You are on page 1of 15

IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 29, NO.

3, MARCH 2014 1239

Step-by-Step Controller Design for LCL-Type


Grid-Connected Inverter with
Capacitor–Current-Feedback Active-Damping
Chenlei Bao, Xinbo Ruan, Senior Member, IEEE, Xuehua Wang, Member, IEEE, Weiwei Li, Student Member, IEEE,
Donghua Pan, Student Member, IEEE, and Kailei Weng

Abstract—The injected grid current regulator and active damp- in injecting high-quality power into the grid [1]. An L filter or
ing of the LCL filter are essential to the control of LCL-type grid- LCL filter is usually placed between the inverter and the grid to
connected inverters. Generally speaking, the current regulator attenuate the switching frequency harmonics produced by the
guarantees the quality of the injected grid current, and the ac-
tive damping suppresses the resonance peak caused by the LCL grid-connected inverter. Compared with L filter, LCL filter has
filter and makes it easier to stabilize the whole system. Based better attenuation of the switching frequency harmonics, which
on the proportional-integral (PI) and proportional-resonant (PR) usually yields lower volume and costs [2], [3]. However, the
compensator together with capacitor–current-feedback active- inherent resonance of the LCL filter requires proper damping
damping which are widely used for their effectiveness and simple methods to avoid the possible instability of the system [4], [5].
implementations, this paper proposes a simple step-by-step con-
troller design method for the LCL-type grid-connected inverter. By A direct way to damp the resonance of the LCL filter is intro-
carefully dealing with the interaction between the current regula- ducing a passive resistor to be in series or parallel with the filter
tor and active damping, the complete satisfactory regions of the inductors or filter capacitor, which is called passive-damping
controller parameters for meeting the system specifications are ob- method. Among which, adding a resistor in series with the fil-
tained, and from which the controller parameters can be easily ter capacitor has been widely adopted for its simplicity and
picked out. Based on these satisfactory regions, it is more conve-
nient and explicit to optimize the system performance. Besides, relatively low power loss. However, it will weaken the switch-
the insight of tuning the controller parameters from these satisfac- ing harmonic attenuation ability [5]–[8]. Adding a resistor in
tory regions is also discussed. Simulation and experimental results parallel with the filter capacitor will not impair the low-and
verify the proposed step-by-step design method. high-frequency characteristics of the LCL filter, but the power
Index Terms—Active damping, controller design, grid- loss brought by this resistor is too large to be accepted [9].
connected inverter, LCL filter, single-phase. In order to avoid the power loss resulted from the passive re-
sistor, the concept of virtual resistor was proposed in place of the
passive resistor, and the virtual resistor can be realized through
I. INTRODUCTION proper control schemes [10]. Such methods are called active-
OWADAYS, distributed power generation system (DPGS) damping methods [11], [12]. It was proved that the proportional
N based on renewable energy, such as wind energy and solar
energy, has been drawing more and more attentions, for its envi-
feedback of the filter capacitor current is equivalent to a resistor
in parallel with the filter capacitor [10]. Besides, multiple-state
ronmental friendly features. As the interface between the DPGS feedback can also be used to achieve LCL resonance damp-
and power grid, grid-connected inverter plays an important role ing, fast dynamic response, and reasonable robustness [13].
Multiple-state feedback can be formalized within general theo-
retical frameworks of state-space control by properly specified
pole placements [13]–[15], predictive control by proper dead-
beat control laws and observers [16]–[18], or h-infinity con-
Manuscript received September 13, 2012; revised November 21, 2012,
January 22, 2013, and March 24, 2013; accepted April 24, 2013. Date of current trol by solving one single optimization problem with specified
version September 18, 2013. This work was supported by the National Natural control constraints [19]–[23], etc. In this paper, the capacitor–
Science Foundation of China under Award 50837003 and Award 51007027, and current-feedback active-damping is studied due to its effective-
the National Basic Research Program of China under Award 2009CB219706.
Recommended for publication by Associate Editor S. Williamson. ness, simple implementation, and wide application [24]–[26].
C. Bao, X. Wang, W. Li, D. Pan, and K. Weng are with the State Key Labora- The capacitor–current feedback coefficient should be selected
tory of Advanced Electromagnetic Engineering and Technology, Huazhong Uni- with great caution, since a too small one cannot damp the res-
versity of Science and Technology, Wuhan 430074, China (e-mail: baochenlei@
hust.edu.cn; wang.xh@hust.edu.cn; Weiwei_Li@hust.edu.cn; pan_dh@hust. onance effectively, and a too large one may result in system
edu.cn; lswkl9331@hust.edu.cn). instability [26].
X. Ruan is with the State Key Laboratory of Advanced Electromagnetic En- Besides the system stability, high-quality injected power is
gineering and Technology, Huazhong University of Science and Technology,
Wuhan 430074, China, and also with the Aero-Power Sci-Tech Center, College another essential object in the control of the grid-connected in-
of Automation Engineering, Nanjing University of Aeronautics and Astronau- verter. Therefore, the design of the injected grid current regulator
tics, Nanjing 210016, China (e-mail: ruanxb@ hust.edu.cn). is very important. The primary goals of the injected grid current
Color versions of one or more of the figures in this paper are available online
at http://ieeexplore.ieee.org. regulator are to minimize the steady-state error, achieve the best
Digital Object Identifier 10.1109/TPEL.2013.2262378 possible dynamic performance, minimize the harmonics in the

0885-8993 © 2013 IEEE


1240 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 29, NO. 3, MARCH 2014

Fig. 1. LCL-type single-phase grid-connected inverter based on capacitor–current-feedback active-damping. (a) Schematic diagram. (b) ASM.

injected grid current, and so on [27]. Generally, these system closed-loop together with capacitor–current-feedback active-
performance and stability margin can be specified by steady- damping [26]–[31] in detail and proposes a simple step-by-
state error, crossover frequency (fc ), phase margin (PM), and step design and optimized method of the current regulator and
gain margin (GM) of the system. As a consequence, these terms capacitor–current feedback coefficient for the LCL-type grid-
will be frequently referred during the design of the current reg- connected inverter. Performance improvements over state-space
ulator and capacitor–current-feedback active-damping in this control, predictive control, h-infinity, etc., are beyond the scope
paper. of this paper and might be discussed in future work. By carefully
In recent years, the design of current regulator and capacitor– dealing with the interaction between the current regulator and
current-feedback active-damping for LCL-type grid-connected active-damping, the satisfactory regions of the controller param-
inverter has been extensively discussed. The root-locus design eters can be obtained with the given specifications of the system
method was used in [24], but the controller parameters were performance and stability margin, which reveal the boundaries
partially tuned according to the simulations and experiments. of the controller parameters and make the choices and optimiza-
Both proportional-integral (PI) and proportional-resonant (PR) tions of these parameters more convenient and explicit. This
current regulators were investigated in [28], and pole-zero can- paper is organized as follows. In Section II, the mathematical
cellation along with pole placement method was introduced. The model of the LCL-type grid-connected inverter using averaged
design procedure was complex, and the feedbacks of the capac- switch model (ASM) is derived. