Professional Documents
Culture Documents
This standard gives material, construction, and design requirements for 3.3—Strength tests
cast-in-place and precast reinforced concrete chimneys. It sets forth mini- 3.4—Forms
mum loadings for design and contains methods for determining the con-
crete and reinforcement required as a result of these loadings. The method 3.5—Reinforcement placement
of analysis applies primarily to circular chimney shells; however, a general 3.6—Concrete placement
procedure for analysis of noncircular shapes is included. 3.7—Concrete curing
This standard is written in explicit, mandatory language, and as such, is
3.8—Construction tolerances
intended for reference in project specifications.
Equations are provided for determining the temperature gradient through 3.9—Precast erection
the concrete resulting from the difference in temperature of the gases inside
the chimney and the surrounding atmosphere. Methods for combining the Chapter 4—Service loads and general design
effects of dead and wind (or earthquake) loads with temperature both verti- criteria, p. 307-3
cally and circumferentially are included in the standard. These methods 4.1—General
permit the designer to establish minimum concrete and reinforcement
4.2—Wind loads
requirements.
This standard refers extensively to “Building Code Requirements for 4.3—Earthquake loads
Structural Concrete” (ACI 318); construction requirements are generally 4.4—Special design considerations and requirements
in accordance with ACI 318; and notation is in accordance with ACI 104. 4.5—Deflection criteria
Keywords: chimneys; compressive strength; concrete construction; Chapter 5—Design of chimney shells:
earthquake-resistant structures; formwork (construction); foundations; high Strength method, p. 307-9
temperature; linings; loads (forces); moments; openings; precast concrete; 5.1—General
quality control; reinforced concrete; reinforcing steels; specifications; 5.2—Design loads
static loads; strength; structural analysis; structural design; temperature; 5.3—Required strength
thermal gradient; wind pressure.
5.4—Design strength
5.5—Nominal moment strength: Circular shells
CONTENTS
Chapter 1—General, p. 307-2 5.6—Noncircular shapes
1.1—Scope 5.7—Design for circumferential bending
1.2—Drawings
1.3—Regulations Chapter 6—Thermal stresses, p. 307-13
1.4—Reference standards 6.1—General
6.2—Vertical temperature stresses
Chapter 2—Materials, p. 307-2 6.3—Circumferential temperature stresses
2.1—General
2.2—Cement Appendix A—Notation, p. 307-15
2.3—Aggregates
2.4—Reinforcement
ACI 307-98 became effective November 1, 1998, and supersedes ACI 307-95.
Copyright © 1998, American Concrete Institute.
All rights reserved including rights of reproduction and use in any form or by any
Chapter 3—Construction requirements, p. 307-2 means, including the making of copies by any photo process, or by any electronic or
3.1—General mechanical device, printed, written, or oral, or recording for sound or visual reproduc-
tion or for use in any knowledge or retrieval system or device, unless permission in
3.2—Concrete quality writing is obtained from the copyright proprietors.
307-1
307-2 ACI STANDARD
4.1.2 The chimney shell shall be designed for load combi- At a height z ft (z m) above ground, the mean hourly design
nations in accordance with the provisions of Chapter 5, speed V(z) in ft/sec (or for V(z) in m/s) shall be computed
Design of chimney shell: Strength method. from Eq. (4-1)
4.1.3
0.154
V ( z ) = ( 1.47 ) V R ------
4.1.3.1 The chimney shell shall not be less than 8 in. z
( 0.65 ) (4-1)
(200 mm) thick when cast in place, or less than 7 in. (180 mm) 33
thick when composed of precast sections.
4.1.3.2 The chimney shell thickness, through openings, for metric units:
shall not be less than 1/24 the height of the opening.
The thickened shell shall extend at least 1/2 the height of z 0.154
V z = 0.2784V R ------ ( 0.65 )
the opening above and below the opening. Properly designed 10
buttresses or other means of lateral restraint may be used in
place of this requirement; however, the buttresses shall be
with VR in km/hr.
ignored when calculating vertical strength.
The provisions with respect to wind load take account of dy-
4.1.3.3 When the internal diameter of the shell exceeds
namic action but are simplified and lead to equivalent static
28 ft (8.5 m), the minimum thickness shall be increased 1/8 in.
loads. A properly substantiated dynamic analysis may be
for each 1 ft (10.4 mm per 1 m) increase in internal diameter.
used in place of these provisions.
