Professional Documents
Culture Documents
MINISPLIT MODELS
YJCA-YJHA 07-24FS
The units comply with one or more of the following marks - see unit for details. EN 035G80001-000
SAFETY PRECAUTIONS
• Please read this installation manual carefully before starting installation of the unit.
• This air conditioning system contains refrigerant under pressure, rotating parts and electrical connection which may
be dangerous and can cause injury. Installation and maintenance of this air conditioning system should only be carried
out by trained and qualified personnel.
• After unpacking, please check the unit carefully for possible damage.
• Before undertaking any work on the unit, make sure that the power supply has been disconnected.
• Do not install the outdoor unit • Do not install the unit in wrong • Do not damage or attempt to • Do not use the air conditioner
in a place exposed regularly to direction. modify the power cord. Do not for food preservation purpose.
a strong wind. use the cord in a damaged
state or tie in a bundle.
10 cm
• Do not install the indoor unit • Do not install the indoor unit at • Do not operate the air • Do not connect the air
in a place where there is an too low position. conditioner with a wet hand. conditioner to a power supply
obstacle near the air inlet or – It may cause an electric shock. different from the specification.
outlet. – It may cause trouble or fire.
ENGLISH 3
• Do not wash the unit with • Do not place a vessel • Do not place anything under • Depending on the environment
water. containing water on the unit. the indoor or outdoor unit and local codes, an earth
which must be kept away from leakage breaker must beOFF
moisture. installed.
ON
• Do not expose plants or • Do not place a burning • Arrange the drain hose to • Do not attempt to install the air
animals directly to the airflow. appliance in a place exposed ensure smooth drainage. conditioner yourself.
to the airflow from the unit or – Incomplete drainage may cause – Consult the service shop or
under the indoor unit. wetting of the building, furniture, qualified technician. Incorrect
etc. installation will result in water
leakage, electric shock or fire. For
installation, consult the service
shop where you bought the unit or
a qualified technician.
• The air conditioner must be earthed in accordance with the local
codes.
– Incomplete earthing may result in electric shock. Do not connect the earth
line to a gas pipe, lightning rod or a telephone earth line.
PART NAMES
■ OUTDOOR UNIT AND INDOOR UNIT
Drain hose
Air outlet Display
Deflector
Drain opening
Left / Right deflector
(Manual operation)
■ DISPLAY PANEL
SLEEP TIMER
SLEEP TIMER
■ HORIZONTAL LOUVER
Hold the knob and move the deflector to change right/left airflow direction. Be careful not to adjust the deflector during
operation as the fan is rotating at a high speed and may pinch your fingers.
4 ENGLISH
Suction inch 3/8 3/8 3/8 3/8 1/2 1/2 1/2 1/2 5/8 5/8
Pipe Size
Liquid inch 1/4 1/4 1/4 1/4 1/4 1/4 1/4 1/4 3/8 3/8
EN
Technical Specifications : High wall YJCA-YJHA R22/60Hz
Indoor YJEA-YJKA
Unit 07CL 07HP 09CL 09HP 12CL 12HP 18CL 18HP 24CL 24HP
Models
Outdoor YJDA-YJJA
Unit 07CL 07HP 09CL 09HP 12CL 12HP 18CL 18HP 24CL 24HP
V/Ph/Hz 208-230/1/60
Power Supply
Ph 1 1 1 1 1 1 1 1 1 1
Power Consumption kw 0.67 0.69/0.69 0.95 0.95/0.85 1.20 1.25/1.25 1.98 1.98/1.92 2.80 2.80/2.80
Running Current A 3.1 3.06/3.06 4.3 4.3/3.8 5.6 5.6/5.6 8.6 8.6/8.3 12.5 12.5/12.5
Refrigerant Type R22
Refrigerant Charge gr 450 500 470 550 560 700 1230 1230 1750 1750
Indoor 32 32 38 38 40 40 46 46 50 50
Noise level dB(A)
Outdoor 49 49 50 50 50 51 56 56 60 60
V/Ph/Hz 208-230/1/60
Power Supply
Ph 1 1 1 1 1 1 1 1 1 1
Air flow m3/h 300 300 430 400 450 450 850 850 1000 1000
Fan
Indoor Unit
Suction inch 3/8 3/8 3/8 3/8 1/2 1/2 1/2 1/2 5/8 5/8
Pipe Size
Liquid inch 1/4 1/4 1/4 1/4 1/4 1/4 1/4 1/4 3/8 3/8
Remark: The above design and specifications are subject to change without pior notice for product improvement.
