You are on page 1of 40

Indoor Air Quality

A Guide to Understanding
ASHRAE Standard 62-2001
Preface

This guide reviews and explains The commentary that follows presents equipment- and system-related concepts
the opinion of Trane and not necessarily proposed here are offered only as
the provisions of ASHRAE that of the American Society of Heating, suggestions. Trane does not assume
Standard 62-2001, “Ventilation Refrigerating, and Air-Conditioning responsibility for the interpretation of
Engineers (ASHRAE). It also represents this standard or for the performance or
for Acceptable Indoor Air Trane’s interpretation of ASHRAE desirability of any system resulting from
Quality.” It also advocates Standard 62-2001 which may or may not these suggestions. Responsibility for final
system and equipment solutions be the interpretation placed on it by system design—like interpretation and
others, including courts, called upon for compliance with Standard 62—ultimately
that meet the explicit and such interpretation. Similarly, the rests with the designer.
suggested requirements of
that standard. We hope the
analysis provided here helps
professionals responsible for
designing, installing,
maintaining, and operating
of HVAC systems achieve
compliance with Standard 62.

© 2002 American Standard Inc. All rights reserved ISS-APG001-EN


Table of Contents

Page Additional pieces of Trane


Introduction .......................................... 3 literature are referenced at
Overview of ASHRAE Standard 62 .... . . . . . . . . . . . . . . . . . . . . 4 various points throughout this
Terminology . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 document. This supplemental
History of Standard 62 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 information is available on the
How ASHRAE 62-2001 Addresses IAQ . . . . . . . . . . . . . . . . . . . . . . 5 Trane Bookstore at
Fundamentals of Good Indoor Air Quality ................ 6 www.trane.com/bookstore/or
Contaminant Source Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 from your local Trane office.
Indoor Sources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Sloped Drain Pans . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Cleanability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Accessibility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Outdoor Sources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Proper Ventilation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Ventilation Rate Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Multi-Space Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
The VAV Ventilation Challenge . . . . . . . . . . . . . . . . . . . . . . . . . 13
Occupied vs. Unoccupied Ventilation . . . . . . . . . . . . . . . . . . . 14
Ventilation Effectiveness . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Intermittent Occupancy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Preoccupancy Purge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Summary of Ventilation Rate Procedure . . . . . . . . . . . . . . . . . 16
Indoor Air Quality Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Cleaning of Recirculated Air . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Summary of the IAQ Procedure . . . . . . . . . . . . . . . . . . . . . . . . 17
Ventilation Control Strategies . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Ventilation Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Scheduled Ventilation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
CO2-Based Demand-Controlled Ventilation . . . . . . . . . . . . . . . 19
Outdoor Airflow Measurement and Control . . . . . . . . . . . . . . . . . 21
Building Pressure Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Humidity Management . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Constant Volume, Variable-Temperature Systems . . . . . . . . . . . . 25
Variable-Air-Volume (VAV) Systems . . . . . . . . . . . . . . . . . . . . . . . . 28
Humidity Control vs. Heat Recovery . . . . . . . . . . . . . . . . . . . . . . . 29
Filtration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Particulate Filtration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Gaseous Filtration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
Addenda Incorporated into ASHRAE Standard 62-2001 . . . .33
Suggested Mechanical Equipment Specifications . . . .34

2
ISS-APG001-EN
Introduction

The American Society of Many building designers and owners approving focused addenda. It is
believe the lack of federal regulation republished every two to three years
Heating, Refrigerating, and renders indoor air quality (IAQ) a soft, to incorporate all approved addenda.
Air-Conditioning Engineers highly subjective issue. But the fact is The 2001 version incorporates twelve
(ASHRAE) comprises that poor IAQ reflects on everyone addenda that have been approved since
involved with the design, construction, 1989. The list of approved addenda and
representatives from all operation, and maintenance of a a brief description of the changes is
vantages of the heating, building. “Sick” buildings hinder included on page 32.
occupant productivity and discourage Ensuring compliance with applicable
ventilation, refrigeration, tenants from renewing their leases. In codes and standards within the
and air-conditioning (HVAC) today’s litigious society, all parties need economic context of each project
industry. Together, Society to be aware of the legal ramifications of challenges building design professionals
an unhealthy indoor environment. to seek innovative HVAC equipment and
members draft standards and
ASHRAE Standard 62-2001 establishes system solutions. This guide attempts
guidelines that provide counsel the standard of care for the design of to clarify the ventilation, equipment, and
on most aspects of HVAC system commercial, institutional, and residential system-related mandates in ASHRAE
ventilation systems to “provide indoor Standard 62-2001, and to identify
selection, design, application, air quality that will be acceptable to practical, cost-effective solutions made
commissioning, safety, and human occupants and is intended to possible by current technology. The
operational criteria for a broad minimize the potential for adverse health material presented in this document
effects.” Building codes in most states reflects only the addenda approved
spectrum of HVAC systems. reference Standard 62, either in part or when the 2001 version of the standard
State and local authorities in its entirety, as part of their definition was printed.
of minimum ventilation requirements.
frequently adopt these As a “continuous maintenance”
standards and write them standard, Standard 62 is modified by
into their codes.

To purchase a copy of
ASHRAE Standard 62-2001,
call 1-800-5 ASHRAE or visit
the online bookstore at
www.ashrae.org.

3 ISS-APG001-EN
Overview of ASHRAE Standard 62

A building’s indoor air quality is the Much of the “meat” related to system History of
result of the decisions and actions of design is contained in two sections:
a wide variety of individuals over an Section 5 presents general requirements Standard 62
extended period of time. Design of that target microbial contamination
the building’s heating, ventilating, and control in HVAC equipment and systems, Like most ASHRAE standards,
air-conditioning system, contaminant while Section 6 describes two Standard 62 is based on input
sources, and air-cleaning efficiency procedures for determining design
all play roles, as do operation and ventilation rates that adequately dilute from interdisciplinary
maintenance of the building and its indoor contaminants. committees of engineers,
mechanical systems. Together, these
variables make achieving acceptable
Section 7 includes requirements for chemists, physiologists, and
system construction and startup, while
indoor air quality a complex, Section 8 contains requirements for the
manufacturers. Standard
multifaceted problem. operation and maintenance of the HVAC 62-1973, “Standard for Natural
ASHRAE Standard 62-2001, “Ventilation system. This document focuses primarily and Mechanical Ventilation,”
for Acceptable Indoor Air Quality,” on system design.
addresses this complexity by was ASHRAE’s first ventilation
establishing IAQ-related guidance for the Terminology standard. It provided a
design, construction, startup, operation, “Shall” and “Should”
and maintenance of heating, ventilating,
prescriptive approach to
ASHRAE Standard 62 presents both
and air-conditioning (HVAC) systems. suggestions (stated as should and may)
ventilation by specifying
Trane advocates full compliance with this and requirements (denoted by shall and minimum and recommended
standard and considers it the minimum must). Obviously, “requirements” must
requisite for ventilation, equipment, and outdoor airflow rates to obtain
be met to claim compliance with the
systems—local codes notwithstanding. standard. While it might seem acceptable indoor air quality.
Although the title of the standard implies
that it focuses strictly on ventilation,
“suggestions” are optional, ignoring Renamed “Ventilation for
them may not be wise as they reflect
it goes much further by including the consensus of the HVAC industry
Acceptable Indoor Air Quality,”
provisions for managing sources and may therefore be viewed as the the 1981 revision of the
of contamination, controlling indoor minimum criteria a prudent design
humidity, and filtration of the building air. standard recommended outdoor
professional would exercise when
designing a ventilation system. airflow rates for smoking and
nonsmoking spaces and added
the Indoor Air Quality
Procedure as an alternative
method for determining
minimum design ventilation
rates. The 1989 version of the
standard increased the per-
person space ventilation rates
from 5 cfm to 15 or 20 cfm per
person based on the type of
occupancy. The 1999 version
incorporated five addenda that
were approved since 1989. The
current 2001 version

4
ISS-APG001-EN
Overview of ASHRAE Standard 62

History of Standard “Outdoor Air” and How ASHRAE Standard


62 (continued) “Ventilation Air” 62 Addresses IAQ
Though the terms outdoor air ASHRAE Standard 62 provides basic
and ventilation air are often used equipment and system requirements
incorporates seven more interchangeably, there is an important and minimum ventilation rates which are
addenda that have been distinction between them. “Outdoor expected to result in indoor air quality
approved since 1999, including air”—also called intake air or first pass “acceptable” to human occupants. The
air—describes air brought into the standard is based on the meaning and
the addition of two new building from the outdoors, while purpose of the various provisions and
sections on construction and “ventilation air” is typically a mixture its implementation is intended to help
of first pass and unused recirculated minimize adverse health effects. As
startup, and operation and outdoor air used to dilute contaminants a “peer-generated and -reviewed”
maintenance. A brief description within a building’s occupied spaces. standard, it establishes the IAQ-related
of the changes from each of standard of care for the design,
these addenda is included construction, startup, operation, and
maintenance of ventilation systems
on page 32. in commercial buildings.

