You are on page 1of 7

Performance of a Pressure Pneumatic Grain Conveying System

Kevin D . Baker, Richard L. Stroshine, George H. Foster, Kevin J. Magee


ASSOC. MEMBER ASSOC. MEMBER FELLOW ASSOC. MEMBER
ASAE ASAE ASAE ASAE

ABSTRACT Chatley's conclusion, stating that vertical conveying


required more power than horizontal conveying, based
OWER, pressure, and grain velocity of a pressure
P pneumatic grain conveying system were evaluated
using dry shelled corn. Two system configurations (10 cm
upon observations of practical, working systems, and
concluding that experience was of greater value than
theory when designing pneumatic systems. In Segler's
or 4 in diameter conveying pipe) were tested at grain flow
(1951) design procedure for pressure-type pneumatic
rates of 3 to 20 t/h (100 to 800 bu/h) and at conveying air
systems, an optimal conveying air velocity was selected
velocities of 15 to 30 m/s (3000 to 6000 fpm). Energy
and the associated pressure drop determined. Gluck
usage per tonne decreased as grain flow increased and
(1968) presented tables of recommended motor sizes and
increased as air velocity increased. All system pressure
pipe sizes for pressure and suction pneumatic systems
components increased proportionally as grain flow
based upon manufacturers' experiences. Stoess (1983)
increased. Total system pressure was minimized with an
described design procedures for vacuum and pressure
air velocity of 20 m/s (4000 fpm). Pressure drop to
pneumatic systems based upon design factors which are
initially accelerate corn was the same for both piping
dependent upon type of material and distance conveyed.
configurations and increased as air velocity increased.
Pressure drop in the vertical pipe section decreased as air Knowledge of power and pressure requirements and
velocity increased. Median grain velocity decreased as product velocities for pneumatic conveying is important
grain flow increased. Reported values for terminal grain to designers. Crane and Carleton (1957) developed and
velocity approximated the difference between air velocity verified an equation to predict pressure drop along
and grain velocity at locations where grain speeds were straight sections of pneumatic conveying pipe at any
highest. At air velocities of 20 m/s (4000 fpm) or less, angle of inclination when steady-state conditions
kernel velocity and corresponding potential for kernel prevailed. Cornish and Charity (1966) presented a
impact damage were low. procedure to determine pressure drop attributed to a
horizontal elbow in a pneumatic system. Wolfe et al.
(1970) developed an equation for predicting pressure
INTRODUCTION
drop in horizontal conveying pipes with accelerating or
Pneumatic conveying systems are being used more steady-state flow. In these studies, static pressure was
frequently in the United States for handling grain, limited to a maximum 5.0 kPa (20 in. H 2 0), and airflow
especially for moving grain from continuous flow and was assumed to be incompressible. The authors*warned
batch type farm dryers to bins. A number of grain that these equations may not apply to systems which
handling companies have added pneumatic systems to operate at higher pressures. Currently, positive
their product lines. Design of pneumatic conveying displacement air pumps are used for pressure pneumatic
systems has generally been regarded as an art, with little conveying of grains, allowing higher air pressures to be
scientific basis, although several design procedures have used. Zenz (1949) reported pressure drops for vertical
been proposed. Based upon theoretical analysis, Cramp and horizontal suction conveying of rapeseed, sand, glass
and Priestly (1924) presented a design procedure for beads, and salt with higher pressure and at varied
vertical suction conveying of grains which they then material flow rates and air velocities. Segler (1951)
verified experimentally. Chatley (1940) presented a reported minimum air velocities and resistance to flow at
procedure for calculating the power requirement for varied grain flow rates and pipe diameters for pressure
vertical and horizontal suction conveying. He concluded conveying of small grains. Susai and Gustafson (1982)
that horizontal conveying required more power per unit reported power requirements, quality change, and kernel
length than vertical conveying, based on the assumption velocities for corn and soybeans in a combination
that the air velocity be sufficiently high to suspend the suction-pressure system. Power required to accelerate
kernels as they were conveyed. Jennings (1940) disputed grain was a significant portion of the total power
requirement and depended upon change in grain kernel
velocity. Foster (1973) and others have reported that
impact damage to corn primarily depends upon its
Article was submitted for publication in May, 1985; reviewed and
approved for publication by the Electric Power and Processing Div. of
velocity.
ASAE in September, 1985. Presented as ASAE Paper No. 84-3515. Magee et al. (1983) reported on damage associated
Journal Paper No. 10254 of the Purdue Agricultural Experiment with pneumatic conveying using the same system as in
Station, W. Lafayette, IN. this study. They found that with conveying air velocities
The authors are: KEVIN BAKER, Graduate Assistant, Agricultural
Engineering Dept, University of Illinois, Urbana, IL, RICHARD
of 20 m/s (4000 fpm) or less, grain damage and dust
STROSHINE, Assistant Professor, GEORGE FOSTER, Professor, generation were similar to levels reported for bucket
Emeritus, and KEVIN MAGEE, (Former Graduate Student), elevators and drag conveyors. Grain damage increased
Agricultural Enginering Dept., Purdue University, W. Lafayette, IN. exponentially as air velocity increased above 20 m/s

