21. GENERATOR LOAD TESTS: CAPABILTIY AT 0 % POWER FACTOR AND MAX +MVAR a) DESCRIPTION Test maximum export +65 MVar capability of generator at 0 MW as per contract requirement b) PRE-CONDITIONS REQUIRED i) Load rejections and 100% heat run complete ii) Permission from COES to export + 65 MVar for short time with 0 MW iii) Exciter (AVR) full commissioned (1) In auto (2) -MVAR limitiation tested in actual condition (3) lex limitiation set and tested in actual condition, if it is possible (PN QN UN) (4) AVR stability checked on load c) KEY SAFETY CONCERNS i) Same as for fully operational unit ii) Stator voltage must not go over 105% of 13.8kV. This might be challenging as Cheves is at the end of the transmission Line. Transformer Taps may have to be changed d) REFERENCE DOCUMENTS i) Jeumont: Generator Procedure Usual Rotation Tests: JE-Y-N-I-A-001 rev 01 (1) Section 9 - Generator Capability at Cos Phi 0 e) DATA TO BE RECORDED i) MW, MVar, |, V ii) MVar iii) Generator Current iv) Generator Voltage saw Commissroning more Oheves 168 MW Hydropower Project “tm Wet Commissioning Unit 1 and 2 sone: Empresa De Generacion Electrica Cheves, S.A. peo: 101670 - a ba ae Ea 1 07 ABB ABB Inc. Ree en ewe 75 f) PROCEDURE i) Start and syne Unit at 0 MW ii) Increase excitation until +65 MVAR. Do not allow voltage to go over 105% (13.8kV nominal) 9) RESULTS Test is passed if 65 MVar is achieved. h) SIGNATURES Test Engineer Commissioning Manager | Client Representative Signature: _| Signature: Signature: | Name: _ _| Nam | Name: Date: Date: Date’ focus Commissioning wee Chaves 168 MW Hydropower Project ru Wet Commissioning Unit 1 and 2 wena Empresa De Generacion Electrica Cheves, S.A om: 101670 ABB Inc a 68 en | 5 how 75 WNW NN NW WWW AWWW VIAN VM eee eens JEUMONT SERVICEEMETTEUR: PMC N°DOCUMENT: Ore Date: 24082018 piscte TITLE: GENERATOR PROCEDURE USUAL ROTATION TESTS unTrN" PAGE: 1478 9. | GENERATOR CAPABILTY AT COS PHI0 This test can be done during the on load test, since it doesn’t request any particular instrumentation 9.1, Requested conditions for test Machine ready for rotation. Loss of field protection and return power protection checked in actual condition AVR -MVAR limitation tested in actual condition AVR lex limitation set and tested in actual condition, if it is possible (PN QN UN). AYR stability checked on load. HT line connected to the network Stator voltage must not go over 105% of 13800V: all depends on the load at the end of the HT line and the transformer ratio, Load and voltage at the end of the HT line must be steady during all the test. 9.2. Test procedure Generator is set at about OMW, + 65 MVAR, 13800V If the generator full load test can be done, this testis finished, generator capability is OK 93. Test Result P (Mw) Q(MVAR) UV) 1A) 94, Test time delay 30 mn, depending on the network representative advices. a Service Emetteur : PMC JEUMONT Document Nb Electric Dates Title : G1 CARACTERISTIC TEST — PQ capability test Page: 1/1 MEASUREMENTS, Test done with G1 in -Q (MVAR) limitation Ua] 14780 | 14700 [142968 | 141864 | 159794] 14e7e | las | 14490 | 14917 | 1404s sauan) 107.1 1035 | 102.7 | 101.3 Pimw) 845 sis | 811 _| #76 | 36 | #1 | 401 | 47 | Sa Govar] 326 | 211 | 406 | 347 | 206 | 324 | 498 | 47 | 60065 | 0235 Taal 3540 | 3438 | 3688 | 3590 | 3717 | 2066 | 3839 | 2462 | 2355 | 2418 cosphf 0953 | 0.971 | 0.896 | 0.919 | 0973 | 0069 | 0.858 | 0.649 | 0077 | 0.086 Ir(Aade]_#43_| 783 | 843) 803 | 731 | 815 | 915 | 763 | 895 | 930 The If limitation was set originally on 845A on Hymateck excitation, ‘Test over this limit were done, changing the If limitation. Network and generator transformer gave a voltage over the generator contractual voltage, when If and the MVAR are increasing. As we got 40 MVAR with 81MW, for a 103.5 % voltage, as the AVR Q regulation is limited at +/- 20 MVAR, it was decided, with Nordconsult, to let the limitation on 845A, generator being able to go further. For the test in negative reactive power (-MVAR), sec excitation ~Q limitation report O85 PO DIAGRAM 58 ACTIVE POWER (mM) ee 20 110-100 -90 -€0 70 -€0 50 -40 30 -20 -10 0 1 20 90 40 6) oo 70 eo 9 100 10 100

You might also like