Professional Documents
Culture Documents
Contents
Rigorous Calculations
Strike Level and Design
Parameters
Risk Analysis
Separation Distance
Air Terminal Selection
Down Conductor Design
Earthing Design
Test and Maintenance
Surge Protection Devices
Actual Lightning Discharge Testing
www.dehn-usa.com
A comparison of
NFPA 780 and IEC 62305
White Paper
Part 1
General principles
Part 2
Risk management
Protection
against lightning
IEC 62305 Part 3
Physical damage to
structures and life hazard
Part 4
Electrical and electronic
systems within structures
Figure 1 The IEC 62305 suite of standards is divided into four use- Figure 2 The NFPA 780 standard is presently under 2014 revision.
ful segments.
The calculation includes, Human Life, Public Services, Cultural loop requirements, surge-protection requirements, and how to
Heritage, Economic risk, and penalties for denial of service. This install protection for trees, towers and similar structures. The
risk assessment is both good and bad in that pole barns will standard however has two primary short falls in that it does
have fewer requirements than would be found in NFPA 780, not require a detailed analytic calculation of the integrity of
but high value assets will have greater requirements. the installed systems ability to handle direct lightning strike
The basic approach to lightning protection is to work within events, nor does it take into consideration what asset the LPS
the accepted step leader behavior of lightning strikes. Imagine is protecting. In other words, NFPA 780 has the same require-
the final lightning strike distance of a bolt seeking any path to ments for a pole barn as it does for a high value asset.
ground as a radius of a sphere that could touch anywhere. The Table 1 defines the basic NFPA classes of lightning protec-
more stringent the class of lightning protection, the smaller the tion and the mechanical difference in materials for structures
radius and more risk the bolt can find the building. above 75 ft (23 m) in height.
The IEC risk mitigation offered by virtue LPS installation of-
fers tiered criteria structure with more sensitive applications Rigorous Calculations
requireing more stringent LPS protection coverege. LPS IEC The IEC 62305:2006 standard requires an actual assessment
Class III (45 m radius sphere) meets the demand of most typi- of the lightning protection system to insure that it is capable
cal commercial buildings and is most similar to the standard of handling a lightning strike. The lightning strike calculations
NFPA (150 ft sphere) . This IEC LPL class III implies a protection are far more significant for both the time domain parameter
system capable of intercepting lightning strikes with currents (10/350 μs vs 8/20 μs) and the actual strike amperages (100 kA
as low as 10 kA and as high as 100 kA 10/350 μs (see lightning to 200 kA) than the US industry standard (often only 20 kA for
strike figure). Based on these parameters, the rolling sphere UL 1449 and UL 467). IEC 62305:2006 calculations that are re-
method can been employed to develop a safety canopy con- quired include:
structed with a geometry of a 45 m (146.25 ft) radius using air ¨¨ The peak lightning strike current to be carried on individual
terminals, down conductors tested and earthing system capa- conductors in DC amps to ensure that current carrying ca-
ble of handling 100 kA direct lightning currents. pacity is not exceeded.
¨¨ Time-domain analysis of the lightning strike on the specific
NFPA 780 Design Theory and Philosophy
structure. This is critical to understanding the amperage
The NFPA LPS design does not include a mandatory risk review
carrying capacity of the conductors.
but instead is based on the standard NFPA Class I lightning
protection system for lower height ordinary building not more ¨¨ The application of the rolling-ball theory of lightning pro-
than 75 ft (23 m) tall. For this class of structure there is no tection tested against 3D computer models of the structure
requirement for a rolling sphere, so the basic air termination and surrounding area.
placement, down conductor cross section design and earth- ¨¨ Spark gap and arc-flash calculations to allow for flashes
ing rod matching system are employed per relevant NFPA 780 from the lightning protection system to adjacent conduc-
clauses. To meet the standard, each rod height can be selected tive utilities.
at 24 in (61 cm) tall, with interconnection along the roof and ¨¨ Separation distance to avoid flashover from down conduc-
down conductors terminating into a dedicated ground elec- tors to electrical aparatus.
trode earthing rod.
NFPA 780 provides guidelines for how often to place air termi-
nals, spacing’s for cross and down conductors, ground rod and LPL
3 kA 200 kA
I
NFPA 780-2011 (99 %) (99 %)
Item Less than 75-ft More than 75-ft 5 kA 150 kA e.g. for LPL II:
II
(97 %) (98 %) 97 % of all light-
Name Class I Class II ning currents
10 kA 100 kA
Air terminal min 3/8-in dia min 1/2-in dia III > 5 kA and
(91 %) (97 %)
(9.5 mm) (12.7 mm) 98 % < 150 kA
16 kA 100 kA
IV
Main / 57 kcmil (between 115 kcmil (between (84 %) (97 %) Ipeak/kA
downcomer #2 and #3 AWG) 1/0 and 2/0)
05 50 100 150 200
Earthing Rods Rods and loop
Table 1 The NFPA 780 standard divides applications into two Figure 3 The IEC 62305 standard divides applications by likely hood
broad categories by height. of capturing both the high and low severity lightning events.
Figure 4 An excerpt of Annex L risk assessment shows it is well suited for the user to create their own work sheet.
