FIRE SAFETY CHECKLIST


ON BUILDING PLANS
Plan Evaluator: __________________________________________________ Checklist # : ___________________________________________
Name of Owner/Establishment: ______________________________________ Location of Const.: _____________________________________
_______________________________________________________________ ______________________________________________________
Project Title: _____________________________________________________ Date Received: _______________ Date Released: ___________
_______________________________________________________________ No. of Storey/s: ________________________________________
Occupancy Classification: __________________________________________ Total Floor Area: ______________ Lot Area: _________________

NOTE: CHECKED ITEMS ARE THE REQUIREMENTS NOT FOUND IN THE SUBMITTED BUILDING PLANS AND SHALL BE COMPLIED OR CORRECTED
BEFORE THE ISSUANCE OF FIRE SAFETY EVALUATION CLEARANCE (FSEC).
Vertical distance between stairway landings are limited to 3.69
MEANS EGRESS 29
m (12 ft) in assembly occupancies, distance is 2.43 m (8 ft)
1 Building exits must about a public street or approved alley. Handrails should be placed not less than 81.28 cm (32 in) above
30 the tread. Two (2) handrails are required when stairways exceed
2 Provide at least two(2) means of egress for each floor, room.
111.7 cm in width.
Provide secondary stairs/exits as far/remote from main stair, to
3 Guardrails for stairs, balconies, stair landings, ramps and aisles
serve _________________________________________.
31 located along the edge of open side floors and mezzanines shall
Enclose all stairways and fire escapes with walls having ______
4 be provided.
hours of fire resistance with access thru self-closing fire doors.
There shall be no enclosed usable space under the stairs in an
5 Provide two (2) doors as exit ways from all rooms. 32 exit enclosure nor shall the open space under such stairs be
used for any purpose.
Non-combustible outside stairs are required to have 2.03 m (6 ft
Interconnect stairs and fire escapes with fire resistive
6 33 8 in) minimum headroom clearance for stairways which should
passageways on corridors at least __________ meters wide.
be indicated on plans.
7 Enclose walls, doors as exit ways from all rooms. 34 Ramp slopes should have be roughened or with nonslip surface.
Provide protected/enclosed horizontal exits with self-closing fire
8 35 Ramp slopes should not exceed 30.3 cm (1 ft) in 3.03 m (10 ft.)
doors.
Travel distance to an exit shall not be more than No openings other than the required exits are permitted and exit
9
_______________ meters. passageways should be one (1) hr fire resistive construction for
36 a three (3) storey building or less and two (2) hrs for four(4)
10 Exit doors shall swing in the direction of exit travel. storey building or more. Any opening therein shall be protected
with an approved self-closing fire doors.
Revolving doors shall not be used as means of egress except
11 37 Exit illumination and directional EXIT signs shall be provided.
___________.
Exit door/s should be opensable from the inside without the use
Panic hardware is required on exit doors. In lieu of this, doors
12 of keys, special knowledge or effort flush bolts or surface bolts 38
shall have no locks or latches.
are prohibited.
Exit door should have a minimum width of 71 cm and a
13 COMPARTMENTATION
maximum width 122 cm and shall not restrict the opening.
14 A floor or landing is required not less than the width of exit door. 39 Provide fire break up to the roof for ceiling areas.
Provide monitored and curtained roof of sheetmetal or non-
Door should be not project into the required corridor width when
combustible material of a minimum of 1.82m (6 ft) high spaced
15 fully opened so as not to reduced the corridor width to less than 40
not more than 76 m (250 ft) & curtained area limited to a
76.17 cm.
minimum of 4,630m2 (50,000 ft2)
Exit doors should provide immediate access to an approved Provide smoke partition at enclosed areas of 2,083 m2 (22,500
16 means of egress. Existing through a bathroom, bedroom or other 41 ft2) or less with the length of 45.7 (150 ft) or less, with self-
room subject to locking does not comply. closing fire doors.
Provide smoke partition of two (2) hours fire resistance from
17 Corridors should have a minimum width of _________ meters. 42
floor to underside of floor above.
Provide interior finish as follows: Exit; Class ________________
Required corridors in ___________ occupancies shall have 2.43
18 43 Access to Exit; Class ____________________
meters (8 ft) minimum width.
Other Spaces; Class ____________________
19 Dead-end corridors and exit balconies is limited to 6.08m (20ft) 44 Provide fire stopping for all concealed spaces.
Aisles in auditorium shall be minimum of ______ meters in
20 WALLS
width.
Walls and ceiling of corridors should be fire resistive Provide standard fire wall with at least 100 cm (39.38 in) high
21 45
construction. parapets on all portion of the building on the property line.
Interior openings into corridors should be fire resistive
22 46 Extend exterior masonry walls to form parapets or wings.
construction materials.
Provide protection of all exterior walls. All exterior walls facing
Main stairways should have a minimum width of 112 cm (44 in)
23 47 approved alleys which are dead-ended must have a fire
in the direction of travel.
resistance of _______ hours.
Landings on stairways should have a minimum dimension of 112
24 48 Provide automatic fire dampers on wall openings.
cm (44 in) in the direction of travel.
Risers on a stairways should not exceed 19 cm and tread
25 WARNING SYSTEMS
exclusive of nosing or projections should not be less than 25 cm.
Doors between guest rooms and corridors shall be self-closing
Provide approved emergency alarm bell system on each floor
26 and shall have a fire protection rating at least twenty (20) 49
with adequate number of sending stations.
minutes.
Openings in corridor partitions other than door openings shall be Provide approved type heat and smoke detection system.
27 50
prohibited.
28 Basement potion of stairways should be provided with an 51 Provide efficient communication system for warning occupants
