You are on page 1of 6

Distance Protection of lines connected to Doubly

Fed Induction Generator based wind farms


Vaishnavi Phadke, Swarada Pathradkar, Akshata Rajput Snehal Unde, Sanjay Dambhare
B.Tech.,Electrical Engineering Department Electrical Engineering Department
College of Engineering Pune College of Engineering Pune
Pune, India 411005. Pune, India 411005.
Email: phadkeva12.elec@coep.ac.in Email: svu.elec@coep.ac.in

Abstract—Penetration of wind farms in High Voltage trans- Another issue can be high presence of harmonics. Nowadays,
mission lines is increasing day by day. Hence the necessity for WPPs are expected to stay connected to the system and
protection of lines connected to the wind farms is also increasing. contribute to system stability even on occurrence of fault [5].
This paper proposes protection scheme for the transmission lines
connected to Doubly Fed Induction Generator based wind farm. Also, undesired operation of distance protection will occur
Generally, distance protection scheme is applied to the trans- as the distance relay will react improperly and sense faults at
mission line protection. The Doubly Fed Induction Generator is zones other than the desired ones. Addtionally, the selectivity
represented as Norton equivalent model. Owing to the variations of the distance relays will be disturbed as incorrect relays
in the frequency of voltages and currents on occurrence of fault will react while those related to the corresponding zone will
on the transmission line, the impedance as seen by the relay is
incorrect. Issues related to such mal operation of the Doubly not issue a trip signal.
Fed Induction Generator during various fault conditions are
analyzed and a solution is proposed. The proposed scheme gives An efficient protection scheme should be designed for
modifications in conventional pilot protection scheme and it is ensuring proper connection with the grid so that the system
validated using PSCAD/EMTDC simulation. Encouraging results remains stable. Hence, we have developed an algorithm for
have been obtained with the new proposed scheme.
Index Terms—Doubly fed Induction Generator (DFIG); Wind distance protection of lines connected to the wind farms
Farm (WF); distance relay; pilot protection; Nortan Equivalent of which will take above factors into consideration and provide
DFIG; Wind Power Plant(WPP). protection accordingly [6], [7]. The focus of this paper is
on the wind turbines which use DFIG, since they comprise
I. I NTRODUCTION the largest installed base of wind turbines and also have

W ITH the amount of fossil fuels depleting day by


day, it is necessary to focus on harnessing energy
by renewable sources. Wind power is extracted from air
more noteworthy effects on the bulk power system than other
machines. A detailed explanation of the proposed solution
taking care of some of the issues, is given along with details of
flow using wind turbines to produce electrical power. As of implementation in PSCAD/EMTDC. The fundamental purpose
31 March 2016, according to Ministry of Non Renewable of this model is to study the interaction between the wind
Energy, the connected capacity of wind power in India was turbine and the power system and its effect on existing distance
26,743 MW. A challenge faced by power system developers protection scheme. Section II discusses about mathematical
and implementers, is the grid integration of large amounts of modeling of current source equivalent of DFIG. Section III
wind power [1]. To limit the impacts of large Wind Power deals with the connection of this model to the grid, and its
Plants (WPP) on system stability, reliable relay algorithms effects for various fault cases, followed by proposed POTT
are essential. These algorithms are essential for complete scheme in section IV. The simulations, analysis and the results
protection of transmission line along with WPP [2]. obtained are described in section V.
The conventional distance protection schemes, for type III
II. MODELING OF SYSTEM
(Wind Turbine Generator) WTG, i.e., DFIG based WPPs face
various challenges [3],[4]. The voltage sag during starting A. Mathematical Model of DFIG
caused due to high starting current and high induced voltages The details of mathematical modeling for the Norton source
or currents in the rotor circuit might damage it [1]. Also, representation of DFIG is studied [8]. The Norton’s equivalent
various faults in the power system, which are far away from of the DFIG model is developed in which three phase currents
the location of the turbine, can also cause a voltage dip at the as produced by DFIG are injected into the grid. The indepen-
connection point of the wind turbine. Then the relay may issue dent control of real and reactive power in DFIG control system
a trip signal which is not in its primary zone of protection. facilitates the use of a regulated current source in the dynamic
model to represent the induction generator and power electron-
This work has been supported by Center of Excellence in Smart Renewable
Energy Systems (CoE - SRES), Technical Education Quality Improvement ics. The use of single-mass model to represent various rotating
Programme - II (TEQIP - II) at COE, Pune, India parts of WTG further simplifies the mechanical modeling of

