You are on page 1of 2

PRESSURE SWITCHES

Designed for use with


ILP, IHP Automatic
Suppression Unit
DESCRIPTION

Pressure switch on valve (P/N 400001) is available as


an optional part of the cylinder valve assembly for low
pressure systems and is connected directly into the
pressurized portion of the cylinder valve. This pressure
switch is used to monitor unit actuation, or to energize
or de-energize electrically operated equipment. This
part also includes the bonded seal (P/N 600033)
required to ensure a pressure-tight connection.

Pressure switch on EOL Adapter (P/N 400004) can


Firetrace recommends that all units are coupled with a
be connected to an End of Line Adapter to provide
pressure switch and tied into a notification or shutdown
additional electrical functions as may be required.
device in the event of a discharge.
This part also includes a Pressure Switch Washer (P/N
400003) to depress the Schrader Valve in the End of
Pressure switch should always be installed at the end of
Line Adapter or Manual Release and an O-ring (P/N
the detection network for optimal signal speed.
400002) to ensure a proper seal is made when the unit
is connected.

A Pressure Switch Assembly with Complete Housing,


Pressure Switch and connector Assembly is also available.

At atmospheric pressure

www.firetrace.com
SWITCH CONFIGURATIONS

SPDT at atmospheric pressure: Closed between brown


and blue

ELECTRICAL DATA

Rising Pressure 135 +/- 10 PSI

Falling Pressure 70 +/- 10 PSIG

Temperature Range -20°F to 150°F

Electrical Rating

120VAC – 25A, 13 FLA, 60 LRA, 125VA


Terminal 1 & 3
240VAC – 25A, 10 FLA, 45 LRA, 125VA

120VAC – 10A, 5.8 FLA, 34.8 LRA, 125VA


Terminal 1 & 3
240VAC – 5A, 2.9 FLA, 17.4 LRA, 125VA

5 – 28 VDC 15A Inductive

PART NUMBER NAME APPLICATON LOCATION SYSTEM TYPE

400001(1) Pressure Switch Valve Mounted ILP

400004(2) Pressure Switch End-of-Line Adaptor DLP(3), ILP

400441 Pressure Switch Assembly 6mm Complete Housing, Pressure Switch and Connector Assembly DLP(3, ILP, IHP

400442 Pressure Switch Assembly 8mm Complete Housing, Pressure Switch and Connector Assembly DLP(3)

(1) 400001 is assembly of pressure switch 400005 with a bonded seal.


(2) 400004 is assembly of pressure switch 400005 with washer and O-ring.
(3) Pressure switch should always be installed at the end of the detection network for optimal signal speed.