4.1.4 A chimney shell that supports lining loads shall com- 4.2.2 Along-wind load: Circular shapes—The along-wind
ply with the requirements of this standard with the lining in load, w(z) per unit length at any height z ft, shall be the sum
place. The interaction of the liner with the shell shall be of the mean load w (z) and the fluctuating load w ′(z).
considered. The mean load w (z) in lb/ft (w (z) in N/m) shall be computed
4.1.5 Consideration shall be given to loadings during the from Eq. (4-2)
construction phase.
4.1.6 If required during construction, temporary access
w ( z ) = C dr ( z ) • d ( z ) • p ( z ) (4-2)
openings may be provided in the concrete shell. For the design
of the shell, these openings shall be designed as permanent
openings. where
4.1.7 Cdr(z) = 0.65 for z < h – 1.5d(h) (4-3a)
4.1.7.1 The maximum foundation bearing pressure shall
be established using unfactored chimney loads. Cdr(z) = 1.0 for z ≥ h – 1.5d(h) (4-3b)
4.1.7.2 The foundation shall be designed by the strength
method in accordance with the procedures of ACI 318. The p(z) = 0.0013 [V(z)]2 (4-4)
foundation design shall be based on a pseudo-bearing pressure
distribution, or pile loads, using the loading combinations for metric units, p(z) in Pa:
given in Section 5.3.1 and 5.3.2.
4.1.7.3 The minimum factor of safety against overturning p(z) = 0.67[V(z)]2
shall be 1.50 using unfactored loads.
4.1.7.4 Consideration shall be given to the effects of d(z) = outside diameter at height z, ft (or d(z) in m)
radiant heat of gases on any part of the foundation, including h = chimney height above ground level, ft (or h in m)
the foundation floor area which is exposed within the liner d(h) = top outside diameter, ft (or d(h) in m)
and also concrete floors supported from the concrete shell. The fluctuating load w′(z), lb/ft, (w′(z) in N/m) shall be taken
equal to
4.2—Wind loads
4.2.1 General—Reinforced concrete chimneys shall be
3.0z • Gw ′ • M w ( b )
designed to resist the wind forces in both the along-wind and w ′ ( z ) = ----------------------------------------------
- (4-5)
3
across-wind directions. In addition, the hollow circular cross h
section shall be designed to resist the loads caused by the
circumferential pressure distribution. where Mw(b) = base bending moment, lb-ft (N-m), due to
The reference design wind speed in mph (km/h), which w(z) and
shall be denoted as VR , shall be the “3-sec gust” wind speed
at 33 ft (10 m) over open terrain where VR = ( I )0.5V. This 0.47
11.0 [ T 1 • V ( 33 ) ]
speed V and importance factor I shall be as specified by Gw ′ = 0.30 + -------------------------------------------------
- (4-6)
0.86
ASCE 7. All chimneys shall be classified as Category IV ( h + 16 )
structures as defined in ASCE 7-95. Terrain effects refer-
enced in Section 6.5.5 of ASCE 7-95 are omitted. for metric units, w(z) in N/m:
REINFORCED CONCRETE CHIMNEYS 307-5
0.47 1
19.227 [ T 1 • V ( 10 ) ] 1⁄2 ---
G w ′ = 0.30 + -------------------------------------------------------
- π 2L 2
( 3.2808 • h + 16 )
0.86 ------------------------
- • S p -------------------------
-
4 ( βs + βa ) h
----------- + C E
d(u)
where V(33) is determined from Eq. (4-1) for z = 33 ft (10 m).