72 © 1985 American Society of Agricultural Engineers 0883-8542/85/0102-0072S02.00 APPLIED ENGINEERING in AGRICULTURE


2-elbow system, (Fig. 1, dashed lines) had total
horizontal and vertical conveying distances of 27 m (88.7
ft) and 4.4 m (14.3 ft) respectively, with two elbows
included.
Sublots of 900 kg (2000 lb) of corn (approximately
13% moisture content, dried using 70°C (160°F) air),
were taken from a storage bin, cleaned by a No. 4 mesh
rotating screen cleaner, and conveyed into a holding bin
above the airlock feeder. Test sublots required from 5 to
10 min to be pneumatically conveyed through the system
to a second holding bin. Each sublot of corn was tested
once.
Air flow rate and grain flow rate were control
variables. Air flow rate was adjusted by differing the
sheave ratio for the V-belt drive connecting the air pump
to its motor. Finer variations were achieved by adjusting
a bypass valve which allowed compressed air to
recirculate from the blower outlet to the blower inlet.
Volumetric air flow rate was measured using the pressure
drop through a 10.2 cm (4 in.) long-radius nozzle located
at the system's air inlet. Dry and wet bulb temperatures
Fig. 1—The pneumatic conveying system, showing the 4-elbow were measured with an aspirated psychrometer and
conveying pipe route (solid lines) and 2-elbow conveying pipe route atmospheric pressure was measured with a mercury
(dashed lines). Sections of plexiglass pipe for the photography are
shaded. (Components are drawn to scale). barometer in order to determine air density. Compressed
air vented from the air lock feeder was also recirculated
back to the blower inlet so that the air flow rate at the
(4000 fpm). Feed rate had little effect upon damage. system inlet would be nearly the same as that at the
Brittle corn had more damage than non-brittle corn. system discharge. Air flow rate was varied to provide
In order to provide information for manufacturers to pipe entrance air velocities from 15 to 30 m/s (3000 to
improve designs and for operators to reduce energy 6000 ft/min).
consumption and operating cost, a pressure pneumatic Grain flow rate was controlled by adjusting the
system handling shelled corn in 10 cm (4 in.) diameter opening in a slide gate between the holding bin and the
conveying pipe was tested. Specific objectives were to: airlock feeder. For each test the grain flow was checked
1. Measure power consumption for a range of grain by weighing the test lot on a platform scale and dividing
flow rates and air velocities and determine operating by the conveying time. The feed rate was varied from 2.5
conditions which give optimum power consumption, to 20 t/h (100 to 800 bu/h).
2. Measure pressure drops for the total system, the The ratio of airflow to grain flow is a factor used in the
acceleration section, vertical section, a horizontal turn, design of pneumatic conveying systems. It can be
and the air filter and silencers and establish the effect of expressed as mass flow of conveyed material to mass flow
varying grain flow rate and air velocity on these pressure of air (solids to gas ratio) or as volumetric air flow to
drops, mass flow of material (saturation ratio). In our tests the
3. Measure kernel velocities and compare with solids to gas ratio ranged from 4 to 32 kg/kg and the
calculated air velocities, over a range of grain flow rates saturation ratio ranged from 27 to 215 liter/kg (.43 to
and air velocities. 3.45 ftVlb). Systems with solid to gas ratios ranging from
0.1 to 5 can be termed dilute phase, while those with
TEST PROCEDURE ratios ranging from 25 to 900 can be termed dense phase
(Wen and O'Brien, 1976). Our system operated in the
The pneumatic system (Fig. 1) was powered by a transitional stage between dilute phase and dense phase
positive displacement, lobe type air pump (4506) driven flow.
by a 15 kW (20 hp) 3-phase electric motor. Air flow rate Two replications of each test (Table 1) were run.
was measured as it entered the system through a nozzle Power drawn by the motor on the air pump was
chamber. A paper cartridge filter removed dust particles measured using a solid-state electrical power transducer.
from the air. Chamber type silencers before and after the A digital phototachometer measured the air pump
air pump reduced noise. Grain was fed into the system by
a rotary air lock feeder placed downstream from the air TABLE 1. SUMMARY OF TESTS CONDUCTED
pump, so that the grain was conveyed by pressurized air
only. The conveying pipe was nominal 10 cm (4 in.) Uncompressed air velocity
diameter galvanized steel tubing. Inside diameter was Grain flow rate 15 20 25 30 (m/s)
9.75 cm (3.84 in.). Grain was decelerated and discharged (t/h) (bu/h) 3000 4000 5000 6000 (fpm)
from the system through a 51 cm (20 in) diameter cyclone 2.5 100 2,4
into a bin with maximum 3 m (10 ft) drop height. 5 200 2,4
Two systems of different lengths were studied. In one, 7.5 300 2
10 400 4 2,4 4 4
the 4-elbow system, (Fig. 1, solid lines) the total 15 600 2,4
horizontal and vertical conveying distances were 45.6 m 20 800 4
(150 ft) and 4.4 m (14.3 ft) respectively, with 4 elbows 2: indicates test conducted on 2-elbow system
included. Elbows had a sweep radius of 1.2 m (4 ft). The 4: indicates test conducted on 4-elbow system