“What Happened to
ASHRAE Standard
62R”?
After years of work, ASHRAE
Standard 62R went out for a
120-day public review in
August of 1996. In June of
1997, after receiving a large
number of comments, the
ASHRAE Board of Directors
decided to change the ANSI
status of the standard from
“periodic” (revised every 5 to
10 years) to “continuous”
maintenance. With this change,
revisions will be made
continuously through focussed
addenda, with the entire
standard being republished
every 2 to 3 years. At the same
time, the Board divided the
standard into two parts:
62.1 for commercial and
institutional buildings and
62.2 for low-rise residential

5 ISS-APG001-EN
Fundamentals of Good Indoor
Air Quality

Acceptable indoor air quality (IAQ) is much more cost-effective strategy than “What Happened to
typically not achieved by addressing any filtering or diluting them once they are
one specific building product, system, or inside the building. ASHRAE Standard
procedure. Rather, it is the result of
Indoor Sources 62R”? (continued)
careful attention to each of the following
fundamental elements: Contamination can originate inside the
building or be brought in from outdoors. buildings. (These designations
• contaminant source control
• proper ventilation The most obvious indoor-generated will be used as soon as the
contaminants are those created by the
• humidity management
activities of the building occupants, such
separate standard for low-rise
• adequate filtration
as cooking, smoking, photocopying, residential buildings is
Careful attention to each of these laser printing, and other processes.
fundamentals during the design and
published.) All addenda will be
To address controlling these types of
construction of the building and HVAC indoor contaminants, ASHRAE written in mandatory language
system, followed by proper operation Standard 62-2001 states: to facilitate easy adoption by
and maintenance throughout the life of
the building, can significantly reduce the “Contaminants from stationary local code authorities and will
sources within the space shall be
risk of IAQ-related problems.
controlled by collection and removal as
include important new
Contaminant close to the source as practical.” requirements pertaining to the
Source Control (Section 5.6) installation, operation, and
Controlling the source of contaminants is maintenance, as well as system
fundamental to any IAQ strategy. Today, “Removal close to the source” refers to
microbial contamination, in the form of local exhaust, but local exhaust is not design. The material presented
mold and mildew, is a major indoor always possible, as in the case of volatile in this document reflects only
pollutant, but it certainly is not the only organic compounds (VOCs). VOCs are
chemicals, such as formaldehyde, that the addenda approved when the
source. Indoor contamination can also
be in the form of particles or chemicals. outgas slowly from manufactured 2001 version of the standard
They may come from building occupants construction materials, furnishings, and was printed.
and their activities, be emitted from cleaning products. All modern buildings
furnishings and wall coverings, or be contain VOCs. Low levels of VOCs
brought into the building with the intake originate from many different locations
air from outdoors. Controlling these within the building, making local exhaust
at the source difficult. In this situation, “Contaminants from stationary
contaminants at the source is typically a
dilution with clean outdoor air is typically local sources within the space
Figure 1: Fundamental Elements of Indoor Air Quality shall be controlled by collection
and removal as close to the
source as practical.”
(Section 5.6)

6
ISS-APG001-EN
Fundamentals of Good Indoor
Air Quality

“Air handling unit condensate the most practical and cost-effective “Air handling unit condensate pans shall
solution. be designed for self-drainage to preclude
pans shall be designed for self- the buildup of microbial slime.”
Microbial contamination (fungi and
drainage to preclude the bacteria) can also be a major source of (Section 5.11)
buildup of microbial slime.” indoor contamination. Microbiological
colonies can grow in or on various To comply with this requirement,
(Section 5.11)
building elements and furnishings, condensate drain pans should be sloped,
including carpets, ceilings, sheetrock preferably in two directions, to assure
walls, and within the HVAC system. positive drainage and eliminate standing
When mold spores and other water both when the system is operating
microbiological particles become and when it is idle. Furthermore, the
airborne, some building occupants may drain pans should be constructed of
experience allergic reactions and other noncorrosive materials, such as stainless
health-related effects. Once the mold is or galvanized steel or polymers, to resist
established, the air-handling system can the deterioration that leads to premature
distribute the contaminants and leakage or porous surfaces which harbor
offensive odors throughout the building.
Because of the variety of potential indoor Figure 2: Double-Sloped, Trapped
sources of microbial and fungal Condensate Drain Pan
contamination, source control using
local exhaust also can be difficult.
What can be done to reduce the
potential for microbial growth inside
buildings? Proper selection and
specification of building materials and
HVAC equipment are key places to start.
ASHRAE Standard 62-2001 cites three
specific air-handling equipment
characteristics that significantly reduce
the likelihood of the HVAC system
becoming a source of microbial
contamination: sloped drain pans,
cleanable interior surfaces, and
accessibility.
Sloped, Noncorrosive Drain Pans
The condensate drain pan located
under the cooling coil is well recognized
as a potential source of microbial
contamination. Until recently, most air
handlers and terminal units with cooling
coils were designed with flat drain pans.
This design allows water to collect in
stagnant pools, fostering the growth of
microbial slime. Because the drain pan is
in the air stream, any microbial spores
that are released can be easily circulated
throughout the system. Also, the residual
slime sometimes clogs drain lines,
forcing condensate to overflow into the
bottom of the air handler or leak out into
the building. This results in more wet
surfaces, further increasing the potential
for mold growth, not to mention the
obvious damage to furnishings,
equipment, and the building structure
itself. ASHRAE Standard 62-2001
addresses these drain pan issues:
7 ISS-APG001-EN
dirt and are difficult to clean. Another cause the equipment and duct system to “Visible microbial
often-overlooked element of proper become wet. Such occurrences demand
condensate drainage is trapping. In a that regular inspections of the air handler contamination shall be
draw-through coil configuration, a and duct system for signs of moisture or investigated and rectified.”
properly designed drain trap eliminates mold and fungi growth become part of (Section 8.4.2)
condensate ‘spitting’ which can dampen the routine HVAC system maintenance. If
the interior insulation of the air handler infestations are found, these areas must
and/or ductwork, creating another be properly cleaned immediately and the
opportunity for mold infestation. cause of the contamination must be
The HVAC equipment manufacturer’s determined and corrected.
installation and trapping instructions ASHRAE 62-2001 addresses the issue of
must be carefully followed to assure inspecting and cleaning ventilation
adequate condensate removal under systems by listing specific inspection
all operating conditions. intervals in Section 8.4.1 (see Figure 5).
All Trane commercial air-handling Additionally, the standard requires that:
products—from the smallest fan-coil to “Visible microbial contamination shall
the largest central station air handler and be investigated and rectified.”
rooftop units—are available with double-
sloped, noncorrosive drain pans. Large (Section 8.4.2)
air-handling equipment typically features
galvanized or stainless steel drain pans, Historically, HVAC equipment and
while the smaller terminal products use ductwork has been lined with porous,
pans constructed of polymer or matte-faced fiberglass for thermal
galvanized steel. Sloped drain pans insulation and acoustical attenuation.
significantly reduce the amount of water The porous surface of the insulation can
in the air-handling system which, in turn, store dirt, creating a habitat for microbial
significantly reduces the risk of microbial growth if moisture is present. Once
contamination. contaminated with mold, the porous
insulation is almost impossible to clean
Cleanability short of removing and replacing it.
Improper HVAC equipment selection, Section 5.5 of the ASHRAE Standard
operation, and maintenance can cause 62-2001 includes specific requirements
dirt and moisture to accumulate within for the materials used on surfaces inside
the equipment and ductwork. Even when HVAC equipment and ductwork that are
operated properly, unexpected and exposed to the airstream.
unavoidable events, such as equipment
malfunctions or power outages, can

Figure 3: Condensate Trap Design Criteria for a Draw-Through Coil Arrangement

Total Trap Height (W) = X + H + 1.5 x D


Where:
X = 1⁄2 H
H = At Least 1" Plus Casing Static Pressure
D = Pipe Diameter

Total H
Trap
Height Housekeeping
(W) X Pad

• Trap “splits” if W is too short


• Pan won’t drain if H is too short

8
ISS-APG001-EN
Fundamentals of Good Indoor
Air Quality

This has prompted many designers to water. Central air handlers and large
specify commercial HVAC equipment rooftop equipment typically require a
with double-wall construction (fiberglass more durable liner (such as sheet metal)
insulation sandwiched between two because of their physical size and
layers of metal) or external insulation maintenance requirements. Today, Trane
for “wet” areas of the equipment and offers cleanable interior surfaces on its
the duct system. This includes areas entire line of commercial air-handling
surrounding and immediately products to simplify inspection and any
downstream of cooling coils and near cleanup that may be required.
humidifiers. Though effective for Accessibility
cleanability, an unlined duct system, Obviously, a cleanable surface is of
whether double-wall or externally limited value if it cannot be accessed
insulated, can be more expensive and easily. ASHRAE Standard 62-2001 states:
may lead to acoustical problems.
“Provision shall be made for periodic
Trane believes that the intent of the in-situ cleaning of cooling coils and
standard can be met by using cleanable condensate pans. Air handling and
surfaces in the sections of the air fan-coil units shall be easily accessible
handlers and ductwork expected to for inspection and preventative
become wet during normal system maintenance.”
operation. This includes outdoor air
intakes and mixing boxes, cooling-coil (Section 5.11)
sections of air handlers, and sections
housing and immediately downstream This section of the standard clearly
of humidifiers. requires that cooling coils and drain pans
must be readily accessible for inspection,
The specific way in which the system cleaning, and maintenance in their
meets the cleanability requirement varies normal operating position (in-situ).
by system type. Terminal equipment Additionally, Section 8.4.1 lists specific
(such as fan-coils, blower coils, unit inspection intervals for filters, cooling
ventilators, and water-source heat coils, drain pans, humidifiers, and
pumps) that has physical space outdoor-air intake louvers. These
constraints, typically uses either closed- maintenance requirements are outlined
cell foam or foil-faced insulation. Both in Table 8-1 of the standard (see Figure
liner materials provide a nonporous 5). Large access doors or removable
outer surface that is impermeable to panels are necessary to meet this
Figure 4: Examples of Cleanability and Accessibility Features on Air Handlers

9 ISS-APG001-EN
Figure 5: Minimum Maintenance Activity and Frequency (Table 8-1) from ASHRAE “Provision shall be made for
Standard 62-2001 periodic in-situ cleaning of
cooling coils and condensate
pans. Air handling and fan-coil
units shall be easily accessible
for inspection and preventative
maintenance.”
(Section 5.11)

“Make-up air inlets and exhaust


air outlets shall be located to
avoid contamination of the
make-up air.”
(Section 5.4)

