Steam Trap
tion Software
Selecting the best type and size
steam trap is easior today for sys-
tem designers who use computer
software. programs. The Spirax
Sarco “STEAM NEEDS ANALY-
SIS PROGRAM" is available at
www.snapfour.com and goes a
stop further. SNAP not only rec-
‘ommends and sizes the rap from
input conditions, but also speci
fies condensate return pumps,
other necessary auxilary equip:
ment, and warns of system
problems that may be encoun-
fered. The SNAP program is
userriendly, menu-drven soft
ware that accurately calculates
the condensate load for a wide
range of drip, tracing and process
applications (described both by
common name. and. generic
description.) Significant is the fact
that a SNAP user has the choice
of selecting either a recommend:
fed type of trap or a different type
that may be preferred for any rea-
son. For all selections, a formal
specification sheet may be print-
ed which contains additional
information,
Steam Trap Selection
‘A QUICK GUIDE TO THE SIZING OF STEAM TRAPS
Need To Know:
1, The steam pressure at the trap—after any pressure drop through
control valves or equipment.
2. THE LIFT, if any, after the trap.
Rule of thumb: 2 ft. = 1 psi back pressure, approximately.
3. Any other possible sources of BACK PRESSURE in the
condensate return system
eg.A) Condensate taken to a pressurized DA. tank,
B) Local back pressure due to discharges of numerous traps
close together into small sized return,
4, QUANTITY of condensate to be handled. Obtained from
A) Measurement, B) Calculation of heat load (see page 24), and
C) Manufacturer's Data
5, SAFETY FACTOR—These factors depend upon particular
applications, typical examples being as follows:
General With Temp. Control
Mains Drainage x2
Storage Heaters x2 =
‘Space Unit Heaters x2 x3.
Air Heating Coils x2 x3
Submerged Coils (low level drain) x2 =
‘Submerged Coils (siphon drain) x3. =
Rotating Cylinders x3. =
Tracing Lines x2 =
Platen Presses x2 =
Rule of thumb: Use factor of 2 on everything except Temperature
Controlled Air Heater Coils and Converters, and
Siphon applications.
How To Use
‘The difference between the steam pressure at the trap, and the total
back pressure, including that due to any lft after the trap, is the
DIFFERENTIAL PRESSURE. The quantity of condensate should be
multiplied by the appropriate factor, to produce SIZING LOAD. The
trap may now be selected using the DIFFERENTIAL PRESSURE and
the SIZING LOAD.
Example
A trap is required to drain 22 Ib/h of condensate from a 4" insulated
‘steam main, which Is supplying steam at 100 PSIG. There will be a lift
after the trap of 20 ft.
Supply Pressure 100 psig
Litt 20 ft = 10 psi approx.
Therefore
Differential Pressure = 100-10 = 90 psi
Quantity, 22 lbihr
2
44 Ibihr
Mains Drainage Factor
Therefore Sizing Load
‘A.small reduced capacity Thermo-Dynamic® steam trap will easily
handle the 44 Ib/h sizing load at a differential pressure of 90 psiSteam Trap Selection Guide
Table 11: Steam Trap Selection Guide
{As the USA's leading provider of steam system solutions, Spirax Sarco recognizes that no two steam trapping
‘ystems ae identical. Because of the wide array of steam trap applications with inherently diferent characteristics,
‘choosing the correct steam trap for optimum performance is dificult, Waterhammer, superheat, corrosive conden-
‘sate, or other damaging operating characteristics dramatically affect performance of a steam trap. With over 80 years
‘of experience in steam technology, Spirax Sarco is committed to helping i's customers design, operate and maintain
an efficient steam system. You have our word on it!
1st Choice 2nd Choice
Flat | hemo: igs iowrts | Fos | Taro: Banos Liga ives
‘Application [emetic bier erpaneon| Suet |rerostte | Orme ‘inate expanin| uct!
Seam Naine _wea0pe—| 7 7Z
3-100 Fa) z 7
72.600 pO z 7
12 900 Be) z Z
72000 peg 7 7
ai Sapeoat z Zz
Separators ¥ 7
[Steam Tracers Giza Z Zz
Norcreal Zz Zz
Heating Equipment
Salk Tae rereaanes | 7 Z
esing Cais |v 7
Unt Heaters | 7 z
jam Fava ae Stans | 7
Fadler Z
General Process Equipment
vw sopeg| 7 TZ
w200pe3| 7 7
wasspea| 7 Z
12.600 pa) Zz
12 000 pe 7Z
200056 Z
spiel Equipment
‘Aucaves | 7 Z
Sais] 7 Z
Foal OF Heating
Buk Storage Tans Z Zz
Te Heats | 7
‘Buk Sora Tans Z Zz
Process Va] 7 Zz
Valeaniare Zz Zz
Evaporators ¥ 7
ebolere Z zZ
Rotating Cylinders z
Freeze Protection Zz