSE
OR6 IN2 OUT2 GENERATE_OPERATE_PULSE
EFHPTOC1_START B1 O
EFIPTOC1_START B2
NSPTOC1_START B3
NSPTOC2_START B4
T2PTTR1_START B5
COLPTOC1_ST_OVLOD B6
OR6
B1 O
B2
OR6 B3
B4
COLPTOC1_ST_UN_I B1 O B5
HCUBPTOC1_START B2 B6
B3
B4
B5
B6
OR6
PHLPTOC1_OPERATE B1 O
PHHPTOC1_OPERATE B2
PHHPTOC2_OPERATE B3
PHIPTOC1_OPERATE B4
EFLPTOC1_OPERATE B5
EFLPTOC2_OPERATE B6
OR6
EFHPTOC1_OPERATE B1 O
EFIPTOC1_OPERATE B2
NSPTOC1_OPERATE B3
NSPTOC2_OPERATE B4
T2PTTR1_OPERATE B5
COLPTOC1_OPR_OVLOD B6
OR6
COLPTOC1_OPR_UN_I B1 O
HCUBPTOC1_OPERATE B2
ARCSARC1_OPERATE B3
ARCSARC2_OPERATE B4
ARCSARC3_OPERATE B5
B6
GUID-F644FD19-1CEB-46B9-92A5-BD30DAFDCD25 V1 EN
The operate signals from the protection functions are connected to two trip logics:
TRPPTRC1 and TRPPTRC2. The output of TRPPTRC1 is available at binary
output X100:PO3. The trip logic functions are provided with a lockout and latching
function, event generation and the trip signal duration setting. If the lockout
operation mode is selected, binary input can been assigned to RST_LKOUT input
of both the trip logic to enable external reset with a push button.
Three other trip logics TRPPTRC3...5 are also available if the IED is ordered with
high speed binary outputs options.
46 REV615
Application Manual
1MRS757946 A Section 3
REV615 standard configurations
TRPPTRC1
OR6 OR6
BLOCK TRIP TRPPTRC1_TRIP
PHLPTOC1_OPERATE B1 O B1 O OPERATE CL_LKOUT
PHHPTOC1_OPERATE B2 B2 RST_LKOUT
PHHPTOC2_OPERATE B3 B3
PHIPTOC1_OPERATE B4 B4
EFLPTOC1_OPERATE B5 B5
EFLPTOC2_OPERATE B6 B6
OR6
EFHPTOC1_OPERATE B1 O
EFIPTOC1_OPERATE B2
NSPTOC1_OPERATE B3
NSPTOC2_OPERATE B4
T2PTTR1_OPERATE B5
COLPTOC1_OPR_OVLOD B6
OR6
COLPTOC1_OPR_UN_I B1 O
HCUBPTOC1_OPERATE B2
SRCPTOC1_OPERATE B3
ARCSARC1_OPERATE B4
ARCSARC2_OPERATE B5
ARCSARC3_OPERATE B6
GUID-D903E6A4-F42A-4BF3-BCD2-0C38F4301B53 V1 EN
TRPPTRC2
OR6 OR6
BLOCK TRIP TRPPTRC2_TRIP
PHLPTOC1_OPERATE B1 O B1 O OPERATE CL_LKOUT
PHHPTOC1_OPERATE B2 B2 RST_LKOUT
PHHPTOC2_OPERATE B3 B3
PHIPTOC1_OPERATE B4 CCBRBRF1_TRRET B4
EFLPTOC1_OPERATE B5 B5
EFLPTOC2_OPERATE B6 B6
OR6
EFHPTOC1_OPERATE B1 O
EFIPTOC1_OPERATE B2
NSPTOC1_OPERATE B3
NSPTOC2_OPERATE B4
T2PTTR1_OPERATE B5
COLPTOC1_OPR_OVLOD B6
OR6
COLPTOC1_OPR_UN_I B1 O
HCUBPTOC1_OPERATE B2
SRCPTOC1_OPERATE B3
ARCSARC1_OPERATE B4
ARCSARC2_OPERATE B5
ARCSARC3_OPERATE B6
GUID-06C6D0C6-F6FB-4B9C-971C-CFDD9C2C914B V1 EN
The START and the OPERATE outputs from the protection stages are routed to
trigger the disturbance recorder or, alternatively, only to be recorded by the
disturbance recorder depending on the parameter settings. Additionally, the
selected signals from different functions and the few binary inputs are also
connected to the disturbance recorder.
REV615 47
Application Manual
Section 3 1MRS757946 A
REV615 standard configurations
RDRE1
OR6
PHIPTOC1_START C1 TRIGGERED DISTURB_RECORD_TRIGGERED
PHIPTOC1_OPERATE B1 O PHHPTOC1_START C2
PHHPTOC1_OPERATE B2 PHHPTOC2_START C3
PHHPTOC2_OPERATE B3 PHLPTOC1_START C4
PHLPTOC1_OPERATE B4 EFHPTOC1_START C5
B5 EFIPTOC1_START C6
B6 EFLPTOC1_START C7
EFLPTOC2_START C8
NSPTOC1_START C9
NSPTOC2_START C10
T2PTTR1_START C11
OR6 COLPTOC1_ST_OVLOD C12
COLPTOC1_ST_UN_I C13
EFHPTOC1_OPERATE B1 O HCUBPTOC1_START C14
EFLPTOC1_OPERATE B2 C15
EFLPTOC2_OPERATE B3 C16
EFIPTOC1_OPERATE B4 C17
B5 T2PTTR1_OPERATE C18
B6 COLPTOC1_OPR_OVLOD C19
COLPTOC1_OPR_UN_I C20
HCUBPTOC1_OPERATE C21
T2PTTR1_ALARM C22
SRCPTOC1_ALARM C23
COLPTOC1_ALARM C24
OR SRCPTOC1_OPERATE C25
CCBRBRF1_TRRET C26
NSPTOC1_OPERATE B1 O CCBRBRF1_TRBU C27
NSPTOC2_OPERATE B2 CCRDIF1_FAIL C28
X110_BI4_CB_CLOSED C29
X110_BI3_CB_OPENED C30
C31
ARCSARC1_OPERATE C32
ARCSARC2_OPERATE C33
ARCSARC3_OPERATE C34
C35
OR6 C36
C37
ARCSARC1_ARC_FLT_DET B1 O C38
ARCSARC2_ARC_FLT_DET B2 C39
ARCSARC3_ARC_FLT_DET B3 C40
B4 C41
B5 C42
B6 C43
C44
C45
C46
C47
C48
C49
C50
C51
C52
C53
C54
C55
C56
C57
C58
C59
C60
C61
C62
C63
C64
GUID-6C2585FD-C0EF-4ED4-8266-85D4E1A9C21A V1 EN
CCRDIF1
BLOCK FAIL CCRDIF1_FAIL
ALARM CCRDIF1_ALARM
GUID-1F1C3820-1BE7-466A-9635-9D1BEE469DA6 V1 EN
The circuit breaker condition monitoring function SSCBR1 supervises the switch
status based on the connected binary input information and the measured current
levels. SSCBR1 introduces various supervision methods.
48 REV615
Application Manual
1MRS757946 A Section 3
REV615 standard configurations
SSCBR1
BLOCK TRV_T_OP_ALM SSCBR1_TRV_T_OP_ALM
X110_BI3_CB_OPENED POSOPEN TRV_T_CL_ALM SSCBR1_TRV_T_CL_ALM
X110_BI4_CB_CLOSED POSCLOSE SPR_CHR_ALM SSCBR1_SPR_CHR_ALM
CB_OPEN_COMMAND OPEN_CB_EXE OPR_ALM SSCBR1_OPR_ALM
CB_CLOSE_COMMAND CLOSE_CB_EXE OPR_LO SSCBR1_OPR_LO
X110_BI1_GAS_PRESSURE_ALARM PRES_ALM_IN IPOW_ALM SSCBR1_IPOW_ALM
PRES_LO_IN IPOW_LO SSCBR1_IPOW_LO
CB_SPRING_DISCHARGED SPR_CHR_ST CB_LIFE_ALM SSCBR1_CB_LIFE_ALM
X110_BI2_CB_SPRING_CHARGED SPR_CHR MON_ALM SSCBR1_MON_ALM
RST_IPOW PRES_ALM SSCBR1_PRES_ALM
RST_CB_WEAR PRES_LO SSCBR1_PRES_LO
RST_TRV_T OPENPOS
RST_SPR_T INVALIDPOS
CLOSEPOS
GUID-42D5E911-3FB1-487D-AF85-9C80EFA0B65C V1 EN
OR6
SSCBR1_TRV_T_OP_ALM B1 O
SSCBR1_TRV_T_CL_ALM B2
SSCBR1_SPR_CHR_ALM B3
SSCBR1_OPR_ALM B4
SSCBR1_OPR_LO B5 OR
SSCBR1_IPOW_ALM B6
B1 O SSCBR1_ALARMS
B2
OR6
SSCBR1_IPOW_LO B1 O
SSCBR1_CB_LIFE_ALM B2
SSCBR1_MON_ALM B3
SSCBR1_PRES_ALM B4
SSCBR1_PRES_LO B5
B6
GUID-A6334A2F-B17C-4689-A5BA-B2C6273ACBFA V1 EN
NOT
X110_BI2_CB_SPRING_CHARGED IN OUT CB_SPRING_DISCHARGED
GUID-627752B9-D32B-4135-914C-71619713971D V1 EN
Two separate trip circuit supervision functions are included: TCSSCBR1 for power
output X100:PO3 and TCSSCBR2 for power output X100:PO4. The functions are
blocked by the Master Trip TRPPTRC1 and TRPPTRC2 and the circuit breaker
open signal.