For preliminary design and evaluation of the critical wind Eq. (4-8) defines the peak base moment Ma for values of
speed Vcr , as described in Section 4.2.3.1, the natural period V, where V is evaluated between 0.5 and 1.30 V(zcr). When V
of an unlined chimney T 1, in seconds per cycle, may be ≥ V(zcr), Ma shall be multiplied by
approximated using Eq. (4-7). However, for final design, the
period shall be computed by dynamic analysis
V – V ( z cr )
------------------------
-
1.0 – 0.95 (4-8a)
h
2 ρ ck t ( h ) 0.3 V ( z cr )
T 1 = 5 ----------- -------
- --------- (4-7)
d ( b ) ck t ( b )
E
where
for metric units: V(zcr) = the mean design wind speed at zcr , zcr = 5/6h,
ft/sec (m/sec)
2 ρ ck g = acceleration due to gravity = 32.2 ft/sec2
h t(h) 0.3
T 1 = 5.32808 ----------- -----------------------------
- --------- G = peak factor = 4.0
d ( b ) ck E • 1099.2 t (b)
Ss = mode shape factor = 0.57 for first mode, 0.18
for second mode
where
C L = C Lo F 1 ( B ) (4-9)
h = chimney height above base, ft (m)
t(h) = thickness at top, ft (m) where
t(b) = thickness at bottom, ft (m)
d(b) = mean diameter at bottom, ft (m) 2
C Lo = – 0.243 + 5.648i – 18.182i (4-10)
ρck = mass density of concrete, kip-sec2/ft4 (mg-sec 2/m4)
Eck = modulus of elasticity of concrete, kip/ft2 (MPa) where
G ρa 2 2
M a = ---- S s C L -----V d(u )h • fd ( u )
g 2 cr V cr = ------------- (4-13)
St
1
1⁄2 --2- f = first-mode frequency, Hz
π -------------------------------
2L
-
------------------------- • Sp (4-8) St = Strouhal number
4 ( βs + βa ) h -+C
----------
d(u) E
S t = 0.25F 1 ( A ) (4-14)
ρa 2 2 h
M a = GS s C L -----V d( u ) h • F 1 ( A ) = 0.333 + 0.206loge ----------- (4-15)
2 cr d(u)
307-6 ACI STANDARD
but not > 1.0 or < 0.60. The period T2 in seconds per cycle for an unlined shell
may be estimated by Eq. (4-24). For final design, T2 shall be
d(u) = mean outside diameter of upper third of chimney,
ft (m) calculated by dynamic analysis
h = chimney height above ground level, ft (m)
0.09 – 0.22
h
2 ρ ck t(h ) d( h )
0.10 [ V – V ( Z ) ] T 2 = 0.82 ----------- -------
- --------- ----------- (4-24)
d ( b ) E ck t(b ) d( b )
β s = 0.01 + --------------------------------------
cr
- (4-16)
V( Z )
cr
for metric units:
but not < 0.01 or > 0.04.
h
2 ρ ck
βa = aerodynamic damping T 2 = 0.82 • 3.2808 ----------- -----------------------------
- •
d ( b ) E ck • 1099.2
2
Ka ρa d ( u )
β a = -------------------------
- (4-17) t(h ) 0.09 d(h) – 0.22
wt ( u ) --------- -------------
t(b ) db ( b )
Ka = Kao F1(B) (4-18)
where t(h) and t(b) are the thicknesses at the top and bottom,
where respectively, and d(h) and d(b) are the mean diameters at the
top and bottom, respectively.
The effect of a shell-supported liner on the period of the
– 1.0
K ao = ----------------------------------------------------- (4-19) second mode shall also be investigated.
( 1 + 5i ) 1 + ----------------- k – 1 - Any method using the modal characteristics of the chim-
i + 0.10 ney shall be used to estimate the across-wind response in the
second mode.
where 4.2.3.4 Grouped chimneys—When two identical chim-
neys are in close proximity, the across-wind load shall be in-
V
k = ------- (4-20) creased to account for the potential increase in vortex-
V cr induced motions. In such cases, the lift coefficient CL in
Eq. (4-9) shall be modified as follows
wt(u) = average weight in top third of chimney, lb/ft (kg/m) a) if s/d(zcr) > 12.75, CL is unaltered
Sp = spectral parameter
b) if 3 < s/d(zcr) < 12.75, CL shall be multiplied by:
3
---
[0.26 – 0.015 s/d(zcr)] + [2 – s/12d(zcr)]
2 –1 2
k 11 – k where
S p = ------------exp – --- ---------------- (4-21)
1 1
--- --- 2 B
2 4 s = center-to-center spacing of chimneys, ft (m)
B π d(zcr) = outside diameter of chimney at critical height zcr,
ft (m)
where For chimneys that are not identical and for identical chim-
B = band-width parameter neys where s/d(zcr) < 3, the value of CL shall be established
B = 0.10 + 2i (4-22) by reference to model tests or observations or test reports of
L = correlation length coefficient similar arrangements.
