You are on page 1of 14

Energy and Buildings 159 (2018) 558–571

Contents lists available at ScienceDirect

Energy and Buildings


journal homepage: www.elsevier.com/locate/enbuild

Experimental study of a local ventilation strategy to protect


semi-exposed relics in a site museum
Xilian Luo a,b,∗ , Zhaolin Gu a,b,∗ , Wei Tian b,c , Yin Xia d , Tao Ma e
a
School of Human Settlements and Civil Engineering, Xi’an Jiaotong University, Xi’an 710049, China
b
Shaanxi Energy environmental & Building Energy Conservation Engineering Technology Research Center, Xi’an Jiaotong University, Xi’an 710049, China
c
China United Northwest Institute for Engineering Design & Research Co., Ltd,No.81 Laodong Road, Xi’an, 710082, China
d
Emperor Qinshihuang’s Mausoleum Site Museum, Xi’an 710600, China
e
Shaanxi Provincial Institute for the Conservation of Cultural Heritage, Xi’an 710075, China

a r t i c l e i n f o a b s t r a c t

Article history: Indoor environmental controls are critical considerations when preserving artifacts in museums. Con-
Received 30 June 2017 trolling the indoor environment of site museum buildings with large space layout typically consumes
Received in revised form 1 December 2017 large amounts of energy. Most of the energy load needed to preserve relics is dissipated throughout
Accepted 1 December 2017
the non-occupied space, because the environments that contain the relics occupy relatively little space
Available online 5 December 2017
compared to the entire exhibition hall. In this study, an energy efficient local ventilation system was
proposed to independently control the environment of a funerary pit, which was preserved within a
Keywords:
museum separate from the large exhibition hall. An experimental hall, which consists of a funerary pit
Local ventilation system
Relic preservation
and an experimental local ventilation system, was built to simulate a site museum building. Experiments
Energy saving were conducted to investigate the system’s performance and to validate its ability to preserve historical
Site museum terracotta figurines in their semi-exposed pits within the exhibition hall. The study evaluated the stability
Local environmental control of the conservation environment and the system’s energy usage by assessing the effects of the ventila-
tion rate. The experimental results showed that the local ventilation system provides an energy-saving
strategy supporting the environmental control of the funerary pit. The LV system significantly decreased
temperature fluctuations in the funerary pit and temperature differences across semi-exposed relics. The
system could be used to control the local preservation environment of the funerary pit separately from
a large space exhibition hall.
© 2017 Elsevier B.V. All rights reserved.

1. Introduction China is an ancient civilized country with more than 4500 muse-
ums [8]; many of which are site museums, indicating that these
Energy consumption within buildings is responsible for 40% of museums are built directly at the place where the relics were found.
the global energy requirement in the EU, the USA, and the UK [1–3], Site museums preserve the original panorama of immovable his-
while it is responsible for more than one-third in China [4,5]. One- toric sites in an exhibition hall, which generally means that most
fifth of utilized energy in China is consumed by public buildings of the museum has a large open space layout [9]. However, this
[5]. Fossil fuel depletion, growing energy demands from build- type of special building consumes significant amounts of energy for
ing users, and governmental policies for reducing environmental air conditioning (AC) systems, to create a stable and clean preser-
pollution emissions have increased the urgency for finding tech- vation microenvironment for the preservation of relics. Energy
nological solutions to reduce energy consumption and increase consumption in a museum building is typically of less importance in
energy efficiency. These solutions are particularly important for comparison to the demands of providing the appropriate preserva-
public buildings with high energy consumption, such as office tion environment for collections [10]. However, wherever possible,
buildings, schools, hotels, and museums [6,7]. energy use should be minimized, because cultural relics require
a continuously working AC system throughout the year. This sig-
nificantly increases the economic burden of the site museum’s
operational costs.
∗ Corresponding authors at: School of Human Settlements and Civil Engineering, Given their significant energy consumption, more studies are
Xi’an Jiaotong University, Xi’an 710049, China required to fully understand microclimate control within site
E-mail addresses: xlluo@mail.xjtu.edu.cn (X. Luo), guzhaoln@mail.xjtu.edu.cn museums. Many recent studies have identified different ther-
(Z. Gu).

https://doi.org/10.1016/j.enbuild.2017.12.001
0378-7788/© 2017 Elsevier B.V. All rights reserved.
X. Luo et al. / Energy and Buildings 159 (2018) 558–571 559