ENGLISH 5
Running Current A 0.2 0.2 0.2 0.2 0.2 0.2 0.3 0.3 0.45 0.45
Height mm 290 290 290 290 290 290 292 292 330 330
Dimension Width mm 800 800 800 800 800 800 860 860 1080 1080
Depth mm 196 196 196 196 196 196 205 205 220 220
Weight kg 10 10 10 10 10 10 12 12 15 15
System Operation Control Wireless Control with LCD Display
V/Ph/Hz 220-240/1/50
Power Supply
Ph 1 1 1 1 1 1 1 1 1 1
Qty 1 1 1 1 1 1 1 1 1 1
Compressor
Compressor Type Rotary
Outdoor Unit
Height mm 480 480 480 480 540 540 680 680 770 770
Dimension Width mm 600 600 600 600 790 790 813 813 885 885
Depth mm 250 250 250 250 245 245 310 310 365 365
Weight kg 25 26 25 26 31 33 45 47 68 70
Type Flare + Nuts
Piping
Suction inch 3/8 3/8 3/8 3/8 1/2 1/2 1/2 1/2 5/8 5/8
Pipe Size
Liquid inch 1/4 1/4 1/4 1/4 1/4 1/4 1/4 1/4 3/8 3/8
Remark: The above design and specifications are subject to change without pior notice for product improvement.
6 ENGLISH
Running Current A 0.2 0.2 0.2 0.2 0.2 0.2 0.3 0.3 0.45 0.45
Height mm 290 290 290 290 290 290 292 292 330 330
Dimension Width mm 800 800 800 800 800 800 860 860 1080 1080
Depth mm 196 196 196 196 196 196 205 205 220 220
Weight kg 10 10 10 10 10 10 12 12 15 15
System Operation Control Wireless Control with LCD Display
V/Ph/Hz 220-240/1/50
Power Supply
Ph 1 1 1 1 1 1 1 1 1 1
Qty 1 1 1 1 1 1 1 1 1 1
Compressor
Compressor Type Rotary EN
Outdoor Unit
Height mm 480 480 480 480 540 540 680 680 770 770
Dimension Width mm 600 600 600 600 790 790 813 813 885 885
Depth mm 250 250 250 250 245 245 310 310 365 365
Weight kg 25 26 25 26 35 37 49 50 68 70
Type Flare + Nuts
Piping
Suction inch 3/8 3/8 3/8 3/8 1/2 1/2 1/2 1/2 5/8 5/8
Pipe Size
Liquid inch 1/4 1/4 1/4 1/4 1/4 1/4 1/4 1/4 3/8 3/8
Remark: The above design and specifications are subject to change without pior notice for product improvement.
OPERATING TEMPERATURE
Mode
Maximum cooling Minimum cooling Maximum heating Minimum heating
Temperature
Indoor side DB/WB (°C) 32/23 21/15 27/-- 20/--
Outdoor side DB/WB (°C) 43/26 21/15 24/18 -5/-6
CAUTIONS
1. If air conditioner is used outside of the above conditions, certain safety protection features may come into operation
cause the unit to function abnormally.
2. Room relative humidity less than 80%. If the air conditioner operates in excess of this figure, the surface of the air
conditioner may attract condensation. Please sets the vertical air flow louver to its maximum angle (Vertically to the
floor), and set HIGH fan mode.
3. Optimum performance will be achieved within these operating temperature.
ENGLISH 7
132.4
146
549.5
148.4
502.7
368.6
286.3
270.4
241
146.6
86.6
149
9.4
90
124.4 115
280
310
243.2
295
256
567
135
146
136.8
541.5
689.4
55.1
349.3
269.3
152.2
346.6
93.2
75
10.1
137.5
98.5
13
85.5
107.8
540
260.1
310
298.6
330
370
Model 24
880
310
157
197.7
804.4
487.8
398.7
146.8
66 13
91.2
59
606.4
400
360
8 ENGLISH
A. B.
Check switch
(Please leave this button to be
used by the maintenance staff)
Emergency
Operation switch
ENGLISH 9
Models 07 09 12 18 24 Models 07 09 12 18 24
A 12cm 12cm 12cm 12cm 12cm A 30cm 30cm 30cm 30cm 30cm
B 70cm 70cm 70cm 70cm 70cm B 200cm 200cm 200cm 200cm 200cm
C 12cm 12cm 12cm 12cm 12cm C 60cm 60cm 60cm 60cm 60cm
D 15cm 15cm 15cm 15cm 15cm D 30cm 30cm 30cm 30cm 30cm
CAUTION
• Do not install in a place that cannot bear the weight of the unit.