4.2.3.5 Combination of across-wind and along-wind
L = 1.20
loads—Across-wind loads shall be combined with the
CE = end effect factor = 3
coexisting along-wind loads. The combined design moment
After solving for Ma , across-wind moments at any height
Mw(z) at any section shall be taken as
Ma(z) may be calculated based on the corresponding mode
shape of the chimney column.
0.5
4.2.3.3 Second mode—Across-wind response in the sec- 2 2
ond mode shall be considered if the critical wind speed Vcr2 Mw ( z ) = [ M a ( z ) ] + [ M l ( z ) ] (4-25)
as computed by Eq. (4-23) is between 0.50 and 1.30 V(zcr),
where V(zcr) is the mean hourly wind speed at 5/6h
where
V cr2 = 5d ( u )-
------------- (4-23) Ma (z) = moment induced by across-wind loads
T2 Ml (z) = moment induced by the mean
REINFORCED CONCRETE CHIMNEYS 307-7
Mi(z) = 0.31pr(z) [r(z)]2, N-m/m Table 4.3.2(a)— Special values for maximum
ground acceleration of 1.0g *
Mo(z) = 0.27pr(z) [r(z)]2, ft-lb/ft (tension on outside) (4-28) Velocity
Frequency, Displacement spectrum, Acceleration
Hz spectrum, in. in./sec spectrum, g
for metric units:
f ≤ 0.25 50.7 318.6f 5.186 f 2
Mo(z) = 0.27pr(z) [r(z)]2, N-m/m
10.39 65.26
where 0.25 ≤ f ≤ 2.5 ----------------
1.1436
----------------
0.1436 1.062f
0.8564
f f
r(z) = mean radius at height z, ft (m)
25.32 159.1 2.589
pr(z) = 0.0013[V(z)]2 • Gr(z), lb/ft2 (4-29) 2.5 ≤ f ≤ 9 -----------------
2.1158
----------------
1.1158
-----------------
0.1158
f f f
Fig. 4.3.2—Normalized horizontal elastic seismic response spectra. (Convert to comparable units. No metric conversion is presented.)
of not being exceeded in 50 years with 5 percent damping. If 4.4—Special design considerations and
a site-specific response spectrum is unavailable, the design requirements
response spectrum for the site shall be obtained by scaling 4.4.1 Two layers of vertical and circumferential reinforce-
down the normalized 1.0g peak ground acceleration ment are required. The total vertical reinforcement shall be
spectrum for 5 percent damping shown in Fig. 4.3.2 or not less than 0.25 percent of the concrete area. The outside
Table 4.3.2(a) by the scaling ratios given in Table 4.3.2(b) vertical reinforcement shall be not less than 50 percent of the
for the Av of the site. total reinforcement. Outside-face vertical bars shall not be
The normalized design response spectrum given in smaller than No. 4, nor shall they be spaced more than 12 in.
Fig. 4.3.2 or Table 4.3.2(a) is suitable for firm soil conditions. (No. 13 M bars at 300 mm) on centers. Inside-face vertical
The response spectrum shall be modified for soft and shallow bars shall not be smaller than No. 4, nor shall they be spaced
soil conditions by any method that is properly substantiated more than 24 in. (No. 13 M bars at 600 mm) on centers.
and complies with the basic principles herein. 4.4.2 The total circumferential reinforcement shall not be
The analytical model of a chimney used in the dynamic less than 0.20 percent of the concrete area. The circumferential
response spectrum analysis shall be sufficiently refined to reinforcement in each face shall be not less than 0.1 percent of
represent variations of chimney and liner masses, variations the concrete area at the section.
of stiffness, and the foundation support condition. A minimum Spacing of outer face circumferential reinforcement shall
of 10 elements shall be included. The total dynamic response not exceed the wall thickness or 12 in. (300 mm). Spacing of
of the chimneys in terms of shear and moment shall be com- circumferential reinforcement on the inner face shall not
puted using the SRSS over a minimum of five normal modal exceed 12 in. (300 mm). The minimum size of circumferen-
responses. SRSS means taking the square root of the sum of the tial reinforcing bars shall be No. 3 (No. 10 M).