mal requirements for artifact preservation compared to visitor hall (see Fig. 1a). This site museum generally faces the problem of
comfort, concluding that both should be treated independently either having no AC system, or having an AC system that wastes
[11–14]. In general, environmental controls in visitor areas can too much energy for cooling and heating the entire large space (see
be conveniently implemented using traditional central AC systems Fig. 1b). Efficient AC systems, such as stratified air conditioning and
[15,16]. However, environmental controls for the preservation of local heating systems are therefore attracting increased attention.
unearthed relics remain a scientific and technological challenge, The total energy usage of a building’s AC system (Q) can be
due to their stringent environmental requirements and unique estimated with Eq. (1).
preservation surroundings. Different requirements for visitor com-
fort and artifact preservation may cause museum staff to overlook Q = qA A (1)
the particular requirements of the relics. As a result, significant fluc-
In this expression, qA represents the cooling load per unit floor
tuations can be observed in the indoor environment, i.e., the daily
area (Q-Index) andA represents the total air-conditioned area of the
temperature fluctuations reach more than 10 ◦ C in the Emperor
building. A site museum’s exhibition hall generally has a high ceil-
Qin’s Mausoleum Site Museum (China) and the Jinsha Site Museum
ing height (≥ 10 m), a large ratio of external building envelope area
(China) [17]. Many relics may suffer deterioration or ruin due to the
to wall area, large interior volumes, and complicated functions. A
adoption of improper preservation environments [18].
traditional central AC system that cools the entire space (see Fig. 1b)
The Emperor Qin’s Mausoleum Site Museum in Xi’an, China is a
will be energy-hungry. The predicted cooling energy consumption
world-famous historical site, designated by United Nations Educa-
and cooling load index of the No. 1 exhibition hall of the Emperor
tional, Scientific, and Cultural Organization as one of the world’s
Qin’s Mausoleum Site Museum would amount to 2860.66 kW and
cultural legacies. To provide an energy efficient AC system that
179 W/m2 [24,25]. In addition, an exhibition hall typically has a very
protects the immobile relics, the Ministry of Science and Tech-
large floor area (A), where only a small proportion is occupied by
nology of China approved a project for the development of an air
collections (see Fig. 1a). For example, at the Emperor’s Mausoleum
curtain system and a capillary radiation cooling system. Research
Site Museum, the area occupied by relics occupies only 34% of the
on these systems has generated promising results [12,14,19,20].
total indoor space of the No. 1 pit exhibition hall [26]. This indicates
Both systems (air curtain and capillary radiation) have specific fea-
that most of the energy load is likely wasted in areas that are not
tures that can create a steady preservation environment for the
occupied by relics.
relics, allowing independent control and local preservation of arti-
Eq. (1) highlights two ways to reduce the energy consumption:
fact environments. However, both systems have limitations: The
reducing the cooling load per unit area (qA ), or decreasing the air-
capillary radiation system belongs to an all-water AC system. The
conditioned area (A). The local environmental strategy achieves
water pipeline for the chilled water is directly fixed in the preserva-
both; it reduces the height of the air-conditioned space to decrease
tion area, which causes the risks of water leakage within exhibition
qA and provides local environmental control within the occupied
areas. Furthermore, the RH of the preservation area is typically very
area to decrease A. In general, it is difficult to implement a local
high, so that moisture easily condensates on the surface of water
heating in the funerary pit for this tall exhibition hall since hot
pipe and flows into the fragile earthen ruins. Moreover, the capillary
air will rise up and move out of the funerary pit [12]. However,
radiant system may encourage fungal growth due to the beneficial
local cooling is particularly viable for the funerary pit because the
high moisture, lack of air purification, and poor ventilation. The air
soil temperature of the underlying funerary pit is typically lower
curtain system belongs to an all-air AC system. The high air veloc-
(cooler) than the air temperature of the space above, once cool air
ity at the jet outlet may cause vibration and noise. The symmetric
is supplied to the pit, a steady thermal layer is created, which main-
arrangement of the jet outlet and return air grille of the air curtain
tains a stable preservation environment (see Fig. 1c). This type of
system cause difficulties in the popularization of funerary pits with
local cooling system is widely used in commercial buildings with
irregular geometrical structure.
large space layouts, including airport terminals, large conference
By fixing both the air supply outlet and return air inlet at
halls, and large open plan offices. This further supports the suc-
the bottom and top of the funerary pit, this study proposes an
cessful implementation of independent controls for both the relic
energy efficient local ventilation (LV) system to control the specific
environment and the visitor environment [14].
preservation environment for semi-exposed relics. This ventilation
system is essentially a type of displacement ventilation without
internal heat sources. Displacement ventilation systems are known 3. Climatic recommendations for semi-exposed terracotta
to effectively control visitor-occupied environments in museums at relics
a relatively low energy cost, and are therefore widely used in pub-
lic buildings with large space layouts. DV systems can also improve The UNI 10829:1999 standard [27] indicates that terracotta
the indoor air quality in occupied areas by separating contaminated relics are insensitive to ambient temperature and RH. Therefore,
air from clean air via stratification. The systems effectively achieve temperature and RH values are not provided as optimal conserva-
energy savings as well as high indoor air quality [21–23]. tion parameters, thus implying that environmental controls may
This research evaluated LV system performance when control- not be necessary for terracotta relics in site museums. However,
ling the local preservation area in an experimental exhibition hall several studies have analyzed the primitive environments of relics
with a large space layout. The study specifically explored both the in site museums, and recommended that environmental conditions
environmental stability and energy consumption of the LV system should be reconsidered in a more differentiated and qualified way
by evaluating the effects of the ventilation flow rate. because these relics are semi-exposed complex (see Fig. 2) [20].
Environmental control systems are therefore required to reduce
differences in temperature and RH between the surrounding soil
2. Preliminary energy consumption analysis and system and air, since a lack of equilibrium would cause fluctuations in envi-
description ronmental parameters and thus allow heat and moisture to transfer
from the soil into the air [20,28].
China has many terracotta pottery relics; most of these have In general, the soil environment underneath the relics is more
been unearthed and preserved in funerary pits. The Emperor Qin’s stable than the air environment. As such, the natural soil parame-
Mausoleum Site Museum displays these types of relics, which are ters should be considered as the target values for relic conservation.
located in pits that form a reservoir at the ground of the exhibition The soil temperature at depths of less than 10 m below the ground
560 X. Luo et al. / Energy and Buildings 159 (2018) 558–571

Fig. 1. Schematic diagrams of environmental control systems for site museums with funerary pits. (a) The No. 1 exhibition hall of Emperor Qin’s Mausoleum Site Museum
(courtesy of the Emperor Qin’s Mausoleum Site Museum). (b) Environmental control provided by a traditional central AC system. (c) The local environmental control provided
in a preservation area using a LV system.

Fig. 2. Schematic diagram of semi-exposed relics in a site museum. (a) Unearthed semi-exposed terracotta relics of the Hanyangling Museum. (b) The soil-air coupled
preservation environment.
X. Luo et al. / Energy and Buildings 159 (2018) 558–571 561

Fig. 3. The LV system experimental device. (a) System flow chart. (b) Environmental controls for the pit. (c) Interior view of the experimental facility.

surface in Xi’an (the museum and study site) has been reported to 4. Experimental setup and procedure
be approximately 20 ◦ C [29]; therefore, the control temperature of
LV system was set at 20–21 ◦ C. It is more difficult to identify a spe- 4.1. Experimental LV system
cific target RH range; however, to mitigate the desiccation cracking
of relics, the preservation environment should be as moist as pos- All conservation measures have to undergo extensive and
sible. This is required because the RH of soil pore air is almost 100%, detailed investigation, testing, and evaluation; only those demon-
with an RH balance point of 99.9% [28]. strated to be effective and safe may then be used [31]. Therefore, an
However, spore germination and mycelium growth both benefit experimental building was built in the campus of the Xi’an Jiaotong
from humidity; a highly humid environment may damage in-situ University to simulate a site museum exhibition hall. The distance
relics due to mold growth. The ambient RH requirement for mold between the experimental building and the Emperor Qin’s Terra-
fungus development has been estimated to range between 80 and Cotta Warriors and Horses Museum is only 31.4 km. The area and
95% [30]. With increasing humidity, the probability that mold fun- height of the experimental building are 100 m2 and 5 m, respec-
gus will form increases as well. The optimal RH for mold fungus tively. A cuboid-shaped pit with a length, width, and depth of 4 m,
development ranges between 90 and 95%. In addition, once the RH 2.8 m, and 2.0 m, respectively, was excavated in the experimental
exceeds 90%, temperature fluctuations may cause water conden- hall. Three soil columns with heights of 0.5 m were placed in the
sation on all semi-exposed relic surfaces. Therefore, the LV system funerary pit to investigate the desiccation cracking process of the
humidifier was not switched on during this study and the average earthen site (see Fig. 3). In general, the desiccation cracking process
RH of the funerary pit was sustained between 80 and 90% approx- takes place continuously and may take several years to complete.
imately. The floors of the indoor gallery of the experimental building for
visitors are paved with floor-bricks; however, in the funerary pit
562 X. Luo et al. / Energy and Buildings 159 (2018) 558–571

Fig. 4. Layout of the monitoring points in the experimental hall.

the soil ground is directly exposed to the air. The width and depth • Vertical temperature and RH profiles in the integrated pit envi-
of the funerary pits, and soil type, and the climatic conditions of ronment were measured using the same model meter at five
the experimental site are similar to those at the Emperor Qin’s observation points (labeled T1 to T5) along a central line in the
mausoleum Site Museum. A LV system was designed and estab- pit. The distances from the ground level of the pit upward to
lished in the experimental funerary pit (see Fig. 3). The air was points T1 through T5 were 0.2 m, 0.5 m, 1.3 m, 1.9 m, and 2.6 m,
supplied at the ground level of the pit into a plenum chamber with respectively. Of these points, T4 was the dividing point between
a length and depth of 2.5 m and 0.7 m, respectively. One façade of the preservation zone and the visitor zone. T5 was in the visitor
the chamber served as the air diffuser, which was composed of a area, at a height of 0.6 m above the pit. To evaluate the effect of
perforated panel with 2.0 mm diameter circular holes. The perfo- the LV system on the visitor passageway away from the funerary
rated plate serves as a type of air supply outlet that is widely used in pit, temperature was also monitored at a sixth observation point
clean air-conditioning systems, since it can effectively decrease the (T6). T6 was located at the same height as T5 (2.6 m) and was 2 m
air velocity and temperature gradients in the air-conditioned area away from the funerary pit. Data from all six points (T1-T6) were
[32]. The returned air was purified and cooled in the air-handling automatically collected and recorded every 2 min.
unit and then directed into the plenum chamber using a centrifu- • The soil temperature and the temperature of the relic body were
gal fan. The air pressure was equalized in the plenum chamber monitored using thermocouples at three measuring points: Ts1,
to ensure a uniform air supply through the perforated panels. A Tr1, and Tr2. Ts1 was placed 0.05 m below the base of the pit.
5100 W air-cooled water chiller was used as the cold source of the Tr1 and Tr2 were inserted into the ceramic pottery block; both
air-handling unit[33].Although there is a significant length differ- monitoring points were 0.25 m from the air-soil interface. Mea-
ence between the experimental funerary pit and the real funerary surements were collected every 2 min; thermocouple accuracy
pits of the Emperor Qin’s mausoleum Site Museum, it will not affect was ± 0.004|T|◦ C.
the performance of the ventilation system since the supply outlet • The air velocity in the center of the funerary pit (TaV) was
and return air inlet of the proposed AC system were installed at measured every 2 min at a height of 0.35 m using a Swema 03
both sides of the width direction and the critical dimensions that micro-velocity sensor, with an accuracy of ± 0.03 m/s. To calcu-
affect the performance of the DV system are the width and depth late the cooling load of the LV system, the volume flow (Lw) and
of the funerary pit. the temperature of the supply and return water (Tws and Twr)
flowing through the air-handling unit were also measured. The
water pump for the chilled water was working at a fixed con-
4.2. Layout of the measuring points dition. The volumetric flow of the chilled water was measured
via turbine flow meter and recorded manually. The duration
A series of LV system tests were performed in the experimental and sampling intervals of the acquisition of volumetric flow
building to monitor environmental parameters, understand local were 15 min and 30 s. The accuracy of the turbine flow meter
environmental controls in the funerary pit, and evaluate LV system was ± 1%|L| L/h; the temperatures of the supply and return water
performance. were monitored via T-type thermocouples recorded with an
Parameters monitored during the study (see Fig. 4) included: ADAM 4018. The sampling intervals were 2 min. The accuracy
of the thermocouple was ± 0.004|T|◦ C.
• The temperature and RH of the outdoor environment were • A temperature controller was placed in the pit at a height of 0.2 m
automatically measured every 10 min by placing the TR-72Ui (Tc) to manage the automatic start and stop of the water pump.
thermos-recorder in a thermometer shelter. The accuracy of the The control temperature was set to 20–21 ◦ C. When the measured
TR-72Ui was ± 0.3 ◦ C for temperature and ± 5% for RH. temperature at Tc exceeded 21 ◦ C, the water pump switched on,
X. Luo et al. / Energy and Buildings 159 (2018) 558–571 563

Table 1
Summary of the test cases.