10 ENGLISH
• After determining the pipe hole position. Drill the hole at Screw
Indoor unit
a slight downward slant towards the outdoor side. terminal
. .. .. .
.. .. .. ..
Note: .. .........
.
Fastener
........ ..
..... ..
. Pull the connecting cable’s Indoor unit Connecting cable
When installing .
. . .. .. wire in completely terminal
the refrigerant pipes from Indoor . .
Outdoor Connecting cable
..
others side. A hole must . .. .
. . . . ..
.. .........
Or
be place to allow fall .
.. ......... .
.
Electrical box cover
........ .. Screw
towards the outdoor unit. ..... .. .
.
Diagram
. .
.. .. .. Indoor unit
.. ..
terminal
Screw
• Make 6 mm 4-6 holes, in the wall at the four corners of mouting
plate (bracket) then insert appropriate mounting devices.
• Install the mounting plate using 4-6 pieces of mounting Fastener
screw securely at four corners and tighten the screw Pull the connecting cable’s Indoor unit Connecting cable
wire in completely terminal EN
completely. Do not over tighten the screws and deform Connecting cable
the back plate.
CAUTIONS
Model 07/12
• Never modify the unit by removing any of the safety guards
fasten string at the central hole at least 250mm
or by passing any of the safety interlock swithces.
at least 105mm at least 155mm • Connect the interconnecting cable correctly and connect
the connecting cable to terminal as identified with their
100mm
respective marking.
Center of hole Center of hole
• Do not damage the conductor core or inner insulation
(ø 65mm) plumb 120mm (ø 65mm) of power supply cables and do not deform or crush the
cables.
Model 09/18
at least 250mm
B Right
45mm
plumb Center of hole D Right
(ø 65mm) C Right F Left
CAUTIONS
• Bend pipes carefully to avoid flattening or obstructing
(ø 90mm) plumb
(ø 90mm) Pipe hole them if the pipes are bent incorrectly, the indoor unit
may be unstable on the wall.
• Carefully arrange pipes so that pipes do not stick out
• Be careful when handling the sharp edge of the mounting plate. of the rear plate of the indoor unit.
ENGLISH 11
Drain hose
Drain cap
• The drain hose can be connected to the left or the right side.
For left and left rear piping (Factory Standard)
Drain cap
Drain hose
12 ENGLISH
NOTES
• Connect the pipe correctly.
• Do not apply the excessive torque. Charging line
• Use an appropriate bending tool to form curves and avoid
over-tightening the refrigerant tubes.
• To prevent heat loss, the two lines must be insulated
separately.
Service port
ENGLISH 13
Manifold
Minimum thickness 6 mm
Gas valve
Heat pump Liquid valve
(discharge) Pressure tap
Outdoor unit Indoor unit
Gas line
Heat pump
Liquid line
Liquid
Cooling R22/R407C/R410A
Cooling
(suction)
Heat pump
GAS
Liquid
Cooling
Cooling
(suction)
OK
14 ENGLISH
To prevent flicker impressions during the start of the compressor (technical process), following installation conditions do apply.
1. The power connection for the air conditioner has to be done at the main power distribution.
The distribution has to be of a low impedance, normally the required impedance reaches at a 32 A fusing point.
2. No other equipment has to be connected with this power line.
3. For detailed installation acceptance, please refer to your contract with the power supplier if restrictions do apply for
products like washing machines, air conditioner or electrical ovens.
4. For power details of the air conditioner, refer to the rating plate of the product.
5. For any question, contact your local dealer.
CAUTIONS
• Never modify the unit by removing any of the safety guards or by bypassing any of the safety interlock swithces.
• Connect the connecting cable correctly and connect the connecting cable to terminal as identified with their respective
marks.
• Do not scratch the conductive core & inner insulator of power supply cables and do not deform or smash on the surface
of cables.
EN
■ Electrical Connections
All electrical wiring and connections must comply with local codes and standards. Power supply cord and interconnection
cord used must not be lighter than Polychloroprene sheeted cord (245 IEC 57 or H05RN-F).
Disconnecting device must have a contact separation of at least 3 mm.
Model 07-12 (Cooling only)
Power supply
220-240V/1Ph/50Hz
208-230V/1Ph/60Hz
Indoor unit N 2
Outdoor unit N 2
Indoor unit N 2
Outdoor unit N 2
ENGLISH 15
Indoor unit N L 2 3
For correct installation, a proper ground connection must be made for unit.