REV615 49
Application Manual
Section 3 1MRS757946 A
REV615 standard configurations
TCSSCBR1
TCSSCBR_BLOCKING BLOCK ALARM TCSSCBR1_ALARM
TCSSCBR2
TCSSCBR_BLOCKING BLOCK ALARM TCSSCBR2_ALARM
OR
TCSSCBR1_ALARM B1 O TCSSCBR_ALARM
TCSSCBR2_ALARM B2
GUID-400C35B2-0D30-40F7-B62B-3021AA09875F V1 EN
OR6
TRPPTRC1_TRIP B1 O TCSSCBR_BLOCKING
TRPPTRC2_TRIP B2
X110_BI3_CB_OPENED B3
B4
B5
B6
GUID-2C52341D-A1CA-429B-8381-ACDBFDAE0558 V1 EN
There are two types of disconnector and earthing switch function blocks.
DCSXSWI1...3 and ESSXSWI1...2 are status only type, and DCXSWI1...2 and
ESXSWI1 are controllable type. By default, the status only blocks are connected in
standard configuration. The disconnector (CB truck) and line side earthing switch
status information are connected to DCSXSWI1 and ESSXSI1.
DCSXSWI1
X110_BI6_CB_TRUCK_IN_TEST POSOPEN OPENPOS
X110_BI5_CB_TRUCK_IN_SERVICE POSCLOSE CLOSEPOS
OKPOS DCSXSWI1_OKPOS
GUID-3C6C5D27-1FD1-4DFF-ADCF-940D1CEF7754 V1 EN
ESSXSWI1
X110_BI7_ES1_OPENED POSOPEN OPENPOS ESSXSWI1_OPENPOS
X110_BI8_ES1_CLOSED POSCLOSE CLOSEPOS
OKPOS
GUID-A4C2DD66-9DDE-4228-80B5-CE7DA09D15E2 V1 EN
The circuit breaker closing is enabled when the ENA_CLOSE input is activated.
The input can be activated using the configuration logic, which is a combination of
50 REV615
Application Manual
1MRS757946 A Section 3
REV615 standard configurations
the disconnector or breaker truck and earth-switch position status, status of the trip
logics, gas pressure alarm and circuit-breaker spring charging status.
The OKPOS output from DCSXSWI defines whether the disconnector or breaker
truck is definitely either open (in test position) or close (in service position). This
output, together with the open earth-switch and non-active trip signals, activates
the close-enable signal to the circuit breaker control function block. The open
operation for circuit breaker is always enabled.
The ITL_BYPASS input can be used, for example, to always enable the closing of
the circuit breaker when the circuit breaker truck is in the test position, despite the
interlocking conditions being active when the circuit breaker truck is closed in
service position.
CBXCBR1
X110_BI3_CB_OPENED POSOPEN SELECTED
X110_BI4_CB_CLOSED POSCLOSE EXE_OP CBXCBR1_EXE_OP
TRUE ENA_OPEN EXE_CL CBXCBR1_EXE_CL
CBXCBR1_ENA_CLOSE ENA_CLOSE OPENPOS
FALSE BLK_OPEN CLOSEPOS
CBXCBR1_BLK_CLOSE BLK_CLOSE OKPOS
CBXBCR1_AU_OPEN AU_OPEN OPEN_ENAD
CBXCBR1_AU_CLOSE AU_CLOSE CLOSE_ENAD
ITL_BYPASS
GUID-36F27E21-4648-44E6-B1F0-69621F0AAB6C V1 EN
OR
CBXCBR1_EXE_CL B1 O CB_CLOSE_COMMAND
B2
GUID-B3C31E9E-9C06-4CB0-A5EF-FFAA8F560A2F V1 EN
Figure 36: Circuit breaker control logic: Signals for closing coil of circuit breaker
OR6
TRPPTRC1_TRIP B1 O CB_OPEN_COMMAND
CBXCBR1_EXE_OP B2
B3
B4
B5
B6
GUID-CA037F31-80A3-4AC2-8632-EA92C34F1474 V1 EN
Figure 37: Circuit breaker control logic: Signals for opening coil of circuit breaker
REV615 51
Application Manual
Section 3 1MRS757946 A
REV615 standard configurations
AND6
DCSXSWI1_OKPOS B1 O CBXCBR1_ENA_CLOSE
X110_BI2_CB_SPRING_CHARGED B2
ESSXSWI1_OPENPOS B3
B4
B5
NOT B6
X110_BI1_GAS_PRESSURE_ALARM IN OUT
NOT
TRPPTRC1_TRIP IN OUT
NOT
TRPPTRC2_TRIP IN OUT
GUID-A0980B62-CA07-4610-890D-973D87E22FBF V1 EN
OR6
COLPTOC1_BLK_CLOSE B1 O CBXCBR1_BLK_CLOSE
T2PTTR1_BLK_CLOSE B2
B3
B4
B5
B6
GUID-38693D6F-1F5A-48CF-9599-BDC4B4966AA1 V1 EN
The configuration includes the logic for generating circuit breaker external closing
and opening command with the IED in local or remote mode.
Check the logic for the external circuit breaker closing command
and modify it according to the application.
AND
CONTROL_LOCAL B1 O
FALSE B2
OR
B1 O CBXCBR1_AU_CLOSE
B2
AND
CONTROL_REMOTE B1 O
FALSE B2
GUID-4F3196A4-C1B0-40C5-B471-4CBBE3FFFBB8 V1 EN
AND
CONTROL_LOCAL B1 O
FALSE B2
OR
B1 O CBXBCR1_AU_OPEN
B2
AND
CONTROL_REMOTE B1 O
FALSE B2
GUID-A78AB2F2-DD2B-41DE-9DCE-C41699F49E51 V1 EN
52 REV615
Application Manual
1MRS757946 A Section 3
REV615 standard configurations
The phase current inputs to the IED are measured by the three-phase current
measurement function CMMXU1. The current input is connected to the X120 card
in the back panel. The sequence current measurement CSMSQI1 measures the
sequence current and the residual current measurement RESCMMXU1 measures
the residual current.
The power quality function CMHAI1 can be used to measure the harmonic
contents of the phase current. By default these power quality functions are not
included in the configuration. Depending on the application, the needed logic
connections can be made by PCM600.
The measurements can be seen in the LHMI and they are available under the
measurement option in the menu selection. Based on the settings, function blocks
can generate low alarm or warning and high alarm or warning signals for the
measured current values.
