-1/1- APPENDIX C
Technical Data: PD calibration
DIAGNOSIS & MONITORING SERVICES

ΘAmbient --- °C Name, Type PDCal20 Name, Type MICAMAXXpdplus

Instrument
Calibrator
RHAmbient --- % Manufacturer PDTech Manufacturer IRIS/PD
IRIS/PD Tech
Clime

ΘWinding --- °C Serial. No: PDT-


PDT-0-09-
09-032 Serial. No: MMplus 1325
ΘDew Point --- °C Cal. date 2011-
2011-11-
11-10 Cal. date 2013
2013-01-30
ρAbsolute --- g/m3 Name, Type MMplus09

Software
Version V 1.1.1
OS 2.04r01

3.00E-05

2.50E-05

Calibration factors, all values


2.00E-05
Cal Factor

1.50E-05

1.00E-05

5.00E-06

0.00E+00
1 5 10 20 50 100 200 400
0.6 6.92E-08 7.57E-08 1.11E-07 1.25E-07 2.21E-07 3.82E-07 7.21E-07 1.31E-06
1 7.31E-08 8.37E-08 1.11E-07 1.28E-07 2.42E-07 4.20E-07 7.76E-07 1.48E-06
2.2 8.53E-08 9.48E-08 1.35E-07 1.46E-07 2.72E-07 5.02E-07 1.00E-06 1.93E-06
3 1.02E-07 1.10E-07 1.71E-07 2.13E-07 4.13E-07 7.53E-07 1.51E-06 3.01E-06
4.2 1.71E-07 1.42E-07 1.46E-07 3.66E-07 8.00E-07 1.60E-06 3.20E-06 6.40E-06
5 3.20E-07 2.13E-07 2.02E-07 2.98E-07 7.19E-07 1.48E-06 2.96E-06 5.92E-06
5.7 4.13E-07 3.61E-07 5.12E-07 1.22E-06 2.44E-06 4.88E-06 9.75E-06
6.3 1.60E-06 1.07E-06 1.38E-06 3.20E-06 6.56E-06 1.31E-05 2.62E-05

Cal Factor according to frequency

Calibration factors, feasible selection


9.00E-07
8.00E-07
7.00E-07
6.00E-07
Cal Factor

5.00E-07
4.00E-07
3.00E-07
2.00E-07
1.00E-07
0.00E+00
0.6 1 2.2 3 4.2
1 6.92E-08 7.31E-08 8.53E-08 1.02E-07 1.71E-07
5 7.57E-08 8.37E-08 9.48E-08 1.10E-07 1.42E-07
10 1.11E-07 1.11E-07 1.35E-07 1.71E-07 1.46E-07
20 1.25E-07 1.28E-07 1.46E-07 2.13E-07 3.66E-07
50 2.21E-07 2.42E-07 2.72E-07 4.13E-07 8.00E-07

Remarks and Comments


Due to nonlinearity it is recommended to perform measurements in the following limits:
• Gain between 1 and 50
• Filter between 0.6 MHz and 4.3 MHz

Document prepared Document checked and released

Christoph Wendel Stephane Betrisey


(RMTS, Rotating Machines Technical Specialist) (Field Service Engineer)