Vol. l(2):November, 1985 73


speed. Air pressures were measured using solid state
pressure transducers located as shown in Fig. 1. Each
transducer measured the pressure in a manifold
connecting two small holes on opposite sides of the
conveying pipe. The transducer immediately before the
airlock feeder measured total system pressure. Voltage
outputs of the pressure transducers and the power
transducer were monitored with a data logger which
sequentially scanned them every 15 s with about 0.5 s ELECTRICAL
ENERGY
between each reading. Pressure transducers were
individually calibrated before installation by connecting PNEUMATIC
ENERGY
o
them in parallel with a U-tube manometer filled with
10 (tonne/h) 15
mercury and applying a range of constant pressures to 400 (bu/h)
the pair of instruments. Calibration curves for the Grain flow rate
15 20 25
transducers converted voltage to pressure. Solids to gas ratio (kg/kg)
Grain kernel velocities were measured with high-speed
Fig. 2—Electrical consumption rate and pneumatic energy for
photography. Sections of clear plexi-glass pipe, of the conveying dry shelled corn with an uncompressed air velocity of 20 m/s
same diameter as the conveying pipe, were installed in (4000 fpm).
the system at five locations (Fig. 1): after 10 m (33 ft) of
horizontal flow, midway up the vertical pipe, after the
last elbow (in the 4-elbow system only) and and removing two turns lowered resistance to flow from
approximately 2 m (6 ft) before the cyclone collector. wall friction. The same acceleration zone and vertical
Kernel velocities were calculated using the camera conveying section were used in the two systems. This
framing rate (determined by counting frames between suggests that energy requirements for accelerating and
timing light cycles) and the number of frames required elevating the grain are greater than energy to convey the
for selected kernels to travel TO cm. grain horizontally or around an elbow.
The 4-elbow system operated most efficiently with
TEST RESULTS uncompressed air velocities near 20 m/s (4000 fpm, Fig.
Energy Requirements 3). Lower and higher air velocities increased electrical
Electrical consumption per unit weight of material consumption per unit weight. The maximum increase
conveyed was calculated by dividing measured electrical was 33% with 30 m/s (6000 fpm) air velocity.
power drawn by the air pump motor (kW) by the grain When operating the pneumatic system with an air
flow rate. Pneumatic energy* per unit weight was velocity of 20 m/s (4000 fpm) and grain flow rates from
calculated from the product of air flow rate and total 10 to 20 t/h (400 to 800 bu/h), pneumatic energy was 10
pressure divided by grain flow rate. Pneumatic energy to 20% greater than the shaft energy needed to achieve
indicated relative system performance more accurately, the same capacity in a 15 cm (6 in.) auger system with
since differing proportions of recirculated air among the equal horizontal and vertical conveying distances. Data
tests, as well as motor efficiency variation with loading, for 14% m.c. shelled corn (White et al., 1962) were used
would affect the electrical consumption, but not the air to estimate full capacity power requirements for augers.
power. Changing the grain flow rate had a much greater However, pneumatic systems use an air pump to convert
effect on electrical power consumption than changing the shaft energy to pneumatic energy, which typically is 55 to
uncompressed air velocityt (Figs. 2 and 3). Pneumatic 70% efficient. Considering an air pump efficiency of
energy was nearly constant for grain flow rates above 5 70%, the 10% greater pneumatic energy, and the same
t/h (200 bu/h, Fig. 2) but increased as air flow increased motor efficiency for both systems, the electricity needed
(Fig. 3). to operate a pneumatic system would be 1.6 times the
Electrical consumption and pneumatic energy per unit amount needed for a comparable auger system. Filters
weight decreased as grain flow rate increased with a
constant uncompressed air velocity (Fig. 2). Thus the
system operated more efficiently at higher grain flow -
rates. Increasing the grain flow rate from 3 to 15 t/h (100
to 600 bu/h) approximately doubled the efficiency.
Pneumatic energy decreased only slightly. Therefore, the .ELECTRICAL"
^-"^ENERGY
higher electrical consumption was primarily the result of -
recirculating more air and motor efficiency reduction
due to lower load. ,04J=