CMMXU1
BLOCK HIGH_ALARM
HIGH_WARN
LOW_WARN
LOW_ALARM
GUID-081ABD5F-61E0-4161-BEB6-BADE5990577A V1 EN
CSMSQI1
GUID-C9FD52FF-A026-4EA8-AA9F-95E181E24868 V1 EN
RESCMMXU1
BLOCK HIGH_ALARM
HIGH_WARN
GUID-F8CB647F-51CB-49BF-9F06-395A8D937F1C V1 EN
FLTMSTA1
BLOCK
CB_CLRD
GUID-A4BDD2EA-21C1-4DDA-BB72-E8D9F3EBA484 V1 EN
REV615 53
Application Manual
Section 3 1MRS757946 A
REV615 standard configurations
LDPMSTA1
RSTMEM MEM_WARN
MEM_ALARM
GUID-167DEAB2-BAA4-43F3-A791-BE39969AE28C V1 EN
X110 (BIO).X110-Input 1 OR
B1 O X110_BI1_GAS_PRESSURE_ALARM
B2
X110 (BIO-H).X110-Input 1
X110 (BIO).X110-Input 2 OR
B1 O X110_BI2_CB_SPRING_CHARGED
B2
X110 (BIO-H).X110-Input 2
X110 (BIO).X110-Input 3 OR
B1 O X110_BI3_CB_OPENED
B2
X110 (BIO-H).X110-Input 3
X110 (BIO).X110-Input 4 OR
B1 O X110_BI4_CB_CLOSED
B2
X110 (BIO-H).X110-Input 4
X110 (BIO).X110-Input 5 OR
B1 O X110_BI5_CB_TRUCK_IN_TEST
B2
X110 (BIO-H).X110-Input 5
X110 (BIO).X110-Input 6 OR
B1 O X110_BI6_CB_TRUCK_IN_SERVICE
B2
X110 (BIO-H).X110-Input 6
X110 (BIO).X110-Input 7 OR
B1 O X110_BI7_ES1_OPENED
B2
X110 (BIO-H).X110-Input 7
X110 (BIO).X110-Input 8 OR
B1 O X110_BI8_ES1_CLOSED
B2
X110 (BIO-H).X110-Input 8
GUID-5E7AA6A5-C2AF-4DCF-8E7D-997517703B33 V1 EN
54 REV615
Application Manual
1MRS757946 A Section 3
REV615 standard configurations
OC_OPERATE_PULSE
X110 (BIO).X110-SO1
TRPPTRC3_TRIP
X110 (BIO-H).X110-HSO1
EF_OPERATE_PULSE
X110 (BIO).X110-SO2
TRPPTRC4_TRIP
X110 (BIO-H).X110-HSO2
CAPACITOR_UNBAL_OPERATE_PULSE
X110 (BIO).X110-SO3
TRPPTRC5_TRIP
X110 (BIO-H).X110-HSO3
OTHER_CAPACITOR_PROT_OPERATE_PULSE
X110 (BIO).X110-SO4
GUID-A39DE49C-C3F7-43B8-A539-39EB86527A52 V1 EN
CB_CLOSE_COMMAND
X100 (PSM).X100-PO1
CCBRBRF1_TRBU
X100 (PSM).X100-PO2
GENERATE_START_PULSE
X100 (PSM).X100-SO1
GENERATE_OPERATE_PULSE
X100 (PSM).X100-SO2
CB_OPEN_COMMAND
X100 (PSM).X100-PO3
RECONNECTION_ENABLE
X100 (PSM).X100-PO4
GUID-17CB6958-2F21-48A9-8376-7E1280C44EF5 V1 EN
REV615 55
Application Manual
Section 3 1MRS757946 A
REV615 standard configurations
LED1
OK
OC_OPERATE ALARM
RESET
LED2
OK
EF_OPERATE ALARM
RESET
LED3
OR
OK
T2PTTR1_OPERATE B1 O ALARM
COLPTOC1_OPR_OVLOD B2 RESET
LED4
OK
COLPTOC1_ALARM ALARM
RESET
LED5
OR
OK
NSPTOC_OPERATE B1 O ALARM
HCUBPTOC1_OPERATE B2 RESET
GUID-53549210-B647-4AED-AFE3-052CEEE79B85 V1 EN
LED6
OK
ALARM
RESET
LED7
OR
OK
SRCPTOC1_OPERATE B1 O ALARM
COLPTOC1_OPR_UN_I B2 RESET
LED8
OK
CCBRBRF1_TRBU ALARM
RESET
LED9
OK
DISTURB_RECORD_TRIGGERED ALARM
RESET
LED10
OR6
OK
CCRDIF1_ALARM B1 O ALARM
TCSSCBR_ALARM B2 RESET
SSCBR1_ALARMS B3
B4
B5
B6
LED11
OK
ARC_OPERATE ALARM
RESET
GUID-A26104E6-2DD2-4064-BDDB-7C11550C9CB0 V1 EN
56 REV615
Application Manual
1MRS757946 A Section 3
REV615 standard configurations
TPGAPC2
OC_OPERATE IN1 OUT1 OC_OPERATE_PULSE
EF_OPERATE IN2 OUT2 EF_OPERATE_PULSE
GUID-D3247DEB-A1BC-4716-B908-8C31258CA237 V1 EN
Figure 51: Timer logic for overcurrent and earth-fault operate pulse
TPGAPC3
HCUBPTOC1_OPERATE IN1 OUT1 CAPACITOR_UNBAL_OPERATE_PULSE
IN2 OUT2 OTHER_CAPACITOR_PROT_OPERATE_PULSE
OR6
SRCPTOC1_OPERATE B1 O
COLPTOC1_OPR_OVLOD B2
COLPTOC1_OPR_UN_I B3
B4
B5
B6
GUID-EBE802C7-6F81-4654-8960-4AC5B5DFFDB5 V1 EN
Figure 52: Timer logic for capacitor unbalance and other capacitor protection
operate pulse
NOT
CBXCBR1_BLK_CLOSE IN OUT RECONNECTION_ENABLE
GUID-D8FCF65B-47B4-402D-AEE9-86A21D42E381 V1 EN
3.4.1 Applications
The standard configuration offers three phase overload protection, unbalance
protection with compensation for natural unbalance and switching resonance
protection for capacitor banks. An integrated undercurrent function in the overload
protection function block detects the disconnection of a capacitor bank and inhibits
REV615 57
Application Manual
Section 3 1MRS757946 A
REV615 standard configurations
the closing of the circuit breaker as long as the capacitor bank is still partially
discharged. A three-phase thermal overload protection is available and can be used
for the thermal protection of the reactors and resistors in the harmonic filter circuits.
The second and third stage of the residual voltage protection in the standard
configuration B can be used as voltage based unbalance protection mainly for
single star-connected capacitor banks, with unearthed star point. A dedicated
voltage input Uob is used for this purpose. This functionality needs to be
configured in order to take into use.
The IED with a standard configuration is delivered from the factory with default
settings and parameters. The end user flexibility for incoming, outgoing and
internal signal designation within the IED enables this configuration to be further
adapted to different primary circuit layouts and the related functionality needs by
modifying the internal functionality using PCM600.
58 REV615
Application Manual
1MRS757946 A Section 3
REV615 standard configurations
3.4.2 Functions
Uo
UL1UL2UL3
Lockout relay A
O
- IED self-supervision
R
L
94/86
U12 0. 0 kV
P 0.00 kW
Q 0.00 kVAr
IL2 0 A
- Local/Remote push button on LHMI
- User management
I ESC Clear
- Web HMI
2×
AND
3I I2> 3Ith>T 3I>>> O R
OR 46 49T 50P/51P
L
OR
3× 3×
ARC 3I>/Io>BF
50L/50NL CONDITION MONITORING COMMUNICATION
51BF/51NBF
3I AND SUPERVISION
Protocols:
0 0 0 1 1 0 0 1 1 0 0
IEC 61850-8-1/-9-2LE
1 0 1 0 0 0 1 1 0 0 1 1 0 0
1 0 0 1 0 1 1 1 0 0 1 0 3I>3I< dI>C 3dI>C 3I> FUSEF CBCM MCS 3I Modbus® 1 0 1 1 0 0 1 0 1 1 1 0 0 1 0
0 1 1 1 0 1 1 0 1 0 51C 51NC-1 51NC-2 51P-1 60 CBCM MCS 3I IEC 60870-5-103 1 1 0 0 1 1 1 0 1 1 0 1 0
1 0 1 1 0 1 1 0 1 0 0 DNP3 1 0 1 1 0 1 1 0 1 1 0 1 0 0
0 0 0 1 1 0 0 1 1 0 0 1 0 1 0 0 0 1 1 0 0 1 1 0 0 1 0 1 0 0 0 1 1 0 0 1 1 0 0 1 0 1 0 0
1 0 0 1 0 1 1 1 0 0 1 0 2× 2× 1 0 1 1 0 0 1 0 1 1 1 0 0 1 0
0 1 1 1 0 1 1 0 1 0 Interfaces: 1 1 0 0 1 1 1 0 1 1 0 1 0
3I>> TD> OPTS TCS
1 0 1 1 0 1 1 0 1 0 0 Ethernet: TX (RJ45),1 FX
0 1(LC)
1 0 1 1 0 1 1 0 1 0 0
51P-2 55TD Io OPTM TCM
Serial: Serial glass fiber (ST),
RS-485, RS-232/485
D-sub 9, IRIG-B
Redundant protocols:
Io HSR
PRP
RSTP
2×
Io Io>> Io>→ Io>>→
CONTROL AND INDICATION 1) MEASUREMENT
51N-2 67N-1 67N-2
- I, U, Io, Uo, P, Q, E, pf, f
Object Ctrl 2)
Ind 3)
- Limit value supervision
CB 1 - - Load profile record
Uo - RTD/mA measurement (optional)
DC 2 3
- Symmetrical components
ES 1 2
1)
Check availability of binary inputs/outputs Analog interface types 1)
2× 3×
3U> Uo> PQM3I PQM3U PQMU
UL1UL2UL3 59 59G PQM3I PQM3V PQMV
REMARKS
18× Optional 3× No. of Calculated OR Alternative
MAP function instances value function to be
MAP Io/Uo defined when
2xRTD ordering
1xmA
Iunb
GUID-393D9B25-06C8-42AE-A7D0-642BBCB89DBE V1 EN
Connector pins for each input and output are presented in the IED physical
connections section.
REV615 59
Application Manual
Section 3 1MRS757946 A
REV615 standard configurations
60 REV615
Application Manual
1MRS757946 A Section 3
REV615 standard configurations
REV615 61
Application Manual
Section 3 1MRS757946 A
REV615 standard configurations
62 REV615
Application Manual
1MRS757946 A Section 3
REV615 standard configurations
The analog channels have fixed connections to the different function blocks inside
the IED’s standard configuration. However, the 12 analog channels available for
the disturbance recorder function are freely selectable as a part of the disturbance
recorder’s parameter settings.