Case Operational model Date f (Hz) La (m3 /h) ACH (ac/h)

1 The LV system switched off July 17–19, 2015 – – –


2 The LV system switched on August 1–3, 2015 15 181.6 8.1
3 The LV system switched on July, 23–25, 2015 20 267.1 11.9
4 The LV system switched on July 29–31, 2015 30 370.4 16.5
5 Both the LV and comfort AC systems switched on July 16–17, 2016 20 267.1 11.9

providing cold water to the air handling unit at a temperature Table 2


Summary of the outdoor temperature (◦ C) and RH (%).
below 20 ◦ C.
• The air velocities in the funerary pit were monitored along the Case Duration Temperature RH
horizontal direction using a Swema 03 micro-velocity sensor at
Max Min Avg Max Min Avg
the five measuring points of Tv1 to Tv5. The distances of the
1 July, 17–19, 2015 35.1 21.7 28.1 83 31 54
five monitoring points from the air supply outlet were 0.05 m,
2 August, 1–3, 2015 42.0 21.3 31.2 100 26 59
0.2 m, 0.4 m 0.8 m, and 1.4 m, respectively. The air velocities were 3 July, 23–25, 2015 39.2 22.5 30.1 64 13 38
manually recorded with duration and sampling interval of each 4 July, 29–31, 2015 41.5 27.5 34.3 59 23 38
monitoring point of 5 min and 5 s. 5 July, 16–17, 2016 35.3 23.3 29.5 99 32 54

4.3. Test cases


indoor environment of the site museum. Consequently, a suitable
AC system is required to create a stable conservation environment
Five tests were conducted during the summer months of 2015
for the semi-exposed relics.
and 2016 (see Table 1). The LV system was initially turned off in case
1 to measure the results of the natural ventilation condition of the
exhibition hall. Then, three experiments were conducted where the 5.2. Indoor preservation environment
LV system for the preservation area was only switched on in case
2 to case 4. Different ventilation rates were established in these Figs. 5 and 6 present the indoor temperatures and RH distri-
three cases to determine a suitable fan frequency for the LV system. butions, respectively, across the test cases of 1–4. Tables 3 and 4
The air conditioning systems in newly built archaeology museums present the mean temperature and RH values (T 1-T 6and RH1-
are typically installed to satisfy the thermal requirements of visi- RH6) as well as daily ranges (T1-T4 and RH1-RH4 for the
tors. A coupling operational mode of the LV system with a comfort funerary pit), respectively. During test case 1, when the LV sys-
AC system was performed in case 5 to validate the simultaneous tem was turned off, the preservation environment of the pit was
environmental control for both visitors and relics area. unstable. The diurnal temperature fluctuation at observation points
T1-T4 (in the conservation area) were 2.5 ◦ C, 3.9 ◦ C, 5.7 ◦ C, and
• In cases 2–4, the temperature of the chilled water (see Tws in 8.0 ◦ C, respectively. These fluctuations were larger than the recom-
mended range (≤ 1.5 ◦ C) for the conservation of cultural relics in
Fig. 4) was set to 10–12 ◦ C. As soon as the water temperature
museums [34]. Outdoor climatic conditions significantly affected
exceeded 12 ◦ C, the refrigeration unit started until the water tem-
the preservation environment; large fluctuations of climatic fac-
perature had dropped below 10 ◦ C. Within this temperature range
tors within the funerary pit corresponded with periodic variations
of the chilled water, the average temperature of the supply air
in the outdoor environment. Higher outdoor temperatures further
varied between 19.6 ◦ C and 20.1 ◦ C.
• In case 5, the traditional comfort AC system for the visitors’ envi- aggravated high temperatures and fluctuations in the funerary pit.
In test cases 2–4, the LV system created a suitable conservation
ronment was operated from 9 a.m. to 6 p.m., while the LV system
environment in the pit. Fig. 5 shows that the LV system significantly
for the preservation area worked 24 h per day.
• The fan frequency (f), air volume flow (La), and air change rate reduced temperature fluctuations in the funerary pit. Even in test
case 2, when only a low level of air volume was supplied to the
are also listed in Table 1; the air changes per hour (ACH) were
funerary pit, the preservation environment significantly improved,
calculated as the supply air volume divided by the pit volume.
when a stable and uniformly cool air reservoir had formed in the
conservation area. The temperature fluctuation at T4 declined by
5. Results and discussion approximately 40% during test case 2 compared to test case 1.
Increasing the volume flow of the supplied air in test case 3 and
Tables 1 summarizes the experimental conditions used to vali- 4 minimized temperature fluctuations in the pit. The temperature
date the ability of the LV system to support the independent control distribution in the funerary pit became more uniform during these
of the preservation environment. The equilibrium between the air- test cases; the vertical temperature difference between the top and
soil interface and the LV system energy consumption was also bottom of the pit (T 4 − T 1) was reduced from 3.0 ◦ C in case 2 to
analyzed. approximately 2 ◦ C in cases 3 and 4. When the volume air increased
by approximately 39.0% from 267.1 m3 /h in case 3–370.4 m3 /h in
5.1. Outdoor environment case 4, there was almost no variation in the mean temperature at
T1-T4. This indicates that case 3 was sufficient to provide a stable
Summer is relatively hot in Xi’an, with significant tempera- preservation environment for the funerary pit.
ture swings between day and night. Table 2 summarizes both the The daily changes in RH aligned with the temperature changes
outdoor temperatures and RH during the test case periods. The out- during the test cases. The RH at the base of the preservation area
door temperature varied between 21.3 ◦ C and 42 ◦ C, with a mean (T1) was high during test case 1, at approximately 100%. This almost
value of 30.9 ◦ C during the test period. These high outdoor tem- saturated RH near the air-soil interface efficiently reduced the
perature and diurnal temperature differences have been known to moisture transport from the soil into the air; however, such a high
accelerate the chemical process of relic deterioration [33], and sig- level caused moisture condensation on relic surfaces and acceler-
nificantly impact the energy consumption required to control the ated bacterial and fungal growth in the funerary pit. This would
564 X. Luo et al. / Energy and Buildings 159 (2018) 558–571