At all grain flow rates, the shorter (39% less distance)


2-elbow system had 20% lower electrical consumption PNEUMATIC
_ + ENERGY
and pneumatic energy per unit weight than the 4-elbow
system (Fig. 2). Apparently, reducing conveying distance - ~+
15 20 (m/s) 25 30
4 0 0 0 (fpm) 5000
Uncompressed air velocity
*Pneumatic energy refers to the sum of the kinetic and potential
12
energy transmitted to the conveying air by the air pump. i ratio (kg/kg)
tUncompressed air velocity refers to the average air speed in an
empty pipe at ambient pressure and temperature, or the inlet air Fig. 3—Electrical consumption rate and pneumatic energy for
velocity. The actual conveying air velocity will vary with temperature, conveying dry shelled corn at a grain flow rate of 10 t/h (400 bu/h) in
pressure and the amount of grain in the conveying pipe. the 4-elbow system.

74 APPLIED ENGINEERING in AGRICULTURE


velocity increased (Figs. 4 and 5), and was approximately
Total
(4-Elbow) the same for both systems at the same grain flow rate.
Therefore, the component needed to accelerate the grain
was almost constant for the same grain flow rate and
conveying air velocity.
> Total
Pressure drop for the vertical section of the 4-elbow
(2-Elbow)
system (including two elbows) increased as grain flow
increased and decreased as air velocity increased (Figs. 4
and 5). Neglecting resistance to flow, the theoretical
^, + Vertical
pressure drop required to lift the grain (Segler, 1951)
f _ _ A Acceleration decreased as air velocity increased as calculated by
equation [1].
-""-"*""" 5 10 (tonne/h)
4 0 0 (bu/h)
Grain flow rate
APV = Ah x rh /(367 x v a x Ap) (SI Units) [la]
Solids to gas ratio (kg/kg)

Fig. 4—Pressure needed to convey dry shelled corn at an uncompressed


air velocity of 20 m/s (4000 fpm). APV = Ah x rh g /(154 x v a x Ap) (English Units)

and silencers on pneumatic systems plus recirculation of [lb]


