Calibration Report

Calibration Report
Site Name
Manufacturer ID Emerson Device Date Time 11/27/2019 7:16:17 PM
Device FB1100 Operator ADMIN

Calibration-Verification Data
Point ID: Press_1-1:Integ
ral Sensor Pr
Point Description: Integral Sensor Pr
Date Time Event Type psi psi Deviation Deviation
psi Percent (%)
27-Nov-2019 12:52:48 Calibration-Set Zero As Found: -0.34 As Left: 0 -0.34 -0.02267
27-Nov-2019 12:58:46 Calibration-Set Span As Found: 1494.95 As Left: 1500 -5.05 -0.33667
27-Nov-2019 13:03:42 Calibration-Set Mid As Found: 295.22 As Left: 300 -4.78 -0.31867
Point 1
27-Nov-2019 13:05:14 Calibration-Set Mid As Found: 600.29 As Left: 600 0.29 0.01933
Point 2
27-Nov-2019 13:07:29 Calibration-Set Mid As Found: 899.79 As Left: 900 -0.21 -0.014
Point 3
27-Nov-2019 13:16:31 Verification Actual: 147.03 Expected: 150 -2.97 -0.198

Page 1 of 1