Fig. 5. Variations in air temperature. (a) The LV system switched off. (b) The LV system switched on at f = 15 Hz. (c) The LV system switched on at f = 20 Hz. (d) The LV system
switched on at f = 30 Hz.

Table 3
Summary of the indoor air temperature (◦ C).

Case Preservation area Visitor’s area

T1 T2 T3 T4 T1−4 T1 T2 T3 T4 T5 T6

1 23.0 24.0 25.1 26.2 24.6 2.5 3.9 5.7 8.0 27.7 28.0
2 20.7 21.4 22.6 23.7 22.1 2.0 2.9 3.4 4.6 29.8 30.5
3 20.5 21.1 21.9 22.8 21.6 1.3 2.0 2.6 4.0 28.3 28.9
4 20.5 20.9 21.7 22.5 21.5 1.2 1.8 2.4 3.2 30.6 31.2
X. Luo et al. / Energy and Buildings 159 (2018) 558–571 565

Fig. 6. Variation of air RH. (a) The LV system switched off. (b) The LV system switched on at f = 15 Hz. (c) The LV system switched on at f = 20 Hz. (d) The LV system switched
on at f = 30 Hz.

Table 4
Summary of the indoor air RH (◦ C).

Cases Preservation area Visitor’s area

RH1 RH2 RH3 RH4 RH1−4 RH1 RH2 RH3 RH4 RH5 RH6

1 98 95 82 71 87 3 11 19 30 59 60
2 82 76 69 70 74 23 28 29 36 60 59
3 88 82 76 77 81 27 36 36 41 56 56
4 86 81 72 73 78 23 24 26 31 50 51
566 X. Luo et al. / Energy and Buildings 159 (2018) 558–571

Fig. 7. Air velocity variations in the pit. (a) The LV system switched off. (b) The LV system switched on at f = 15 Hz. (c) The LV system switched on at f = 20 Hz. (d) The LV
system switched on at f = 30 Hz.

Table 5
Summary of the air velocity.

Cases 1 2 3 4

UMax 0.013 0.106 0.182 0.280


UAVG 0.004 0022 0.026 0.070

result in relic deterioration, especially in the absence of air ventila-


tion. In test cases 2–4, the funerary pit experienced high humidity,
but at a RH lower than 90%, which could prevent moisture conden-
sation on relic surfaces.
In all test cases (with and without operation of the LV system),
the temperatures and RH at T5 and T6 were almost approximately
equal for all cases. This means that the LV system created a cool
air lake in the pit without influencing the visitor area. Although
the environment of the funerary pits was mainly governed by the
LV system, the outdoor climatic conditions still posed an impor-
Fig. 8. Attenuation curves of the air supply velocity along the along the horizontal
tant influence on the operation of the system since the visitors’
direction of the funerary pit.
area was naturally ventilated and could be regarded as an upper
boundary condition of the funerary pit. The return air inlet will
entrain air from the visitors’ area, which will lead to an increment significantly larger than a traditional grill opening. Significant fluc-
in environmental fluctuation and energy consumption. tuations were observed in the velocity profiles when the LV system
Air motion in the preservation area typically attracts little atten- was switched on; however, average velocities were lower than the
tion; however, air velocity significantly impacts the desiccation recommended range (≤0.15 m/s) for museum collections [37].
cracking of earthen sites, since the soil’s drying rate is proportional The air supply outlet of the LV system was fixed in the funer-
to the air velocity of the preservation environment [35,36]. Fig. 7 ary pit. The flow features of the regions adjacent to the outlet were
and Table 5 provide the air velocities at the monitoring point TaV critical for the evaluation of LV system performance. The attenua-
(see Fig. 4) in different test conditions. The air velocities varied little, tion curves of the air supply velocity along the horizontal direction
regardless of whether the LV system was operating or not; the mean in the funerary pit are shown in Fig. 8. The velocities attenuated
values of case 1–3 were even below the manufacturer’s specified quickly and reached the recommended range (≤0.15 m/s) at dis-
low value (0.040 m/s) of the air velocity sensor. The preservation tances of less than 0.1 m, 0.2 m, and 0.4 m for case 2, case 3, and case
area may have had negligible air velocities since the effective aer- 4, respectively. Considering that case 3 was sufficient to provide a
ated area provided by the perforated panel of the LV system was stable preservation environment for the funerary pit, a distance of
X. Luo et al. / Energy and Buildings 159 (2018) 558–571 567

Fig. 9. The soil-air preservation environments of semi-exposed relics. (a) Unearthed terra-cotta relics in the Hanyangling Museum, China. (b) Unearthed ivory artifacts in
the Jinsha Site Museum, China.

Fig. 10. Temperature profiles of the soil-air environment. (a) The LV system switched off. (b) The LV system switched on at f = 15 Hz. (c) The LV system switched on at f = 20 Hz.
(d) The LV system switched on at f = 30 Hz.