squares of modal maxima. The use of the CQC method (com- 4.4.3 The circumferential reinforcement for a distance of
plete quadratic combination) is also permitted. 0.2d(h) from the top of the chimney or 7.5 ft (2.3 m), whichever
REINFORCED CONCRETE CHIMNEYS 307-9
where where
α = one-half the central angle subtended Mn = nominal moment strength of section
307-12 ACI STANDARD
2 fc
( ψ – µ ) ( 1 + 2 cos α ) a b
+ ( 1 ⁄ 2 ) ( 4 sin 2 α + sin 2 ψ – sin 2 µ ) 0.85fc′
Stress
K = sinψ + sinµ + (π – ψ – µ) cosα (5-14)
εc
Strain
R = sinτ – (τ – n1β) cosα – (n1/2)[sin (γ + β) – sin(γ – β)] (5-15a) 0.002 0.003
Strain
γ = 1
/2 angle between center lines of two openings 2ε c ε c 2
and for no openings, n1 = γ = β = 0; for one a) fc = 0.85fc′ ------------
- – -------------
0.002 0.002
opening in compression zone, n1 = 1, γ = 0;
for two openings in compression zone, n1 = 2 fc = 0.85fc′ (1000εc - 250,000 εc2)
5.5.2 Two symmetric openings partly in compression zone— fc = 850fc′ εc (1 - 250 εc)
Refer to Fig. 5.5.1(c). This condition exists when γ + β > τ ( ε c – 0.002 )
b) fc = 0.85fc′ 1 – 0.15 ----------------------------
-
and γ – β < τ. For this case, let δ = γ – β. Then in Eq. (5-2), λ 0.001
= δ. fc = 0.85fc′ (1 - 150εc + 0.30)
And in Eq. (5-11)
fc = 0.85fc′ (1.30 - 150 εc)
Fig. 6.2.2—Curves for determining Ki . (Convert to comparable units. No metric conversion is presented.)
filling in space between lining and shell, Btu/ft2/in. dco = outside diameter of concrete chimney shell, ft (m)
of thickness/hr/F difference in temperature (watt/ 6.2.2 Unless complete heat balance studies are made for
meter Kelvin and 0.43 watt/meter Kelvin for the particular chimney, it is permissible to use the approxi-
lightweight concrete) (3 for lightweight concrete) mate values given below. These constants when entered into
Ki = coefficient of heat transmission from gas to inner equations for temperature differential through the chimney
surface of chimney lining when chimney is lined, shell Tx will give values of accuracy in keeping with the
or to inner surface of chimney shell when basic design assumptions.
chimney is unlined, Btu/(ft2 • hr • F) [watt/(m2 •
rq = 0.5
Kelvin)] difference in temperature
Cc = 12 (or 1.73 watt/(meter Kelvin))
Ko = coefficient of heat transmission from outside Cs = to be obtained from the manufacturer of the
surface of chimney shell to surrounding air, materials used
Btu/(ft2 • hr • F) [watt/(m2 • Kelvin)] difference in Cb = to be obtained from the manufacturer of the
temperature materials used
Kr = coefficient of heat transfer by radiation Ki = to be determined from curves in Fig. 6.2.2
between outside surface of lining and inside Ko = 12 Btu/(ft2 • hr • F) [68 watts/(m2 • Kelvin)]
surface of concrete chimney shell, Btu/(ft2 • hr • F) Kr = Ti /120 (or Ti /9.75 in metric)
[watt/(m2 • Kelvin)] difference in temperature Ks = Ti /150 (or Ti /9.75 in metric)
Ks = coefficient of heat transfer between outside surface The value of rq = 0.5 shall apply only where the distance
of lining, and inside surface of shell for chimneys between the lining and the chimney shell is not less than 4 in.
with ventilated air spaces, Btu/(ft2 • hr • F) [watt/
throughout the entire height of the lining and air inlet and
(m2 • Kelvin)] difference in temperature
dbi = inside diameter of uninsulated lining or insulation outlet openings are provided at the bottom and top of the
around liner, ft (m) chimney shell. The area of the inlet and outlet openings in
db = mean diameter of uninsulated lining or insulation square feet shall numerically equal two-thirds the inside
around liner, ft (m) diameter in feet of the chimney shell at the top of the lining.
ds = mean diameter of space between lining and shell, Local obstructions in the air space between the lining and the
ft (m) chimney shell shall not restrict the area of the air space at any
dc = mean diameter of concrete chimney shell, ft (m) horizontal section to less than that specified for air inlet or
dci = inside diameter of concrete chimney shell, ft (m) outlet.