a portion of the compressed air increased the difference
in electrical demand in our tests. where: APV = pressure drop to lift grain (kPa or psi)
Ah = height grain is lifted (m or ft)
Pressure Requirements rhg = grain mass flow rate (t/h or bu/h)
Pressure required to convey grain increased as grain va = conveying air velocity (m/s or fpm)
flow increased with constant uncompressed air velocity Ap = pipe cross-sectional area (m2 or ft2)
(Fig. 4). The pressure increase appeared to be Calculated theoretical values were about one-tenth the
proportional to grain flow for both systems. Thus value of our measurements, indicating energy loss due to
doubling of grain flow rate would double the required friction was highly significant. Trends observed for
pressure. Total pressure in the 2-elbow system was about pressure drop are similar to those reported by Crane and
25% less than that in the 4-elbow system, while Carleton (1957) for conveying with essentially
conveying distance was reduced 39%. This indicates that uncompressed air.
the pressure needed to accelerate and lift the grain was Pressure drop across a horizontal elbow (sweep radius
greater than the pressure to convey grain horizontally or to diameter ratio of 12.5) was small. The maximum drop
to move it around elbows. Pressure data are consistent was 1.0 kPa (0.15 psi) for the 20 t/h (800 bu/h) feedrate.
with measured energy requirements. At lower grain flows, pressure drop was less and
Required pressure in the 4-elbow system was sometimes appeared to increase. If pressure drop across
minimized with an uncompressed air velocity of 20 m/s elbows is to be measured, sensitivity of the measurement
(4000 fpm, Fig. 5). At 15 m/s (3000 fpm) the pressure must be improved. For example, the error caused by
was higher than at other velocities in the 4-elbow system. using different pressure transducers before and after the
Apparently the conveying pipe filled with grain, causing elbow could be eliminated by using a single differential
the portion of cross sectional area available for air flow to transducer. Actual pressure drop caused by the elbow
decrease and the pressure to increase. would be measured using a technique such as that used
Pressure drop across the 8.7 m (28.9 ft) horizontal by Cornish and Charity (1966).
acceleration zone was calculated using the difference in Pressure drop across combinations of filter and
pressure readings at the two ends of this pipe section. silencer, and silencer and bypass tee increased as
Pressure increased as grain flow rate and conveying air conveying air velocity increased (Table 2). Pressure drop
across a silencer and bypass tee was relatively low. Thus,
by adding the silencers to the system, overall
- performance was not significantly affected. Pressure
- drop across the air filter and first silencer was much
greater, indicating the air filter could have a significant
- - effect upon performance.

^________—V Total
-
- TABLE 2. PRESSURE DROP ACROSS AIR FILTER,
SILENCERS AND BYPASS TEE.
Pressure drop
Vertical (4.4 m)
-
for air filter for second silencer
" Acceleration (8.7 m)
Uncompressed and first silencer and bypass tee
15 (m/s) 25 air velocity
, 2 l° 3

4 0 0 0 (fpm) 5000
(m/s) (fpm) (kPa) (psi) (kPa) (psi)
Uncompressed air velocity
15 12 15.9 3130 1.9 0.28 0.2 0.03
Solids to gas ratio (kg/kg)
20.9 4110 2.1 0.31 0.5 0.07
25.9 5100 3.0 0.44 1.0 0.15
Fig. 5—Pressure needed to convey dry shelled corn with a grain flow 30.7 6040 4.0 0.59 1.1 0.17
rate of 10 tonne/h (400 bu/h) in the 4-elbow system.

Vol. l(2):November, 1985


TABLE 3. PERFORMANCE CHARACTERISTICS OF THE PNEUMATIC
SYSTEM WHEN OPERATING WITH NO AIR RECIRCULATION
(MAXIMUM AIR VELOCITY).
.1 \
Grain Blower P o w sr to System M a x air
flow rate speed blower motor pressure velocity

(t/h) (bu/h) (rpm) (kW) (hp) (kPa) (psi) (m/s) (fpm)

2-elbow system
0. 0. 3171 5.9 7.9 5.2 0.75 28.4 5590
5.8 228 3161 7.5 10.1 11.2 1.62 27.4 5390
10.0 394 3151 9.3 12.5 18.2 2.64 26.5 5220
15.3 602 3138 11.5 15.4 27.7 4.02 25.5 5020
22.5 886 3120 14.7 19.7 39.2 5.69 24.4 4800

