ACONIS Power Management System Energy Edition Parameter List
ACONIS PMS
Energy Edition
Parameter List
‘ACONIS PMS Energy Edition
Shipyard : HMDACONIS Power Management System Energy Edition.
1 ACONIS PMS Energy Edition Parameters
Parameter List
Category | P.No Description unit | pai | pez | pes Remarks
Poot | Bus Bar Nominal Voltage v 430
Bus Bar sting
002 | Bus Bar Nominal Frequency He. 0
Genersor | PO3_| GIE Nominal Power kw | 1030 | 1030 | 1050
seting oot | GWE Nominal Current A | tose | 684 | 10st
stat Conot | _P005_ | Start Command Pulse Wid see 25
setting 006 | Control Try (Attempts) Num 1 Fixed | Item
007 | Max Unloading Time see o
Stop Coat | POO | CB Open at Load % 10
setting 009 _| Idle Running Time sec 180)
POIO | Stop Command Pulse Width see 10
020 | synchronize Time see 6
port | Delta Frequency He 02
po22_ | Detta Voltage v 23
Po23_ | CB Make Time see 40
o2t | Min Pulse Time soe 500
|
Syoctvonize | PU2S_| Synchronize ACB Close Degree Offiet_| Deg °
Conwolseting | po26 | Synchronize ACB Close Dead Band Deg 8
027 | Synchonizing Kp Gain Num 50
028. | synchonizing Ki Gain Nur 80
029 | Synchonizing Pa Gain Num 03
030 | Synchonizing Control Interval ms 0 10ms unit
O31 _| Synchonizing Sart PID Delay as o
‘ACONIS PMS Energy Edition 22
Shipyard : KMD
Hull No: H2708-12
class: ABS
Rev. No: RO|CONIS Power Management System Energy Edition
Parameter
Category | P-No Description unit | par | paz | ves | Remarts
Poi | Frequency Dead Band Me 02
Pot | Frequeney Pop Band He 2
Pot | Acive Load Dead Rand Kw 1s
AwoGovemor |” poss | active Load Pop Band so
oad | Cycle Time see 3
o4s. | Min Pate Time ee as
oss | Max Pulse Time sxe 1s
080 | Lood High Limittp 1 % %
POs1_ | Load High Delay sep 1 = 5
0s2__| Curent igh Lit sep 1 % 190
oss. | Curent High Delay step 1 5 Not used
ust | Load High Limit sep? % 95
Heavy Load [P05 | Load igh Delay sep? we 0
demand Ata
Staring | PUS6 | Curent High Limit ep 2 195
0s? | Curent High Delay ep? 5 Nocused
ose | Load High Limit sep % 100
1089 | Lood High Delay sep 3 see 3
060 | Curent High Lint sep 3 200
ost | Curent High Delay step3 se 4 Nosed
LigntLoad | P70 | Maxallowed Loader Low Load Sop | 9% 10
demand Ato -
Stopping [O71 | Low Load sop dey 180
puto | Lost High Limit group % 100
ost | Load igh Delay group 1 x 5
Load Demand | PO82 | Current High Limit group | % 100 Pr)
Prefretal Tip (Delay ine -4
Group 1” | Poss | CuretHigh Delay group 1 we 5 Noes)
ost | Frequeney Law Limit group He sas
oss | Frequency Low Delay group 1 5 5
[ACONIS PMS Energy Baton 372
Shipyard: HMD
Hull No :112705~12
Clas: ABS
Rev.No- ROICONIS Power Management System Energy Edition Parameter List
Category | P.No Description Unk [ G1 | pc2 | DGS | Remarks
86 | Loa igh init roup? % 100
os7_| Load igh Dey soup 2 0
oss_| Corer High Linit group 2 % 109 ra
(Det tine
oy Curent igh Delay roy? 5 0 oN)
090 | Freueney Low Limi group? He sas
root | Freuengy Low Delay group? “ 10
o92__| Load High Limi group 3 % 100
9 _| Load tigh Demy group 3 =
5 m3
Load Demand [P09 | Curent ih Limit group 3 % 100
Pree Tip (Det tne:
Groups| 095 | Caren High Delay group 3 = Nos
106 | Frequency Low Limit pop 3 He 585
1007 | regen Low Delay greup3 =
100 [ Low Voge Limi vf as
Beret Trio | ow Voge Del 5
Besar ®
atest | pia | High Voge Lin v ams
103_| High Votage Deny = 5
lot [ Low Freqcny Lin Ma 7