0.2 m between the relics and the air supply outlet could ensure air Fig. 10 shows the soil temperatures (Ts) and air temperatures
velocities below 0.15 m/s. (T1) detected during the experimental tests. The mean temperature
differences (T = |T1-Ts|) for test cases 1–4 were 1.14 ◦ C, 0.47 ◦ C,
0.33 ◦ C, and 0.27 ◦ C, respectively (see Fig. 11). The outdoor climatic
5.3. Balance of the soil-air coupled preservation environment
conditions during test case 1 were relatively cool, with an average
outdoor temperature of 28.1 ◦ C (see Table 3); a significant temper-
Fig. 9 shows in-situ cultural relics in site museums that remain
ature difference was observed at the air-soil interface (Fig. 10a).
partly buried in the soil environment. In such a scenario, semi-
Additionally, both soil and air temperatures became unstable, fol-
exposed relics are surrounded by both soil and air. Moisture
lowing an upward trend. When the LV system was switched on
transport in the soil-air environment is closely correlated with tem-
for test cases 2–4, the temperature differences were significantly
perature differences at the soil-air interface and this difference is
lower than for test case 1. Soil and air temperatures at the inter-
a primary driver of desiccation cracking and salt damage to semi-
face almost overlapped during test cases 3 and 4, suggesting that
exposed relics [20,28]. A uniform temperature distribution in the
the in-situ relics were preserved in a stable and balanced soil-air
air-soil preservation environment is required to delay relic deteri-
environment.
oration.
568 X. Luo et al. / Energy and Buildings 159 (2018) 558–571

Fig. 11. The average temperature difference across the soil-air interface in cases Fig. 13. The average temperature difference between parts of the semi-exposed
1–4. relics in cases 1–4.

Fig. 12 shows the time-series for temperatures at Tr1 and Tr2


across all four test cases. The differences in mean temperature
(T = |Tr2-Tr1|) along the terracotta pottery block placed in the
test pit in cases 1–4 were 2.09 ◦ C, 0.80 ◦ C, 0.48 ◦ C, and 0.43 ◦ C,
respectively (see Fig. 13). The daily temperature variations were the air-soil environment and relic bodies mitigated heat transport
analogous to the variations at the soil-air interface. The tempera- and moisture transfer.
ture profiles were lower, and the temperature differences along the The temperature differences were very small and were almost
ceramic pottery block were also lower during LV system operation. identical in test cases 3 and 4. As noted above, this confirmed that
The LV system provided a balanced conservation environment for case 3 would provide a uniform and stable local environment for
semi-exposed relics, as the lower temperature differences across the funerary pit.

Fig. 12. Temperature profiles along the relic body. (a) The LV system switched off. (b) The LV system switched on at f = 15 Hz. (c) The LV system switched on at f = 20 Hz. (d)
The LV system switched on at f = 30 Hz.
X. Luo et al. / Energy and Buildings 159 (2018) 558–571 569

Table 6
Summary of energy consumption.

Cases Case 2 Case 3 Case 4

Tw (◦ C) 1.1 1.2 1.78


Lw (m3 /h) 1.0 1.0 1.0
Q (W) 1279.9 1396.2 2094.3
Q-Index (W/m2 ) 114.3 124.7 187.0

Table 7
Summary of the coupled experimental case.

AC system Air conditioned zones Operational time

Comfort AC system Visitors’ area Switched on from 9 a.m. to 6 p.m.