4-elbow system
0. 0. 3168 6.5 8.7 7.2 1.04 27.9 5490
5.7 224 3155 8.8 11.8 17.5 2.54 26.6 5240
9.6 378 3140 11.1 14.9 26.5 3.84 25.6 5040
15.4 606 3113 14.8 19.8 41.0 5.95 24.0 4720
21.8 858 3057 20.6 27.6 60.7 8.80 21.9 4310 Fig. 6—Grain flow patterns in the 4-elbow pneumatic conveying
system.
A. At the end of the acceleration zone (dispersed flow).
The 4-elbow system operated best with a grain flow of B. In vertical section (dispersed flow).
C. After the last elbow (slug flow).
15 t/h (600 bu/h) and an uncompressed air velocity of 20
m/s (4000 fpm). Increased grain flows overloaded the
motor. Lowest pressure and energy requirements were conveying air velocity to increase unless some
with 20 m/s (4000 fpm) conveying air velocity. compensation were made. Higher conveying velocity
Recommended design factors (Stoess, 1983) for pressure could cause more damage to grain. Power, pressure, and
conveying of shelled corn over an equivalent distance are: maximum air velocity appeared to vary linearly with
saturation - 62 L/kg (1.0 ftVlb), power factor - 1.6 grain flow (Baker et al., 1984).
kWh/t (1.9 hp-h/ton), pressure factor - 5.0, and
compressed air velocity 16.8 m/s (55 ft/s). Calculated Grain Kernel Velocities
values for the 15 t/h, 20 m/s (600 bu/h, 4000 fpm) test At the first horizontal section of plexiglass tube (Fig.
were: saturation - 36 L/kg (0.6 ftVlb), power factor - 1.0 1) and at the vertical section, grain flow (shown by high-
kWh/t (1.2 hp-h/ton), pressure factor - 3.6, and speed photography) was relatively dispersed (Fig. 6)
compressed air velocity - 16.0 m/s (52.5 ft/s). similar to chopped forage (Brusewitz and Wolfe, 1967).
Recommended design factors were higher than necessary Kernels rotated and slid around each other, most of
which may have been due to incorporation of a factor of which flowed at an average speed reported as median
safety. Over design can result in higher kernel velocities grain speed. Approximately 1% of the kernels moved
and more physical damage to the corn. faster. Near the discharge, grain flowed as a collected
mass along the bottom of the pipe, with almost no
Maximum Velocity Relationships change in relative position or velocity (Fig. 6).
The data reported above were collected using With 20 and 30 m/s (4000 and 6000 fpm)
controlled conveying air velocity. In actual practice, uncompressed air velocities, as the grain flowed through
velocity would not be controlled unless a velocity the system, it accelerated to the first horizontal position,
compensator were installed. Components of a pneumatic slowed down as it was elevated, and then picked up speed
system are sized to provide a minimum design value for again before it reached the final horizontal position
air velocity in the conveying pipes (20 m/s or 4000 fpm (Table 5). With 15 m/s (3000 fpm) air velocity, grain
for dry shelled corn). If the same system is used for velocity at the second horizontal section was the same as
differing grain flow rates or conveying distances, the at the vertical section. Grain velocity was highest at the
components must be sized to meet maximum demand. first horizontal position.
Data in Table 3 were collected with the air bypass valve For horizontal flow, speeds in the 2-elbow system were
in the fully closed position providing the maximum faster than those in the 4-elbow system (Table 4). For
possible air flow at a given air pump speed. Blower speed vertical flow, speeds in the 2-elbow system were slower
was the lowest used in our tests. As grain flow or than those in the 4-elbow system. Speeds near the
conveying distance decreased, system pressure cyclone were over 25% faster for the 2-elbow system. The
decreased, causing the pump airflow output and the position of the elbows may have affected kernel velocity,

TABLE 4. GRAIN SPEEDS WITH A 2 0 m/s ( 4 0 0 0 f p m ) U N C O M P R E S S E D AIR V E L O C I T Y .

Photographing location
Horizontal Vertical Horizontal*
at feeder (after acceleration)
Grain Compressed
flow rate air velocity Median Maximum Median Maximum Median Maximum
System (t/h) (bu/h) (m/s) (fpm) (m/s) (fpm) (m/s) (fpm) (m/s) (fpm) (m/s) (fpm) (m/s) (fpm) (m/s) (fpm)

2-elbow 5 200 19.0 3740 7.6 1500 9.9 1950 2.8 550 7.1 1400 6.9 1360 9.3 1830
15 600 16.2 3190 5.3 1040 9.5 1870 2.4 470 8.6 1690 6.0 1180 9.5 1870

4-elbow 5 200 18.3 3600 7.1 1400 9.7 1910 3.4 670 7.1 1400 5.5 1080 9.9 1950
15 600 16.0 3150 4.5 890 8.1 1590 2.8 550 7.5 1480 3.6 710 9.1 1790

*This is n o t t h e same p o s i t i o n as is s h o w n in Table 5.

