Professional Documents
Culture Documents
Cable Resistance (R): 12.3 ohm/Km Refer attachment 2, Vendor Cable Datasheet
I x 2L x R
Voltage Drop (Vd):
3.7884
Volts
Cable Adequacy:
Minumum Voltage Required for the Device (Vmin) 20.4 VDC (Note 1, Attachment 3)
Remarks / Notes:
1. Solenoid valve operating voltage range will be -15% to +10% of the nominal voltage (24VDC) as per
manufacturer.