Model FSV-1 Fail-Safe Valve


Trim Component For Model DV-5 Deluge Valve
Used In Deluge and Preaction Systems
General Technical
Description Data
The Model FSV-1 Fail-Safe Valve Approvals
(Ref. Figure 1) is intended for use with UL and C-UL Listed, as well as FM
the Model DV-5 Deluge Valve in cer- Approved, as a valve trim component
tain types of trim arrangements for del- for the Model DV-5 Deluge Valve.
uge and preaction systems. Provided
as part of specific DV-5 Valve trim ar- Maximum Working Water Pressure
rangements, it is installed adjacent to 250 psi (17,2 bar).
the releasing devices (dry pilot actua- Assembly
tor, solenoid valve, etc.). When prop- The body and cover in Figure 1 are
erly installed, it is intended to prevent bronze. The elastomer water seal is
inadvertent resetting of the DV-5 Valve Buna-N, and the diaphragm is nylon
after initial operation of the DV-5 reinforced natural rubber.
Valve.

WARNING Operation
The Model FSV-1 Fail-Safe Valve de-
scribed herein must be installed and
maintained in compliance with this
When the FSV-1 Fail-Safe Valve is in
its closed position (Ref. Figure 1) it Installation
document, as well as with the applica- retains water pressure in the Dia- Refer to the applicable technical data
phragm Chamber of the DV-5 Valve sheets describing the various options
ble standards of the National Fire Pro-
when the DV-5 is set for service. Upon for installing the Model DV-5 Deluge
tection Association, in addition to the
operation of the DV-5 Valve, the piping Valve (i.e., deluge and preaction sys-
standards of any other authorities hav- downstream of the DV-5 Valve be-
ing jurisdiction. Failure to do so may tems utilizing the Model DV-5 Deluge
comes pressurized. The Pilot Cham- Valve).
impair the performance of this de- ber of the FSV-1 is then pressurized
vice. via its trim connection to the down-
The owner is responsible for maintain-
ing their fire protection system and de-
stream side of the DV-5 Valve. Pres-
surization of the Pilot Chamber opens
Setting
vices in proper operating condition.
The installing contractor or sprinkler
the FSV-1 (Ref. Figure 1). After open-
ing of the FSV-1, make-up pressure to
Procedure
manufacturer should be contacted the Diaphragm Chamber of the DV-5 The Model FSV-1 Fail-Safe Valve
with any questions. Valve cannot occur. Even if the releas- automatically resets after the system
ing device that originally released piping downstream of the Model DV-5
water from the Diaphragm Chamber Deluge Valve is drained and returned
were to close, the FSV-1 prevents the to its normal 0 psi gauge pressure.
DV-5 Valve from inadvertently reset-
ting after its initial opening. Upon op-
eration, the FSV-1 will vent the DV-5
Diaphragm Chamber to atmosphere
quicker than it can be repressurized
through the 1/8 inch (3,2 mm) restric-
tion in the diaphragm supply connec-
tion to the DV-5.

Page 1 of 4 MAY, 2008 TFP1386


Page 2 of 4 TFP1386

5-1/8" DIA.
(130,2 mm)
1/2" NPT ACTUATING PORT 1-3/16" HEX
OPEN TO ATMOSPHERE VIA (30,0 mm)
VALVE TRIM CONNECTED TO
DOWNSTREAM SIDE OF 2
DELUGE VALVE

9
8
2-1/8"
(54,0 mm) 10
5 3-3/8"
(85,7 mm)
11
1/2" NPT OUTLET
PORT OPEN TO
ATMOSPHERE 13 1

1-1/4" 1/2" NPT INLET FLOW


(31,8 mm) PORT PRESSURIZED PATH
FROM DELUGE CLOSED
VALVE DIAPHRAGM
CHAMBER SUPPLY 1-3/8" HEX
(35,0 mm)
1-11/16"
NO. DESCRIPTION QTY. (42,9 mm) NO. DESCRIPTION QTY.
1 Valve Body . . . . . . . . . . . 1 11 Spring Lead . . . . . . . . . . . 2
2 Valve Cover . . . . . . . . . . . 1 SET CONDITION 12 Valve Shaft . . . . . . . . . . . 1
3 Diaphragm Plate . . . . . . . 1 13 O-Ring . . . . . . . . . . . . . . . 1
4 Diaphragm . . . . . . . . . . . . 1 14 Hex Nut, M5 . . . . . . . . . . . 1
5 Valve Seat Ring . . . . . . . . 1 1/2" NPT ACTUATING
6 Valve Disc Retainer . . . . . 1 PORT PRESSURIZED NOTES:
7 Valve Disc . . . . . . . . . . . . 1 BY WATERFLOW FROM
8 Spring . . . . . . . . . . . . . . . 2 1. Unit is not field serviceable,
DOWNSTREAM SIDE
9 Hex Screw, M8 x 25 . . . . 8 no replaceament parts are
10 Hex Nut, M8 . . . . . . . . . . . 8 OF DELUGE VALVE
available.
3 4