10
ISS-APG001-EN
Fundamentals of Good Indoor
Air Quality

“Contaminants from sources requirement. In addition, the equipment For more information on these
must be positioned and installed within “IAQ Equipment Basics,” contact
such as cooling towers, sanitary the building to assure adequate access your local Trane representative for
vents, vehicular exhaust from to all major components without a copy of “Practice the Basics of
parking garages, loading docks, substantial unit disassembly. Microbial Growth Control” (literature
It is reasonable to conclude that order number TECH-R-168).
and street traffic should be
equipment that is easy to access will be
avoided.” maintained and serviced more often. In Outdoor Sources
(Section 5.4) commercial central-station air-handling Contaminants can also enter a building
equipment, access is typically provided from outdoors through the outdoor air
with hinged doors or removable panels. intake, or by infiltration through cracks
This same logic applies to system and openings in the building envelope.
“Special care should be taken to ductwork. Ductwork access should be Regarding the former, ASHRAE
provided at areas where dirt is likely to Standard 62-2001 states:
avoid entrainment of moisture accumulate—for example, at changes
in velocity or direction—as well as “Make-up air inlets and exhaust air
drift from cooling towers into outlets shall be located to avoid
immediately before and after any duct-
the make-up air and building mounted devices such as humidifiers, contamination of the make-up air.”
vents.” turning vanes, and fire dampers. (Section 5.4)
(Section 5.11) Equipment designs for commercial
This statement requires the building
terminal products, such as fan-coils,
designer to situate equipment in a way
water-source heat pumps and unit
that prevents make-up air contamination.
ventilators, should also allow easy
In other words, the outdoor air intake
“If the outdoor air contaminant inspection and maintenance (such
must not reintroduce exhaust air into
as filter replacement) with minimal
levels exceed the values given in disassembly of the equipment. Easy
the building. In built-up (applied)
6.1.1 (Table 1), the air should be systems, this requirement usually can
access is especially important for
be met through careful placement of
treated to control the offending equipment located in the occupied
outdoor air intakes relative to exhaust
space. Terminal unit systems typically
contaminants.” fans, flue vents, etc. However, packaged
consist of multiple units, making
roof-mounted unitary equipment can be
(Section 6.1.2) inspection and maintenance a time-
more challenging. In these systems, the
consuming process. Although
designer must subjectively determine the
fan-powered VAV terminals do not have
likelihood of outdoor air contamination,
cooling coils or drain pans, they do have
then select and locate equipment
filters which must be replaced regularly.
accordingly. The standard identifies
Access to the filters, as well as to the
specific contaminants to be avoided:
terminal units themselves, is critical.
“Contaminants from sources such as
Trane designs all of its applied air-
cooling towers, sanitary vents, vehicular
handling products with accessibility in
exhaust from parking garages, loading
mind. The panel-and-post construction
docks, and street traffic should be
of the Modular Climate Changer™ air
avoided.”
handler, for instance, offers the flexibility
of hinged access doors for regularly (Section 5.4)
accessed areas, and fully removable
panels for areas accessed less often. and…
Likewise, filters in UniTrane™ fan-coil “Special care should be taken to avoid
units can be changed without removing entrainment of moisture drift from
the front panel for faster filter cooling towers into the make-up air and
maintenance and less disruption to the building vents.”
occupants. If further maintenance is
required, the entire front panel of the (Section 5.11)
unit, as well as the drain pans, can be
Although this is only advisory language,
removed. VariTrane™ fan-powered VAV
it seems to be a corollary to the
terminals provide complete access also.
requirement for locating the make-up
The entire bottom panel of the unit is
air intakes previously discussed in
removable to permit inspection,
Section 5.4, they simply name additional
cleaning, and maintenance of the unit.
11 ISS-APG001-EN
contaminant sources. If viewed as six months, and requires cleaning or Equation 6-1 of the standard is
corollaries, these statements require repair if necessary.
the designer to account for all possible used to calculate the minimum
Obviously, the number of possible
contamination sources when locating the paths through the building shell make it outdoor airflow required at the
system outdoor air intake. Vehicle traffic difficult to filter contaminants that enter system level:
patterns around the property, prevailing the building via infiltration. Proper
wind direction, and the location of building pressure control can effectively
cooling towers, garbage dumpsters,
and other contaminant sources must be
reduce infiltration, and thus limit the Y = X / (1+ X - Z)
considered. Incidentally, the statement
intrusion of contaminants and moisture
from outdoors. Internal building pressure
Vot = Y x Vst
in Section 5.11 should be interpreted to should be controlled to equal or slightly WHERE:
include any piece of outdoor equipment positive relative to the outdoors during X = Von /Vst = uncorrected
with standing water as a potential both occupied and unoccupied periods. outdoor airflow fraction
external contaminant source. According Building pressurization is discussed in Y = Vot /Vst = corrected outdoor
to Standard 62, if outdoor contaminants more detail later in this guide. airflow fraction
cannot be eliminated or avoided, local air
Z = largest F = critical-space
cleaning of the outdoor air and dilution Proper Ventilation ventilation fraction
ventilation must be employed. (See the Another very important element of
“Filtration” section on pages 29 - 30.) F = Vo /Vs = space
achieving acceptable indoor air quality
ventilation fraction
Even outdoor air of acceptable quality is proper ventilation. ASHRAE Standard
Von = ∑Vo = sum of space
can become contaminated if it is brought 62-2001 offers two methods for
ventilation airflows
into the building through contaminated determining the amount of outdoor
air required to properly ventilate indoor Vot = Y x Vst = required system
outdoor air intakes and ductwork. outdoor airflow
Missing or damaged screens on outdoor occupied spaces for acceptable IAQ:
the Ventilation Rate Procedure and the Vo = space ventilation airflow
air intake openings can allow birds and
rodents to enter these areas and soil IAQ Procedure. Vs = space primary airflow
them with nesting materials and feces. Vst = ∑Vs = total supply airflow
Section 8.4.1.6 requires inspection of
outdoor air intakes at least once every
“Indoor air quality shall be
Figure 6: Excerpt from Table 2 of ASHRAE Standard 62-2001 considered acceptable if the
required rates of acceptable
outdoor air in Table 2 are
provided for the occupied
space.”
(Section 6.1.3)

12
ISS-APG001-EN
Fundamentals of Good Indoor
Air Quality

“Where more than one space is Ventilation Rate Procedure Figure 6. To use Table 2, you must first
(Section 6.1) determine the expected usage of that
served by a common supply space within the facility. The ventilation
The Ventilation Rate Procedure dictates
system, the ratio of outdoor air both the quantity and quality of rates are expressed as a volume flow
to supply air required…may ventilation air necessary to assure rate per person, or per square foot, for a
adequate dilution of contaminants wide variety of space uses (such as office
differ from space to space. The spaces, classrooms, corridors, and
generated in the occupied space.
system outdoor air quantity Sometimes referred to as the “dilution auditoriums). Once you know the design
occupancy or floor area, you can
shall then be determined using solution,” it provides a prescriptive
calculate the ventilation flow rate
ventilation method for achieving
Equation 6-1.” acceptable indoor air quality. Specifically, required for each space.
(Section 6.1.3.1) it prescribes a three-step approach: Multiple-Space Systems
• First, determine the quality of the When a common supply air system
outdoor air. The designer cannot serves multiple spaces (Figure 7) the
simply assume that the quality of the building designer must calculate the
“When spaces are unoccupied, outdoor air surrounding the building system minimum outdoor airflow rate
is acceptable for use as ventilation air. (that is, the quantity of outdoor air
ventilation is not generally required at the air handler) based on the
Table 1 of the standard cites the
required unless it is needed “EPA National Ambient-Air Quality space-level ventilation requirements (per
to prevent accumulation of Standards for Outdoor Air” for Table 2). Specifically, the standard states:
contaminants injurious to particulate and gaseous contaminants. “Where more than one space is served
Particulate or gaseous filtration is by a common supply system, the ratio
people, contents, or structure.” necessary if outdoor air exceeds of outdoor air to supply air required
(Section 6.1.3.1) the threshold levels referenced. …may differ from space to space. The
• Second, if the outdoor air is system outdoor air quantity shall then
unacceptable, the standard advises be determined using Equation 6-1.”
that it be cleaned or filtered: (Section 6.1.3.1)
“If the outdoor air contaminant levels
exceed the values given in 6.1.1 (Table This requirement applies to both
1), the air should be treated to control constant-volume and variable-air-volume
the offending contaminants.” (VAV) systems. Many constant-volume
air handlers and almost all VAV air
(Section 6.1.2) handlers serve more than one space.
In other words, a building designer When a common supply system serves
faced with unacceptable outdoor air more than one occupied space, each
is encouraged to treat the outdoor air space is likely to require a different ratio
before it enters the building. of outdoor air to supply airflow (space
• Lastly, determine the amount of ventilation fraction). Simply bringing in
outdoor air required in each space. a quantity of outdoor air that equals the
Standard 62 states: sum of the individual space ventilation
requirements usually results in most of
“Indoor air quality shall be considered the spaces being underventilated much
acceptable if the required rates of of the time.
acceptable outdoor air in Table 2 are
The VAV Ventilation Challenge
provided for the occupied space.”
To properly ventilate a multiple-space,
(Section 6.1.3) VAV system, the percentage of outdoor
air in the supply air stream must change
Using the Ventilation Rate Procedure, as the amount of supply airflow to the
an occupied space is considered to have spaces changes. Equation 6-1 links the
acceptable IAQ if it is ventilated at the individual space ventilation requirements
airflow rate specified in Table 2 of the to the amount of outdoor air that must
standard. Said another way, compliance enter the air handler that serves the
with the Ventilation Rate Procedure entire system. Some designers believe
requires that individual spaces be that Equation 6-1 is excessively complex,
ventilated using the values in Table 2. but it is really quite straightforward. It
An excerpt from this table is shown in involves comparing several ratios to

13 ISS-APG001-EN
calculate the amount of outdoor air detail later in the “Ventilation Control “The ventilation effectiveness is
required at the system-level air handler. Strategies” section of this guide
(Pages 17 - 21).
defined by the fraction of the
The challenge of VAV system design is to
properly ventilate all spaces at all load Occupied vs. Unoccupied Ventilation
outdoor air delivered to the
conditions. Supply air in VAV systems is If the potential exists for contaminants space that reaches the occupied
a mixture of ventilation air and to accumulate in a space when it is zone…It is, however, not
recirculated air that is carried to the unoccupied, ventilation may be required
space by a single duct. That means the even when the space is unoccupied. uncommon to find some of the
proportion of outdoor air in this supply Standard 62 states: ventilation air bypassing the
air mixture must change as the supply
airflow changes to maintain proper
“When spaces are unoccupied, occupants (moving from supply
ventilation is not generally required
ventilation levels in the spaces. Many
unless it is needed to prevent
to exhaust without fully mixing
designers erroneously use the sum of in the occupied zone)…Such
accumulation of contaminants injurious
the outdoor air requirements of all the
to people, contents, or structure.” flow conditions should be
spaces (Von in Equation 6-1) in the
system as the system-level ventilation (Section 6.1.3.1) avoided.”
rate. This method, sometimes referred to
as the “average ventilation method,” In this case, the term “contaminants” (Section 6.1.3.3)
does not comply with ASHRAE Standard seems to include humidity, due to the
62-2001 because it underventilates the reference to a contaminant which is
spaces at most operating conditions. “injurious to contents or structure,” as
well as those listed in Tables 1, 3, B-1,
For more information on the challenge B-2, B-3, and B-4 of the standard.
of properly ventilating VAV systems, The unoccupied ventilation rate is
refer to the “The Threefold Challenge of determined by the contaminant emission
Ventilating Single-Duct VAV Systems” rate. Indoor humidity can be measured
Engineers Newsletter (Volume 27, and controlled by mechanical systems,
Number 1). but many of the other contaminants
listed cannot be easily or reliably
monitored. This leaves the designer with
One way to address this problem is to limited options, the most basic of which
dynamically vary the amount of outdoor is time-of-day scheduling of ventilation
air being introduced at the air handler in during unoccupied periods.
response to actual system operating
conditions. This approach is referred to Ventilation Effectiveness
as Ventilation Reset and is discussed in “Ventilation effectiveness” is defined as
the fraction of the outdoor air delivered
Figure 7: Multiple-Space System

