Company: M/s WVA Engineering Consultant Page: 1
Specifier: Mr. Atul Project: LNG Petronet
Address: Fastening point: revised to wall connection
Phone | Fax: | Date: 20/03/2020
E-Mail:
Specifiers comments: 10mm rebar at 100mm c/c using Re 500 V3 chemical
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Rebar ( c ) 2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.in Hilti PROFIS Rebar 2.5.1
Company: M/s WVA Engineering Consultant Page: 2
Specifier: Mr. Atul Project: LNG Petronet
Address: Fastening point: revised to wall connection
Phone | Fax: | Date: 20/03/2020
E-Mail:
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Rebar ( c ) 2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.in Hilti PROFIS Rebar 2.5.1
Company: M/s WVA Engineering Consultant Page: 3
Specifier: Mr. Atul Project: LNG Petronet
Address: Fastening point: revised to wall connection
Phone | Fax: | Date: 20/03/2020
E-Mail:
Selected solution
Bar size Drill bit size Bar spacing Distance Drilled hole required
centre/centre centre/surface
Layer of bars Φ [mm] D [mm] s [mm] cs [mm] ℓvreq [mm]
Top / left 1 10.0 14.0 100 1,055 204
Bottom / right 1 10.0 14.0 100 1,055 109
Required accessories
Section Analysis
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Rebar ( c ) 2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.in Hilti PROFIS Rebar 2.5.1
Company: M/s WVA Engineering Consultant Page: 4
Specifier: Mr. Atul Project: LNG Petronet
Address: Fastening point: revised to wall connection
Phone | Fax: | Date: 20/03/2020
E-Mail:
a) Reactions
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Rebar ( c ) 2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.in Hilti PROFIS Rebar 2.5.1
Company: M/s WVA Engineering Consultant Page: 5
Specifier: Mr. Atul Project: LNG Petronet
Address: Fastening point: revised to wall connection
Phone | Fax: | Date: 20/03/2020
E-Mail:
Lower layer
Design Input
Remarks
This design exclusively considers the local load transfer from the post-installed tensile reinforcement at the intersection between new and
existing concrete. The joint surfaces for concreting must be roughened to at least such an extent that aggregates protrude. It assumes that
adequate transverse reinforcement is provided in the anchorage area if required.
The shear load carrying capacity of the cross section has to be designed separately.
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Rebar ( c ) 2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.in Hilti PROFIS Rebar 2.5.1
Company: M/s WVA Engineering Consultant Page: 6
Specifier: Mr. Atul Project: LNG Petronet
Address: Fastening point: revised to wall connection
Phone | Fax: | Date: 20/03/2020
E-Mail:
The HIT Rebar Design is used in this calculation evaluates solely the strength of the connection; serviceability criteria are not considered.
Indications on displacements and creep of post-installed rebars can be found in the European Technical Approvals for anchors. The Installation
(drilling, cleaning, setting) must be according to the approval!
The user is repsonsible to check the amount of reinforcement in the existing structure. The frame node only works if there is sufficient
reinforcement in the existing part!
Fixed diameter and spacing selected. Please be aware that over-reinforcement of the section may lead to brittle failure of the fastening.
The accessory list in this report is for the information of the user only. In any case, the instructions for use provided with the product have to be
followed to ensure a proper installation.
User has defined the frame node strut angle as 30 degrees with engineering judgement.
Minimum reinforcement requirements are not checked by the software.
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Rebar ( c ) 2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan