You are on page 1of 9

A comparison of

NFPA 780 and IEC 62305


White Paper

Contents
Rigorous Calculations
Strike Level and Design
Parameters
Risk Analysis
Separation Distance
Air Terminal Selection
Down Conductor Design
Earthing Design
Test and Maintenance
Surge Protection Devices
Actual Lightning Discharge Testing

www.dehn-usa.com
A comparison of
NFPA 780 and IEC 62305
White Paper

Introduction ¨¨ Surge Protection Devices


The objective of this article is to present why the IEC 62305 ¨¨ Actual lightning discharge testing
Certified Master Label Compliant Lightning Protection Systems
(LPS) are comparable and useful as an alternative to NFPA 780 Background
designs for North American markets. Both the IEC and NFPA documents are peer reviewed on a
This article promotes the acceptance and utilization of regular basis by subject matter experts.
IEC 62305 certification as a more thorough approach, produc- As of the date of this report, the IEC 62305 standard is pub-
ing a superior LPS design, than NFPA 780 for UL96A master lished as Edition 2:2010 and is updated by committee TC81
label for LPS installations by showing that IEC accomplishes under the regular maintenance process with new versions ex-
all safety and best practice requirements for North American pected in 2017 and 2018.
installations. The IEC 62305 suite of standards is ilustrated as a systematic
Per UL announcement, they will grant their Master Label to a approach in Figure 1.
LPS that is compliant with UL 96A. This means that UL will pro- The NFPA 780 standard is currently published under the 2014
vide their Master Label for a LPS designed to meet IEC 62305 if edition, with public input for consideration of the Technical
installed by a UL certified installer and passing a UL inspection Committee for the next 2017 edition (Figure 2).
by a UL LPS inspector.
To show that the IEC 62305 is a more thorough approach pro- Design Theory and Philosophy
ducing a superior LPS design this article will first provide some The basic requirements of IEC 62305 cover a detailed risk fac-
background. After this background, the following sections will tor assessment which then guides the air terminal design,
illustrate how the IEC standard produces a more detailed and down conductors, bondiong and application of SPD‘s to reduce
superior LPS implimentation: the risk below a tolerable threshold. This risk assessment re-
¨¨ Design philosophy & calculations methods quires a fairly detailed knowledge of the structure and end use,
¨¨ Rigorous calculation and software is almost always used to perform the calculation.
¨¨ Strike Levels and Design Parameters
¨¨ Risk analysis required vs optional
¨¨ Separation distance calculations methods
¨¨ Air terminals selection
¨¨ Down conductor design
¨¨ Earthing design
¨¨ Test and maintenance

Part 1
General principles

Part 2
Risk management
Protection
against lightning
IEC 62305 Part 3
Physical damage to
structures and life hazard

Part 4
Electrical and electronic
systems within structures

Figure 1 The IEC 62305 suite of standards is divided into four use- Figure 2 The NFPA 780 standard is presently under 2014 revision.
ful segments.

2 WP045/USA/1016 © Copyright 2016 DEHN, Inc.


A comparison of
NFPA 780 and IEC 62305
White Paper

The calculation includes, Human Life, Public Services, Cultural loop requirements, surge-protection requirements, and how to
Heritage, Economic risk, and penalties for denial of service. This install protection for trees, towers and similar structures. The
risk assessment is both good and bad in that pole barns will standard however has two primary short falls in that it does
have fewer requirements than would be found in NFPA 780, not require a detailed analytic calculation of the integrity of
but high value assets will have greater requirements. the installed systems ability to handle direct lightning strike
The basic approach to lightning protection is to work within events, nor does it take into consideration what asset the LPS
the accepted step leader behavior of lightning strikes. Imagine is protecting. In other words, NFPA 780 has the same require-
the final lightning strike distance of a bolt seeking any path to ments for a pole barn as it does for a high value asset.
ground as a radius of a sphere that could touch anywhere. The Table 1 defines the basic NFPA classes of lightning protec-
more stringent the class of lightning protection, the smaller the tion and the mechanical difference in materials for structures
radius and more risk the bolt can find the building. above 75 ft (23 m) in height.
The IEC risk mitigation offered by virtue LPS installation of-
fers tiered criteria structure with more sensitive applications Rigorous Calculations
requireing more stringent LPS protection coverege. LPS IEC The IEC 62305:2006 standard requires an actual assessment
Class III (45 m radius sphere) meets the demand of most typi- of the lightning protection system to insure that it is capable
cal commercial buildings and is most similar to the standard of handling a lightning strike. The lightning strike calculations
NFPA (150 ft sphere) . This IEC LPL class III implies a protection are far more significant for both the time domain parameter
system capable of intercepting lightning strikes with currents (10/350 μs vs 8/20 μs) and the actual strike amperages (100 kA
as low as 10 kA and as high as 100 kA 10/350 μs (see lightning to 200 kA) than the US industry standard (often only 20 kA for
strike figure). Based on these parameters, the rolling sphere UL 1449 and UL 467). IEC 62305:2006 calculations that are re-
method can been employed to develop a safety canopy con- quired include:
structed with a geometry of a 45 m (146.25 ft) radius using air ¨¨ The peak lightning strike current to be carried on individual
terminals, down conductors tested and earthing system capa- conductors in DC amps to ensure that current carrying ca-
ble of handling 100 kA direct lightning currents. pacity is not exceeded.
¨¨ Time-domain analysis of the lightning strike on the specific
NFPA 780 Design Theory and Philosophy
structure. This is critical to understanding the amperage
The NFPA LPS design does not include a mandatory risk review
carrying capacity of the conductors.
but instead is based on the standard NFPA Class I lightning
protection system for lower height ordinary building not more ¨¨ The application of the rolling-ball theory of lightning pro-
than 75 ft (23 m) tall. For this class of structure there is no tection tested against 3D computer models of the structure
requirement for a rolling sphere, so the basic air termination and surrounding area.
placement, down conductor cross section design and earth- ¨¨ Spark gap and arc-flash calculations to allow for flashes
ing rod matching system are employed per relevant NFPA 780 from the lightning protection system to adjacent conduc-
clauses. To meet the standard, each rod height can be selected tive utilities.
at 24 in (61 cm) tall, with interconnection along the roof and ¨¨ Separation distance to avoid flashover from down conduc-
down conductors terminating into a dedicated ground elec- tors to electrical aparatus.
trode earthing rod.
NFPA 780 provides guidelines for how often to place air termi-
nals, spacing’s for cross and down conductors, ground rod and LPL
3 kA 200 kA
I
NFPA  780-2011 (99 %) (99 %)

Item Less than 75-ft More than 75-ft 5 kA 150 kA e.g. for LPL II:
II
(97 %) (98 %) 97 % of all light-
Name Class I Class II ning currents
10 kA 100 kA
Air terminal min 3/8-in dia min 1/2-in dia III > 5 kA and
(91 %) (97 %)
(9.5 mm) (12.7 mm) 98 % < 150 kA
16 kA 100 kA
IV
Main / 57 kcmil (between 115 kcmil (between (84 %) (97 %) Ipeak/kA
downcomer #2 and #3 AWG) 1/0 and 2/0)
05 50 100 150 200
Earthing Rods Rods and loop
Table 1 The NFPA 780 standard divides applications into two Figure 3 The IEC 62305 standard divides applications by likely hood
broad categories by height. of capturing both the high and low severity lightning events.

WP045/USA/1016 © Copyright 2016 DEHN, Inc. 3


A comparison of
NFPA 780 and IEC 62305
White Paper

DETAILED RISK ASSESSMENT WORKSHEET

Equivalent Collective Area Probability of Damage

Ae = LW+6H(L+W)+9�H2 L= Ae = Injury Due to a Direct Strike – PA


(for rectangular structure) W= See Table L.6.7.3 PA =

(substitute formula for


other structures) H=
Physical Damage Due to a Direct Strike – Pn
See Table L.6.7.4 Pn =
Annual Threat of Occurence

Direct Strikes to Structure Failure of Internal Systems Due to a Direct Strike – PC


Ng = See Table L.6.7.5 PC =
Nd = (Ng)(Ae)(Cl)(10-6) Ae = Nd =

See Table L.4.2. Cl = Failure of Internal Systems Due to a Direct Strike – PM


PM = See Table
L.6.7.6
Strikes Near Structure
KS = (KS1)(KS2)(KS3)(KS4) KS1 = KS =
NM = (Ng)(Am - Ae)(Cl)(10-6) Ng = Nm =
KS1 = KS2 = 0.12ω KS2 =
Am =
See Table L.6.7.7 KS3 =
Ae =
KS4 = 1.5/UW KS4 = UW is the
See Table L.4.2. Cl = lowest
withstand
voltage of
protected
Strikes to an Incoming Service equipment
NL = (Ng)(Al )(Cl)(Cl)(10-6) Ng = NL = Without coordinated surge
protective devices – PM = 1.0
See Table L.6.7.1 Al =

See Table L.4.2. Cl =

Figure 4 An excerpt of Annex L risk assessment shows it is well suited for the user to create their own work sheet.

Strike Levels and Design Parameters risk level and then allows selection of features to reduce the
Additional advantages of the IEC methods show up in strike risk. The final rolling sphere coverage result will confirm the
levels and design parameters. structure is protected.
In the IEC 62305 standards, the frequency spectrum of the NFPA 780 annex L describes the informative (suggested but
lightning strike on the specific structure leads to a higher not required) risk review procedure. It does include many of
charge transfer than seen in NFPA strike levels. This forms the the features of the IEC review, but does not actually help deter-
basis for both surge-protection and for timing of circuit break- mine the LPL severity as in the IEC method. The designer does
ers to prevent power outages. not actually select a more rigorous approach as a result of the
Figure 3 shows the Lightning strike levels suggested under IEC NFPA risk review.
to select the LPL measures leading to suggested rolling sphere It is important to note the NEC does require critical operations
diameter (lower strike likelyhood implies a smaller diameter). providers to conduct the annex L risk assesment. The final LPS
design may incorporate these findings but the system does not
Risk Analysis drive improvement.
The IEC requirements imply a normative risk analysis. It is re- The review from NFPA annex L is shown in Figure 4 and lends
quired, and through this excerise the mitigation measures are itself to a spreadhseet calculation.
selected and possibly drive the Lightning Protection Level from The IEC risk review walks through the structure to develop a
a default LPL III to a higher more sever level with smaller roll- fully exposed base line and prompts the designer to increase
ing sphere diameter and higher density of lightning rod air ter- mitigation levels until a tolerable risk level has been estab-
minals. The analysis takes into account the physical structure, lished. These features and lightning strike levels then guide the
hazard location level and occupency to build the un –protected designer to a suitable LPS for the specific structure and use.

4 WP045/USA/1016 © Copyright 2016 DEHN, Inc.


A comparison of
NFPA 780 and IEC 62305
White Paper

Figure 5 The DEHN Support Toolbox helps calculate the direct and
indirect strike collection area.

The direct (solid lines) and indirect (dashed lines) expo- Figure 6 The DEHN software helps the user through the whole
sure area calculations for IEC risk analysis are shown in process to derive the protection measures needed to
Figure 5. reduce risk below the tolerable thresholds and drive
The calculations for intolerable risk, and then mitigated and continuous improvement.
tolerable risk levels can be illustrated like in Figure 6.
The final protected state using the LPL rolling sphere diameter
determined through risk mitigation selection will then be il- NFPA has only a loose discussion on allowing sufficient sep-
lustrated to show coverage like in Figure 7. eration between the LPS conductors and unbonded electrical
systems.
Seperation Distance A sample calculation from NFPA 780 is shown in Figure 8.
Any electrical component or wire will be influenced by the EMP But the IEC involes a detailed review of the separation
from the down conductor as it diverts lightning to ground. The of down conductors from electrical aparatus and wiring

Figure 7 Water cooling towers and electrical distribution centers are illustrated in 3D with the overlay of the theoretical blanket of protection.

WP045/USA/1016 © Copyright 2016 DEHN, Inc. 5


A comparison of
NFPA 780 and IEC 62305
White Paper

Figure 10 Both IEC and NFPA indicate where insulation must be


installed on the down conductors near public access
areas.

Air Terminal Selection


NFPA 780 for Class I designs allows the spacing of the air ter-
minals to be placed at intervals of 25 feet (7.6 m) instead of
the 20 foot (6 m) spacing required for air terminals of less than
24-inches (61 cm) in height.
According to the IEC 62305 standard, longer rod designs are
allowed that have been tested to show the integrity to han-
Figure 8 Separation distance is calculated in NFPA 780. dle real lightning strike energies. These longer rods can also
reduces the total number of rods needed to avoid any strikes
to the building or any roof top mounted electrical systems. Be-
cause there can be unknown features on the roof, these rods
assure lightning will not seek weaker metal structures and still
provide a minimal impact to the aesthetic view of the building.

Down Conductor Design


The IEC 62305 indicates the down conductors vary from
10-meter to 20-meter (32.5 ft to 65 ft) spacing, where as in
the NFPA 780 a one-size-fits-all 30-meter (76 ft) spacing is em-
Figure 9 The DEHN support tool helps show the flashover distance ployed.
(cm) to guide designers in spacing and separation dis- The material for higher Class II roofs does double in diameter
tance. over 75 ft (23 m) from 57 to 115 kcmil to account for higher
weight and a more extreme environment.

(Figure 9). Software modling allows the designer to see how Earthing System Design
many cm spacing would be required around the LPS based on If there are adjacent structures between which electrical pow-
the suggested maximum surge likely to be introduced per the er supply lines and measuring/control lines are installed, the
strike level chart. This allows a designer to take flashover into earth-termination systems have to connect between reinforce-
account systematically through the structure and not neglect ment, down conductor and earthing systems for equipotential
these effects accidentally. bonding. It is advantageous to reduce the currents in the lines
Isolation spacing and insulation materials are suggested under via many parallel paths. This aim is fulfilled by means of an
the IEC methods to prevent touch and step voltages next to intermeshed earth termination system.
the down conductors and earthing electrodes. Concrete columns that are used for down conductors must be
Figure 10 illustrates the 3 m (9.75 ft) limit for touch and step tested a 0.2 ohms or less continuity, and rebar must be welded
insulation as recommened by IEC. This is a key issue in select- with 20 x diameter overlaps. These must be bonded to the floor
ing LPS components with intrinsic safety insulation features. slab according to IEC 62305.
This allows the designer to minimize spacing and cost to Ground rings are required for all non-conductive buildings,
achieve the safest effective control of risk. buildings housing electronic systems, and certain risk factors

6 WP045/USA/1016 © Copyright 2016 DEHN, Inc.


A comparison of
NFPA 780 and IEC 62305
White Paper

Figure 11 Typical test joints and inspection boxes.

in the IEC 62305 guidelines. Individual rod installations (before


attachement into the ground ring) must be tested so that each
electrode is at the same resistance to ground as in the NFPA. Figure 12 Here is an example of extreme wear and tear of the down
conductor. (Photo courtesy MHD)

Test and Maintenance


The IEC specifies that a LPS will inlcude test points for future may also be required to have protection systems installed,
measurements of the LPS connections and earthing integrety based on the risk assessment.
(Figure 11). Both internal SPD’s and external lightning protection systems
The implementation of a long term preventative maintenance are mandatory in the IEC 62305 suite of standards.
program is required to uphold the integrity of the LPS system The IEC 62305:2006 has stringent requirements for annual test-
components. The IEC standards identifies this to be impera- ing and inspection of the lightning protection systems. This of
tive in order to sustain safe AC electrical power reference, the course, goes along with mandatory maintenance requirements.
diversion of lightning and the return on investment of both the The NEC does require SPD’s to be installed at emergency panels,
LPS and customer equipment. critical operation providers and where wind generation facilties
The key inspections include: connect back into the grid, but this requirement does not extend
to the prevention of loss at industrial or commercial facilities.
¨¨ Inspection at the design stage Figure 13 shows a diagram depicting all of these IEC best
¨¨ Inspections during the construction phase practice concepts to achieve a system level solution with high-
¨¨ Acceptance test est withstand and safe, noise free operation.
¨¨ Visual inspections
MEB
¨¨ On-site inspections
¨¨ Measurements
DNO
¨¨ Documentation
¨¨ Maintenance Telecontrol /
telecommunication
¨¨ Final Inspection and UL Master Label Certification Ex i Measuring and control equipment

In Figure 12 we see the short term degeneration of the PROFI


BUS
down conductor portion of the LPS due to local wear and heater
tear effects.
gas

Surge Protection Devices


The application of spark gaps between lightning conductors foundation earth electrode external LPS

and other metallic objects must be considered. In addition, the Figure 13 Here, the equipotential bonding of incoming metal pipes
IEC 62305 standards suggests that incoming utility services and the application of SPD’s are illustrated with connec-
(such as overhead power lines) and adjoining public spaces tions to the Master Earthing Bar (MEB).

WP045/USA/1016 © Copyright 2016 DEHN, Inc. 7


A comparison of
NFPA 780 and IEC 62305
White Paper

tion and protection of the value of the building asset. UL will


now offer a UL Master Label for IEC 62305 compliant lightning
protection systems.
An important limitation of NFPA 780 is that each building
that is part of a complex LPS system must be endowed with
all of its own LPS lightning rods, down conductors and earth-
ing, with no consideration of the benefit of the rolling sphere
coverage offered by adjacent, taller structures. IEC 62305 risk
assessment is normative while the NFPA less detailed risk as-
sessment is informative. IEC 62305 risk assessment drives im-
provement and results in four LPS classes, with air termination,
down conductor, and earth termination systems dependent on
LPS class. NFPA 780 risk assessment results in a go / no go one
size fits all LPS, with a rolling sphere equivalent to IEC LPS
Figure 14 All DEHN products are 100% tested to show they with-
Class III. NEC requires risk assessment for critical operations
stand lightning events. power systems (COPS).
(Photo courtesy DEHN) The IEC suite of standards provides a more comprehensive and
thorough set of design tools for the creation of effective light-
ning protection systems.
Actual lightning discharge testing
The IEC standards dictate that all lightning protection rods,
down conductors and clamps must meet the extreme direct
lightning currents.
All SPD’s are tested to assure they can withstand both the
indirect strike 8/20 μs testing seen in UL 1449 standards, but Acknowledgements:
also the extreme 100 kA 10/350 μs withstand associated direct DEHN protects. For the past 105 years we’ve led the way in
lightning strikes. Both the NFPA 780 and UL standards advise Lightning and Surge protection solutions for people, industry
testing to 20 kA 8/20 μs. and electrical / electronic systems against the effects of light-
The IEC establishes a higher energy transfer mechanism, ning and surges.
shows the mathematical relationships for charge transfer. This
assures mechanical integrity of the components through labo-
ratory proof testing. About the author:
In Figure 14 we see the IEC accredited, DEHN laboratory fa- Mark Hendricks – Mark has contributed to various IEC and
cilities in Germany which accommodate the leading surge test IEEE standards groups and has served the power quality in-
equipment and safety practices. dustry for over 19 years.

Summary
In summary, the IEC 62305 certification for achievement of References:
UL 96A master label requirements meet best practice installa- NFPA 780:2014, IEC 62305:2010, UL 1449 4th edition, UL 467

8 WP045/USA/1016 © Copyright 2016 DEHN, Inc.


www.dehn-international.com/partners

DEHN, Inc. Office 772 460 9315


851 South Kings Highway Fax 772 460 9316
Fort Pierce, FL 34945 info@dehn-usa.com
www.dehn-usa.com

Surge Protection DEHN + SÖHNE Hans-Dehn-Str. 1 Tel. +49 9181 906-0


Lightning Protection GmbH + Co.KG. Postfach 1640 Fax +49 9181 906-1100
Safety Equipment 92306 Neumarkt info@dehn.de
DEHN protects. Germany www.dehn-international.com

www.dehn-international.com/partners

Type designations of products mentioned in the white paper being at the same time registered trademarks are not especially marked. So if there is no marking of ™ or ® this does not
mean that the type designation is a free trade name. Neither it can be seen whether patents or utility models and other intellectual and industrial property rights are available. We reserve
the right to introduce changes in performance, configuration and technology, dimensions, weights and materials in the course of technical progress. The figures are shown without obligation.
Misprints, errors and modifications excepted. Reproduction in any form whatsoever is forbidden without our authorisation.
For information on our registered trademarks, please visit www.dehn-international.com/en/our-registered-trademarks.

WP045/USA/1016 © Copyright 2016 DEHN, Inc.

You might also like