Vot
VAV Rooftop Unit or
OA
Air Handler

RA
VAV
Boxes

SA RA RA SA RA SA

Space 1 Space 2 Space 3

14
ISS-APG001-EN
Fundamentals of Good Indoor
Air Quality

“Where peak occupancies of less to the space that actually reaches the Ventilation effectiveness can have a
occupants. The section of the standard significant effect on the amount of
than three hours duration occur, dealing with ventilation effectiveness is outdoor air required for the system. It
the outdoor airflow rate may more descriptive than prescriptive. It is important to understand that even a
be determined on the basis of does not tell the designer what to do modest amount of short circuiting of the
as much as it explains the concept. outdoor air to the return, say 10 percent,
average occupancy for buildings ASHRAE Standard 62-2001 allows the results in a 10 percent increase in the
for the duration of operation of use of outdoor air delivered to the amount of outdoor air required to
occupied space to both dilute the properly ventilate the system.
the system, provided the average concentration of contaminants and to This requirement points to the need to
occupancy used is not less than transport them out of the occupied specify high quality supply-air diffusers
one-half of the maximum.” space. The ventilation rates listed in with good throw characteristics at all
Table 2 of the standard assume that the flow conditions. Trane’s line of linear slot
(Section 6.1.3.4) air in the occupied space is well-mixed, diffusers provides superior room airflow
with relatively uniform contaminant mixing performance, even at low airflow,
concentration levels throughout the and with minimal “dumping.” Models
space. It states: are available for most popular ceiling
“Ventilating systems for “The values in Table 2 define the types.
spaces with intermittent or outdoor air needed in the occupied zone Intermittent Occupancy
variable occupancy may have for well-mixed conditions (ventilation For some variable-occupancy spaces, the
effectiveness approaches 100 percent.”) standard allows a calculated minimum
their outdoor air quantity
(Section 6.1.3.3) space ventilation rate based on average
adjusted…to provide sufficient space occupancy rather than peak space
dilution to maintain The important point of this section is that occupancy. Specifically, Standard 62
the space ventilation rates listed in Table states:
contaminant concentrations 2 assume “well-mixed” air within the
“Where peak occupancies of less than
within acceptable levels at space. In reality, however, the designer
three hours duration occur, the outdoor
should not necessarily assume that all of
all times.” the outdoor air entering the building gets
air flow rate may be determined on the
(Section 6.1.3.4) basis of average occupancy for buildings
to the occupied space, or more
for the duration of operation of the
importantly, to the occupants. The air
system, provided the average occupancy
that passes from the supply diffuser to
used is not less than one-half of the
the return grille without reaching the
maximum.”
“When contaminants are occupants should be discounted since it
generated in the space or offers no dilution benefit. The standard (Section 6.1.3.4)
states:
the conditioning system Suppose, for example, a conference
“The ventilation effectiveness is defined room has an average occupancy of 75
independent of occupants by the fraction of the outdoor air percent and that it will be occupied at
or their activities, supply delivered to the space that reaches the design levels for less than three hours in
occupied zone…It is, however, not duration. Under these circumstances, the
of outdoor air should lead uncommon to find some of the design space ventilation rate could be
occupancy so that the acceptable ventilation air to be bypassing the calculated using the average space
conditions will exist at the start occupants (moving from supply to population (75 percent) rather than peak
exhaust without fully mixing in the population (100 percent). The per person
of occupancy.” occupied zone)…Such flow conditions ventilation rate remains the Table 2
(Section 6.1.3.4) should be avoided.” values. Auditoriums, conference rooms,
(Section 6.1.3.3) and training or meeting rooms often
qualify as intermittently occupied spaces.
The standard suggests that air
Interpretation IC 62-1999-18 helps clarify
distribution systems be designed to
this provision by stating:
minimize bypass. The engineer must
make a judgment on this value and The occupancy is to be averaged over
increase the space ventilation rate by an the duration of operation of the system
appropriate amount to assure delivery of …The intermittent occupancy provision
the proper amount of outdoor air, per contained in 6.1.3.4 of the Standard also
Table 2, after accounting for ventilation can be applied to multiple daily episodes
effectiveness. of peak occupancy as long as each is for
15 ISS-APG001-EN
less than three hours. It is intended to building materials and furnishings, and “Tables B-1 and B-3
apply to occupancy profiles that permit accumulate during unoccupied periods.
pollutant reduction through over- The standard prescribes the required do not include all known
ventilation (on a per person basis) lead time based on occupant density contaminants that may
during intervening periods of reduced and the required ventilation rate. This be of concern, and these
occupancy between peaks. type of “lead-ventilation” control scheme
is similar to night purge operation. concentration limits may not,
Standard 62 adds:
Preoccupancy purge may be an effective ipso facto, ensure acceptable
“Ventilating systems for spaces with
intermittent or variable occupancy may way to assure that contaminants that indoor air quality with respect
have their outdoor air quantity adjusted may build up during unoccupied periods
are removed prior to occupancy. to other contaminants.”
…to provide sufficient dilution to
maintain contaminant concentrations However, it may still be necessary to (Section 6.2.1)
within acceptable levels at all times.” manage indoor humidity levels during
these intervals. As explained in the
(Section 6.1.3.4) “Humidity Management” section of
this guide, indoor humidity levels over “Recirculation with air-cleaning
Although ASHRAE Standard 62-2001 60 percent RH for periods as short as
allows the quantity of outdoor air being 24 hours can support the growth of systems is also an effective
delivered to intermittently occupied some forms of mold and fungi. means for controlling
spaces to be reduced below the values in
Table 2, acceptable contaminant levels Summary of Ventilation Rate Procedure contaminants when using the
must also be maintained. Additionally, Section 6.1 of ASHRAE Standard 62-2001 Indoor Air Quality Procedure.”
the intermittent occupancy provision provides the building designer with a
prescriptive method for achieving (Section 6.2.3)
cannot be used if the outdoor airflow is
to be reduced during periods of partial acceptable indoor air quality. It is very
occupancy (such as the case with CO2- concise and complete for some design
based demand-controlled ventilation). issues and somewhat unclear on others.
Interpretation IC 62-1999-4 states that: Overall, it provides the engineer with a
valuable, relatively well-defined
If the total outdoor air supply based on procedure for designing and specifying
the occupied space is reduced during ventilation systems.
periods of less occupancy by demand
control, it is improper to also apply For more information on the Ventilation
the variable provision of 6.1.3.4. Rate Procedure, refer to ASHRAE
Concentration of occupant generated Standard 62-2001 and to the Trane
contaminants would not then be Engineers Newsletter titled “ASHRAE
adequately decreased with reduced 62-89 Analysis, Part 2: Ventilation Rate
occupancy to render the space suitable Procedure” (Volume 22, Number 1).
for future occupancy.
Preoccupancy Purge
The standard suggests that ventilation Indoor Air Quality Procedure
may need to precede occupancy for (Section 6.2)
variable-occupancy spaces to assure that The Indoor Air Quality (IAQ) Procedure
the indoor air is acceptable by the time presents an alternative, performance-
occupancy begins. Specifically, the based method for achieving acceptable
standard says: indoor air quality by setting limits on the
“When contaminants are generated in concentration of all known and
the space or the conditioning system specifiable contaminants. More
independent of occupants or their specifically, the IAQ Procedure sets limits
activities, supply of outdoor air should for 10 contaminants, prescribes a
lead occupancy so that the acceptable subjective analysis to determine
conditions will exist at the start of acceptable odor levels, and describes the
occupancy.” use of treated, recirculated air to reduce
the minimum outdoor airflow rates
(Section 6.1.3.4) presented in the standard.
In most buildings, contaminants (namely Tables 1 and 3 of Standard 62 list the
VOCs) continuously out-gas from maximum acceptable indoor