1/2" NPT
OUTLET PORT
WATERFLOW FLOW
TO DRAIN PATH
12 OPENED

6
7
1/2" NPT INLET
PORT WATERFLOW 14
FROM DELUGE
VALVE DIAPHRAGM
CHAMBER SUPPLY

ACTUATED CONDITION

FIGURE 1 - MODEL FSV-1 FAIL-SAFE VALVE


TFP1386 Page 3 of 4

Care and Limited Ordering


Maintenance Warranty Information
The following inspection procedure Products manufactured by Tyco Fire & Orders for the FSV-1 must include the
must be performed as indicated, in ad- Building Products (TFBP) are war- description and Part Number (P/N).
dition to any specific requirements of ranted solely to the original Buyer for
the NFPA, and any impairment must ten (10) years against defects in mate- FSV-1:
be immediately corrected. rial and workmanship when paid for Specify: Model FSV-1 Fail-Safe Valve,
and properly installed and maintained P/N 52-343-1-001.
The owner is responsible for the in-
under normal use and service. This
spection, testing, and maintenance of
warranty will expire ten (10) years
their fire protection system and de-
from date of shipment by TFBP. No
vices in compliance with this docu-
warranty is given for products or com-
ment, as well as with the applicable
ponents manufactured by companies
standards of the National Fire Protec-
not affiliated by ownership with TFBP
tion Association (e.g., NFPA 25), in
or for products and components which
addition to the standards of any
have been subject to misuse, improper
authority having jurisdiction. The in-
installation, corrosion, or which have
stalling contractor or product manufac-
not been installed, maintained, modi-
turer should be contacted relative to
fied or repaired in accordance with ap-
any questions.
plicable Standards of the National Fire
It is recommended that automatic Protection Association, and/or the
sprinkler systems be inspected, standards of any other Authorities
tested, and maintained by a qualified Having Jurisdiction. Materials found
Inspection Service in accordance with by TFBP to be defective shall be either
local requirements and/or national repaired or replaced, at TFBP’s sole
codes. option. TFBP neither assumes, nor
NOTES authorizes any person to assume for it,
No attempt is to be made to repair an any other obligation in connection with
impaired Model FSV-1 Fail-Safe the sale of products or parts of prod-
Valve. The complete assembly must ucts. TFBP shall not be responsible for
be replaced if their is indication of mal- sprinkler system design errors or inac-
function. curate or incomplete information sup-
plied by Buyer or Buyer’s repre-
Before closing a fire protection system sentatives.
control valve for inspection or mainte-
nance work on the fire protection sys- In no event shall TFBP be liable, in
tem that it controls, permission to shut contract, tort, strict liability or under
down the effected fire protection sys- any other legal theory, for incidental,
tem must first be obtained from the indirect, special or consequential dam-
proper authorities and all personnel ages, including but not limited to labor
who may be affected by this action charges, regardless of whether TFBP
must be notified. was informed about the possibility of
such damages, and in no event shall
After placing a fire protection system TFBP’s liability exceed an amount
in service, notify the proper authorities equal to the sales price.
and advise those responsible for moni- The foregoing warranty is made in lieu
toring proprietary and/or central sta- of any and all other warranties, ex-
tion alarms. press or implied, including warranties
INSPECTION PROCEDURE of merchantability and fitness for a par-
The Model FSV-1 Fail-Safe Valve ticular purpose.
must be inspected quarterly in accord- This limited warranty sets forth the ex-
ance with the following instructions, clusive remedy for claims based on
and any impairment must be corrected failure of or defect in products, materi-
by replacing the FSV-1. als or components, whether the claim
Step 1. When in the set position there is made in contract, tort, strict liability
should not be any water leakage from or any other legal theory.
the outlet connection to drain. This warranty will apply to the full ex-
Step 2. During the quarterly test of the tent permitted by law. The invalidity, in
actuation devices, verify that the whole or part, of any portion of this
FSV-1 has operated correctly as evi- warranty will not affect the remainder.
denced by a continuous waterflow
from its outlet to drain.
Page 4 of 4 TFP1386

© 2008 TYCO FIRE & BUILDING PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446