■ Wiring Size
Model Wiring size
7000-9000 Btu/h f 1.0 mm2
12000 Btu/h f 1.5 mm2
18000-24000 Btu/h f 2.5 mm2
NOTE
The supply voltage must be consistent with the rate voltage of the air conditioner.
T3 (°C) Starting Defrosting Mode under condition a. 2. Condition to stop defrosting: Units will switch back to
heating mode when either of the following conditions
2
is met.
1
0 5 10 15 20 25 30 35 40 45 50 Time
0
Elapsed a. Unit has been running at defrosting mode for 10
(min)
minutes.
-1
b. T3 > 20 ºC
-2
16 ENGLISH
CAUTION
Thinner
• Use a dry cloth to wipe the indoor unit and remote controller.
• A cloth dampened with cold water may be used on the indoor unit if it
is very dirty.
• The front panel of the indoor unit can be removed and cleaned with
water. Then wipe it with a dry cloth.
• Do not use a chemically treated cloth or duster to clean the unit.
• Do not use benzine, thinner, polishing powder, or similar solvents for
cleaning. These may cause the plastic surface to crack or deform.
CAUTION
• Do not touch the metal parts of the unit when removing the filter.
Injuries can occur when handling sharp metal edges.
• Do not use water to clean inside the air conditioner.
Exposure to water can destroy the insulation, leading to possible
electric shock.
• When cleaning the unit, first make sure that the power and circuit
breaker are turned off.
ENGLISH 17
6. The air conditioner turns to FAN only mode from COOL or HEAT (for cooling and heating models only)
mode.
When indoor temperature reaches the temperature setting on air conditioner, the compressor will stop automatically,
and the air conditioner turns to FAN only mode. The compressor will start again when the indoor temperature rises
on COOL mode or falls on HEAT mode (for cooling and heating models only) to the set point.
7. Dripping water may generate on the surface of the indoor unit when cooling in a high relatively humidity (relative
humidity higher than 80%). Adjust the horizontal louver to the maximum air outlet position and select HIGH fan
speed.
10. Lightning or a car wireless telephone operating nearby may cause the unit to malfunction.
Disconnect the unit with power and then re-connect the unit with power again. Push the ON/OFF button on the remote
controller to restart operation.
18 ENGLISH
ENGLISH 19
DECLARATION OF CONFORMITY
Type of Equipment Air Conditioners
Brand Name YORK
Type Designation YJEA-YJDA 07/09/12/18/24FS, YJKA-YJJA 07/09/12/18/24FS, YJEB-YJDB 07/09/12/18/24FS,
YJKB-YJJB 07/09/12/18/24FS, YJEC-YJDC 07/09/12/18/24FS, YJKC-YJJC 07/09/12/18/24FS
Application of Council EMC Directive 89/336/EEC, Low Voltage Directive 73/23/EEC and Machine Safety Directive: MSD 98/37/CE
Directive (s)
The following harmonized standards have been applied:
Standard (s)
EN 60335-1:2002+A1+A11
EN 60335-2-40:2003+A1+A12
EN 55014-1:2000+A1+A2
EN 55014-2:1997+A1
EN 61000-3-2:2000
EN 61000-3-11:2000
The product complies with the harmonized European safety standards and harmonized EMC standards listed above.
We have internal production control system that ensures compliance between the manufacturer products and the technical documentation.
The product is CE mark.
We declare under our sold responsibility that the equipment follows the provisions of the Directives stated above.
Authorized Representative:
CM Choi
Shipping Manager
Read the Manual Risk of electric shock Unit is remotely controlled and
may start without warning
1. Isolate all sources of electrical supply to the unit including any control system supplies switched by the unit. Ensure that all points of electrical and gas
isolation are secured in the OFF position. The supply cables and gas pipework may then be disconnected and removed. For points of connection refer
to unit installation instructions.
2. Remove all refrigerant from each system of the unit into a suitable container using a refrigerant reclaim or recovery unit. This refrigerant may then be
reused, if appropriate, or returned to the manufacturer for disposal. Under No circumstances should refrigerant be vented to atmosphere. Where
appropriate, drain the refrigerant oil from each system into a suitable container and dispose of according to local laws and regulations governing disposal
of oily wastes.
3. Packaged unit can generally be removed in one piece after disconnection as above. Any fixing down bolts should be removed and then unit lifted from
position using the points provided and equipment of adequate lifting capacity. Reference MUST be made to the unit installation instructions for unit weight
and correct methods of lifting. Note that any residual or spilt refrigerant oil should be mopped up and disposed of as described above.
4. After removal from position the unit parts may be disposed of according to local laws and regulations.