Strike Levels and Design Parameters risk level and then allows selection of features to reduce the
Additional advantages of the IEC methods show up in strike risk. The final rolling sphere coverage result will confirm the
levels and design parameters. structure is protected.
In the IEC 62305 standards, the frequency spectrum of the NFPA 780 annex L describes the informative (suggested but
lightning strike on the specific structure leads to a higher not required) risk review procedure. It does include many of
charge transfer than seen in NFPA strike levels. This forms the the features of the IEC review, but does not actually help deter-
basis for both surge-protection and for timing of circuit break- mine the LPL severity as in the IEC method. The designer does
ers to prevent power outages. not actually select a more rigorous approach as a result of the
Figure 3 shows the Lightning strike levels suggested under IEC NFPA risk review.
to select the LPL measures leading to suggested rolling sphere It is important to note the NEC does require critical operations
diameter (lower strike likelyhood implies a smaller diameter). providers to conduct the annex L risk assesment. The final LPS
design may incorporate these findings but the system does not
Risk Analysis drive improvement.
The IEC requirements imply a normative risk analysis. It is re- The review from NFPA annex L is shown in Figure 4 and lends
quired, and through this excerise the mitigation measures are itself to a spreadhseet calculation.
selected and possibly drive the Lightning Protection Level from The IEC risk review walks through the structure to develop a
a default LPL III to a higher more sever level with smaller roll- fully exposed base line and prompts the designer to increase
ing sphere diameter and higher density of lightning rod air ter- mitigation levels until a tolerable risk level has been estab-
minals. The analysis takes into account the physical structure, lished. These features and lightning strike levels then guide the
hazard location level and occupency to build the un –protected designer to a suitable LPS for the specific structure and use.
Figure 5 The DEHN Support Toolbox helps calculate the direct and
indirect strike collection area.
The direct (solid lines) and indirect (dashed lines) expo- Figure 6 The DEHN software helps the user through the whole
sure area calculations for IEC risk analysis are shown in process to derive the protection measures needed to
Figure 5. reduce risk below the tolerable thresholds and drive
The calculations for intolerable risk, and then mitigated and continuous improvement.
tolerable risk levels can be illustrated like in Figure 6.
The final protected state using the LPL rolling sphere diameter
determined through risk mitigation selection will then be il- NFPA has only a loose discussion on allowing sufficient sep-
lustrated to show coverage like in Figure 7. eration between the LPS conductors and unbonded electrical
systems.
Seperation Distance A sample calculation from NFPA 780 is shown in Figure 8.
Any electrical component or wire will be influenced by the EMP But the IEC involes a detailed review of the separation
from the down conductor as it diverts lightning to ground. The of down conductors from electrical aparatus and wiring
Figure 7 Water cooling towers and electrical distribution centers are illustrated in 3D with the overlay of the theoretical blanket of protection.
(Figure 9). Software modling allows the designer to see how Earthing System Design
many cm spacing would be required around the LPS based on If there are adjacent structures between which electrical pow-
the suggested maximum surge likely to be introduced per the er supply lines and measuring/control lines are installed, the
strike level chart. This allows a designer to take flashover into earth-termination systems have to connect between reinforce-
account systematically through the structure and not neglect ment, down conductor and earthing systems for equipotential
these effects accidentally. bonding. It is advantageous to reduce the currents in the lines
Isolation spacing and insulation materials are suggested under via many parallel paths. This aim is fulfilled by means of an
the IEC methods to prevent touch and step voltages next to intermeshed earth termination system.
the down conductors and earthing electrodes. Concrete columns that are used for down conductors must be
Figure 10 illustrates the 3 m (9.75 ft) limit for touch and step tested a 0.2 ohms or less continuity, and rebar must be welded
insulation as recommened by IEC. This is a key issue in select- with 20 x diameter overlaps. These must be bonded to the floor
ing LPS components with intrinsic safety insulation features. slab according to IEC 62305.
This allows the designer to minimize spacing and cost to Ground rings are required for all non-conductive buildings,
achieve the safest effective control of risk. buildings housing electronic systems, and certain risk factors
and other metallic objects must be considered. In addition, the Figure 13 Here, the equipotential bonding of incoming metal pipes
IEC 62305 standards suggests that incoming utility services and the application of SPD’s are illustrated with connec-
(such as overhead power lines) and adjoining public spaces tions to the Master Earthing Bar (MEB).
Summary
In summary, the IEC 62305 certification for achievement of References:
UL 96A master label requirements meet best practice installa- NFPA 780:2014, IEC 62305:2010, UL 1449 4th edition, UL 467
www.dehn-international.com/partners
Type designations of products mentioned in the white paper being at the same time registered trademarks are not especially marked. So if there is no marking of ™ or ® this does not
mean that the type designation is a free trade name. Neither it can be seen whether patents or utility models and other intellectual and industrial property rights are available. We reserve
the right to introduce changes in performance, configuration and technology, dimensions, weights and materials in the course of technical progress. The figures are shown without obligation.
Misprints, errors and modifications excepted. Reproduction in any form whatsoever is forbidden without our authorisation.
For information on our registered trademarks, please visit www.dehn-international.com/en/our-registered-trademarks.