978-1-4673-6680-4/16/$31.00 2016
c IEEE
the system. The stator flux oriented vector control method is III. DFIG CONNECTION TO GRID
used for this dynamic modeling of DFIG. The three phase The total integrated system obtained by connecting this
voltages and currents are transformed into their respective dq0 DFIG current source represented circuit along with the dis-
components. The d-axis of the reference frame is oriented tance protection scheme is as shown in Fig. 2.
to align it with the vector of the stator magnetic field. The
equations for real and reactive power in terms of q- and d-
axis are-
3
Ps = (Vqs Iqs ) (1)
2 B1 B2
3
Qs = − (Vqs Ids ) (2)
2
The current source emulates the working of an actual
DFIG wind turbine in controlling real and reactive power DFIG Transformer Transmission Line Grid
independently at the point of connection.
B. Modeling of Norton Equivalent
The DFIG WPP model [8], [9] developed is divided into
four subsystems to emulate all the functions of DFIG. These
are as follows- Fig. 2: SLD of the system implemented
• Generator-Converter Subsystem - This model is the point
of connection to the external network through which Bus1 is the DFIG connected bus and grid is connected
three phase current is injected in response to the control to Bus2. Grid is represented by a constant voltage source. The
commands from converter control subsystem. Terminal voltages at Bus1 are measured and given as feedback to the
voltages at the point of connection to the system are used DFIG control circuit so as to obtain the currents to be injected.
as inputs to emulate the currents as per DFIG behavior There are two breakers viz. B1 and B2 which are connected at
• Converter Control Subsystem - This subsystem consists DFIG side and Grid side respectively. The transmission line is
of real and reactive power control. Independent control simulated by using distributed parameter model. All 11 faults
is possible as shown in eqns (1) and (2) respectively. can be created at the line and at different fault locations. The
• Wind Turbine Subsystem - It is represented as a single relays which operate breakers B1 and B2 are conventional
mass model. Mechanical input power and shaft speed (ω) distance relays.
is determined in this block using pitch angle (θ). The conventional Protection Scheme uses mho relays,
• Pitch Control Subsystem - The desired blade pitch angle which measures the line impedance. The voltage and current
is determined from the angular speed of the rotor and the are estimated by taking its Fast Fourier Transform (FFT). The
real power. Typical Pitch angle curves can be used as an impedance seen by the relay is evaluated and compared with
input to this subsystem. Pitch Angle is maintained zero the set value of the relay logic. If the impedance seen is less
for below rated speed opeartions and has a fixed value than the set value a trip signal is issued. The system consists of
for wind speed above rated speed. 6 measurement units for detection of all 11 faults. The phase
The overall DFIG model with all the above subsystems and ground faults are detected and trip signal is given to the
interlinked is shown in the Fig. 1. breakers.
IV. PROPOSED ALGORITHM
A distance relay is not able to provide non delayed tripping
over 100 percent of the line length unless it is linked with the
relay on the other end of the line through a communication
channel. The key feature of this channel that distinguishes
distance relays as a preferred choice for HV grids is its very
low bandwidth requirement. A variety of pilot schemes are
already deployed to reach fast and selective distance relaying.
Among them, POTT (Permissive Overreach Transfer Trip) is
a relatively inexpensive, yet competent scheme, and is widely
practiced in industrial applications.
The conventional distance scheme fails to operate accu-
rately for the lines connected to IG-based WFs during balanced
short-circuits, due to incorrect impedance measurement by the
Fig. 1: Schematic diagram for Current Source equivalent of DFIG distance relay at the WF substation. A modified POTT scheme
[5] [6] is developed to tackle this problem.
For this modified POTT scheme, the relay located at the V. CASE STUDY
remote end of the line, i.e., relay 2, is a regular impedance- The system is shown in Fig. 8. The voltage generated by
based relay with a directional over-reaching zone. The relay the DFIG is 690 V and at transmission level it is stepped
located at the WF substation, however, detects faults in its up to 230 kV by a transformer. The system parameters i.e.
forward direction not based only on the measured impedance, proportional gain, integral constants, etc. are evaluated from
but according to the fault signal issued by the relay 2 as well. typical values [9]. Th mho relay impedance settings are done
The relay 2 is connected to the grid side and hence works by calculating the impedance from line parameters. The line
properly with the existing conventional protection scheme. It parameters are specified in the Appendix at the end of this
will detect any three phase fault on the line and will send a paper. The behavior of the system is studied in the subsequent
trip signal to the breaker B1. This signal from relay B2 can sections.
be delayed so that relay 1 has a margin to detect the fault
at the DFIG end by itself. Hence signal from relay B2, i.e. A. Fault analysis when conventional distance protection is
R2 which can be delayed based on system requirements, and used
the signal obtained from relay 1, i.e. R1 are passed through The fault is created at the middle of the line i.e. at 50 km
a logical disjunction. The output of this gate is then given from both the ends. The results obtained for single line to
to the breaker B1 as a trip signal. Hence if the relay 1 fails ground fault and three phase symmetric fault are shown below:
to sense the fault in one cycle, the grid side relay will send 1) LG fault at phase A-: We can see in Fig. 4 that when
the trip signal to the breaker B1. The relay 1 will sense the fault occurs, the current levels do not deviate much, however
unsymmetrical faults and will issue trip signal to breaker B1. harmonics are introduced. The fault is cleared within almost
Only for symmetrical faults, breaker B1 will depend on the one cycle. The protection system works efficiently. The Relay
signal from the relay 2. impedance characteristics are shown in Fig. 5. It can be seen
The detailed algorithm can be expressed as follows: that the characteristic enters in the trip region of relay 1 and
1) Sample the current waveforms continuously through hence the relay issues a trip signal and B1 trips. And the
FFT system is isolated from the fault successfully [10].
2) Analyze the samples for any fault
3) In case of fault, check for trip signal by relay 1
4) If signal has been issued, proceed with regular opening
of breaker 1
5) In case of no Trip signal by relay 1, check for trip by
breaker 2
6) For trip signal issued by relay 2, check for balanced fault
7) For a balanced Fault, communicate with relay 1 and
issue a trip signal to breaker 1 with some delay