The capacitor phase currents as well as capacitor unbalance current to the IED are
fed from a current transformer. The residual current to the IED is fed either from
residually connected current transformers, an external core balance CT, neutral CT
or internally calculated.
The capacitor phase voltages to the IED are fed from a voltage transformer. The
residual voltage to the IED is fed either from residually connected voltage
transformers, an open delta connected VT or internally calculated.
The IED offers six different settings group which can be set based on the individual
needs. Each group can be activated or deactivated using the setting group settings
available in the IED.
The functional diagrams describe the IED's protection functionality in detail and
according to the factory set default connections.
Four non-directional overcurrent stages are offered for capacitor overcurrent and
short-circuit protection.
REV615 63
Application Manual
Section 3 1MRS757946 A
REV615 standard configurations
PHIPTOC1
BLOCK OPERATE PHIPTOC1_OPERATE
ENA_MULT START PHIPTOC1_START
PHHPTOC1
BLOCK OPERATE PHHPTOC1_OPERATE
ENA_MULT START PHHPTOC1_START
PHHPTOC2
BLOCK OPERATE PHHPTOC2_OPERATE
ENA_MULT START PHHPTOC2_START
PHLPTOC1
BLOCK OPERATE PHLPTOC1_OPERATE
ENA_MULT START PHLPTOC1_START
OR6
PHIPTOC1_OPERATE B1 O OC_OPERATE
PHLPTOC1_OPERATE B2
PHHPTOC1_OPERATE B3
PHHPTOC2_OPERATE B4
B5
B6
GUID-6E8841C3-F6CA-400D-8FB4-334950973E62 V1 EN
Two negative sequence overcurrent stages NSPTOC1 and NSPTOC2 are provided
for phase unbalance protection. These functions are used to protect the capacitor
against unbalance conditions. The negative sequence overcurrent protection
functions are blocked in case of detection in failure in secondary circuit of current
transformer.
64 REV615
Application Manual
1MRS757946 A Section 3
REV615 standard configurations
NSPTOC1
CCRDIF1_FAIL BLOCK OPERATE NSPTOC1_OPERATE
ENA_MULT START NSPTOC1_START
NSPTOC2
CCRDIF1_FAIL BLOCK OPERATE NSPTOC2_OPERATE
ENA_MULT START NSPTOC2_START
OR
NSPTOC1_OPERATE B1 O NSPTOC_OPERATE
NSPTOC2_OPERATE B2
GUID-5D442EE5-77B1-46F7-B8D8-B846D6DEF541 V1 EN
Four stages are provided for earth-fault protection. Three stages are dedicated for
directional earth-fault protection.
DEFHPDEF1
BLOCK OPERATE DEFHPDEF1_OPERATE
ENA_MULT START DEFHPDEF1_START
RCA_CTL
DEFLPDEF1
BLOCK OPERATE DEFLPDEF1_OPERATE
ENA_MULT START DEFLPDEF1_START
RCA_CTL
DEFLPDEF2
BLOCK OPERATE DEFLPDEF2_OPERATE
ENA_MULT START DEFLPDEF2_START
RCA_CTL
EFHPTOC1
BLOCK OPERATE EFHPTOC1_OPERATE
ENA_MULT START EFHPTOC1_START
OR6
DEFHPDEF1_OPERATE B1 O EF_OPERATE
DEFLPDEF2_OPERATE B2
DEFLPDEF1_OPERATE B3
EFHPTOC1_OPERATE B4
B5
B6
GUID-E57792A0-0380-4B27-AB24-8EB001BABA8F V1 EN
REV615 65
Application Manual
Section 3 1MRS757946 A
REV615 standard configurations
The thermal overload protection T2PTTR1 with two time constants detects
overload under varying load conditions. The BLK_CLOSE output of the function is
used to block the closing operation of circuit breaker.
T2PTTR1
BLOCK OPERATE T2PTTR1_OPERATE
TEMP_AMB START T2PTTR1_START
ALARM T2PTTR1_ALARM
BLK_CLOSE T2PTTR1_BLK_CLOSE
GUID-39968CD7-297E-451D-BE56-97E126A257D4 V1 EN
The breaker failure protection CCBRBRF1 is initiated via the START input by
number of different protection functions available in the IED. The breaker failure
protection function offers different operating modes associated with the circuit
breaker position and the measured phase and residual currents.
The breaker failure protection function has two operating outputs: TRRET and
TRBU. The TRRET operate output is used for retripping its own breaker through
TRPPTRC2_TRIP. The TRBU output is used to give a backup trip to the breaker
feeding upstream. For this purpose, the TRBU operate output signal is connected to
the binary output X100:PO2.
CCBRBRF1
OR6 OR6
BLOCK CB_FAULT_AL
PHIPTOC1_OPERATE B1 O B1 O START TRBU CCBRBRF1_TRBU
PHHPTOC1_OPERATE B2 B2
X110_BI4_CB_CLOSED POSCLOSE TRRET CCBRBRF1_TRRET
PHHPTOC2_OPERATE B3 B3 CB_FAULT
PHLPTOC1_OPERATE B4 B4
NSPTOC1_OPERATE B5 B5
NSPTOC2_OPERATE B6 B6
OR6
COLPTOC1_OPR_OVLOD B1 O
COLPTOC1_OPR_UN_I B2
DEFHPDEF1_OPERATE B3
DEFLPDEF2_OPERATE B4
DEFLPDEF1_OPERATE B5
EFHPTOC1_OPERATE B6
OR6
T2PTTR1_OPERATE B1 O
SRCPTOC1_OPERATE B2
CUBPTOC1_OPERATE B3
NSPTOV1_OPERATE B4
ROVPTOV1_OPERATE B5
PSPTUV1_OPERATE B6
OR6
PHPTOV1_OPERATE B1 O
PHPTOV2_OPERATE B2
PHPTUV1_OPERATE B3
PHPTUV2_OPERATE B4
B5
B6
OR6
ARCSARC1_OPERATE B1 O
ARCSARC2_OPERATE B2
ARCSARC3_OPERATE B3
B4
B5
B6
GUID-A5095A7B-4341-46B8-B10E-07849EF3D52D V1 EN
66 REV615
Application Manual
1MRS757946 A Section 3
REV615 standard configurations
Three arc protection stages ARCSARC1...3 are included as optional functions. The
arc protection offers individual function blocks for three arc sensors that can be
connected to the IED. Each arc protection function block has two different
operation modes, that is, with or without the phase and residual current check.
The operate signals from ARCSARC1...3 are connected to both trip logic
TRPPTRC1 and TRPPTRC2. If the IED has been ordered with high speed binary
outputs, the individual operate signals from ARCSARC1...3 are connected to
dedicated trip logic TRPPTRC3...5. The outputs of TRPPTRC3...5 are available at
high speed outputs X110:HSO1, X110:HSO2 and X110:HSO3.