LV system Funerary pit Remained on 24 h per day

5.4. Energy consumption

Energy consumption is an essential variable when selecting an


HVAC system for a museum building. The energy consumption of
an environmental control system (Q) can be determined via Eq. (2):
Q = Lw w C Pw Tw = Lw w C Pw (Tws − Twr ) (2)
Fig. 14. The operating model of the independent environmental control systems.
In this expression, Lw , CPw , w , and w represent the volume flow
rate, specific heat, and water density, respectively. The variables Tws
and Twr represent the supply and return water temperatures in the The air volume flow and working temperature of the LV were iden-
air handing unit, respectively (Table 6). The cooling capacity was tical to those of case 3. The working temperature of the comfort AC
then transferred from the chilled water to the supplied air in the air system was set to 26 ◦ C.
handling unit. A 120 W supply fan was used to convey recirculat- Fig. 15 shows the temperature and RH distribution in the funer-
ing air. During the tests, the volumetric flow remained constant at ary pit (T1 to T4) and visitor area (T5) during the test. The statistics
Lw = 1.0m3 /h. Table 7 summarizes the energy consumption of the for the mean temperature and RH are listed in Table 8. The mean
LV system when Tws , Twr , and Lw values and the physical parame- temperature and RH at the preservation area (T1 to T4) were almost
ters of water are substituted into Eq. (2). The differences of energy identical to those of case 3: a steady preservation environment was
consumption in case 2–4 were mainly caused by the increasing created in the funerary pit throughout all days. Furthermore, dur-
recirculating air volume of the return air inlet and enhanced heat ing the opening hours of the site museum (from 9 a.m. to 6 p.m.),
transfer of surface-type heat exchanger in the air-handling unit. As the temperature and RH at the visitors’ area (T5) varied between
discussed above, test case 3 achieved to provide a suitable envi- 25.4 ◦ C and 27.5 ◦ C and 46% and 63%, respectively, which remains
ronment for the pit area and the LV system energy used in this entirely within the comfort level of humans[38]. The requirements
case was 1396.2 W. The floor area of the preservation zone was for both visitors and relics are simultaneously satisfied, indicating
11.2 m2 and as such, the cooling load per unit floor area (Q-index) that such a LV system for the relic preservation area could be oper-
was 124.7 W/m2 . This cooling load per unit floor area is signifi- ated simultaneously with and independently from already existing
cantly lower than the predicted energy consumption required to comfort AC systems.
operate traditional central AC systems such as those in use at the
No. 1 exhibition hall of the Emperor Qin’s Mausoleum Site Museum 6. Conclusion
[24,25]. The LV system also saves significant energy because the air-
conditioned area is quite small compared to the large area covered Designing environmental controls to preserve site museum
by a traditional central AC system. relics remains a technical challenge for environmental scientists
and technologists; all currently feasible solutions consume high
5.5. Coupling operational mode of the LV system with comfort AC amounts of energy. This study involved testing and validating a LV
system system, which resulted in a tentative protocol that allows for local
environmental control of semi-exposed relics in site museums. This
For many newly built exhibition halls of site museums (such as is an efficient energy control strategy, because the conservation
the K0006 and K9901 funerary pits of the of the Emperor Qin’s Mau- area is separately regulated from the large exhibition hall.
soleum Site Museum), traditional central AC systems have been LV system performance was studied by investigating the effects
installed for the visitors’ area. These existing AC systems operate of different ventilation flow rates. Experimental tests assessed
from 9 a.m. to 6 p.m. to provide a comfortable thermal environment climatic conditions, environmental parameters in the pit, tem-
(24 ◦ C ≤ T ≤ 28 ◦ C, 40 ≤ RH ≤ 70) [38] for the visitors during open- perature differences across the soil-air environment, and energy
ing time. However, the specialized needs of the unearthed relics consumption. The results demonstrate that the LV system could
are typically ignored in these site museums due to financial and efficiently create a cool reservoir in the funerary pit and maintain
technological reasons. an adequate environment for local preservation, independent of
To evaluate the performance of the LV system in the case where the visitor environment. LV system energy consumption was lower
a traditional comfort AC system has been equipped to the visitors’ than the consumption of a traditional central AC system used in site
area, an experimental test that separately employs an AC system museum, because the area being cooled and the cooling load per
for the visitors’ area and a LV system for the funerary pit was per- unit floor area were significantly reduced.
formed in July 16–17, 2016 (see Fig. 14). The operating parameters Further research will consider the relationship between the
of both systems are listed in Table 7. The arrangement of both the height of air supply outlets and the temperature gradient along
temperature and RH sensors are identical to that of case 1 to case 4. the vertical direction of the funerary pit. This will inform different
570 X. Luo et al. / Energy and Buildings 159 (2018) 558–571

Fig. 15. Variation of the air temperature and RH for the coupled operated test.

Table 8
Statistics of indoor air temperature (◦ C) and RH (%) of case 5.

Zone Preservation area Visitor’s area

T1 T2 T3 T4 T1−4 T1 T2 T3 T4 T5 T5

T 20.4 21.3 21.7 22.5 21.5 1.5 2.2 2.8 3.3 26.1 3.4
RH 85 81 79 78 81 23 28 31 24 58 21

approaches for preserving relics at different heights. In addition, [6] J.N. Huang, H.L. Lv, T. Gao, W. Feng, Y.X. Chen, T. Zhou, Thermal properties
future studies should consider coupled operation of a LV system optimization of envelope in energy-saving renovation of existing public
buildings, Build. Environ. 75 (2014) 504–510.
and another HVAC system, as such an approach may accommodate [7] X.T. Li, C.W. Yu, China’s building energy efficiency targets: challenges or
the different thermal environments needed by relics and visitors. opportunities, Indoor Built Environ. 21 (2012) 609–613.
[8] Xinhuanet.com.,
http://news.xinhuanet.com/politics/2015-05/18/c 1115323223. htm
(Accessed: 3rd October 2017).
Acknowledgements [9] Z.L. Gu, X.L. Luo, X.Z. Meng, Z.S. Wang, T. Ma, C. Yu, B. Rong, W.W. Li, Y. Tan,
Primitive environment control for preservation of pit relics in archaeology
museum of China, Environ. Sci. Technol. 47 (2013) 1504–1509.
This study was supported by the Key Scientific Research [10] B. Bøhm, M. Ryhl-svendsen, Analysis of the thermal conditions in an unheated
Innovation Team Project of Shaanxi Province (under grant No. museum store in a temperate climate. On the thermal interaction of earth and
2016KCT-14), the China Postdoctoral Science Foundation (under store, Energ Build. 43 (2011) 3337–3342.
[11] M.L. Gennusa, G. Lascari, G. Rizzo, G. Scaccianoce, Conflicting needs of the
grant No. 2016T90923), and the Fundamental Research Funds for thermal indoor environment of museums: in search of a practical
the Central Universities (under grant No. zrzd2017003). compromise, J. Cult. Herit. 9 (2008) 125–134.
[12] X.L. Luo, Z.L. Gu, C.W. Yu, K. Li, B. Xiao, Preservation of in situ artefacts by local
heating in earthen pit in archaeology museum in cold winter, Build. Environ.
99 (2016) 29–43.
References [13] D. Camuffo, E. Pagan, S. Rissanen, L. Bratasz, R. Kozlowski, M. Camuffo, A.D.
Valle, An advanced church heating system favourable to art works: a
[1] M. Zhao, Z.L. Gu, W.B. Kang, X. Liu, L.Y. Zhang, L.W. Jin, Q.L. Zhang, contribution to European standardization, J. Cult. Herit. 11 (2010) 205–219.
Experimental investigation and feasibility analysis on a capillary radiant [14] X.L. Luo, Z.L. Gu, Z.S. Wang, W. Tian, K. Li, An independent and simultaneous
heating system based on solar and air source heat pump dual heat source, operational mode of air conditioning systems for visitors and relics in
Appl. Energy 185 (2016) 2094–2105. archaeology museum, Appl. Therm. Eng. 100 (2016) 911–924.
[2] R. Barzin, et al., Application of PCM underfloor heating in combination with [15] H.E. Silva, F.M.A. Henriques, T.A.S. Henriques, G. Coelho, A sequential process
PCM wallboards for space heating using price based control system, Appl. to assess and optimize the indoor climate in museums, Build. Environ. 104
Energy 148 (2015) 39–48. (2016) 21–34.
[3] G.M. Huebner, et al., Explaining domestic energy consumption–the [16] F. Sciurpi, C. Carletti, G. Cella, L. Pirrangioli, Environmental monitoring and
comparative contribution of building factors, socio-demographics, behaviours microclimatic control strategies in La specola museum of Florence, Energy
and attitudes, Appl. Energy 159 (2015) 589–600. Build. 95 (2015) 190–201.
[4] Z.J. Liu, W. Xu, X. Zhai, Q. Cheng, X. Chen, Feasibility and performance study of [17] W.T. Jia, The Physical and Chemical Relationship Between Indoor Air Quality
the hybrid ground-source heat pump system for one office building in and Atmospheric Corrosion in Site Museums. Master Thesis, The University of
Chinese heating dominated areas, Renew. Energy 101 (2017) 1131–1140. Chinese Academy of Sciences, 2015.
[5] G.W. Liu, Z.Z. Wu, M.M. Hu, Energy consumption and management in public [18] J. Ferdyn-Grygierek, Indoor environment quality in the museum building and
buildings in China: an investigation of Chongqing, Energy Procedia 14 (2012) its effect on heating and cooling demand, Energ Build. 85 (2014) 32–44.
1925–1930.
X. Luo et al. / Energy and Buildings 159 (2018) 558–571 571