START

Current Samples

N Fault
Detection
Fig. 4: Line current, fault signal and trip signal issued for LG fault
Y
Trip N Breaker 2 N
signal 1? trip?
Y Y
Open Y Balanced
Breaker 1 Fault
N
Modified POTT
Scheme Not Activated

STOP

Fig. 3: Algorithm for modified Pilot Protection Scheme

Hence the breaker will trip at all types of faults thereby


protecting the transmission line. For transmission of the trip
signal from grid side relay to the DFIG side relay, radio link
is used. As it is just on/off information, bandwidth required is
less. Hence the trip signal is transmitted wireless from the grid
side and received by the receiver placed at the DFIG station. Fig. 5: Mho relay characteristics of the relay 1 for LG fault
This signal is then decoded and given to the relay circuit.
2) Three Phase fault-: We can see in Fig. 6 that when measurement relations still hold true and offer a true
LLLG fault occurs, the fault is not cleared within one cycle. measure of the distance to the fault location. Conversely,
Thfcaption e protection system mal operates. The Relay char- in the case of DFIG-based WFs during balanced faults,
acteristics are shown in Fig. 7. The impedance characteristic only the current frequency significantly deviates from
does not enter in the trip region of relay 1 and hence the relay the nominal frequency. The voltage frequency remains
fails to operate. within a narrow margin of 50 Hz. For such conditions,
impedance measurement equations do not hold true and
the relay fails.
• Crowbar protection circuit [10]: On occurrence of three
phase fault the rotor current is too high, the thyristors are
fired and the crowbar is connected to the rotor windings.
Therefore, the high currents do not flow through the
converter but instead pass through the crowbar resistors.
The higher crowbar resistance in series with the rotor
windings lowers the peak current and prevents the detec-
tion of a fault. The quick insertion of the crowbar affects
the detection properties of the relay. A lower crowbar
resistance causes an unpredictable behavior of the relay.

C. Results
Fig. 6: Line current, fault signal and trip signal is not issued on After implementing the modified Pilot Protection scheme,
three phase fault faults were created on the line. The results obtained for three
phase faults are given in Fig. 9 and Fig. 10. This system con-
tains various parameters such as proportional gain constants,
integral constants of various control systems whose response
is dependent on grid voltage which works as feedback to the
system. DFIG gets faulty or random values of voltages as a
feedback to the system from grid on occurrence of Balanced
faults. This error in feedback voltages gets amplified through
various components of control systems, which results into
abnormal increaseof the current values of DFIG which are
injected into the grid as shown in Fig. 9 and Fig. 10
Hence, it can be seen that, the relay operated correctly at
all the faults including the three phase faults. The trip signal
was issued just after the delay which was set to 10 ms. It can
also be observed that trip signal 1 has not been activated in
case of LLL and LLLG faults. But, the breaker B1 has tripped
Fig. 7: Mho relay characteristics of the relay 1 on three phase fault and the current has become zero. This is due to the trip signal
from the other end. Hence this scheme can be implemented
for distance protection of transmission lines connected to wind
B. Analysis and observations farms and works efficiently.
For LG, LL and LLG faults, the relay works optimally
without any error. This means that the relay works correctly VI. C ONCLUSION
for unsymmetrical faults. It issues trip signals and the breaker Computer analysis and modeling of DFIG is carried out in
is tripped in almost one cycle i.e. in 20 ms as frequency is PSCAD/EMTDC. The current source representation is used
50 Hz. The relay fails to identify the fault for 3 phase faults. for fault analysis. A simulation model of stator flux oriented
This means that the relay mal operates at LLL and LLLG vector control is used. It was possible to obtain decoupled
faults. Few reasons for the same have been listed out in [10], real and reactive power control with the help of this model.
[5] some standard research work and those are summarized Then fault analysis is carried out. The DFIG side relay i.e.
below: relay 1 operates accurately in case of unbalanced faults, but
• Frequency deviation [5]: Protective relays contain fre- fails to operate when balanced fault occurs. This mal-operation
quency tracking algorithm which modify filters during of relay is due to DFIG behavior. The main reason is the
frequency deviations to give correct voltage and currents difference in frequencies of current and voltage. the current
measurements. During LG, LL, LLG fault conditions, frequency varies significantly with respect to the nominal
both voltage and current frequency exhibit the same frequency while, the voltage frequency remains in narrow
deviation from the nominal frequency. Hence, impedance margin of 50 Hz. Due to this difference, the impedance
Fig. 8: Overall System