REINFORCED CONCRETE CHIMNEYS 307-15
6.2.3 The maximum stress in the vertical steel fSTV in psi Cb = coefficient of thermal conductivity of chimney
(or MPa), occurring at the outside face of the chimney uninsulated lining or insulation around steel
shell due to temperature, shall be computed by Eq. (6-4) liner, Btu ⋅ ft/(hr ⋅ ft2 ⋅ F) of thickness/hr/F (watt/
[meter Kelvin]) difference in temperature
(Chapter 6)
f STV = α te • ( γ 2 – c ) • T x • E s (6-4)
Cc = coefficient of thermal conductivity of concrete
of chimney shell, Btu ⋅ ft/(hr ⋅ ft2 ⋅ F) of
where thickness/hr/F (watt/[meter Kelvin]) difference
in temperature (12 for normalweight concrete)
Es = modulus of elasticity of the reinforcement, psi (or 1.73 watt/meter Kelvin) (Chapter 6)
(MPa)
Cdr = drag coefficient for along-wind load
(Chapter 4 and Commentary Chapter 4)
6.3—Circumferential temperature stresses
6.3.1 The maximum circumferential stress in psi (or MPa) CE = end effect factor (Chapter 4)
in the concrete due to temperature f ″CTC occurring at the in- CL = rms lift coefficient (Chapter 4)
side of the chimney shell shall be computed by Eq. (6-5) CLo = rms lift coefficient modified for local turbulence
(Chapter 4)
f ″CTC = αte • c′ • Tx • Ec (6-5)
Cs = coefficient of thermal conductivity of insulation
filling in space between lining and shell,
where Btu ⋅ ft/(hr ⋅ ft2 ⋅ F) of thickness/hr/F (watt/meter
c′ = Kelvin) difference in temperature (3 for
lightweight concrete) (or 0.43 watt/meter Kelvin)
– ρ′ n ( γ 1 ′ + 1 ) (Chapter 6)
(6-6) d = diameter of chimney (Commentary Chapter 4)
2
+ [ ρ′ n ( γ 1 ′ + 1 ) ] + 2 ρ′ n [ γ 2 ′ + γ 1 ′ ( 1 – γ 2 ′ ) ]
db = mean diameter of uninsulated lining or
insulation around liner, ft (m) (Chapter 6)
and dbi = inside diameter of uninsulated lining or
insulation around liner, ft (m) (Chapter 6)
Tx = value determined for vertical temperature stresses
dc = mean diameter of concrete chimney shell, ft (m)
ρ′ = ratio of cross-sectional area of circumferential (Chapter 6)
outside face reinforcing steel per unit of height to
cross-sectional area of chimney shell per unit of dci = inside diameter of concrete chimney shell, ft (m)
height (Chapter 6)
γ1′ = ratio of inside face circumferential reinforcing dco = outside diameter of concrete chimney shell, ft (m)
steel area to outside circumferential reinforcing (Chapter 6)
steel area ds = mean diameter of space between lining and
γ2′ = ratio of distance between inner surface of chimney shell, ft (or m) (Chapter 6)
shell and circumferential outside face reinforcing d(b) = bottom outside diameter of chimney, ft (m)
steel to total thickness t (Chapter 4)
All other notations are the same as for vertical temperature d(b) = mean diameter at bottom of chimney, ft (m)
(Chapter 4)
stresses.