[19] X.L. Luo, Z.L. Gu, C. Yu, T. Ma, K. Kase, Efficacy of an air curtain system for local [28] X.L. Luo, Z.L. Gu, C. Yu, Desiccation cracking of earthen sites in archaeology
pit environmental control for relic preservation in Archaeology Museums, museum-a viewpoint of chemical potential difference of water content,
Indoor Built Environ. 25 (2016) 29–40. Indoor Built Environ. 24 (2015) 147–152.
[20] X.L. Luo, Z.L. Gu, T.Y. Li, X.Z. Meng, T. Ma, C. Yu, Environmental control [29] X. Zhang, The Theory on Heat Transfer of Vertical Ground Heat Exchanger and
strategies for the in situ preservation of unearthed relics in archaeology the Test Method for Parameter of the Rock–Soil Thermal Properties Thesis,
museums, J. Cult. Herit. 16 (2015) 790–797. Master Degree, Chang’ an University, 2012.
[21] Y. Wang, F.Y. Zhao, J. Kuckelkorn, D. Liu, J. Liu, J.L. Zhang, Classroom energy [30] H. Viitanen, J. Vinha, K. Salminen, T. Ojanen, R. Peuhkuri, Moisture and
efficiency and air environment with displacement natural ventilation in a bio-deterioration risk of building materials and structures, J. Build. Phys. 33
passive public school building, Energ Build. 70 (2014) 258–270. (2010) 201–224.
[22] T. Gil-Lopez, M.A. Galvez-Huerta, P.G. O’Donohoe, J. Castejon-Navas, P.M. [31] Chinese National Committee for the International Council on Monuments and
Dieguez-Elizondo, Analysis of the influence of the return position in the Sites. Principles for Conservation of Heritage Site in China, Cultural Relics
vertical temperature gradient in displacement ventilation systems for large Press, Beijing, 2015.
halls, Energ Build. 140 (2017) 371–379. [32] S.C. Hu, Y.K. Chuah, M.C. Yen, Design and evaluation of a minienvironment for
[23] A. Makhoul, K. Ghali, N. Ghaddar, The Energy saving potential and the semiconductor manufacture process, Build. Environ. 37 (2016) 201–208.
associated thermal comfort of displacement ventilation systems assisted by [33] G. Pavlogeoratos, Environmental parameters in museums, Build. Environ. 38
personalised ventilation, Indoor Built Environ. 22 (2013) 508–519. (2003) 1457–1462.
[24] C. Cao, X. Meng, X. Liu, X.H. Yang, W.Y. Hu, L.W. Jin, Energy analysis of relics [34] G. Thomson, The Museum Environment, second ed., Butterworld-Heinemann,
museum buildings, Energy Procedia 75 (2015) 1809–1818. London, 1986.
[25] C. Cao, Energy Consumption Analysis and Energy Conservation Strategies [35] A.W. Fan, W. Liu, C.Q. Wang, Simulation on the daily change of soil
Research of a Typical Relics Museum, Thesis, Master Degree, Xi’an Jiaotong temperature under various environment conditions, Acta Energi Sin. 24
University, 2015. (2003) 167–171.
[26] The No.1 pit exhibition hall of Emperor Qinshihuang’s Mausoleum Site [36] J. Rogers, M. Kaviany, Funicular and evaporative-front regimes in convective
Museum, http://www.qinling360.com/bingmayong/yihaokeng/ (Accessed: drying of granular beds, Int. J. Heat Mass Transf. 35 (1992) 469–480.
3rd October 2017). [37] Y.H. Yau, B.T. Chew, A.Z.A. Saifullah, A field study on thermal comfort of
[27] UNI 10829, Works of Art of Historical Importance. Ambient Conditions for the occupants and acceptable neutral temperature at the National Museum in
Conservation, Measurement and Analysis, UNI-Ente Italiano di Unificazione, Malaysia, Indoor built Environ. 22 (2013) 433–444.
Milano, 1999 (In Italian). [38] GB 50736-2012, Design Code for Heating Ventilation and Air Conditioning of
Civil Buildings, The Standardization Administration of the People’s Republic
of China (SAC), Beijing, 2012.

You might also like