21. GENERATOR LOAD TESTS: CAPABILTIY AT 0 % POWER FACTOR
AND MAX +MVAR
a) DESCRIPTION
Test maximum export +65 MVar capability of generator at 0 MW as per contract
requirement
b) PRE-CONDITIONS REQUIRED
i) Load rejections and 100% heat run complete
ii) Permission from COES to export + 65 MVar for short time with 0 MW
iii) Exciter (AVR) full commissioned
(1) In auto
(2) -MVAR limitiation tested in actual condition
(3) lex limitiation set and tested in actual condition, if it is possible (PN QN UN)
(4) AVR stability checked on load
c) KEY SAFETY CONCERNS
i) Same as for fully operational unit
ii) Stator voltage must not go over 105% of 13.8kV. This might be challenging as
Cheves is at the end of the transmission Line. Transformer Taps may have to be
changed
d) REFERENCE DOCUMENTS
i) Jeumont: Generator Procedure Usual Rotation Tests: JE-Y-N-I-A-001 rev 01
(1) Section 9 - Generator Capability at Cos Phi 0
e) DATA TO BE RECORDED
i) MW, MVar, |, V
ii) MVar
iii) Generator Current
iv) Generator Voltage
saw Commissroning more Oheves 168 MW Hydropower Project
“tm Wet Commissioning Unit 1 and 2 sone: Empresa De Generacion Electrica Cheves, S.A.
peo: 101670
- a ba ae Ea
1 07
ABB ABB Inc. Ree
en ewe 75f) PROCEDURE
i) Start and syne Unit at 0 MW
ii) Increase excitation until +65 MVAR. Do not allow voltage to go over 105%
(13.8kV nominal)
9) RESULTS
Test is passed if 65 MVar is achieved.
h) SIGNATURES
Test Engineer Commissioning Manager | Client Representative
Signature: _| Signature: Signature:
| Name: _ _| Nam | Name:
Date: Date: Date’
focus Commissioning wee Chaves 168 MW Hydropower Project
ru Wet Commissioning Unit 1 and 2 wena Empresa De Generacion Electrica Cheves, S.A
om: 101670
ABB Inc
a 68
en | 5
how 75WNW
NN
NW
WWW
AWWW
VIAN VM
eee eensJEUMONT SERVICEEMETTEUR: PMC
N°DOCUMENT: Ore Date: 24082018
piscte TITLE: GENERATOR PROCEDURE USUAL ROTATION TESTS
unTrN" PAGE: 1478
9. | GENERATOR CAPABILTY AT COS PHI0
This test can be done during the on load test, since it doesn’t request any particular
instrumentation
9.1, Requested conditions for test
Machine ready for rotation.
Loss of field protection and return power protection checked in actual condition
AVR -MVAR limitation tested in actual condition
AVR lex limitation set and tested in actual condition, if it is possible (PN QN UN).
AYR stability checked on load.
HT line connected to the network
Stator voltage must not go over 105% of 13800V: all depends on the load at the end of the HT
line and the transformer ratio, Load and voltage at the end of the HT line must be steady during all
the test.
9.2. Test procedure
Generator is set at about OMW, + 65 MVAR, 13800V
If the generator full load test can be done, this testis finished, generator capability is OK
93. Test Result
P (Mw) Q(MVAR) UV) 1A)
94, Test time delay
30 mn, depending on the network representative advices.a
Service Emetteur : PMC
JEUMONT Document Nb
Electric Dates
Title : G1 CARACTERISTIC TEST — PQ capability test
Page: 1/1
MEASUREMENTS,
Test done with G1 in -Q (MVAR) limitation
Ua] 14780 | 14700 [142968 | 141864 | 159794] 14e7e | las | 14490 | 14917 | 1404s
sauan) 107.1 1035 | 102.7 | 101.3
Pimw) 845 sis | 811 _| #76 | 36 | #1 | 401 | 47 | Sa
Govar] 326 | 211 | 406 | 347 | 206 | 324 | 498 | 47 | 60065 | 0235
Taal 3540 | 3438 | 3688 | 3590 | 3717 | 2066 | 3839 | 2462 | 2355 | 2418
cosphf 0953 | 0.971 | 0.896 | 0.919 | 0973 | 0069 | 0.858 | 0.649 | 0077 | 0.086
Ir(Aade]_#43_| 783 | 843) 803 | 731 | 815 | 915 | 763 | 895 | 930
The If limitation was set originally on 845A on Hymateck excitation,
‘Test over this limit were done, changing the If limitation.
Network and generator transformer gave a voltage over the generator contractual voltage, when If
and the MVAR are increasing.
As we got 40 MVAR with 81MW, for a 103.5 % voltage, as the AVR Q regulation is limited at +/-
20 MVAR, it was decided, with Nordconsult, to let the limitation on 845A, generator being able to
go further.
For the test in negative reactive power (-MVAR), sec excitation ~Q limitation report
O85