You are on page 1of 4

Instrumentation Cable EN 50288-7

Zero Halogen, Flame Retardant, Sunlight Resistant 90 °C / 300 V


Single & Multi-Pair, XLPE-Insulation, Collective Screen, LSZH-Sheath

ICON SAFE 20100 M3 OS


Application
For transmission of analogue and digital signals in instrument and control systems; where people are potentially endangered in case of fire; allowed
for use in zone 1 and zone 2 group II classified areas (IEC 60079-14); not allowed for direct connection to low impedance source, e.g. the public mains
electricity. (Please note possible additional or special installation requirements of IEC 60079-14).
Recommended for indoor and outdoor installation, on racks, trays, in conduits, in dry and wet locations; not for direct burial. Indoor installations are
allowed in areas, where the construction products regulation (CPR) acc. to EN 50575 of fire class is not required. (Please note the relevant legal / local
installation requirements)
Construction
Conductor 2 2
plain annealed copper wire, stranded, size: 0,5 mm , 0,75 mm , 1,0 mm ,
2

................................................. 1,3 mm2, 1,5 mm2, 2,5 mm2


Insulation cross-linked polyethylene XLPE
.................................................
Colour black / white, continuously numbered on white core (1, 2, 3..) for multi-ele-
................................................. ment
Wrapping at least 1 layer of plastic tape
.................................................
Collective aluminium polyester foil in contact with stranded tinned copper drain wire
.................................................
Outer low smoke, zero halogen, flame retardant compound LSZH, black, blue for
................................................. intrinsically safe systems
Cable LEONI KERPEN ICON SAFE Type Code Size 300V LSZH EN 50288-7
................................................. Production Lot Code Year Length Marking
Technical data Abbreviations
Flame propagation Temperature range ICON SAFE
- Test on single cable IEC 60332-1-2 -30°C up to +90°C OS overall screen
- Test on bunched cables IEC 60332-3-24 (Cat. C) (during operation)
-5°C up to +50°C
Smoke density IEC 61034-2 (L.T. > 60 %)
(during installation)
Limiting Oxygen Index (LOI) ASTM D 2863 (min. 30 %)
Minimum bending radius
Flammability temperature (FT) ISO 4589-3 ann. A (min. +250 ° C)
7,5 x cable diameter
Amount of halogen acid gas IEC 60754-1 (0%)
Degree of acidity of gases IEC 60754-2 (pH ≥ 4.3, C ≤ 10µS/mm)
Oil resistance ICEA S-73-532*
Sunlight resistance UL 1581 section 1200

Technical datasheet © LEONI Kerpen GmbH · Phone: +49 24 02 17 1 · www.leoni-process-industry.com/en/


Print date: 28.03.2020 Transfer to third parties only by authority of LEONI Kerpen GmbH Creator: TF/MY
Date of version: 03.02.2020 Printing errors excepted. Subject to alterations. Image serves as an example. Page: 1/4
For cable disposal please note the relevant local legal disposal requirements.
7E03010000_EN_50288-7_300_ICON_SAFE_20100_M3_OS_black_stranded_Pair_en.pdf
Instrumentation Cable EN 50288-7

Zero Halogen, Flame Retardant, Sunlight Resistant 90 °C / 300 V


Single & Multi-Pair, XLPE-Insulation, Collective Screen, LSZH-Sheath

ICON SAFE 20100 M3 OS


Electrical Properties at 20 °C
Conductor nom. mm
2 0,5 0,75 1,0 1,3 1,5 2,5
cross-section
Conductor max. Ω/km 36,7 25,0 18,5 14,2 12,3 7,6
resistance
Insulation min. MΩ x km 5000
resistance
Mutual max. nF/km 150 150 150 150 150 150
capacitance
Inductance max. mH/km 1
Capacitance max. pF/500 m 500
unbalance
L/R ratio max. µH/Ω 25 40 60
Test voltage V 1500
Urms (core :
core)
Test voltage V 1500
Urms (core :
screen)
Operating V 300
voltage
*(Test temperature + 60 °C; duration 4 h. Retention: min. 60 % of tensile strength/min. 60 % of elongation)

Technical datasheet © LEONI Kerpen GmbH · Phone: +49 24 02 17 1 · www.leoni-process-industry.com/en/


Print date: 28.03.2020 Transfer to third parties only by authority of LEONI Kerpen GmbH Creator: TF/MY
Date of version: 03.02.2020 Printing errors excepted. Subject to alterations. Image serves as an example. Page: 2/4
For cable disposal please note the relevant local legal disposal requirements.
7E03010000_EN_50288-7_300_ICON_SAFE_20100_M3_OS_black_stranded_Pair_en.pdf
Instrumentation Cable EN 50288-7