6.3.2 The maximum stress in psi in the outside circumfer- d(h) = top outside diameter of chimney, ft (m)
(Chapter 4 and Commentary Chapter 4)
ential reinforcement fSTC due to temperature shall be comput-
ed by Eq. (6-7) d(h) = mean diameter at top of chimney, ft (m)
(Chapter 4)
fSTC = αte • (γ2′ – c′) • Tx • Es (6-7) d(u) = mean outside diameter of upper third of
chimney, ft (m) (Chapter 4)
APPENDIX A—NOTATION d(z) = outside diameter of chimney at height z, ft (m)
As = area of reinforcing steel at top and bottom of (Chapter 4 and Commentary Chapter 4)
opening, in.2 (mm2) (Chapter 4) d(zcr) = outside diameter of chimney at critical height
B = band width parameter (Chapter 4) zcr, ft (m) (Chapter 4)
c = ratio of distance from extreme compression D = dead load (Chapter 5)
fiber to neutral axis for vertical stresses to total E = earthquake loads or forces (Chapter 5)
thickness t (Chapter 6)
Ec = modulus of elasticity of concrete, psi (MPa)
c′ = c for circumferential stresses (Chapter 6) (Chapter 6)
307-16 ACI STANDARD
Eck = modulus of elasticity of concrete, kip/ft2 (MPa) ks = equivalent sand-grained surface roughness
(Chapter 4) factor (Commentary Chapter 4)
Es = modulus of elasticity of reinforcement, psi K = parameter for nominal moment strength
(MPa) (Chapters 5 and 6) in Chapter 5 or horizontal force factor
EPV = effective peak velocity (Commentary Chapter 4) for earthquake design in Commentary
Introduction
f = frequency, Hz (Chapter 4)
Ke = Es /fy (Chapter 5)
fc′ = specified compressive strength of concrete, psi
(MPa) (Chapter 4) Ki = coefficient of heat transmission from gas to
inner surface of chimney lining when chimney
fc″(c) = fc′ modified for temperature effects, is lined, or to inner surface of chimney shell
circumferential, psi (MPa) (Chapter 5) when chimney is unlined, Btu/ft2/hr/F
fc″(v) = fc′ modified for temperature effects, vertical, psi difference (watt/[m2 Kelvin]) in temperature
(MPa) (Chapter 5) (Chapter 6)
f ″CTC = maximum circumferential stress in concrete due Ko = coefficient of heat transmission from outside
to temperature at inside of chimney shell, psi surface of chimney shell to surrounding air,
(MPa) (Chapters 5 and 6) Btu/ft2/hr/F (watt/[m2 Kelvin]) difference in
f ″CTV = maximum vertical stress in concrete at inside of temperature (Chapter 6)
chimney shell due to temperature, psi (MPa) Kr = coefficient of heat transfer by radiation between
(Chapters 5 and 6) outside surface of lining and inside surface of
fSTC = maximum stress in outside circumferential concrete chimney shell, Btu/ft2/hr/F (watt/[m2
reinforcement due to temperature, psi (MPa) Kelvin]) difference in temperature (Chapter 6)
(Chapters 5 and 6) Ks = coefficient of heat transfer between outside
fSTV = maximum stress in outside vertical surface of lining and inside surface of shell for
reinforcement due to temperature, psi (MPa) chimneys with ventilated air spaces,
(Chapters 5 and 6) Btu/ft2/hr/F (watt/[m2 Kelvin]) difference in
temperature (Chapter 6)
f ″STV = maximum stress in inside vertical reinforcement
due to temperature, psi (MPa) (Chapters 5 and 6) K1, K2,
fy = specified yield strength of reinforcing steel, psi K3 = parameters for nominal moment strength
(MPa) (Chapters 4 and 5) (Chapter 5)
fy′(c) = fy modified for temperature effects, l = width of opening in concrete chimney shell, in.