REV615 67
Application Manual
Section 3 1MRS757946 A
REV615 standard configurations
ARCSARC1
BLOCK OPERATE ARCSARC1_OPERATE
REM_FLT_ARC ARC_FLT_DET ARCSARC1_ARC_FLT_DET
OPR_MODE
ARCSARC2
BLOCK OPERATE ARCSARC2_OPERATE
REM_FLT_ARC ARC_FLT_DET ARCSARC2_ARC_FLT_DET
OPR_MODE
ARCSARC3
BLOCK OPERATE ARCSARC3_OPERATE
REM_FLT_ARC ARC_FLT_DET ARCSARC3_ARC_FLT_DET
OPR_MODE
OR6
ARCSARC1_OPERATE B1 O ARCSARC_OPERATE
ARCSARC2_OPERATE B2
ARCSARC3_OPERATE B3
B4
B5
B6
GUID-FC4A254A-CE67-47F8-9D4E-27895E228DB8 V1 EN
TRPPTRC3
BLOCK TRIP TRPPTRC3_TRIP
ARCSARC1_OPERATE OPERATE CL_LKOUT
RST_LKOUT
TRPPTRC4
BLOCK TRIP TRPPTRC4_TRIP
ARCSARC2_OPERATE OPERATE CL_LKOUT
RST_LKOUT
TRPPTRC5
BLOCK TRIP TRPPTRC5_TRIP
ARCSARC3_OPERATE OPERATE CL_LKOUT
RST_LKOUT
GUID-47E92FB9-061E-414C-AD0F-91C1C3F55C35 V1 EN
68 REV615
Application Manual
1MRS757946 A Section 3
REV615 standard configurations
COLPTOC1
BLOCK OPR_OVLOD COLPTOC1_OPR_OVLOD
X110_BI4_CB_CLOSED CB_CLOSED OPR_UN_I COLPTOC1_OPR_UN_I
ST_OVLOD COLPTOC1_ST_OVLOD
ST_UN_I COLPTOC1_ST_UN_I
ALARM COLPTOC1_ALARM
BLK_CLOSE COLPTOC1_BLK_CLOSE
GUID-CF723E8E-F01F-4A51-BE58-2083B45AC03F V1 EN
CUBPTOC1
BLOCK OPERATE CUBPTOC1_OPERATE
START CUBPTOC1_START
ALARM
GUID-E065DA6C-6BA6-4373-B7D4-3F7A65C73BDD V1 EN
SRCPTOC1
BLOCK ALARM SRCPTOC1_ALARM
RESO_IN OPERATE SRCPTOC1_OPERATE
GUID-00CB236D-D5DF-47C7-B0D4-1542CA5340B7 V1 EN
REV615 69
Application Manual
Section 3 1MRS757946 A
REV615 standard configurations
PHPTOV1
BLOCK OPERATE PHPTOV1_OPERATE
START PHPTOV1_START
PHPTOV2
BLOCK OPERATE PHPTOV2_OPERATE
START PHPTOV2_START
OR
PHPTOV1_OPERATE B1 O PHPTOV_OPERATE
PHPTOV2_OPERATE B2
GUID-1FAE48E8-3B41-4120-8723-3A35E2A95B7B V1 EN
PHPTUV1
SEQRFUF1_FUSEF_U BLOCK OPERATE PHPTUV1_OPERATE
START PHPTUV1_START
PHPTUV2
SEQRFUF1_FUSEF_U BLOCK OPERATE PHPTUV2_OPERATE
START PHPTUV2_START
OR
PHPTUV1_OPERATE B1 O PHPTUV_OPERATE
PHPTUV2_OPERATE B2
GUID-40782C23-9A95-443B-A63D-3FC19DA4DCFD V1 EN
NSPTOV1
SEQRFUF1_FUSEF_U BLOCK OPERATE NSPTOV1_OPERATE
START NSPTOV1_START
GUID-95CB25CE-F1C6-48DA-8F05-9E51C6022D29 V1 EN
PSPTUV1
SEQRFUF1_FUSEF_U BLOCK OPERATE PSPTUV1_OPERATE
START PSPTUV1_START
GUID-A43E5917-B556-413C-AE66-76CEB81EC0BA V1 EN
70 REV615
Application Manual
1MRS757946 A Section 3
REV615 standard configurations
ROVPTOV1
BLOCK OPERATE ROVPTOV1_OPERATE
START ROVPTOV1_START
GUID-DFEF6E25-69DA-4D8B-B25E-B501296A6976 V1 EN
General start and operate from all the functions are connected to pulse timer
TPGAPC1 for setting the minimum pulse length for the outputs. The output from
TPGAPC1 is connected to binary outputs.
OR6 OR6 TPGAPC1
PHLPTOC1_START B1 O B1 O IN1 OUT1 GENERATE_START_PULSE
PHHPTOC1_START B2 B2 IN2 OUT2 GENERATE_OPERATE_PULSE
PHHPTOC2_START B3 B3
PHIPTOC1_START B4 B4
DEFLPDEF2_START B5 B5
DEFLPDEF1_START B6 B6
OR6 OR6
COLPTOC1_ST_UN_I B1 O EFHPTOC1_OPERATE B1 O
CUBPTOC1_START B2 DEFHPDEF1_OPERATE B2
PSPTUV1_START B3 NSPTOC1_OPERATE B3
NSPTOV1_START B4 NSPTOC2_OPERATE B4
ROVPTOV1_START B5 T2PTTR1_OPERATE B5
B6 COLPTOC1_OPR_OVLOD B6
OR6
OR6
COLPTOC1_OPR_UN_I B1 O
PHPTOV1_START B1 O CUBPTOC1_OPERATE B2
PHPTOV2_START B2 ARCSARC1_OPERATE B3
PHPTUV1_START B3 ARCSARC2_OPERATE B4
PHPTUV2_START B4 ARCSARC3_OPERATE B5
B5 B6
B6
OR6
PSPTUV1_OPERATE B1 O
NSPTOV1_OPERATE B2
ROVPTOV1_OPERATE B3
PHPTOV1_OPERATE B4
PHPTOV2_OPERATE B5
B6
OR6
PHPTUV1_OPERATE B1 O
PHPTUV2_OPERATE B2
B3
B4
B5
B6
GUID-B0156B17-37B4-42D9-BB6D-D59D5EEA07B9 V1 EN
The operate signals from the protection functions are connected to the two trip
logics TRPPTRC1 and TRPPTRC2. The output of TRPPTRC1 is available at
binary output X100:PO3. The trip logic functions are provided with lockout and
latching function, event generation and the trip signal duration setting. If the
lockout operation mode is selected, binary input can been assigned to RST_LKOUT
input of both the trip logic to enable external reset with a push button.
Three other trip logics TRPPTRC3...5 are available if the IED is ordered with high
speed binary outputs options.
REV615 71
Application Manual
Section 3 1MRS757946 A
REV615 standard configurations
TRPPTRC1
OR6 OR6
BLOCK TRIP TRPPTRC1_TRIP
PHLPTOC1_OPERATE B1 O B1 O OPERATE CL_LKOUT
PHHPTOC1_OPERATE B2 B2 RST_LKOUT
PHHPTOC2_OPERATE B3 B3
PHIPTOC1_OPERATE B4 B4
DEFLPDEF2_OPERATE B5 NSPTOV1_OPERATE B5
DEFLPDEF1_OPERATE B6 B6
OR6
EFHPTOC1_OPERATE B1 O
DEFHPDEF1_OPERATE B2
NSPTOC1_OPERATE B3
NSPTOC2_OPERATE B4
T2PTTR1_OPERATE B5
COLPTOC1_OPR_OVLOD B6
OR6
COLPTOC1_OPR_UN_I B1 O
SRCPTOC1_OPERATE B2
CUBPTOC1_OPERATE B3
ARCSARC1_OPERATE B4
ARCSARC2_OPERATE B5
ARCSARC3_OPERATE B6
OR6
PSPTUV1_OPERATE B1 O
PHPTOV1_OPERATE B2
PHPTOV2_OPERATE B3
PHPTUV1_OPERATE B4
PHPTUV2_OPERATE B5
ROVPTOV1_OPERATE B6
GUID-DA366F32-487C-4C0D-A8D7-5C9A8E4D2B38 V1 EN
TRPPTRC2
OR6 OR6
BLOCK TRIP TRPPTRC2_TRIP
PHLPTOC1_OPERATE B1 O B1 O OPERATE CL_LKOUT
PHHPTOC1_OPERATE B2 B2 RST_LKOUT
PHHPTOC2_OPERATE B3 B3
PHIPTOC1_OPERATE B4 B4
DEFLPDEF2_OPERATE B5 B5
DEFLPDEF1_OPERATE B6 B6
OR6
EFHPTOC1_OPERATE B1 O
DEFHPDEF1_OPERATE B2
NSPTOC1_OPERATE B3
NSPTOC2_OPERATE B4
T2PTTR1_OPERATE B5
COLPTOC1_OPR_OVLOD B6
OR6
COLPTOC1_OPR_UN_I B1 O
SRCPTOC1_OPERATE B2
CUBPTOC1_OPERATE B3
ARCSARC1_OPERATE B4
ARCSARC2_OPERATE B5
ARCSARC3_OPERATE B6
OR6
PSPTUV1_OPERATE B1 O
PHPTOV1_OPERATE B2
PHPTOV2_OPERATE B3
PHPTUV1_OPERATE B4
PHPTUV2_OPERATE B5
ROVPTOV1_OPERATE B6
OR6
NSPTOV1_OPERATE B1 O
CCBRBRF1_TRRET B2
B3
B4
B5
B6
GUID-242BA8D7-D803-461D-88B3-8D1431CE5982 V1 EN
72 REV615
Application Manual
1MRS757946 A Section 3
REV615 standard configurations
The START and the OPERATE outputs from the protection stages are routed to
trigger the disturbance recorder or, alternatively, only to be recorded by the
disturbance recorder depending on the parameter settings. Additionally, the
selected signals from different functions and the few binary inputs are also
connected to the disturbance recorder.
