You are on page 1of 3
OPERATION INSTRUCTION OIL LEVEL GAUGE TYPE YZF-200 | Brier introduction 1.1 Application Pin-indicatoe oil level gauge is used for indicating the level of oil in the conservator of oil immersed transformer in the censervater of OLTC, and alarming at the lowest or highest oil level. It is also suitable for indicating the liquid level and alarming for pressure container with open type or inner pressure not less than 245Kpa. 1.2. Type and meanings Yz2 0 O-200 = For special region use Diameter of dise face (mm) ‘Designation serial number Structure (F-Float type) Pin-indicator oil level gauge Note: TH—Humid and tropic region, TA—Arid and tropic region. 1.3. Service condition 1.5.1 Ambient temperature :-40~+50°C. 1.3.2 Allowed working temperature:-40-+105'C. 1. 8.8 Installer at where any violent vibration and jolt are not exist 2. Structure and working principle 2.1 Structure of oil level gauge The oil level gauge mainly consists of indication part which includes point and dise face, alarming part which includes magnet and switch, gears for revering and changing, transmission part which includes swing bar and float, as shown in figure 1~2. 2.2 When the level of oil in the transformer conservator goes up and down, the float ofthe oil level gauge will move up and down accordingly, which drives the transmission mechanism by swing the bar up and down. The magnet of the alarming part and the point of the indication part will rotate to proper position by means of the coupling magnet When the oil level goes up to the highost level or down to the lowest level, the magnet will attract the corresponding contact switch and initiate the alarming signal. 1 Float 2 Swinging bar 3 Axis 4 Gears 5 Coupling magnet 6 Switeb, 7Dise 8 Point 9 Magnet 10 Switch IE Barrel Figure 1 Transmission prinsiple diagram for type YZF-200 1 3.1 in vari ificati i ‘The main variety specification und technical parameters of ol level gauge are shown in table 1. Table 1 direction of swinging bar Rotation angle Swinging bar position at the lowest oil level Witkg) (ke) s Note: Special requirement of contact capacity is marked on the nameplate. 3.2 The tolerance of the oil level should be less than -2.5%, 3.3 It can withstand 2000 V power frequency voltage between lead terminal and ground. 3.4 The oil level gauge (include float) can withstand 245°Kpa and is leak-less 3.5 The protecting grade of the IPXS 4 Overall dimension and installation dimension ‘The overall dimension of oil level gauge is shown in Figure 2 and table 2 Figure 2 Diagram for type YZF-200 ‘Table 2 i § sg | g ification q |Afsle2| ge ln Speciticatio rae de a3| 23 - of gasket 2673 £ 135 107/196 100 : | # }——_; 610 4 oe | | ene tower20° | special 170 137/0151x07 0130 ° Speci 2 5 Installation and commission 5.1 Installation 5.11 Thei i i i an The installation dimension of the oil level gauge is shown in Figure 2 and table 2. Type YZF-200 Float Swing axis are installed on the lowest oil level of the conservator. Type Float swing radial are installed on the ‘central line of the cover of the conservator. 5. L. 2 During installation .the swinging bar float shall have sufficient space to move without any obstacle from the other part 5.1.3 ‘The terminal wiring diagram is shown in Figure 3. 5.2 Checking before installation 5.2. 1 Before installation, check whether is any damage and rusty during storage and transportation, and do some necessary treatment. 5.2.2 Before installation lightly tur the swinging bar with hand to check whether it ean move flexibly, and ‘can reliably initiate the alarming signal at the limit position, 5. 2.3 Before installation, check whether the insulation character of the lead cable terminal and signal switch are good. DI ——— _P2__ D1 Common D2 Lowest oil level D3 D3 Highest oil level Figure3 Flectric wiring diagram 6 Operation and maintenance 6.1 Operation 6. 1.1 When designing the conservator of a transformer, the designer shall select proper oil level indicator, specially for the length of swinging bar (the distance from the center of the float sphere to the Tink ofthe oil ‘pauge), in order to keep the indication be in correspondence with the actual oil level 6.1.2 The measured liquid surface shall not wave violently, the swinging bar shall not shake rapidly and drastically, During transportation .he oil gauge shall be dismantled and packed separately. or fix the swinging bar firmly. 6.2 Maintenance uring operation, check the oil level gauge once a year, Check whether the insulation of lead and switch is in good condition, and whether the gaskets need replacement. ‘Note: When ordering. please indicate the type, installation dimension (Do, ®D) length of the swinging par (L) (the distance from the center of float sphere to the of oil level gauge) Product standard Number: JB/T10692

You might also like