6.6 kn/m
Gable Column Spacing, 20.00 ft
Spacing of Purling 3.28 ft
Total Dead Load, DL 4 Psf
Total Live Load, LL 12.5 Psf
Wind Load, Vb 190 Km/hr
Co-efficient, Cc 4.72E-05
Importance factor, CI 1
Height & Exposure Co-efficient, Cz 0.429 Exp=A at Height H
Wind Pressure at height, H, q z 0.73 KN/m2
Guest Co-efficient at H, CG 1.57 Exp=A at Height H
Degree of Building, Ѳ 19.57 Degree
Average height & Length ratio, H/L 0.29
Length & Width Ratio, L/B 0.54
Co-efficient, Cpe for L/B (Windward Wall) 0.8 Windward Wall From table external Pressure coeffi
Co-efficient, Cpe for H/L (Windward Roof) 0.29 Windward Roof From table external Pressure coeffi
Co-efficient, Cpe for H/L (Leeward Roof) -0.7 Leeward Roof From table external Pressure coeffi
Co-efficient, Cpe for L/B (Leeward Wall) -0.58 Leeward Wall From table external Pressure coeffi
Side or End walls (Gable Wall), Cpe = -0.7 Gable Wall
Internal peak pressure coefficient, C' pi 0.25 Table 6.2.14 IF Opening is more than 10% then u
Hence internal pressure or internal suction = C' piqz 0.18 KN/m2
Eave Height
13.12 ft
3.1 kn/m -3.7 kn/m
Ѳ Degree
21 ft
-2.9 kn/m
15 ft
2100
Table 6.2.14
Internal Peak Pressure Co-efficients for Buildings, C'pi
Condition C'pi
Percentage of total wall area occupied by openings in one wall 0.75 and -0.25
exceeds that of all other walls by 10% or more and opeinings in
all other walls do not exceed 20% of respective wall area.
All cases ±0.25
Table 6.2.15
Overall Pressue Coefficients, Cp for Rectanglar Buildings with Flat Roofs
L/B
h/B
0.1 0.5 0.65 1.0 2.0 >=3.0
<=0.5 1.4 1.45 1.55 1.4 1.15 1.1
10.00 1.55 1.85 2.00 1.70 1.30 1.15
20.00 1.80 2.25 2.55 2.00 1.40 1.20
>=40.0 1.95 2.50 2.80 2.20 1.60 1.25
Note: 1)These coefficients are to be used with Method-2 given in sec 2.4.6.6a(ii). Use Cp=±0.7 for
roof in all cases 2) Linear interpolation may
be made for intermediate values of h/B and L/B
Table 6.2.17
Overall Pressure coefficients Cp for Moneslope Roofs Over Unenclosed Buildings and Structures
L/B
Degrees(Ѳ)
5 3 2 1 1/2 1/3 1/5
10 0.2 0.25 0.3 0.45 0.55 0.7 0.75
15 0.35 0.45 0.5 0.7 0.85 0.9 0.85
20 0.5 0.6 0.75 0.9 1 0.95 0.9
25 0.7 0.8 0.95 1.15 1.1 1.05 0.95
30 0.9 1 1.2 1.3 1.2 1.1 1
Location of centre of pressure, X/L, for L/B of:
2 to 5 1 1/5 to 1/2
10 to 20 0.35 0.3 0.3
25 0.35 0.35 0.4
30 0.35 0.4 0.45
Note: 1) Wind forces act normal to the surface and shall be directed inward or outward. 2) Wind
shall be assumed to deviate by ±10 degrees from horizontal. 3) Notation:
B: dimension of roof
measured normal to wind direction, meters L: dimension of roof measured
parallel to wind direction, meters X: distance to centre of pressure from
wind ward edge of roof, meters Q: Angle of plane of roof from horizontal, degrees
Length=L
Width =B
X1 X2 Cpe(X)
-0.5 -0.6 -0.524
Height=h
Leeward
Side
>60
0.01Ѳ Length=L
0.01Ѳ (-0.7) for
all values
0.01Ѳ
of h/L &
0.01Ѳ LINEAR INTERPOLATION
-0.7 Deg, (Y) Y1 Y2 X1 X2 Cpe(X)
-0.8 11.00 0 10 -0.7 -0.9 -0.920
BUILDING IMPORTANCE FACTOR
CATEGORY GENERAL
I Essencial Facilities
II Hazardous Facilities
Special Occupancy
III
Structures
Standard Occupancy
IV
Structures
EXPOSURE
NAME
Exposure-A
Exposure-B
Exposure-C
CE FACTOR
PARTICULAR FACTOR
Hospital & other medical facilities, Fire & Police station, Central Water Tanks ,
Emergency vehicle shelters & garages, Cyclone & Flood center, Government 1.25
communication center
Public Assembly >300 person, School, College, Medical with 500 resident, Jail
1
& detension facility, Power Plant, Public Utility.
Buildign Low risk to human life, Agricultural buildings, minor storage facilities,
0.8
temporary facility, costruction facality, Boundary wall.
EXPOSURE
PARTICULAR
Urban and sub-urban areas, industrial areas, wooded areas, hilly or other
terrian covering at least 20 percent of the area with obstruction of 6meters or
more in height and extending from the site at least 500meters or 10 times the
height of the structure, whichever is greater
Open terrian with scattered obstructions having heights generally less than
10m extending 800m or more from the site in any full quadrant, This category
includes air fields, open park lands, sparasely build-up outskrits of towns, flat
open country and grasslands
Flat and unobstructed open terrian, coastel areas and riversides facing large
bodies of water, over 1.5km or more in width. Exposure C extends inland from
the shoreline 400m or 10 times the height of structure, whichever is greater
Combined Height & Exposure Co-efficient, Cz
Gust Co-Efficient, Gz
Y1 Y2 X1 X2 Cz(X)
6 9 0.415 0.497 0.445
9 12 0.497 0.565 0.528
12 15 0.565 0.624 0.593
15 18 0.624 0.677 0.650
EAR INTERPOLATION
Y1 Y2 X1 X2 Gz(X)
6 9 1.592 1.511 1.562
9 12 1.511 1.457 1.486
12 15 1.457 1.418 1.439
15 18 1.418 1.388 1.403