OR6 RDRE
PHIPTOC1_OPERATE B1 O RDRE1
PHHPTOC1_OPERATE B2
PHHPTOC2_OPERATE B3 PHIPTOC1_START C1 TRIGGERED DISTURB_RECORD_TRIGGERED
PHLPTOC1_OPERATE B4 PHHPTOC1_START C2
B5 PHHPTOC2_START C3
B6 PHLPTOC1_START C4
EFHPTOC1_START C5
DEFHPDEF1_OPERATE C6
DEFLPDEF1_OPERATE C7
DEFLPDEF2_OPERATE C8
OR6 NSPTOC1_START C9
NSPTOC2_START C10
EFHPTOC1_OPERATE B1 O T2PTTR1_START C11
DEFLPDEF1_OPERATE B2 COLPTOC1_ST_OVLOD C12
DEFLPDEF2_OPERATE B3 COLPTOC1_ST_UN_I C13
DEFHPDEF1_OPERATE B4 CUBPTOC1_START C14
B5 PSPTUV1_START C15
B6 NSPTOV1_START C16
PHPTOV1_START C17
PHPTOV2_START C18
PHPTUV1_START C19
PHPTUV2_START C20
OR ROVPTOV1_START C21
C22
NSPTOC1_OPERATE B1 O C23
NSPTOC2_OPERATE B2 C24
T2PTTR1_OPERATE C25
COLPTOC1_OPR_OVLOD C26
COLPTOC1_OPR_UN_I C27
CUBPTOC1_OPERATE C28
OR PSPTUV1_OPERATE C29
NSPTOC_OPERATE C30
PHPTOV1_OPERATE B1 O C31
PHPTOV2_OPERATE B2 C32
ROVPTOV1_OPERATE C33
T2PTTR1_ALARM C34
SRCPTOC1_ALARM C35
COLPTOC1_ALARM C36
OR SRCPTOC1_OPERATE C37
CCBRBRF1_TRRET C38
PHPTUV1_OPERATE B1 O CCBRBRF1_TRBU C39
PHPTUV2_OPERATE B2 CCRDIF1_FAIL C40
SEQRFUF1_FUSEF_3PH C41
SEQRFUF1_FUSEF_U C42
X110_BI4_CB_CLOSED C43
X110_BI3_CB_OPENED C44
OR6 C45
ARCSARC1_OPERATE C46
ARCSARC1_ARC_FLT_DET B1 O ARCSARC2_OPERATE C47
ARCSARC2_ARC_FLT_DET B2 ARCSARC3_OPERATE C48
ARCSARC3_ARC_FLT_DET B3 C49
B4 C50
B5 C51
B6 C52
C53
C54
C55
C56
C57
C58
C59
C60
C61
C62
C63
C64
GUID-BB8813B7-5E22-42CA-A7C1-4F454043B82E V1 EN
CCRDIF1
BLOCK FAIL CCRDIF1_FAIL
ALARM CCRDIF1_ALARM
GUID-0901A287-4CF6-41C5-ABC9-7CFACAF28E93 V1 EN
REV615 73
Application Manual
Section 3 1MRS757946 A
REV615 standard configurations
SEQRFUF1
BLOCK FUSEF_3PH SEQRFUF1_FUSEF_3PH
X110_BI4_CB_CLOSED CB_CLOSED FUSEF_U SEQRFUF1_FUSEF_U
DISCON_OPEN
MINCB_OPEN
GUID-30621F93-B811-4D23-A76B-3363C75366E2 V1 EN
The circuit breaker condition monitoring function SSCBR1 supervises the switch
status based on the connected binary input information and the measured current
levels. SSCBR1 introduces various supervision methods.
SSCBR1
BLOCK TRV_T_OP_ALM SSCBR1_TRV_T_OP_ALM
X110_BI3_CB_OPENED POSOPEN TRV_T_CL_ALM SSCBR1_TRV_T_CL_ALM
X110_BI4_CB_CLOSED POSCLOSE SPR_CHR_ALM SSCBR1_SPR_CHR_ALM
CB_OPEN_COMMAND OPEN_CB_EXE OPR_ALM SSCBR1_OPR_ALM
CB_CLOSE_COMMAND CLOSE_CB_EXE OPR_LO SSCBR1_OPR_LO
X110_BI1_GAS_PRESSURE_ALARM PRES_ALM_IN IPOW_ALM SSCBR1_IPOW_ALM
PRES_LO_IN IPOW_LO SSCBR1_IPOW_LO
CB_SPRING_DISCHARGED SPR_CHR_ST CB_LIFE_ALM SSCBR1_CB_LIFE_ALM
X110_BI2_CB_SPRING_CHARGED SPR_CHR MON_ALM SSCBR1_MON_ALM
RST_IPOW PRES_ALM SSCBR1_PRES_ALM
RST_CB_WEAR PRES_LO SSCBR1_PRES_LO
RST_TRV_T OPENPOS
RST_SPR_T INVALIDPOS
CLOSEPOS
GUID-82B807F1-4925-4F86-B2AD-E9C68E4E2077 V1 EN
OR6
SSCBR1_TRV_T_OP_ALM B1 O
SSCBR1_TRV_T_CL_ALM B2
SSCBR1_SPR_CHR_ALM B3
SSCBR1_OPR_ALM B4
SSCBR1_OPR_LO B5 OR
SSCBR1_IPOW_ALM B6
B1 O SSCBR1_ALARMS
B2
OR6
SSCBR1_IPOW_LO B1 O
SSCBR1_CB_LIFE_ALM B2
SSCBR1_MON_ALM B3
SSCBR1_PRES_ALM B4
SSCBR1_PRES_LO B5
B6
GUID-5A3707E3-871F-4F33-8A76-59974E91E7ED V1 EN
NOT
X110_BI2_CB_SPRING_CHARGED IN OUT CB_SPRING_DISCHARGED
GUID-E93EEC82-5605-4086-B786-EA15DE48AA1B V1 EN
Figure 77: Logic for the start of circuit breaker spring charging
Two separate trip circuit supervision functions are included, TCSSCBR1 for power
output X100:PO3 and TCSSCBR2 for power output X100:PO4. These functions
are blocked by the Master Trip TRPPTRC1 and TRPPTRC2 and the circuit breaker
open signal.
74 REV615
Application Manual
1MRS757946 A Section 3
REV615 standard configurations
TCSSCBR1
TCSSCBR_BLOCKING BLOCK ALARM TCSSCBR1_ALARM
TCSSCBR2
TCSSCBR_BLOCKING BLOCK ALARM TCSSCBR2_ALARM
OR
TCSSCBR1_ALARM B1 O TCSSCBR_ALARM
TCSSCBR2_ALARM B2
GUID-AAF693BE-5F31-4350-8844-CB6B0394FB9A V1 EN
OR6
TRPPTRC1_TRIP B1 O TCSSCBR_BLOCKING
TRPPTRC2_TRIP B2
X110_BI3_CB_OPENED B3
B4
B5
B6
GUID-7251F682-D8AB-4FD2-97B0-C398FA983917 V1 EN
There are two types of disconnector and earthing switch function blocks available.
DCSXSWI1...3 and ESSXSWI1...2 are status only type, and DCXSWI1...2 and
ESXSWI1 are controllable type. By default, the status only blocks are connected in
standard configuration. The disconnector (CB truck) and line side earthing switch
status information are connected to DCSXSWI1 and ESSXSI1.
DCSXSWI1
X110_BI5_CB_TRUCK_IN_TEST POSOPEN OPENPOS
X110_BI6_CB_TRUCK_IN_SERVICE POSCLOSE CLOSEPOS
OKPOS DCSXSWI1_OKPOS
GUID-917DED22-0873-4158-B452-356037D604B5 V1 EN
ESSXSWI1
X110_BI7_ES1_OPENED POSOPEN OPENPOS ESSXSWI1_OPENPOS
X110_BI8_ES1_CLOSED POSCLOSE CLOSEPOS
OKPOS
GUID-E4232E76-8561-47E0-8630-6BF27FA27A04 V1 EN
The circuit breaker closing is enabled when the ENA_CLOSE input is activated.
The input can be activated by the configuration logic, which is a combination of
REV615 75
Application Manual
Section 3 1MRS757946 A
REV615 standard configurations
the disconnector or breaker truck and earth-switch position status, status of the trip
logics, gas pressure alarm and circuit breaker spring charging status.
The OKPOS output from DCSXSWI defines whether the disconnector or breaker
truck is definitely either open (in test position) or close (in service position). This
output, together with the open earth-switch and non-active trip signals, activates
the close-enable signal to the circuit breaker control function block. The open
operation for circuit breaker is always enabled.
The ITL_BYPASS input can be used, for example, to always enable the closing of
the circuit breaker when the circuit breaker truck is in the test position, despite the
interlocking conditions being active when the circuit breaker truck is closed in
service position.
CBXCBR1
X110_BI3_CB_OPENED POSOPEN SELECTED
X110_BI4_CB_CLOSED POSCLOSE EXE_OP CBXCBR1_EXE_OP
TRUE ENA_OPEN EXE_CL CBXCBR1_EXE_CL
CBXCBR1_ENA_CLOSE ENA_CLOSE OPENPOS
FALSE BLK_OPEN CLOSEPOS
CBXCBR1_BLK_CLOSE BLK_CLOSE OKPOS
CBXBCR1_AU_OPEN AU_OPEN OPEN_ENAD
CBXCBR1_AU_CLOSE AU_CLOSE CLOSE_ENAD
ITL_BYPASS
GUID-662D3A55-AC01-4504-B854-B59C7E96A95B V1 EN
OR
CBXCBR1_EXE_CL B1 O CB_CLOSE_COMMAND
B2
GUID-94855B51-1607-4D62-B689-F8DE655DAD57 V1 EN
Figure 83: Circuit breaker control logic: Signals for closing coil of circuit breaker
OR6
TRPPTRC1_TRIP B1 O CB_OPEN_COMMAND
CBXCBR1_EXE_OP B2
B3
B4
B5
B6
GUID-977C3B88-70DB-4FBD-802A-88A08B6A1E08 V1 EN
Figure 84: Circuit breaker control logic: Signals for opening coil of circuit breaker
76 REV615
Application Manual
1MRS757946 A Section 3
REV615 standard configurations
AND6
DCSXSWI1_OKPOS B1 O CBXCBR1_ENA_CLOSE
X110_BI2_CB_SPRING_CHARGED B2
ESSXSWI1_OPENPOS B3
B4
B5
NOT B6
X110_BI1_GAS_PRESSURE_ALARM IN OUT
NOT
TRPPTRC1_TRIP IN OUT
NOT
TRPPTRC2_TRIP IN OUT
GUID-13A2F026-96B7-4F6A-9FCD-9334B5E4A576 V1 EN
OR6
COLPTOC1_BLK_CLOSE B1 O CBXCBR1_BLK_CLOSE
T2PTTR1_BLK_CLOSE B2
B3
B4
B5
B6
GUID-DB3717DF-6999-49B1-8DF7-FF9CDED1FF5B V1 EN
The configuration includes logic for generating circuit breaker external closing and
opening command with IED in local or remote mode.
