Ref: JC/MAV/NDS/DCC/36798 Did.- 31/03/2020
To,
Mls Dhar Construction Company,
In JV with Shri Chanchal Paul,
Maccabe Road, Demseiong,
Shillong, Meghalaya-793001
E-mail:- decshg@gmail.com, donbokdee@gmail.com
Subject: Comments & Observations for Reinforcement Drawings of CC Ret
for the project.
ing wall & Breast wall
Project: Consultancy Services of Authority’s Engineer for Package-I:- “Improvement/ Widening to 2-
Lane with Earthen Shoulders from Ranikor to Nongjri existing chainage from km 0.000 to km 31.700
(Design Length- 33.250 km) in the state of Meghalaya on EPC mode under - SARDP-NE”
Dear Sir,
We have reviewed the compliance of our comments & observations for Reinforcement Drawings of
Retaining wall & Breast wall raised vide our office letter no. JC/MA V/NDS/DCC/36761 dtd 13/03/2020,
submitted for the project vides your Email from Mr. Chandan Kumar Das at
(05:38pm dtd.-17/03/2020. After reviewing the same, our Comments & Observations are attached herewith.
Thanking you,
for Authority’s Engineer
o
Mls Jindals Consortium.
In Asso. with MAV Associates
D/A- 1. Comments & Observations for Reinforcement Drawings of CC Retaining wall & Breast wall
forthe project.
Copy for kind information to—
1. The General Manager, NHIDCL,B.O. Shillong,
2. NHIDCL, SO- Mawkyrwat
“Wead Office’ S CFG, Vikas Vihar, Ambala City, Haryana 134003, Emal: indals S@ameilcom Tel: 0171-2580013, 9806670918
Branch Ofice: #102, lock No. C2B, GolfLink Residency, Sector 188, Dwaka, New Deli-f 10075; dehi@jndalsconsortum.in; Tel-011 49036895, 9958739419,
Scanned with CamScannerConsultancy Services for Design Reviewal of "Improvement/Widening to 2 lar
DIA with Letter no. JCIMAVINDS/DCC/36798 _Dtd.- 31/03/2020
ith Earthen Shoulder
from Ranikor to Nongjrl Existing Chainage from km 0+000 to km 31+700 (Design Length ~ 33.250
kms)".
Revised Comments and Observations for Reinforcement drawing of
Retaining Wall and Breast Wall are as follows:
Active Earth Pressure
acting point must be
2 | considered as 0.42H, as
per IRC:6-2017 214.1
214.1.1 states that Active
Pressure point of application
is 0.3h for wet soil and as
we have considered
saturated wet soil for our
design it remains valid
S.No. Comment Compliance Status
Load factors must be
considered as per IRC:
2017 Table 8.1
1 | Equilibrium by Incorporated Closed
considering causing and
restoring factors as
different.
Please ensure calculations by
considering by taking dry
density of back fill and take
earth pressure force acting at
0.42h from bottom.
Sample calculations are show
by considering 3m height of
backfill. It shows that dry with
As per IRC:6-2017 clause | 0.42h case gives more
overturning moment
compared to wet case.
ka 0.33
gamma dry 18 kN/m3
gamma sat 20 kN/m3
Height of retaining backfill 3 m
Moment at bottom 33.6798
kNm Dry case
(0.33*18*3%2*0.5*3*0.42)
Moment at bottom 29.7 kNm
Wet case (0.33*20*3%3/6)
Please check the revised
design calculations:
«In page 3 of 29 at check
for tension chapter.
+ In page 4 of 29, tension
is there at heel location.
11Page
yr
Scanned with CamScannerDIA with Letter no.- JCIMAVINDS/DCC/36798 Dtd-31/03/2020
Consultancy Services for Design Reviewal of "Improvement/Widening to 2 lane with Earthen Shoulder
from Ranikor to Nongjri Existing Chainage from km 0+000 to km 31+700 (Design Length ~ 33.250
kms)".
Comment
‘Compliance Status
* In page 25 of 29,
maximum allowable
pressure also exceeded
than allowable.
Same checks to be done
for other heights of wall
same checks to be done.
for Authority's Engineer
i
Jindals Consortium
in asso. with MAV Associates
2Pace