16
ISS-APG001-EN
Fundamentals of Good Indoor
Air Quality

“If cleaned, recirculated air concentration levels of 10 contaminants. To clean air returning from the occupied
By reference to these tables, the indoor space, recirculate it as ventilating air, and
is used to reduce the outdoor concentration of the listed contaminants thereby reduce the minimum outdoor
airflow rate below the values must be maintained below the levels airflow rates listed in Table 2, the
shown in Table 2, the Indoor listed. Even if levels are maintained designer must use the IAQ Procedure—
below the maximum allowed, however, not the Ventilation Rate Procedure. Some
Air Quality Procedure, 6.2, acceptable indoor air quality is not contaminants, particularly gaseous ones,
must be used.” necessarily assured. The standard states: may not be adequately cleaned from
“Tables B-1 and B-3 do not include all the recirculated air stream. Such
(Section 6.1.3.2) contaminants can accumulate in the
known contaminants that may be of
concern, and these concentration limits occupied space, eventually reaching
may not, ipso facto, ensure acceptable unacceptable concentration levels.
indoor air quality with respect to other Therefore, acceptable indoor air
contaminants.” quality must be determined using the
performance-based IAQ Procedure.
(Section 6.2.1) To avoid this necessity, many building
designers do not specify cleaning
Odor control is another objective of recirculated air solely to reduce the
this procedure. Many odor-causing minimum ventilation rate.
contaminants cannot be measured
in terms of concentration levels or Summary of the IAQ Procedure
do not have established concentration Section 6.2 of ASHRAE Standard 62-2001
thresholds. Therefore, a designer cannot attempts to provide the building
comply with the IAQ Procedure without designer with an alternate method for
a subjective evaluation of the completed providing acceptable indoor air quality
system. The standard speaks to this through direct contaminant control.
subjective evaluation by stating: Unfortunately, the standard presents
only a short list of acceptable
“One method that may be used for contaminant levels. It also includes a
measuring subjective response is requirement for a post-design, subjective
described in Appendix B.” evaluation for odors, and requires
(Section 6.2.2) ongoing building system vigilance on
the part of the designer after the building
Appendix B outlines a method whereby is designed and occupied. This leaves
if 80 percent of a panel of at least 20 the building designer without a clear
untrained observers deems the air definition of acceptable indoor air quality.
unobjectionable under representative Consequently, most designers prefer the
use, the air quality is acceptable. These Ventilation Rate Procedure because its
observations are intended to detect more prescriptive nature and clearer
offensive odors only. The standard also requirements provide a more
cautions that meeting the requirements straightforward path to compliance.
of the subjective test does not guarantee
that other contaminants are not present. For more information on the Indoor Air
Cleaning of Recirculated Air Quality Procedure, refer to ASHRAE
The IAQ Procedure allows cleaning Standard 62-2001 and the Trane
(filtering) of recirculated air as a means Engineers Newsletter titled “ASHRAE
to reduce the minimum space ventilation 62-89 Analysis, Part 3: Indoor Air Quality
rates given in Table 2. It states: Procedure” (Volume 22, Number 2).

“Recirculation with air-cleaning systems


is also an effective means for controlling Ventilation Control Strategies
contaminants when using the Indoor Air Typically, spaces within buildings are not
Quality Procedure…If cleaned, occupied at the same levels at all times
recirculated air is used to reduce the throughout the day. ASHRAE Standard
outdoor airflow rate below the values 62-2001 requires that all spaces in a
shown in Table 2, the Indoor Air Quality building must be properly ventilated
Procedure, 6.2, must be used.” at all system load conditions whenever
the spaces are occupied. Specifically it
(Sections 6.2.3 and 6.1.3.2) states:

17 ISS-APG001-EN
“When the supply of air is reduced control the volume of outdoor air “When the supply of air is
during times the space is occupied assures that the desired outdoor airflow
(e.g. in variable-air-volume systems), is actually introduced into the system. reduced during times the space
provision shall be made to maintain It may also be beneficial as verification is occupied (e.g. in variable-air-
acceptable indoor air quality throughout of the system’s actual performance. volume systems), provision
the occupied zone.” Ventilation Reset shall be made to maintain
(Section 5.3) This control strategy uses the actual
airflow and design ventilation rate of acceptable indoor air quality
As we discussed earlier in the “Multiple- each space in VAV systems to determine throughout the occupied zone.”
Space Systems” section of this guide, how much outdoor air is required at the
systems serving more than one space system-level air handler. In a typical VAV (Section 5.3)
must be capable of varying the ratio system, the supply air is a mixture of
of outdoor air to supply air. This outdoor air and recirculated return air
requirement has fostered a number of that is delivered to the space through
ventilation control strategies. All of them a common duct. While the amount of
directly or indirectly attempt to track supply air to each space varies with
occupancy levels (count people) and/or thermal load, the amount of ventilation
loads within the spaces and reset the air required by that space often remains
system outdoor airflow rate based on constant. Herein lies the challenge of
the need (or demand) for ventilation at properly ventilating buildings with VAV
that time. systems. To properly ventilate spaces
Controlling a system operating served by VAV systems, the richness (or
parameter such as temperature or percentage) of outdoor air contained in
airflow by means other than directly the supply airstream must change as the
measuring it can be difficult and many volume of air delivered to the spaces
times inaccurate. In the case of outdoor changes. As noted earlier in our
airflow, the ability to measure and discussion of the Ventilation Rate
control the amount of outdoor air Procedure, Equation 6-1 links the
brought into the system is fundamental ventilation requirements of the individual
to properly ventilating multiple-space spaces to the amount of outdoor air
systems. The ability to measure and required at the system-level air handler.

Figure 8: Ventilation Reset System Control Strategy

RA

Central Station
Air Handlers with
Controls

OA SA

DDC/VAV
Outdoor Airflow Measurement Terminal
and Control Device
Total Supply
Airflow Required
Communicating Ventilation
BAS Primary Airflow
Calculated Space
Calculated Minimum Outdoor Ventilation Fraction
Airflow Setpoint
Critical Space

18
ISS-APG001-EN
Fundamentals of Good Indoor
Air Quality

“Comfort (odor) criteria with As the name implies, ventilation reset package called the Traq™ Comfort
dynamically adjusts the amount of System. For complete details, see your
respect to human bioeffluents outdoor air brought into the building local Trane representative for a copy of
are likely to be satisfied if the based on real-time system operating SYS-EB-2 and CLCH-S-26.
ventilation results in indoor parameters to assure that each zone is
properly ventilated at all times. Key Scheduled Ventilation
CO2 concentrations less than hardware needed to implement a The amount of ventilation air delivered
700 ppm above the outdoor air ventilation reset control system are: to a space can also be varied based on a
concentration.” • direct digital controls (DDC) at the VAV time-of-day schedule. This is especially
terminals and air handler, appropriate for facilities with repeatable
(Section 6.1.3) and documented occupancy patterns,
• a building automation system (BAS)
capable of calculating Equation 6-1, such as schools. In this strategy, the
• and the ability to measure and control ventilation schedule resides in the
the outdoor airflow at the air handler. building automation system (BAS)
which, in turn, communicates the
Here is how ventilation reset works: The outdoor airflow setpoint to the air
DDC/VAV terminals continually measure handler or terminal unit serving the
the amount of supply air delivered to space. The outdoor airflow is reset as
each space. The design ventilation rate necessary (typically hourly in the case
for each space is known by the DDC/VAV of schools) to match space occupancy
terminal controller or the BAS. Knowing schedules and associated ventilation
the current supply airflow and the design requirements.
ventilation rate, a ventilation fraction (F)
can be continually calculated for each Resetting outdoor airflow based on
space. As the BAS polls the VAV a schedule of space occupancy can
terminals, it continually identifies the significantly reduce outdoor airflow
space with the critical (highest) space during periods of low occupancy
ventilation fraction. By summing the while complying with the standard’s
supply airflow from the VAV zones (Vst) requirement to properly ventilate at all
and knowing the ventilation fraction of times and at all operating conditions.
the critical space (Z), the BAS system The key again is the ability to measure
can solve Equation 6-1 to determine and control system outdoor airflow.
the exact amount of outdoor air that is Trane has successfully implemented this
needed at the air handler (Vot). The BAS control strategy on numerous school
sends the new outdoor airflow setpoint projects.
to the air handler which repositions the CO2-Based Demand-Controlled
outdoor-air damper to satisfy that Ventilation
specific operating condition. The result is Another method of controlling
a VAV system that fully complies with the ventilation is based on measured carbon
ventilation requirements of ASHRAE dioxide (CO2) levels within the occupied
Standard 62-2001 and minimizes costly space. CO2, a byproduct of human
overventilation. respiration, can serve as an indicator of
Another important benefit that should space ventilation rate (outdoor airflow
not be overlooked is the ability of a per person) or of the number of people
“communicating” DDC control system occupying a space, and thus some use it
to document system performance. The to determine the amount of ventilation
airflows for each zone can be easily air required. ASHRAE Standard 62-2001
logged by the BAS to provide verification offers the following comment on CO2:
of the ventilation provided to each zone “Comfort (odor) criteria with respect to
in the event of legal challenges. The human bioeffluents are likely to be
“data-rich” environment of a DDC satisfied if the ventilation results in
control system can help prove that indoor CO2 concentrations less than
you are “doing it right.” 700 ppm above the outdoor air
concentration.”
Trane combines the ventilation reset (Section 6.1.3)
control strategy with a supply fan
pressure optimization routine in a

19 ISS-APG001-EN
Unlike the other excerpts we have the system has been controversial. For copies of these
examined, this statement is an To date, ASHRAE has published four
observation rather than a requirement or official interpretations dealing with this interpretations, visit the
a suggestion. As such, it notes that odors issue. In the first three interpretations, the Standards section of the
associated with people are likely to be ASHRAE committee concluded that just ASHRAE Web site
controlled if the space CO2 concentration limiting the indoor CO2 level to 700 ppm
is maintained at a level less than 700 above the outdoor concentration, (www.ashrae.org).
ppm above the outdoor concentration. through either dilution or treatment,
This observation is often interpreted to does not assure acceptable indoor air
mean that acceptable indoor air quality quality and does not meet the
can be assured by maintaining the space requirements of Standard 62.
CO2 concentration at 700 ppm above the The first interpretation (IC 62-1989-7)
outdoor concentration. While this might states that:
be true in some cases, achieving
acceptable indoor air quality is not The Ventilation Rate Procedure is
always this easy. Many experts claim intended to control many more factors
that the correlation between CO2 and than the level of CO2. That very fact
acceptable indoor air quality is weak. disallows the use of CO2 control to
At concentrations typically found in reduce outdoor air intake below Table 2
buildings, CO2 is not considered harmful. values, if compliance with the
CO2 is a “tracer gas” used to indicate Ventilation Rate Procedure is claimed.
the amount of people-generated The Indoor Air Quality Procedure
contaminants (odors) in the space, requires consideration of many more
but it does not reflect the indoor factors than the level of CO2. Therefore,
concentrations of other contaminants, CO2 control of outdoor air intake or the
such as those generated within the filtration of CO2 cannot be used as sole
building (VOCs) or those brought in proof of compliance under the Indoor Air
from outdoors. Quality Procedure.
The acceptability of using measured Filtration of CO2 is not an appropriate
space CO2 concentrations to control the way to comply with Standard 62, since
amount of outdoor air introduced into CO2 is a surrogate for other