Check the logic for the external circuit breaker closing command
and modify it according to the application.
AND
CONTROL_LOCAL B1 O
FALSE B2
OR
B1 O CBXCBR1_AU_CLOSE
B2
AND
CONTROL_REMOTE B1 O
FALSE B2
GUID-3893E4E5-21BD-4A79-AB47-865162E9ECEF V1 EN
AND
CONTROL_LOCAL B1 O
FALSE B2
OR
B1 O CBXBCR1_AU_OPEN
B2
AND
CONTROL_REMOTE B1 O
FALSE B2
GUID-E4861647-EF79-432A-B3B7-344BE9086611 V1 EN
REV615 77
Application Manual
Section 3 1MRS757946 A
REV615 standard configurations
The phase current inputs to the IED are measured by the three-phase current
measurement function CMMXU1. The current input is connected to the X120 card
in the back panel. The sequence current measurement CSMSQI1 measures the
sequence current and the residual current measurement RESCMMXU1 measures
the residual current.
The three-phase capacitor phase voltage inputs to the IED are measured by voltage
measurement function VMMXU1. The voltage input is connected to the X130 card
in the back panel. The sequence voltage measurement VSMSQI1 measures the
sequence voltage and the residual voltage measurement RESVMMXU1 measures
the residual voltage. It is also possible to measure capacitor unbalance voltage by
the residual voltage measurement RESVMMXU2.
The measurements can be seen in the LHMI and they are available under the
measurement option in the menu selection. Based on the settings, function blocks
can generate low alarm or warning and high alarm or warning signals for the
measured current values.
The frequency measurement FMMXU1 of the power system and the three-phase
power measurement PEMMXU1 are available. The load profile function
LDPMSTA1 is included in the measurements sheet. LDPMSTA1 offers the ability
to observe the loading history of the corresponding feeder.
The power quality function CMHAI1 and VMHAI1 can be used to measure the
harmonic contents of the phase current and phase voltages. The voltage variation
that is sage and swells can be measured by power quality function PHQVVR1. By
default these power quality functions are not included in the configuration.
Depending on the application, the needed logic connections can be made by
PCM600.
CMMXU1
BLOCK HIGH_ALARM
HIGH_WARN
LOW_WARN
LOW_ALARM
GUID-7D33AD69-87B7-4875-B6C5-BCD11765D01E V1 EN
CSMSQI1
GUID-2E927E0C-A69B-4BAF-AE6C-F4C36A364C7A V1 EN
78 REV615
Application Manual
1MRS757946 A Section 3
REV615 standard configurations
RESCMMXU1
BLOCK HIGH_ALARM
HIGH_WARN
GUID-DE551B8B-EB01-4A43-A1E6-7F71A3582127 V1 EN
VMMXU1
BLOCK HIGH_ALARM
HIGH_WARN
LOW_WARN
LOW_ALARM
GUID-DC4AF28A-8EDC-4C11-BE1F-FA53B6AAF32C V1 EN
VSMSQI1
GUID-65195485-13A8-499C-A42B-EB13420C3572 V1 EN
RESVMMXU1
BLOCK HIGH_ALARM
HIGH_WARN
GUID-EC2F4C74-8D81-49C9-ACEC-2AA8A2FB2A08 V1 EN
RESVMMXU2
BLOCK HIGH_ALARM
HIGH_WARN
GUID-5064DB91-B408-4F8F-8663-3CAAE80AB1A1 V1 EN
FMMXU1
GUID-54CC5EF8-58FF-4BE0-B949-67F9EBF71866 V1 EN
PEMMXU1
RSTACM
GUID-CC1BD7C9-AE56-43AF-B5D7-CDAD75F66C3A V1 EN
FLTMSTA1
BLOCK
CB_CLRD
GUID-4D1D82CD-D056-48F0-8256-7DEE5B9EB508 V1 EN
REV615 79
Application Manual
Section 3 1MRS757946 A
REV615 standard configurations
LDPMSTA1
RSTMEM MEM_WARN
MEM_ALARM
GUID-E8309685-F8F7-4A24-B7C7-B4013CAAF73C V1 EN
X110 (BIO).X110-Input 1 OR
B1 O X110_BI1_GAS_PRESSURE_ALARM
B2
X110 (BIO-H).X110-Input 1
X110 (BIO).X110-Input 2 OR
B1 O X110_BI2_CB_SPRING_CHARGED
B2
X110 (BIO-H).X110-Input 2
X110 (BIO).X110-Input 3 OR
B1 O X110_BI3_CB_OPENED
B2
X110 (BIO-H).X110-Input 3
X110 (BIO).X110-Input 4 OR
B1 O X110_BI4_CB_CLOSED
B2
X110 (BIO-H).X110-Input 4
X110 (BIO).X110-Input 5 OR
B1 O X110_BI5_CB_TRUCK_IN_TEST
B2
X110 (BIO-H).X110-Input 5
X110 (BIO).X110-Input 6 OR
B1 O X110_BI6_CB_TRUCK_IN_SERVICE
B2
X110 (BIO-H).X110-Input 6
X110 (BIO).X110-Input 7 OR
B1 O X110_BI7_ES1_OPENED
B2
X110 (BIO-H).X110-Input 7
X110 (BIO).X110-Input 8 OR
B1 O X110_BI8_ES1_CLOSED
B2
X110 (BIO-H).X110-Input 8
GUID-6882F0CC-DED6-478D-A3D1-1212DEBF94EE V1 EN
80 REV615
Application Manual
1MRS757946 A Section 3
REV615 standard configurations
OC_OPERATE_PULSE
X110 (BIO).X110-SO1
TRPPTRC3_TRIP
X110 (BIO-H).X110-HSO1
EF_OPERATE_PULSE
X110 (BIO).X110-SO2
TRPPTRC4_TRIP
X110 (BIO-H).X110-HSO2
CAPACITOR_PROT_OPERATE_PULSE
X110 (BIO).X110-SO3
TRPPTRC5_TRIP
X110 (BIO-H).X110-HSO3
VOLT_PROT_OPERATE_PULSE
X110 (BIO).X110-SO4
GUID-74426DDE-E873-4BDC-BBC2-7C90353DFE8A V1 EN
CB_CLOSE_COMMAND
X100 (PSM).X100-PO1
CCBRBRF1_TRBU
X100 (PSM).X100-PO2
GENERATE_START_PULSE
X100 (PSM).X100-SO1
GENERATE_OPERATE_PULSE
X100 (PSM).X100-SO2
CB_OPEN_COMMAND
X100 (PSM).X100-PO3
RECONNECTION_ENABLE
X100 (PSM).X100-PO4
GUID-D99E8E01-20C1-4984-B2E7-48EE3832A767 V1 EN
REV615 81
Application Manual
Section 3 1MRS757946 A
REV615 standard configurations
LED1
OK
OC_OPERATE ALARM
RESET
LED2
OR
OK
EF_OPERATE B1 O ALARM
ROVPTOV1_OPERATE B2 RESET
LED3
OR
OK
T2PTTR1_OPERATE B1 O ALARM
COLPTOC1_OPR_OVLOD B2 RESET
LED4
OK
COLPTOC1_ALARM ALARM
RESET
LED5
OR
OK
NSPTOC_OPERATE B1 O ALARM
CUBPTOC1_OPERATE B2 RESET
GUID-80779A4D-5275-48DE-BE11-1F1018C9C1AC V1 EN
LED6
OR6
OK
PSPTUV1_OPERATE B1 O ALARM
NSPTOV1_OPERATE B2 RESET
PHPTOV_OPERATE B3
PHPTUV_OPERATE B4
B5
B6
LED7
OR
OK
SRCPTOC1_OPERATE B1 O ALARM
COLPTOC1_OPR_UN_I B2 RESET
LED8
OK
CCBRBRF1_TRBU ALARM
RESET
LED9
OK
DISTURB_RECORD_TRIGGERED ALARM
RESET
LED10
OR6
OK
CCRDIF1_ALARM B1 O ALARM
TCSSCBR_ALARM B2 RESET
SSCBR1_ALARMS B3
SEQRFUF1_FUSEF_3PH B4
SEQRFUF1_FUSEF_U B5
B6
LED11
OK
ARC_OPERATE ALARM
RESET
GUID-507BAA3A-B10F-4662-B2D1-689FD2166B8B V1 EN
82 REV615
Application Manual
1MRS757946 A Section 3
REV615 standard configurations
OR
EF_OPERATE B1 O
ROVPTOV1_OPERATE B2
GUID-0B01B564-9EDE-4321-AA9A-51EA6FED31E1 V1 EN
Figure 103: Timer logic for overcurrent and earth-fault operate pulse
OR6 TPGAPC3
CUBPTOC1_OPERATE B1 O IN1 OUT1 CAPACITOR_PROT_OPERATE_PULSE
SRCPTOC1_OPERATE B2 IN2 OUT2 VOLT_PROT_OPERATE_PULSE
COLPTOC1_OPR_OVLOD B3
COLPTOC1_OPR_UN_I B4
B5
B6
OR6
PSPTUV1_OPERATE B1 O
NSPTOV1_OPERATE B2
PHPTOV_OPERATE B3
PHPTUV_OPERATE B4
B5
B6
GUID-1A9D5CB7-C895-43E6-BF69-2A7D21DF6645 V1 EN
Figure 104: Timer logic for capacitor protection and voltage protection operate
pulse
NOT
CBXCBR1_BLK_CLOSE IN OUT RECONNECTION_ENABLE
GUID-930F13E7-4F13-4AB3-AE51-C3AE4FC0D2BD V1 EN
REV615 83
Application Manual
84
1MRS757946 A Section 4
Requirements for measurement transformers
The selection of a CT depends not only on the CT specifications but also on the
network fault current magnitude, desired protection objectives, and the actual CT
burden. The protection settings of the IED should be defined in accordance with
the CT performance as well as other factors.