Fig. 9: DFIG side Fault currents, Fault signal and Trip signal Fig. 10: Grid side Fault currents, Fault signal and Trip signal

can be analyzed. Then validity of the proposed pilot protection


measurement unit of the relay fails to measure it correctly scheme can be checked successfully.
and hence the relay fails.
Hence, to isolate the transmission line in such cases, a pilot A PPENDIX
scheme is proposed and the results obtained are also shown.
TABLE I: line parameters
The scheme works correctly and issues the trip signal at all
faults thereby protecting the system from any damage. This Parameter Positive Sequence Zero Sequence
proposed scheme provides quick and non-delayed protection Resistance (ohm/km) 0.03206 0.2676
Inductance (H/km) 1.35e-3 3.008e-3
over the entire transmission line. Hence, it delivers promising Capacitance (F/km) 8.55e-9 7.751e-9
results for DFIG connected wind farms. As DFIG is widely
used generator type in wind farms, further development in this
scheme will provide greater levels of protection. R EFERENCES
The proposed scheme can be extended as, the protection [1] Jadhav HT Ror R, A critical review on the grid integration issues of DFIG
scheme proposed for DFIG can be applied to squirrel cage based wind farms, 10 th International conference on EEEIC,May 2011
induction generator (SCIG), direct-drive synchronous genera- [2] A. K. Pradhan; Gza Joos, ”Adaptive Distance Relay Setting for Lines
Connecting Wind Farms”, IEEE Transactions on Energy Conversion,
tor (DDSG) and synchronous generator with full scale power Volume: 22, Issue: 1, Pages: 206 - 213, IEEE Journals and Magazines,
electronic converter. The system behavior at different faults Year: 2007.
[3] Mohit Singh, Surya Santoso,”Dynamic Models for Wind Turbines and [7] Rahul Dubey; Subhransu Ranjan Samantaray; Bijay Ketan Panigrahi,
Wind Power Plants”, University of Texas at Austin, Texas NREL Tech- ”Adaptive distance protection scheme for shunt-FACTS compensated line
nical Monitor: Eduard Muljadi Prepared under Subcontract No. XEE-8- connecting wind farm”, IET Generation, Transmission and Distribution,
77567-01 Volume: 10, Issue: 1 Pages: 247 - 256, Year: 2016.
[4] Mithunprakash G Vyas, ”Simulation and Modeling of Wind Power Plants: [8] E. Muljadi and V. Gevorgian, ”Short-Circuit Modelling of a Wind Power
A Pedagogical Approach”, BSEE, THESIS Presented to the Faculty of Plant”, NREL.
the Graduate School of the University of Texas at Austin. [9] ”WECC Wind Power Plant Dynamic Modelling Guide”, November 2010,
[5] Ali Hooshyar; Maher Abdelkhalek Azzouz; Ehab F. El-Saadany, ”Dis- Prepared by WECC Renewable Energy Modeling Task Force.
tance Protection of Lines Connected to Induction Generator-Based Wind [10] Simon De Rijcke; Paula Souto Prez; Johan Driesen, ”Impact of wind
Farms During Balanced Faults”, IEEE Transactions on Sustainable En- turbines equipped with doubly-fed induction generators ondistance relay-
ergy, Volume: 5, Issue: 4, Pages: 1193 - 1203, Year: 2014. ing”,IEEE Conference Publications, Pages: 1 - 6, Year: 2010.
[6] Nidhi Chauhan1, M. Tripathy and R. P. Maheshwari, ”Performance [11] Ali Hooshyar; Maher Abdelkhalek Azzouz; Ehab F. El-Saadany, ”Three-
Evaluation of Mho and Quadrilateral Characteristic Relays on UPFC Phase Fault Direction Identification for Distribution Systems with DFIG-
Incorporated Transmission Line”, Department of Electrical Engineering, Based Wind DG”, IEEE Transactions on Sustainable Energy, Volume: 5,
Indian Institute of Technology Roorkee Issue: 3, Pages: 747 - 756, Year: 2014.

You might also like