Figure 9: Equilibrium of CO2 Concentration at Various Ventilation Rates

2000
Indoor CO2 Concentration (ppm)

1500
10 cfm/person

1000 15 cfm/person

20 cfm/person
700
ppm

500
350 ppm Outside CO2 Concentration

Time

20
ISS-APG001-EN
Fundamentals of Good Indoor
Air Quality

contaminants. Removal of CO2 may not The fourth and most recent
have any effect on the contaminants for interpretation (IC 62-1999-33) allows the
which it is a surrogate (e.g., occupant use of CO2-based demand-controlled
odors). ventilation to reduce the outdoor air
In the second interpretation (IC 62-1999-03), supply during periods of reduced
the committee clarified the 700 ppm occupancy, provided other system and
value as follows: control provisions are met. One such
requirement is that the intermittent
The reference to 700 ppm CO2 in Section occupancy provision in Section 6.1.3.4
6.1.3 is only a point of information. This (see pages 15 - 16 of this guide) cannot
is not a requirement of ASHRAE be used to lower the maximum
62-2001. Since it is not a requirement occupancy for the purpose of reducing
it is neither a ceiling value nor a time- the design ventilation rate.
weighted average value. Rather, it can
be considered an indicator that the A second provision suggests the need
outdoor air ventilation may not meet the for a non-zero base ventilation rate
minimum requirements of the standard. However, good practice, and the
The third interpretation (IC 62-1999-04) rationale on which the ventilation rates
further states: in Table 2 are based, indicates the need
for a non-zero base ventilation rate to
The CO2 level of 700 ppm above handle non-occupant sources whenever
outdoors is a guideline based on the the space is occupied.
perception of human bioeffluents, not
a ceiling value for air quality. Neither this interpretation nor the
standard currently defines this base
While CO2 cannot be used to directly ventilation rate. All the requirements
determine whether there is acceptable listed in interpretation IC 62-1999-33
IAQ in the space, it can be used to should be carefully studied before
determine the quantity of outdoor air a CO2-based demand-controlled
(on a per person basis) that is being ventilation control strategy is adopted.
delivered to the space. By measuring
the CO2 concentration within a space Using measured CO2 levels to control
and the outdoor concentration, we can ventilation can reduce system operating
determine the real-time CO2 differential costs, especially in applications where
between indoors and outdoors. contaminant levels result primarily from
people and where population varies
The relationship between indoor/outdoor significantly (such as gymnasiums, large
CO2 differential and the quantity of meeting rooms, and auditoriums). Since
outdoor air (on a per person basis) being occupancy of these types of spaces is
supplied to a space depends on the level generally planned and therefore known
of occupant activity and the associated in advance, scheduling the ventilation
CO2 generation rate. An example of this requirements of these spaces may
relationship is depicted in Figure 9. For be simpler than meeting all of the
example, when 15 cfm/person of provisions listed in interpretation
outdoor air (with a CO2 concentration IC 62-1999-33. Additionally, if the space
of 350 ppm) is delivered to a space, at qualifies for the intermittent occupancy
equilibrium, the CO2 concentration in provision of the standard, it may be
that space will be about 1050 ppm. easier to reduce the design population
This equates to a 700 ppm difference (and therefore the design ventilation
between indoor and outdoor CO2 rate), which also results in smaller
concentrations. equipment.
This CO2 differential can be used to reset Outdoor Airflow
the ventilation system to deliver the
proper amount of outdoor air per person Measurement and Control
(according to Table 2 in the standard), The ability to measure and control
based on actual occupancy and air outdoor airflow at the air handler is
delivery operation. This practice is often fundamental to implementing any of
called “CO2-based demand-controlled the ventilation control strategies just
ventilation”. discussed. One way to cost-effectively

21 ISS-APG001-EN
measure outdoor air in central station are no leaving ductwork restrictions.
or large commercial rooftop air-handling In effect, the Traq damper delivers the
units is to use airflow measurement performance of an airflow measuring
dampers. An example of this technology station in the space of a standard
is Trane’s Traq™ damper, which louvered outdoor air damper.
combines airflow measurement and Indirect methods of outdoor air
control in a single, factory-mounted measurement such as damper position,
device in lieu of standard blade dampers the use of the mixing equations (based
in the mixing box. The Traq damper on CO2 or temperature), or fan speed
directly measures airflow and can be usually do not provide the required
used to measure outdoor air, return air, accuracy at low airflow conditions to
or both. properly implement these ventilation
Trane Traq dampers perform the control strategies. Therefore, direct
combined functions of a flow-measuring measurement of outdoor airflow, with
station and a set of control dampers, a device such as the Traq damper or an
but with some important differences. airflow measurement station, is
Traditional airflow-measuring stations recommended.
require additional lengths (up to three
duct diameters) of straight ductwork Traq airflow sensing and control
entering and leaving the measurement technology is available today on
device to obtain the cataloged accuracy. Trane M-Series™ and T-Series™ Climate
The unique flow-shaping bellmouth inlet Changers, IntelliPak™ rooftop units,
of the Traq damper straightens and and commercial self-contained units.
accelerates the airflow before it passes For technical application information
over the flow-sensing ring. Measurement on Traq damper systems, contact
accuracy is enhanced by temperature your local Trane representative and
compensation and periodic automatic re- ask for CLCH-TS-8.
zeroing of the pressure transducer. From
the standpoint of installation space, the The new Operations and Maintenance
bellmouth inlet design reduces the Traq section of Standard 62 (Section 8)
damper’s entering ductwork requirement addresses the calibration of outdoor
to merely a low velocity, 90-degree airflow measurement devices as follows:
radius elbow directly ahead of the
damper or one hydraulic duct diameter “Sensors whose primary function is
upstream for mitered elbows. Because it dynamic minimum outdoor air control,
is an integral part of the air handler, there

Figure 10: Minimum Ventilation Rate with CO2-Based Demand-Controlled


Ventilation

Vot

VPeople
Outdoor Air (cfm)

Variable Ventilation
Based on CO2 Level

VBuilding

22
ISS-APG001-EN
Fundamentals of Good Indoor
Air Quality

such as flow stations at an air handler Exhaust systems used in buildings with
and those used for demand control variable-air-volume (VAV) systems must
ventilation, shall have their accuracy be capable of modulating airflow in
verified…This activity shall occur at a response to the varying system supply
minimum of once every six months.” air. A constant volume exhaust system
(Section 8.4.1.7)
can create a negative pressure within the
building as the system supply airflow
Additionally, Section 8.4.1.8 requires that throttles down at part-load conditions.
the minimum outdoor air quantity (in Another important consideration is
units designed to deliver less than 2,000 coordination of the exhaust and supply
cfm of supply air) be measured at least air systems during unoccupied periods.
every five years to verify the airflow rates A similar negative pressure situation will
are in compliance with the standard. occur if the exhaust system (including
bathroom exhaust and other local
Building Pressure Control exhaust fans) operates when the main
An HVAC system should be controlled
supply air system is idle. Coordination of
to maintain a neutral or slightly positive
building exhaust and intake at all times is
pressure inside the building relative to
crucial to proper building pressurization.
outdoors. A positive pressure prevents
uncontrolled infiltration of outdoor air Many designers try to control building
into the building through cracks and pressure by indirectly tracking system
other small openings in the building exhaust and outdoor air intake based
shell. However, maintaining the correct on fan speed, or inlet vane or discharge
pressure relationships at all operating damper position. Often, this approach
conditions during occupied and does not yield the accuracy necessary
unoccupied periods requires careful for proper building pressure control.
consideration in the design and Variable resistances caused by filter
operation of the system. Building loading, stack effect, and wind can
pressure will be affected by natural considerably affect building pressure
stack and wind effects, as well as by balance. For this reason, Trane
mechanical effects such as bathroom, recommends controlling space pressure
kitchen, and building exhaust fans, or by directly measuring the pressure
the operation of an airside economizer. differential across the building envelope.

Figure 11: Trane Traq Damper

Traq Damper
Mixing Box

Flow-Shaping
Bellmouth Inlet

Averaging Flow
Sensor

Low Leak
Dampers

23 ISS-APG001-EN
Direct building pressure control can be recommends maintaining indoor relative “High humidities can support
accomplished at the unit level (stand- humidity levels between 30 percent and
alone) with devices such as the 60 percent. Humidity levels less than the growth of pathogenic or
Statitrac™ system on Trane IntelliPak 30 percent cause some people allergenic organisms. Examples
rooftop units or through coordination of respiratory discomfort while humidity include certain species of fungi,
system components using a Trane Tracer levels over 70 percent near surfaces
Summit™ building automation system. for extended periods of time promote associated mycotoxins, and dust
Contact your Trane representative to the growth of some forms of mold mites…Relative humidity in
discuss available building pressure and fungi. Today, microbiological
control options. contamination (mold and fungi) is a habitable spaces preferably
common cause of occupant complaints should be maintained between
For more information on building and IAQ problems in buildings. 30 percent and 60 percent
pressurization control, contact your local Although there are many different
Trane representative for a copy of the relative humidity to minimize
species of fungi, they all share the
“Building Pressurization Control” same basic needs for survival: growth of allergenic and
application manual (literature order
number AM-CON 17). • organic matter (nourishment) pathogenic organisms.”
• moisture (liquid water or relative (Section 5.10)
humidity > 70 percent)
Humidity Management • moderate temperatures (40°F to 100°F)
Uncontrolled moisture in buildings can
contribute to unacceptable indoor air • source of spores
quality, occupant discomfort, and Controlling indoor moisture levels is one
damage to the building structure and way to control propagation of fungi and
furnishings. One source of building dust mites inside buildings: in the
moisture is water vapor contained in the carpets, wall coverings, and furnishings,
indoor air. ASHRAE Standard 62-2001 as well as within the HVAC system itself.