The rated accuracy limit factor (Fn) is the ratio of the rated accuracy limit primary
current to the rated primary current. For example, a protective current transformer
of type 5P10 has the accuracy class 5P and the accuracy limit factor 10. For
protective current transformers, the accuracy class is designed by the highest
permissible percentage composite error at the rated accuracy limit primary current
prescribed for the accuracy class concerned, followed by the letter "P" (meaning
protection).
Table 21: Limits of errors according to IEC 60044-1 for protective current transformers
Accuracy class Current error at Phase displacement at rated primary Composite error at
rated primary current rated accuracy limit
current (%) minutes centiradians primary current (%)
5P ±1 ±60 ±1.8 5
10P ±3 - - 10
The accuracy classes 5P and 10P are both suitable for non-directional overcurrent
protection. The 5P class provides a better accuracy. This should be noted also if
there are accuracy requirements for the metering functions (current metering,
power metering, and so on) of the IED.
REV615 85
Application Manual
Section 4 1MRS757946 A
Requirements for measurement transformers
The CT accuracy primary limit current describes the highest fault current
magnitude at which the CT fulfils the specified accuracy. Beyond this level, the
secondary current of the CT is distorted and it might have severe effects on the
performance of the protection IED.
In practise, the actual accuracy limit factor (Fa) differs from the rated accuracy
limit factor (Fn) and is proportional to the ratio of the rated CT burden and the
actual CT burden.
Sin + Sn
Fa ≈ Fn ×
Sin + S
A071141 V1 EN
The nominal primary current I1n should be chosen in such a way that the thermal
and dynamic strength of the current measuring input of the IED is not exceeded.
This is always fulfilled when
The saturation of the CT protects the measuring circuit and the current input of the
IED. For that reason, in practice, even a few times smaller nominal primary current
can be used than given by the formula.
86 REV615
Application Manual
1MRS757946 A Section 4
Requirements for measurement transformers
The factor 0.7 takes into account the protection IED inaccuracy, current
transformer errors, and imperfections of the short circuit calculations.
The adequate performance of the CT should be checked when the setting of the
high set stage overcurrent protection is defined. The operate time delay caused by
the CT saturation is typically small enough when the overcurrent setting is
noticeably lower than Fa.
When defining the setting values for the low set stages, the saturation of the CT
does not need to be taken into account and the start current setting is simply
according to the formula.
With definite time mode of operation, the saturation of CT may cause a delay that
is as long as the time the constant of the DC component of the fault current, when
the current is only slightly higher than the starting current. This depends on the
accuracy limit factor of the CT, on the remanence flux of the core of the CT, and
on the operate time setting.
With inverse time mode of operation, the delay should always be considered as
being as long as the time constant of the DC component.
With inverse time mode of operation and when the high-set stages are not used, the
AC component of the fault current should not saturate the CT less than 20 times the
starting current. Otherwise, the inverse operation time can be further prolonged.
Therefore, the accuracy limit factor Fa should be chosen using the formula:
The Current start value is the primary start current setting of the IED.
The following figure describes a typical medium voltage feeder. The protection is
implemented as three-stage definite time non-directional overcurrent protection.
REV615 87
Application Manual
Section 4 1MRS757946 A
Requirements for measurement transformers
A071142 V1 EN
The maximum three-phase fault current is 41.7 kA and the minimum three-phase
short circuit current is 22.8 kA. The actual accuracy limit factor of the CT is
calculated to be 59.
The start current setting for low-set stage (3I>) is selected to be about twice the
nominal current of the cable. The operate time is selected so that it is selective with
the next IED (not visible in the figure above). The settings for the high-set stage
and instantaneous stage are defined also so that grading is ensured with the
downstream protection. In addition, the start current settings have to be defined so
that the IED operates with the minimum fault current and it does not operate with
the maximum load current. The settings for all three stages are as in the figure above.
For the application point of view, the suitable setting for instantaneous stage (I>>>)
in this example is 3 500 A (5.83 x I2n). For the CT characteristics point of view, the
criteria given by the current transformer selection formula is fulfilled and also the
IED setting is considerably below the Fa. In this application, the CT rated burden
could have been selected much lower than 10 VA for economical reasons.
88 REV615
Application Manual
1MRS757946 A Section 5
IED physical connections
5.1 Inputs
REV615 89
Application Manual
Section 5 1MRS757946 A
IED physical connections
90 REV615
Application Manual
1MRS757946 A Section 5
IED physical connections
Terminal Description
X110-12 BI7, -
X110-12 BI8, -
X110-13 BI8, +
Table 29: Optional binary input terminals X130-1...9 with BIO0006 module
Terminal Description
X130-1 BI1, +
X130-2 BI1, -
X130-2 BI2, -
X130-3 BI2, +
X130-4 BI3, +
X130-5 BI3, -
X130-5 BI4, -
X130-6 BI4, +
X130-7 BI5, +
X130-8 BI5, -
X130-8 BI6, -
X130-9 BI6, +
REV615 91
Application Manual
Section 5 1MRS757946 A
IED physical connections
Table 30: Optional binary input terminals X130-1...8 with AIM0006 module
Terminal Description
X130-1 BI1, +
X130-2 BI1, -
X130-3 BI2, +
X130-4 BI2, -
X130-5 BI3, +
X130-6 BI3, -
X130-7 BI4, +
X130-8 BI4, -
The IED is provided with connection sockets X13, X14 and X15
only if the optional communication module with light sensor inputs
has been installed. If the arc protection option is selected when
ordering an IED, the light sensor inputs are included in the
communication module.
92 REV615
Application Manual
1MRS757946 A Section 5
IED physical connections
Terminal Description
X130-4 mA2 (AI2), -
X130-5 RTD1 (AI3), +
X130-6 RTD1 (AI3), -
X130-7 RTD2 (AI4), +
X130-8 RTD2 (AI4), -
X130-9 RTD3 (AI5), +
X130-10 RTD3 (AI5), -
X130-11 Common1)
X130-12 Common2)
X130-13 RTD4 (AI6), +
X130-14 RTD4 (AI6), -
X130-15 RTD5 (AI7), +
X130-16 RTD5 (AI7), -
X130-17 RTD6 (AI8), +
X130-18 RTD6 (AI8), -
5.2 Outputs
REV615 93
Application Manual
Section 5 1MRS757946 A
IED physical connections
94 REV615
Application Manual
1MRS757946 A Section 5
IED physical connections
Output contacts of slot X130 are available in the optional BIO module (BIO0006).
5.2.3 IRF
The IRF contact functions as an output contact for the self-supervision system of
the protection IED. Under normal operating conditions, the IED is energized and
the contact is closed (X100/3-5). When a fault is detected by the self-supervision
system or the auxiliary voltage is disconnected, the output contact drops off and the
contact closes (X100/3-4).
REV615 95
Application Manual
96
1MRS757946 A Section 6
Glossary
Section 6 Glossary
REV615 97
Application Manual
Section 6 1MRS757946 A
Glossary
98 REV615
Application Manual
1MRS757946 A Section 6
Glossary
REV615 99
Application Manual
100
101
Contact us
ABB Limited
Distribution Automation
Maneja
Vadodara 390013, India
Phone +91 265 2604032
Fax +91 265 2638922
www.abb.com/substationautomation