circumferential, psi (MPa) (Chapter 5) (mm) (Chapter 4)
fy′(v) = fy modified for temperature effects, vertical, psi L = length coefficient (Chapter 4)
(MPa) (Chapter 5) Ma(z) = moment induced at height z by across-wind
F1A = strouhal number parameter (Chapter 4) loads, ft-lb (m-N) (Chapter 4)
F1B = lift coefficient parameter (Chapter 4) Mi(z) = maximum circumferential bending moment due
g = acceleration due to gravity, 32.2 ft/sec 2 to radial wind pressure, at height z, tension on
(9.8 m/sec2) (Chapter 4 and Commentary inside, ft-lb/ft (m-N/m) (Chapter 4)
Chapter 4) Ml (z) = moment induced at height z by mean along-
G = across-wind peaking factor (Chapter 4) wind load, ft-lb (m-N) (Chapter 4)
Gr(z) = gust factor for radial wind pressure at height z Mn = nominal moment strength at section (Chapter 5)
(Chapter 4 and Commentary Chapter 4) Mo(z)= maximum circumferential bending moment due
Gw′ = gust factor for along-wind fluctuating load to radial wind pressure, at height z, tension on
(Chapter 4 and Commentary Chapter 4) outside, ft-lb/ft (m-N/m) (Chapter 4)
h = chimney height above ground level, ft (m) Mu = factored moment at section (Chapter 5)
(Chapter 4 and Commentary Chapter 4) Mw (b)= bending moment at base due to mean along-
i = local turbulence parameter (Chapter 4) wind load, ft-lb (m-N) (Chapter 4)
I = importance factor for wind design in Chapter 4 Mw(z)= combined design moment at height z for across-
and ASCE 7 wind and along-wind loads (Chapter 4)
k = ratio of wind speed (V) to critical wind speed n = modular ratio of elasticity Es /Ec (Chapter 6)
(Vcr ) n1 = number of openings entirely in compression
ka = aerodynamic damping parameter (Chapter 4) zone (Chapter 5)
kao = mass damping parameter of small amplitudes p(z) = pressure due to mean hourly design wind speed
(Chapter 4) at height z, lb/ft2 (Pa) (Chapter 4)
REINFORCED CONCRETE CHIMNEYS 307-17
pr(z) = radial wind pressure at height z, lb/ft2 (Pa) Vr = V(I 0.5 ), mph (km/hr) (Chapter 4)
(Chapter 4 and Commentary Chapter 4) V = mean hourly wind speed at 5/6h varying
Pcr = pressure due to wind at critical speed (Chapter 4) over a range of 0.50 and 1.30 V(zcr), ft/sec (m/sec)
Pu = factored vertical load (Chapter 5) V(h) = mean hourly wind speed at top of chimney, ft/
Q = stress level correction parameter sec (m/sec) (Chapter 4)
(Chapter 5 and Commentary Chapter 5) V(z) = mean hourly design wind speed at height z, ft/
Q′, Q1, sec (m/sec) (Chapter 4)
Q2, Q3= parameters for nominal moment strength V(zcr) = mean hourly design wind speed at 5/6h, ft/sec
(Chapter 5) (m/sec) (Chapter 4)
r = average radius of section (Chapter 5) V(33) = mean hourly wind speed at a height
of 33 ft, ft/sec (m/sec) (Chapter 4)
rq = ratio of heat transmission through chimney shell
to heat transmission through lining for w(z) = total along-wind load per unit length at height z,
chimneys with ventilated air spaces (Chapter 6) lb/ft (N/m) (Chapter 4)
r(z) = mean radius at height z, ft (m) (Chapter 4) w(z) = mean along-wind load per unit length at height
z, lb/ft (N/m) (Chapter 4 and Commentary
R = parameter for nominal moment strength Chapter 4)
(Chapter 5)
w′(h) = fluctuating along-wind load per unit length
s = center-to-center spacing of chimneys, ft (m) at top of chimney, lb/ft (N/m) (Commentary
(Chapter 4 and Commentary Chapter 4) Chapter 4)
Sp = spectral parameter (Chapter 4) w′(z) = fluctuating along-wind load per unit length
Ss = mode shape factor (Chapter 4) at height z, lb/ft (N/m) (Chapter 4)
St = strouhal number (Chapter 4) wa(h) = across-wind load per unit length at top
of chimney, lb/ft (N/m) (Chapter 4)
t = thickness of concrete shell (m) (Chapters 5 and 6)
wa(z) = across-wind load per unit length at height z, lb/ft
tb = thickness of uninsulated lining or insulation
(N/m) (Chapter 4)
around steel liner, in. (m) (Chapter 6)
ts = thickness of air space or insulation filling the wt(u) = average weight per unit length for top third of
space between lining and shell, in. (m) chimney, lb/ft (N/m) (Chapter 4)
(Chapter 6) w1(z) = mean along-wind load per unit length as given
t(b) = thickness of concrete shell at bottom, ft (m) by Eq. (4-27), lb/ft (N/m) (Chapter 4)
(Chapter 4) W = wind load (Chapter 5)
t(h) = thickness of concrete shell at top, ft (m) (Chapter 4) Ymax = maximum lateral deflection of top of chimney,
T = normal temperature effect, F (C) (Chapter 6) in. (mm) (Chapter 4)