Figure 12: Traq Damper Installation with Radius Elbow

Radius Elbow
R/H ≥ 0.75

Traq Damper
Mixing Box

24
ISS-APG001-EN
Fundamentals of Good Indoor
Air Quality

ASHRAE Standard 62-2001 addresses For more detailed information on


the need to control indoor humidity: the problem of moisture in buildings,
“High humidities can support the contact your local Trane representative
growth of pathogenic or allergenic for a copy of the “Managing Building
organisms. Examples include certain Moisture” application manual
species of fungi, associated mycotoxins, (literature order number SYS-AM-15).
and dust mites…Relative humidity in
habitable spaces preferably should be Most buildings require some form of
maintained between 30 percent and 60 humidity control: dehumidification,
percent relative humidity to minimize humidification, or both. HVAC systems
growth of allergenic and pathogenic differ in their ability to control humidity.
organisms.” Most air-conditioning systems use a
(Section 5.10)
cooling coil to sensibly cool the supply
air and remove moisture by lowering the
Building shell leaks, spills, and air temperature below its dew point. (The
condensation on cold surfaces are some latter causes much of the water vapor in
of the most obvious forms of water the supply air to condense on the surface
intrusion into a building. However, of the coil and be drained away.)
moisture also enters buildings with Reducing the cooling coil’s leaving
humid outdoor air brought in for air temperature below its dew point is
ventilation purposes. Uncontrolled key to the system’s ability to properly
infiltration of outdoor air due to dehumidify. Let’s look at the two most
inadequate building pressurization, common types of HVAC systems from
permeation through porous building the standpoint of their ability to control
materials, and from respiration and space humidity.
perspiration of the building occupants Constant-Volume (CV)
all contribute moisture to the indoor
environment. Humidity control is
Systems
In constant-volume, variable-temperature
especially challenging in buildings with
systems, the amount of air supplied to
high occupant densities, such as schools
a space is held constant while the
and auditoriums, due to their high
temperature of the air delivered is
ventilation rates.

Figure 13: Prerequisites for Microbial Growth (add “40°F to 100°F” under
Temperature callout)

Organic Matter
(dirt) Temperature
(40°F - 100°F)

Sources of
Spores Water or RH>70%

25 ISS-APG001-EN
varied to satisfy the thermal comfort your local Trane representative for a
requirements of the space. Outdoor air is copy of the “Dehumidify with Constant-
introduced at the air handler or terminal Volume Systems” Engineers Newsletter
unit and distributed with the supply air. (volume 29, number 4) and the
Systems controlled in this manner “Dehumidification in HVAC Systems”
typically have leaving air temperatures application manual (literature order
sufficient to dehumidify effectively at number SYS-APM004-EN).
design load conditions, but their ability
to dehumidify can decrease significantly Two common methods used to address
at part-load conditions. This can result this part-load humidity control challenge
in serious building humidity control in a constant-volume system are:
problems at off-peak conditions, which
represent the majority of the operating • use of an active humidity control
hours. strategy with supply-air tempering
(reheat)
The dehumidification challenge with CV
• use of a dedicated, central air handler
systems is driven by the fact that these
to separately condition the outdoor air
systems are usually controlled to
respond to the sensible load in the space Active humidity control involves
only, by maintaining the space dry-bulb monitoring and controlling both the dry-
temperature at setpoint. When the space bulb temperature and humidity in the
sensible load is high, the temperature of occupied space. Whenever the space
the air leaving the cooling coil is low, humidity is below the preset upper limit
which allows moisture to condense out (typically 60 percent relative humidity),
of the air. At this condition, the system’s the system operates just like a normal
latent cooling (dehumidification) capacity constant-volume system. However, if the
is usually sufficient to control space space humidity reaches or exceeds the
relative humidity below 60 percent. upper limit, the cooling coil control valve
However, in the morning, or during the is driven open, (or in the case of a direct-
fall and spring, when the space sensible expansion (DX) system, the compressors
load is low, the air leaves the cooling are commanded to operate) regardless
coil at a higher temperature to avoid of the need for sensible cooling in
overcooling the space. The dry-bulb the space. The coil overcools the air,
temperature of the air leaving the coil increasing the dehumidification
often exceeds the dew point of the air, capacity of the system.
which significantly reduces the system’s With this control sequence, a reheat coil
ability to dehumidify. For the most part, is needed downstream of the cooling coil
only sensible cooling occurs and control to temper (reheat) the cold air leaving the
of space humidity is lost. cooling coil during the dehumidification
mode to avoid overcooling the space at
For more detailed discussion of the low sensible load conditions. Normally,
humidity control challenges associated only a 5°F to 15°F temperature increase
with constant-volume systems, contact is required of the reheat coil. Many times

Figure 14: Recommended Indoor Relative Humidity

ASHRAE
Recommended

Comfort Mildew
Problems Growth

0 10 20 30 40 50 60 70 80 90 100
Relative Humidity, %

26
ISS-APG001-EN
Fundamentals of Good Indoor
Air Quality

this relatively small amount of heat can flexibility of the system by treating
be recovered from the condenser of a the outdoor air independent of the
water-cooled chiller or from the hot recirculated air. The dedicated outdoor-
refrigerant in a DX system. The key to air unit cools, heats, dehumidifies, and/or
cost-effectively applying an active humidifies all of the outdoor air required
humidity control system is the ability to by the system for ventilation. During the
use reheat only when it is needed. This cooling season, the outdoor air is
requires the sensing of both humidity dehumidified to a dew point lower than
and temperature in the occupied space. the space. This removes the internally-
When the space humidity level falls generated latent loads from the local
below the upper limit, the system returns terminal units, requiring them to handle
to the standard cooling mode and again only the internal sensible loads. The
operates like a traditional constant- dedicated outdoor-air unit, therefore,
volume system. handles the entire outdoor-air load
(sensible and latent) and the internally-
For complete information on Trane’s generated latent loads.
active humidity control system for This conditioned outdoor air is then
unit ventilators, ask your local Trane delivered directly to the occupied spaces
representative for a copy of the “Active or to the outdoor-air intake of one or
Humidity Control with Unit Ventilator more local units (Figure 16). As
Systems” engineering bulletin mentioned, the outdoor air is
(literature order number UV-EB-11) dehumidified to a low dew point. This
and the “Dehumidification in HVAC conditioned outdoor air can be delivered
Systems” application manual (literature to the rest of the system at this cold
order number SYS-APM004-EN). temperature or reheated to a “room-
neutral” dry-bulb temperature (typically
A system configuration, commonly 70°F to 72°F).
referred to as a dedicated outdoor-air Dedicated outdoor-air ventilation
system, has emerged as an interesting systems can be provided with DX or
twist to ventilating terminal unit systems. chilled-water cooling. The primary
Most terminal unit systems are constant- advantage of this approach is enhanced
volume (CV) systems. One way to deal humidity control at all load conditions.
with the reduced dehumidification In addition, this system can result in
capacity of these systems at part-load smaller, quieter, and, in some cases,
conditions is to separate the outdoor lower-cost terminal units in the spaces.
air from the recirculated air. Decoupling
these two air paths increases the

Figure 15: Basic Components of an Active Humidity Control Strategy

RA Cooling Reheat
Coil Coil

SA
OA

Economizer
Sensor OA Damper
Actuator
T RH

Unit
Controller
Space
(zone)
Tracer
Summit

27 ISS-APG001-EN
For more information on designing outdoor air for the system and distribute
dedicated outdoor-air systems, contact it to the spaces along with the supply air.
your local Trane representative for VAV systems typically control humidity
a copy of the “Designing Dedicated well at all system load conditions
Outdoor-Air Systems” engineering because the temperature of the air
bulletin (literature order number leaving the cooling coil is held constant
SYS-EB-3) and the “Dehumidification and does not vary with space load. Low
in HVAC Systems” application manual temperature air, typically between 45°F
(literature order number and 55°F, is supplied to the spaces at all
SYS-APM004-EN). times. Since this is usually below the
target space dew point, it provides
adequate dehumidification. Obviously,
Variable-Air-Volume (VAV) resetting the supply-air temperature
Systems upward in a VAV system can significantly
Another popular air delivery system impair its ability to control humidity and
is the variable-volume, constant- must be carefully evaluated.
temperature system commonly known
as the VAV system. In a VAV system, the For more information on the
temperature of the supply air is held dehumidification performance of VAV
constant while the amount of air systems, contact your local Trane
delivered to each space is varied in representative for a copy of the
response to the thermal load in that “Dehumidification in HVAC Systems”
space. VAV system air handlers, either application manual (literature order
indoor or rooftop-mounted, introduce number SYS-APM004-EN).

Figure 16: Dedicated Outdoor-Air System Configurations

OA

CA

RA RA
SA SA

OA

CA

CA CA

SA SA

RA RA

28
ISS-APG001-EN
Fundamentals of Good Indoor
Air Quality

As discussed earlier, Standard 62 also load profile and the associated


specifies a low limit of 30 percent for psychrometric performance of the HVAC
indoor relative humidity. This low limit system at all operating conditions to
is primarily based on personal comfort. assure that the performance parameters
Low humidity levels can necessitate can be met.
higher space temperatures for the same
level of thermal comfort and can cause Humidity Control vs. Heat
physical discomfort by drying occupants’ Recovery
nasal passages. Consequently, there are The requirement for larger amounts of
situations—usually in the winter—where outdoor air in buildings has prompted
indoor humidity levels must be the use of various air-to-air energy
increased to maintain comfort. When recovery devices to reduce the energy
applying humidifiers, it is important to required to condition this outdoor air.
add no more moisture than the supply One popular device is the total-energy
air can absorb without condensing. wheel (sometimes referred to as an
Saturated or nearly saturated supply “enthalpy wheel”). This desiccant-coated
air can lead to condensation in other device rotates between the outdoor and
cooler parts of the system, such as the exhaust air streams. In the summer,
ductwork or diffusers. when the outdoor air is hot and humid,
the total-energy wheel is used to
In summary, complying with the pre-cool and pre-dry the outdoor air
standard’s recommendation of by transferring both sensible heat and
managing indoor humidity between moisture to the exhaust air stream. In the
30 percent and 60 percent RH is a matter winter, when the outdoor air is cold and
of system selection, equipment sizing, dry, this same device is used to preheat
and control. Traditional constant-volume and pre-humidify the outdoor air by
systems rely on coincidental recovering both sensible heat and
dehumidification to control space moisture from the exhaust air stream
humidity. Their inability to manage and transferring it to the entering
humidity levels at all operating outdoor air stream.
conditions, specifically at part load, can
result in high space humidity levels that Preconditioning the outdoor air with a
can support the growth of mold and total-energy wheel reduces the energy
fungi. This, in turn, can lead to health required to heat, cool, humidify, and
problems and costly building damage. dehumidify the outdoor air. It also allows
Today, there are ways to “actively” the mechanical equipment to be
control indoor humidity with all system downsized. Figure 17 psychrometrically
types. Carefully analyze the building’s illustrates the effect of a total-energy
wheel on a system.