76 APPLIED ENGINEERING in AGRICULTURE


TABLE 5. MAXIMUM AND MEDIAN GRAIN SPEEDS WITH A 15 t/h (600 bu/h) GRAIN FLOW RATE IN THE 4-ELBOW SYSTEM.
Photographing location
Horizontal Horizontal
Compressed (After acceleration) Vertical (After final elbow)
Uncompressed air velocity
air velocity at feeder Median Maximum Median Maximum Median Maximum
(m/s) (fpm) (m/s) (fpm) (m/s) (fpm) (m/s) (fpm) (m/s) (fpm) (m/s) (fpm) (m/s) (fpm) (m/s) (fpm)
15 3000 12.7 2500 2.2 430 5.8 1140 1.9 370 6.0 1180 1.9 370 8.5 1670
20 4000 16.0 3150 4.5 890 8.1 1590 2.8 550 7.5 1480 4.5 890 18.5 3640
30 6000 23.4 4600 11.0 2170 14.5 2850 6.0 1180 8.5 1670 9.4 1850 18.5 3640

since grain typically decelerates when flowing around system which had less distance for grain acceleration
elbows and accelerates in straight pipe sections following than the 2-elbow system.
elbows. Thus, grain accelerated more in straight pipe Moreira et al. (1981) reported that impact damage to
preceeding the cyclone in the 2-elbow system (16 m or 52 corn was not significant at velocities below 10 m/s (32.8
ft of straight pipe) than in the 4-elbow system (8 m of 26 ft/s). Measured median velocities were less than this
ft of straight pipe). Kernel velocity increased as grain except with uncompressed air velocities of 30 m/s (6000
flow decreased with conveying air velocity held constant. fpm). Several maximum velocities were greater than 10
Median grain speeds (Table 5) were about 50% lower m/s (32.8 ft/s); however, since few kernels were traveling
than values for the suction side of a vacuum pressure at the maximum velocity, potential for damage would be
system (Susai and Gustafsion, 1982). Grain speed low. When kernel velocity measurements were taken, the
increased significantly as air velocity increased. Actual bypass valve was opened to control air velocity, similar to
air velocities were calculated using equations [2], [3] and a system operating with a velocity compensator. In
[4]. Temperature, humidity and pressure measurements systems where airflow is not controlled, a decrease in
were used to correct for density changes and calculate the feed rate or conveying distance from system design levels
nominal compressed air velocity using the ideal gas law. could result in higher kernel velocity and greater
damage.
A = 2.78 x m g /(p x v ) (SI Units) [2a]
SUMMARY AND CONCLUSIONS
Performance of a pressure-type pneumatic conveying
A g = 0.933 x m g / ( p g x v g ) (English units) [2b] system was evaluated using dry shelled corn in 2 system
configurations. Grain flow varied from 3 to 20 t/h (100 to
800 bu/h). Conveying air velocity varied from 15 to 30
e^-VAp W m/s (3000 to 6000 fpm). Conclusions are as follows:
• Electrical consumption and pneumatic energy per
unit weight of material conveyed decreased as grain flow
v
a,ac = v
a,nc/e [4] increased and were more responsive to changes in grain
flow than to changes in air velocity. Electrical
consumption was optimized with an air velocity of 20
where: Ap pipe cross sectional area (cm2 or ft2)
= m/s (4000 fpm). Power consumption for initial
Ag area of pipe occupied by grain (cm2 or ft2)
= acceleration and vertical conveying appeared to be
£ =
void fraction in pipe greater than that for conveying through horizontal
v
a,ac —
actual compressed air velocity (m/s or sections which included elbows.
fpm) • The pneumatic system required at least 1.6 times
v
a,nc — nominal compressed air velocity (m/s or more electricity than indicated by design data for a 15 cm
fpm) (6 in) auger with equal grain flow and equal horizontal
vg = grain velocity (m/s or fpm) and vertical conveying distance.
mg = grain flow rate (t/h or bu/h) • Relationships between pressure and grain flow and
p g = grain specific density (g/cm 3 or lb/ft3) between pressure and air velocity were similar to those
For the first horizontal photographing location, the reported for pneumatic systems in which there was very
little compression of the air. System operating pressure
difference between actual air velocity and grain velocity
increased almost linearly as grain flow increased.
(11.4 to 14.0 m/s or 37.3 to 45.9 ft/s) was nearly equal to
Pressure drop across the silencer was small, but that
the terminal velocity of free-falling corn (7.9 to 12.8 m/s