Zero Halogen, Flame Retardant, Sunlight Resistant 90 °C / 300 V


Single & Multi-Pair, XLPE-Insulation, Collective Screen, LSZH-Sheath

ICON SAFE 20100 M3 OS


Geometrical data
No. of elements RT of insulation RT of outer sheath Outer dia. Weight Part No.
min. nom. approx. approx. Colour
mm mm mm kg/km black
2
0,5 mm /7
1 0,26 0,8 5,0 33 LKX7076E0010000
2 0,26 0,9 7,4 61 LKX7076E0040000
4 0,26 0,9 8,5 87 LKX7076E0070000
5 0,26 1,0 9,4 109 LKX7076E1510000
6 0,26 1,0 10,2 128 LKX7076E0100000
8 0,26 1,0 10,8 150 LKX7076E0130000
10 0,26 1,1 12,4 188 LKX7076E0160000
12 0,26 1,1 13,0 217 LKX7076E0190000
16 0,26 1,1 14,6 278 LKX7076E0220000
20 0,26 1,2 16,2 340 LKX7076E0250000
24 0,26 1,2 17,5 394 LKX7076E0280000
2
0,75 mm /7
1 0,26 0,8 5,4 41 LKX7076E0310000
2 0,26 0,9 8,1 74 LKX7076E0340000
4 0,26 1,0 9,6 113 LKX7076E0370000
5 0,26 1,0 10,4 137 LKX7076E1540000
6 0,26 1,0 11,3 161 LKX7076E0400000
8 0,28 1,1 12,2 199 LKX7076E0430000
10 0,26 1,1 13,8 242 LKX7076E0460000
12 0,26 1,1 14,4 280 LKX7076E0490000
16 0,28 1,2 16,5 365 LKX7076E0520000
20 0,26 1,3 18,3 448 LKX7076E0550000
24 0,28 1,3 19,8 521 LKX7076E0580000
2
1,0 mm /7
1 0,26 0,9 6,1 50 LKX7076E0610000
2 0,26 0,9 8,9 90 LKX7076E0640000
4 0,26 1,0 10,5 141 LKX7076E0670000
5 0,26 1,0 11,5 173 LKX7076E1570000
6 0,26 1,0 12,4 199 LKX7076E0700000
8 0,26 1,1 13,4 249 LKX7076E0730000
10 0,26 1,1 15,2 309 LKX7076E0760000
12 0,26 1,2 16,1 358 LKX7076E0790000
16 0,26 1,2 18,2 474 LKX7076E0820000
20 0,26 1,3 20,3 584 LKX7076E0850000
24 0,26 1,4 22,1 688 LKX7076E0880000
2
1,3 mm /7
1 0,35 0,9 6,6 59 LKX7076E0910000
2 0,35 1,0 10,0 114 LKX7076E0940000
4 0,35 1,0 11,6 174 LKX7076E0970000
5 0,35 1,1 12,9 221 LKX7076E1600000
6 0,35 1,1 14,1 261 LKX7076E1000000

Technical datasheet © LEONI Kerpen GmbH · Phone: +49 24 02 17 1 · www.leoni-process-industry.com/en/


Print date: 28.03.2020 Transfer to third parties only by authority of LEONI Kerpen GmbH Creator: TF/MY
Date of version: 03.02.2020 Printing errors excepted. Subject to alterations. Image serves as an example. Page: 3/4
For cable disposal please note the relevant local legal disposal requirements.
7E03010000_EN_50288-7_300_ICON_SAFE_20100_M3_OS_black_stranded_Pair_en.pdf
Instrumentation Cable EN 50288-7

Zero Halogen, Flame Retardant, Sunlight Resistant 90 °C / 300 V


Single & Multi-Pair, XLPE-Insulation, Collective Screen, LSZH-Sheath

ICON SAFE 20100 M3 OS


Geometrical data
No. of elements RT of insulation RT of outer sheath Outer dia. Weight Part No.
min. nom. approx. approx. Colour
mm mm mm kg/km black
8 0,35 1,2 15,2 322 LKX7076E1030000
10 0,35 1,2 17,2 397 LKX7076E1060000
12 0,35 1,3 18,2 468 LKX7076E1090000
16 0,35 1,3 20,6 607 LKX7076E1120000
20 0,35 1,4 22,9 743 LKX7076E1150000
24 0,35 1,5 25,0 881 LKX7076E1180000
2
1,5 mm /7
1 0,35 0,9 6,9 64 LKX7076E1210000
2 0,35 1,0 10,4 122 LKX7076E1240000
4 0,35 1,1 12,3 200 LKX7076E1270000
5 0,35 1,1 13,5 246 LKX7076E1630000
6 0,35 1,1 14,7 291 LKX7076E1300000
8 0,35 1,2 15,9 361 LKX7076E1330000
10 0,35 1,3 18,2 436 LKX7076E1360000
12 0,35 1,3 19,0 527 LKX7076E1390000
16 0,35 1,4 21,7 697 LKX7076E1420000
20 0,35 1,5 24,1 822 LKX7076E1450000
24 0,35 1,5 26,1 966 LKX7076E1480000
2
2,5 mm /7
1 0,44 0,9 8,1 94 LKX7076E9550000
RT = Radial Thickness

Technical datasheet © LEONI Kerpen GmbH · Phone: +49 24 02 17 1 · www.leoni-process-industry.com/en/


Print date: 28.03.2020 Transfer to third parties only by authority of LEONI Kerpen GmbH Creator: TF/MY
Date of version: 03.02.2020 Printing errors excepted. Subject to alterations. Image serves as an example. Page: 4/4
For cable disposal please note the relevant local legal disposal requirements.
7E03010000_EN_50288-7_300_ICON_SAFE_20100_M3_OS_black_stranded_Pair_en.pdf