approved barrier where continuous to upper floor in an exit and calling fire department.
enclosure.
FIRE PROTECTION Provide /post allowable occupant load sign/s. Such signs shall
69
be conspicuous and suitable located.
70 Provide fire protection/suppression during construction.
Provide approved type portable fire extinguisher (dry chemical)
Provide fire exit plan for each floor of the building showing the
52 ABC type, __________ lbs. Capacity for every 278m2 (3000ft2)
71 routes from exit room to appropriate exits, displayed prominently
of floor area or 22.8m (75 ft) travel distance on every floor level.
on the door of each room.
53 Provide dry and wet standpipe system with ______ mm ɸ riser
No heating or lighting apparatus or equipment capable of
and coupling of fire department standards with pumps of reliable
igniting flammable materials shall be used in any storage or
pressure & connected to an adequate water supply tank. Hose 72
work area where rags, excelsior and other highly flammable or
and hose cabinet shall be provided at every hose gate valve on
combustible materials are stored or used.
all floors.
54 Provide/post “NO SMOKING” sign/s where combustible
Provide Fire Service connection with a standard outlet of 64mmɸ
73 materials are stored and handled. Such signs shall be
and 102mm ɸ dry standpipe, and shall located on a street front
conspicuously and suitable located.
55 Provide automatic fire extinguishing system where kitchen If high hazard commodities will be stored/handled, automatic fire
74
equipment is located (Kitchenhood) suppress systems shall be provided.
56 Provide automatic chemical extinguishing system on all areas Provide/post “DO NOT USE ELEVATOR IN CASE OF FIRE”
75
where electronic/electrical equipments are located. sign/s.
57 Provide approved-type automatic fire extinguishing system in LPG tank/s must be installed outside the building and should be
accordance with NFPA13. Approval of system plan is required 76 provided with safety devices that automatically stop the flow of
prior to installation. gas should a leak develop.
MISCELLANEOUS 77 Provide fire resistive walls between stair and kitchen area.
58 Provide outside window opening on bedrooms with a clear
opening of not less than fifty six (56) cm in least dimension and Provide outside window/s for rescue and ventilation with a
forty five-hundredths (0.45)m2 in area. The bottom of the minimum clear opening of 55 cm and approximately one half
window shall be not more than one hundred twenty two (122) cm (0.5)m2 in area; the bottom of window opening is not more than
above the floor. eighty two (82)cm above the floor; It can readily opened from the
78
59 All liquefied petroleum gas equipment including such equipment inside without the use of tools, where storm windows, screens,
installed at utility gas plants shall be installed in accordance with antiburglar devices are used, these can be provided with quick
the provisions of NFPA 59. mechanism so that they may be so arranged that when opened
60 No grills or any obstruction shall be installed on window they will not drop to the ground.
openings and /or fire exits.
61 Provide emergency lighting facilities with automatic transfer Rooms used for kindergarten, first or second grade pupils shall
switch to AC/DC power source. not be located above or below the floor of exit discharge. Rooms
79
62 Air conditioning ducts must be provided with approved fire used for second grade pupils shall not be located more than one
dampers. (1) storey above the floor of exit discharge.
63 Roof covering must be of non-combustible materials.
80 Provide firefighters’ elevators
Combustible roof covering must have fire retardant treatment.
64 All correction indicated on the original approved plan from this
Provide fire escape ladder/s. 81
office _____________________ shall be followed.
65 Any changes in occupancy other than stated shall be in
Provide fire escape stair/s. 82
accordance with Rule 10.
66 All units partition wall shall be extended up to upper floor slab
83 Subject to inspection during construction.
and/or one (1)meter above the roofline.
67 Provide effective means of smoke ventilation such as access Fire Safety Inspection Certificate must be secured before/prior to
84
panels, movable windows. issuance of Certificate of Occupancy.
68 Subject to additional requirements upon recommendation of the
Project activity shall not affect the affectivity of the existing fire
85 Fire Safety Inspector during construction phase and final
protection facilities.
inspection.

Amount of Fire Code Fee to be Paid: Php _______________________________ Total Construction Cost: Php : _____________________________
Official Receipt No: _________________________________________________
Date Paid: ________________________________________________________

ADDITIONAL REQUIREMENTS/RECOMMENDATIONS:
__________________________________________________________________________________________________________________________
__________________________________________________________________________________________________________________________
__________________________________________________________________________________________________________________________
__________________________________________________________________________________________________________________________
__________________________________________________________________________________________________________________________
__________________________________________________________________________________________________________________________
__________________________________________________________________________________________________________________________
__________________________________________________________________________________________________________________________
These sheets are part of the plans and shall remain attached hereto. Corrections indicated above must be complied.

____________________________________________
Signature of Owner/Applicant/Representative

Reviewed By: Recommending Approval:


____________________________________ ____________________________________
Plan Evaluator Chief, Fire Safety Enforcement Section

Approved By:
_________________________________
Municipal Fire Marshall