Figure 17: Air-to-Air Energy Recovery for Outdoor-Air Preconditioning

EA RA

OA OA MA SA
T

OA
96°F DB, 76°F WB

Preconditioned OA 81°F DB
MA
SA RA 76°F DB
55.7°F DB 74°F DB, 50% RH

29 ISS-APG001-EN
However, this device does little to from the air stream altogether. Filtration “Particulate matter filters or air
improve the indoor humidity control takes one or two forms, reflecting the
performance of a system. Even if the two general types of contaminants: cleaners having a minimum
total-energy wheel was 100 percent particulate and gaseous. Most HVAC efficiency reporting value
effective, the outdoor air passing through applications implement particulate (MERV) of not less than
the supply side of the wheel can only filtration to remove particles from the
equal the condition of the air passing air brought into and recirculated within 6…shall be provided upstream
through the exhaust side of the wheel. the building. of all cooling coils or other
Because the exhaust air came from the To aid designers, the standard
space, it has the same moisture level as devices with wetted surfaces
specifically addresses how to handle
the space. So, the air leaving the supply- outdoor air known or thought to contain through which air is supplied
side of the wheel can never be drier than contaminant concentrations that exceed to an occupiable space.”
the air entering the exhaust side, and, safe levels. (See “Ventilation Rate
therefore, cannot dehumidify the space. (Section 5.8)
Procedure” in the Ventilation section
of this guide.)
For more information on the use of air-
to-air energy recovery devices in HVAC Particulate Filtration
systems, contact your local Trane “Particulate contaminants” describes a
representative for a copy of the broad class of airborne physical matter
Engineers Newsletter titled “Dehumidify that exists as discrete grains or particles.
with Constant-Volume Systems” Members of this class include pollen,
(volume 29, number 5) and the “Air-to- microorganisms, skin flakes, dust, fumes,
Air Energy Recovery in HVAC Systems” and smoke; and their particle sizes range
application manual (literature order from 0.01 to more than 100 microns.
number SYS-APM003-EN). Particles of 10 microns or less generally
pose the greatest health hazard because
they are small enough to penetrate
Filtration the natural defenses of the body’s
The fourth IAQ fundamental, filtration, respiratory system. Unfortunately,
is a means of controlling contaminants their microscopic size makes them
by reducing their concentrations to the most difficult to remove.
acceptable levels, or by removing them

Figure 18: Common Particle Contaminants and Their Characteristics


Microns
.001 .005 .01 .05 .1 .5 1 5 10 50 100 1000
Human
Hair
Particulate Contaminants

Atmospheric Dust Visible to Human Eye

Plant Spores and Mold

Bacteria

Carbon Black Pollens

Tobacco Smoke

Insecticide Dust
Filter Types

Common Filters
High Efficiency Air Filters

Electrical Precipitators

.001 .005 .01 .05 .1 .5 1 5 10 50 100 1000


Microns

30
ISS-APG001-EN
Fundamentals of Good Indoor
Air Quality

“When compliance with this ASHRAE Standard 62-2001 makes contains thousands of different VOCs of
the use of particulate filters part of the countless origins, including construction
section (5.8) does not provide “standard of care” for ventilation system materials, furnishings, and cleaning
adequate control of gaseous design by stating: supplies.
contaminants, methods based “Particulate matter filters or air cleaners Standard 62 specifies maximum indoor
on sorption with or without having a minimum efficiency reporting concentration limits for a number of
value (MERV) of not less than 6…shall gaseous contaminants in Appendix B,
oxidation or other scientifically be provided upstream of all cooling coils and states that:
proven technology shall be or other devices with wetted surfaces “When compliance with this section
through which air is supplied to an (5.8) does not provide adequate control
used.” occupiable space.” of gaseous contaminants, methods
(Section 5.9)
(Section 5.8) based on sorption with or without
oxidation or other scientifically proven
Additionally, Section 7.1.2 states that technology shall be used.”
systems “shall not be operated without
(Section 5.9)
filters in place,” and Section 8.4.1
requires the replacement or maintenance Table B-1 in Appendix B identifies
of filters in accordance with the system’s “acceptable indoor concentration levels”
operation and maintenance manual (see for nine gaseous contaminants, but the
Figure 5). standard cautions that this list does not
Gaseous Filtration include all the known gaseous
Particulates are not the only contaminants that may need to be
contaminants of concern in recirculated addressed. The overwhelming number
and outdoor air streams. When inside of potential VOCs inside a building
a building, concentrations of certain makes individual measurement difficult
gases and vapors can be detrimental and expensive. As a result, the most
to occupant health. The most common common way of dealing with indoor
gaseous indoor contaminants include VOCs is to eliminate their sources
carbon monoxide, radon, oxidants whenever possible, then dilute whatever
(ozone), nitrogen oxides (NO and NO2), concentrations remain with outdoor air.
and volatile organic compounds (VOCs) The design engineer should carefully
such as formaldehyde and tolulene. consider out-gassing rates when
Controlling VOC concentrations pose a specifying construction materials and
special challenge. Filtration and source furnishings, while the building manager
control are difficult because a building needs to carefully evaluate the chemical
content of cleaning and maintenance
supplies used in the building.

31 ISS-APG001-EN
Summary

ASHRAE Standard 62-2001 provides and relationship to the four IAQ


sound direction on basic equipment and fundamentals of source control,
system design requirements, minimum ventilation, humidity management, and
ventilation rates, and construction, filtration must be carefully considered
operation, and maintenance procedures throughout the life of the building. Trane
which, together, will minimize the has responded by making sure all of its
potential for adverse health effect and applied HVAC products, from the
provide acceptable indoor air quality. smallest fan-coil units to the largest
It establishes the “standard-of-care” for central-station air-handling units, offer
ventilation system design, installation, features that strictly comply with the
operation, and maintenance. The requirements of ASHRAE Standard
informative and mandatory language 62-2001.
of the standard is interpreted as the Trane has over 80 years of experience
minimum requirements on which HVAC with all aspects of indoor comfort
system designers should base their systems. We have the design tools,
work. As such, full compliance with the products, and systems expertise to help
provisions of the standard is the only provide acceptable IAQ in a wide variety
prudent course for design professionals. of HVAC system types without
compromising the Standard 62
Acceptable IAQ is much more than requirements. Our offices are staffed
providing 15 cfm of outdoor air per with HVAC professionals ready to work
person! There is no single “silver bullet” with you to address any IAQ or system
that can assure good indoor air quality. selection and design issues you may
Instead it is the result of proper HVAC have on your new or existing buildings.
system selection and design, IAQ is a complex issue, but one answer
specification of equipment and is simple. Make Trane a member of your
furnishings, along with proper building team on your next building project.
operation and maintenance. Their impact

32
ISS-APG001-EN
Addenda Incorporated into ASHRAE
Standard 62-2001

33 ISS-APG001-EN
Suggested Mechanical Specifications

We have identified many HVAC Cleanable Interior


equipment and system features in this
guide. Clearly, acceptable indoor air Surfaces
quality requires a carefully considered, The wet section of the unit, defined
multifaceted strategy that begins with as the entering-air side of the
the type of HVAC system, equipment, dehumidification coil to the leaving
and control sequences selected, and edge of the drain pan, shall be insulated.
continues through how the building is The insulation shall meet UL 181
constructed, operated, and maintained. requirements. The air-stream surface
of the insulation shall be constructed
The example mechanical specification or coated so that it is not biodegradable,
language that follows addresses this repels water, and is nonporous to
strategy. We strongly encourage you to facilitate effective cleaning of dirt and/or
adopt it to ensure that the air-handling microbial growth. The manufacturer’s
equipment you specify includes the maintenance instructions shall describe
features essential to compliance with the proper cleaning procedure for the
ASHRAE Standard 62-2001. materials used.
Sloped, Noncorrosive Accessibility for Cleaning
Drain Pan and Inspection
The cooling-coil condensate drain pan Access for inspection and cleaning of
shall be constructed of smooth, the cooling-coil drain pan, coils, and fan
corrosion-resistant material. The bottom section shall be provided. The unit shall
of the drain pan shall be sloped in two be located and installed for proper
planes that pitch the condensate to the access. Procedures for proper access,
drain connection. Units with drain pans inspection, and cleaning of the unit
constructed of polymer material must shall be included in the manufacturer’s
meet the requirements of UL 1995. installation, operation, and maintenance
When the unit is installed and trapped literature.
per the manufacturer’s installation
manual, the drain pan shall not leave Airflow Measuring
puddles larger than 2 inches in
diameter and 1⁄8 inch deep for more Damper
than 3 minutes if subjected to the Provide a factory-mounted damper
following test: (or airflow monitoring station) in the
outdoor-air damper opening of the
• Temporarily plug the drain pan air handler mixing box as specified on
• Fill the drain pan with 1⁄2 inch of water the schedule. Damper blades shall be
(or the maximum allowed by the galvanized steel, housed in a galvanized
drain pan) steel frame, and mechanically fastened
• With a draw-through unit to an axle rod rotating on bearings. The
configuration, start the fan. Do dampers shall be rated for a maximum
not operate the fan if it is a blow- leakage rate of less than 1 percent of
through unit nominal cfm at 1 in. wg. The airflow
measurement station shall measure
• Remove the temporary plug
up to 100 percent of unit airflow. The
Note: Units with polymer drain pans airflow monitoring station shall output
must be UL 1995-listed to address fire a 2–10 VDC signal representing velocity,
code issues related to the presence of and shall have a total accuracy of
plastic material in the air stream. “UL +/-5 percent of actual airflow down to
1995 listing” means the entire UNIT 15 percent of nominal flow between
complies with the requirements of -40°F and 158°F. If required, field
NFPA 90A. assembly and calibration of the airflow
measurement station shall be the
responsibility of the installing contractor.

34
ISS-APG001-EN
Notes

35 ISS-APG001-EN
Notes

36
ISS-APG001-EN
Notes

37 ISS-APG001-EN
Notes

38
ISS-APG001-EN
ISS-APG001-EN
February 2002
IAQ-TS-1-07-98
La Crosse

You might also like