Light Fa
105 | Low Freueney Delay = 5
Bosbar
atsconal |p105_[ High Freon Lint He 8
107 | igh reaueny Delay ss 5
[NOONIS PMS Energy Eaton wi
Ship: HMD
Ph HMOS2
Chas ABS
Rev No-ROACONIS Power Management System Energy Edition Parameter List
Category | P.No Description unit | per | poz | pcs Remarks
P11 | Low Low Voltage Limit v 31s
70%
P11 _| LowLow Voltage Delay see 1
PUI. | High High Vottage Limit v 5855
130%
PLS | High High Voltage Delay see 5
P14 | Low Low Frequency Limit He 3
90%
DG Protection | PIIS | Low Low Frequency Delay x 3
setting
(cB Trp) | P16 | High High Frequency Limit He 66
110%
PII? | High High Frequeney Delay 3
P120_ | Curent High Limit % 150
P12 | Curent High Delay see 4 Not used
122 | Reverse Power Limit % 10
P123_ | Reverse Power Delay see 3
2 System / Hardware Configuration
Category No Description unit | per | pez | pes Remarks |
P130_ | GE Running Voltage Build up Dead Band | V 30
ttadware | PI31_ | GE Stable Running Delay Time see 3
sting | 140. | GE Stop by user Laad Shit % 85
PI4I_ | Short Parallel Running(GE Abnormal) | see 20 Fixed
P160 | GE Running Voluge> Nominal Voltage | 9% 70
PI61_ | GE Stopped Voltaze
Conon
Parater#3 | Off Delay Time ee)
Parameter #1 | Toa Available Power kW] Limi
Parameter #2
Parameter #3
[ omretay Time (see)
‘ACONIS PMS Energy Edition
Shipyard: HMO
Hull No H2705-12
Clas ABS
Rev.No:RO
10712|CONIS Power Management System Energy Edition
Parameter List
esrgtion | Function Code Famsan vile Remark
Porat #1 | Toul Used Power Lin
Foal Used
Tower) | code=23 | Parner?
Cann
Parameters [ OFF Del Tine Gee)
Parameter #1 | Total Used Power [kW] Linit
Total Used +
rower (a) | Code=24 [Paamacrt2
Condon
Parameter #3 | Off Delay Time (sec)
Single DG Parameter #1_ | Single DG Available Power [%] Limit
‘uate | Gygee > Tonia
Aube | caden2s | Panmeer [o--<1
Condition Parameter #3. | Off Delay Time (sec)
Simic oe Parameter Sipe DG Avalbe Powe) Limit
‘rate
Ame Paraner #2
Condition Parameter #3. | Off Delay Time (sec)
ParmeerA | Sip DG Used Power Pt Limi
singe DG
Usitoree | cotes27 [ranean [ome
[2%] Condition
Paamaer#3 [Off ele Tine ox)
ParancterAt| Single DG Used Power IW] Limit
SinleDG
Ustomer | cade=28 | Parnaiet? [O= == 1=
(Wi) Conon
Paranter#s [OF ety Tine ee)
vine e2 ParanserAt| Muli 182 6 Used Power Bl Lit
Dent mo
Dovet Parameter? [O° 1
Condition Parameter #3. | Off Delay Time (sec)
stp ed ParanterA| Mule 12 DO Used Power V7) Limit
Deve |g
peetist | cadens | romeerta [0
Condition Parameter #3. | OffDelay Time (see)
ont Paramacr#t | Aso od String Power Lit
Soaring Fale | cag Paramaer?2| Auto Lod Sharing Cec Tine (Sex Limit
Condition Parameter #3 | Off Delay Time (sec)
ACONIS PMS Energy Edition
Shipyard: HMO
Hull No 2705-12
Class ABS
Rev.No:RO
nzACONIS Power Management System Energy Edition Parameter List
5 AXITable
Function Code Description Parameter Value Remark
Code=00 | Aux DI Function Disable
Code=01 | Power Request Input of Heavy Consumer Block
Code=02 | Light Load Auto-Stop Blocking
Co
Power Request Input and Auto Light Load Cancel
Unbalanced Load Sharing Control Input
Cod
08 | Generator Abnormal Input
Code 06 | AXI Special Pulse Input
Cote 1o | Bigmotorsun (Signal Type- Cominwous) and ‘Use as (AXO code 07)
‘Auto Light Load Cancel
‘ACONIS PMS Energy Edition 1/2
Shipyard : KMD
Hull No “H2705-12
Class: ABS
Rev.No:RO