Kat: 1 Kat
Projektna Povrsina Unutarnji
Br.oj Naziv temperatura prostorije volumen
Tun [C] Au [m2] V_ [m3]
1 1.01.Spavaća soba 20 11.9 33.3
2 1.02.Spavaća soba 20 11.9 33.3
3 1.03.Ulazni prostor 20 5.4 15.3
4 1.04.Kupatilo 24 2.9 8.1
5 1.05.Kuhinja 20 10.1 28.4
6 1.06.Dnevni boravak+blagovaonica 20 38.9 108.9
7 1.07.Spavaća soba 20 12.2 34.3
8 1.08.Spavaća soba 20 8.3 23.2
9 1.09.Kupatilo 24 4.6 12.7
10 1.10.Kupatilo 24 5.2 14.6
11 0.11.Hodnik 20 8.4 23.4
Qt=(H1+H2+H3+H4+H5+H6)*(Tun-Tsp)=431 W
Ventilacioni gubici
Vmin=Nmin*V=0.5*33.32=16.7 m3/h Vinf=2*V*N50*e*eps=2*33.32*5*0.02*1=6.7 m3/h
V_=maks(Vmin,Vinf)=16.7 m3/h
Hv=0.34*V=5.66 W/K Qvent=Hv*(Tun-Tsp)=5.66*(20-(-9))=164 W
Toplina za kompenzaciju prekida grijanja
Qrh = A x Frh =11.9 x 11=131 W
Qt=(H1+H2+H3+H4+H5+H6)*(Tun-Tsp)=323 W
Ventilacioni gubici
Vmin=Nmin*V=0.5*33.32=16.7 m3/h Vinf=2*V*N50*e*eps=2*33.32*5*0.02*1=6.7 m3/h
V_=maks(Vmin,Vinf)=16.7 m3/h
Hv=0.34*V=5.66 W/K Qvent=Hv*(Tun-Tsp)=5.66*(20-(-9))=164 W
Toplina za kompenzaciju prekida grijanja
Qrh = A x Frh =11.9 x 11=131 W
Qt=(H1+H2+H3+H4+H5+H6)*(Tun-Tsp)=215 W
Ventilacioni gubici
Vmin=Nmin*V=0.5*15.26=7.6 m3/h Vinf=2*V*N50*e*eps=2*15.26*5*0.02*1=3.1 m3/h
V_=maks(Vmin,Vinf)=7.6 m3/h
Hv=0.34*V=2.59 W/K Qvent=Hv*(Tun-Tsp)=2.59*(20-(-9))=75 W
Toplina za kompenzaciju prekida grijanja
Qrh = A x Frh =5.45 x 11=60 W
Qt=(H1+H2+H3+H4+H5+H6)*(Tun-Tsp)=227 W
Ventilacioni gubici
Vmin=Nmin*V=1.5*8.12=12.2 m3/h Vinf=2*V*N50*e*eps=2*8.12*5*0.02*1=1.6 m3/h
V_=maks(Vmin,Vinf)=12.2 m3/h
Hv=0.34*V=4.14 W/K Qvent=Hv*(Tun-Tsp)=4.14*(24-(-9))=137 W
Toplina za kompenzaciju prekida grijanja
Qrh = A x Frh =2.9 x 11=32 W
Qt=(H1+H2+H3+H4+H5+H6)*(Tun-Tsp)=388 W
Ventilacioni gubici
Vmin=Nmin*V=1.5*28.42=42.6 m3/h Vinf=2*V*N50*e*eps=2*28.42*5*0.02*1=5.7 m3/h
V_=maks(Vmin,Vinf)=42.6 m3/h
Hv=0.34*V=14.49 W/K Qvent=Hv*(Tun-Tsp)=14.49*(20-(-9))=420 W
Toplina za kompenzaciju prekida grijanja
Qrh = A x Frh =10.15 x 11=112 W
Qt=(H1+H2+H3+H4+H5+H6)*(Tun-Tsp)=1298 W
Ventilacioni gubici
Vmin=Nmin*V=1.5*108.92=163.4 m3/h Vinf=2*V*N50*e*eps=2*108.92*5*0.02*1=21.8 m3/h
V_=maks(Vmin,Vinf)=163.4 m3/h
Hv=0.34*V=55.55 W/K Qvent=Hv*(Tun-Tsp)=55.55*(20-(-9))=1611 W
Toplina za kompenzaciju prekida grijanja
Qrh = A x Frh =38.9 x 11=428 W
Qt=(H1+H2+H3+H4+H5+H6)*(Tun-Tsp)=347 W
Ventilacioni gubici
Vmin=Nmin*V=1.5*34.3=51.5 m3/h Vinf=2*V*N50*e*eps=2*34.3*5*0.02*1=6.9 m3/h
V_=maks(Vmin,Vinf)=51.5 m3/h
Hv=0.34*V=17.49 W/K Qvent=Hv*(Tun-Tsp)=17.49*(20-(-9))=507 W
Toplina za kompenzaciju prekida grijanja
Qrh = A x Frh =12.25 x 11=135 W
Qt=(H1+H2+H3+H4+H5+H6)*(Tun-Tsp)=323 W
Ventilacioni gubici
Vmin=Nmin*V=1.5*23.24=34.9 m3/h Vinf=2*V*N50*e*eps=2*23.24*5*0.02*1=4.6 m3/h
V_=maks(Vmin,Vinf)=34.9 m3/h
Hv=0.34*V=11.85 W/K Qvent=Hv*(Tun-Tsp)=11.85*(20-(-9))=344 W
Toplina za kompenzaciju prekida grijanja
Qrh = A x Frh =8.3 x 11=91 W
Qt=(H1+H2+H3+H4+H5+H6)*(Tun-Tsp)=193 W
Ventilacioni gubici
Vmin=Nmin*V=1.5*12.74=19.1 m3/h Vinf=2*V*N50*e*eps=2*12.74*5*0.02*1=2.5 m3/h
V_=maks(Vmin,Vinf)=19.1 m3/h
Hv=0.34*V=6.5 W/K Qvent=Hv*(Tun-Tsp)=6.5*(24-(-9))=214 W
Toplina za kompenzaciju prekida grijanja
Qrh = A x Frh =4.55 x 11=50 W
Qt=(H1+H2+H3+H4+H5+H6)*(Tun-Tsp)=215 W
Ventilacioni gubici
Vmin=Nmin*V=1.5*14.56=21.8 m3/h Vinf=2*V*N50*e*eps=2*14.56*5*0.02*1=2.9 m3/h
V_=maks(Vmin,Vinf)=21.8 m3/h
Hv=0.34*V=7.43 W/K Qvent=Hv*(Tun-Tsp)=7.43*(24-(-9))=245 W
Toplina za kompenzaciju prekida grijanja
Qrh = A x Frh =5.2 x 11=57 W
Qt=(H1+H2+H3+H4+H5+H6)*(Tun-Tsp)=197 W
Ventilacioni gubici
Vmin=Nmin*V=0.5*23.38=11.7 m3/h Vinf=2*V*N50*e*eps=2*23.38*5*0.02*1=4.7 m3/h
V_=maks(Vmin,Vinf)=11.7 m3/h
Hv=0.34*V=3.97 W/K Qvent=Hv*(Tun-Tsp)=3.97*(20-(-9))=115 W
Toplina za kompenzaciju prekida grijanja
Qrh = A x Frh =8.35 x 11=92 W