across the filter was significant. Recommended design
or 26 to 42 ft/s, Uhl and Lamp, 1966). For design
factors by Stoess (1983) were higher than minimums
purposes, grain speeds in pneumatic systems may be
needed, perhaps due to a safety factor.
estimated using the difference between actual conveying
• Median grain kernel velocities were less than half
air velocity and reported values for terminal grain
the conveying air velocity. Reported values for terminal
velocity. For the vertical photographing location, the
velocity of free-falling corn closely approximated the
difference between actual air velocity and grain velocity
difference between actual air velocity and kernel velocity
(14.4 to 20.3 m/s or 47.2 to 66.6 ft/s) was greater;
at locations where grain speeds were highest.
however, there was little distance to allow grain
• At airflows of 20 m/s (4000 fpm or less), kernel
acceleration in the vertical section. For the
velocities were less than 10 m/s (2000 fpm), and,
photographing location preceeding the cyclone, terminal according to the literature, potential for impact damage
grain velocity approximated the velocity difference in the is low.
2-elbow system. The difference was higher in the 4-elbow
Vol. l(2):November, 1985 77
References 12. Mohsenin, N. N. 1970. Physical properties of plant and animal
1. Baker, K. D., R. L. Stroshine, G. H. Foster and K. J. Magee. materials. Vol I: Structure, physical characteristics, and mechanical
1984. Performance of a pressure pneumatic grain conveying system. properties. Gordon and Breach Science Publishers, New York.
ASAE Paper No. 84-3515, ASAE, St. Joseph, MI 49085. 13. Moreira, S. M. C , G. W. Krutz, and G. H. Foster. 1981.
2. Brusewitz, G. H., and R. R. Wolfe. 1967. Flow characteristics Crack formation in corn kernels subject to impact. TRANSACTIONS
in the pneumatic conveying of chopped forage. TRANSACTIONS of of the ASAE. 24(4):889-892.
the ASAE 10(3):320-324, 329. 14. Segler, G. 1951. Pneumatic grain conveying. National Institute
3. Chatley, H. 1940. The pumping of granular solids in fluid of Agricultural Engineering. Silsoe, Bedfordshire.
suspension. Engineering. London. 149:230-231. 15. Stoess, H. A. Jr. 1983. Pneumatic conveying. John Wiley &
4. Cornish, G. K. and L. F. Charity. 1966. Pressure drop in Sons, Inc.
elbows of a pneumatic conveying system. TRANSACTIONS of the 16. Susai, A. D. and R. J. Gustafson. 1982. Power requirements
ASAE9(1):29-31. and quality change of material for a pneumatic conveying system.
5. Crane, J. W. and W. M. Carleton. 1957. Predicting pressure ASAE Paper No. 82-3559, ASAE, St. Joseph, MI 49085.
drop in pneumatic conveying of grains. AGRICULTURAL 17. Uhl, J. B. and B.J. Lamp. 1966. Pneumatic separation of grain
ENGINEERING 36(3):168-171, 180. and straw mixtures. TRANSACTIONS of the ASAE 9(2):244-246.
6. Cramp, W. and H. Priestly. 1924. Pneumatic grain elevators. 18. Wen, C. Y. and W. S. O'Brien. 1976. Chapter 3. Pneumatic
The Engineer. London. 137:34-36ff. conveying and transporting. In: Gas-Solids Handling in the Process
7. Foster, G. H. 1973. Grain breakage caused by commercial Industries (Marchello and Gomezplata, ed.). Marcell Dekker, Inc.
handling methods. USDA Market Research Report No. 968. 19. White, G. M., L. A. Schaper, I. J. Ross, and G. W. Isaacs.
8. Gluck, S. E. 1968. Design tips for pneumatic conveyors. 1962. Performance characteristics of enclosed screw conveyors
Hydrocarbon Processing, 47(1):88-95. handling shelled corn and soybeans. Research bulletin No. 740. Purdue
9. Jennings, M. 1940. Pneumatic conveying in theory and University, Agricultural Experiment Station, West Lafayette, IN
practice. Engineering. London. 150:361-363. 47907.
10. Leva, M. 1959. Fluidization. McGraw-Hill Book Co., Inc. 20. Wolfe, R. R., M. M. Smetana, and G. W. Krutz. 1970.
11. Magee, K. J., R. L. Stroshine, G. H. Foster and K. D. Baker. Performance characteristics and feeder design in pneumatic conveying
1983. Nature and extent of grain damage caused by pneumatic of chopped forage. TRANSACTIONS of the ASAE 13(3):332-334, 339.
conveying systems. ASAE Paper No. 83-3508. ASAE, St. Joseph, MI 21. Zenz, F. A. 1949. Two-phase fluid-solid flow. Industrial and
49085. Engineering Chemistry. 41(12):2801-06.

78 APPLIED ENGINEERING in AGRICULTURE

You might also like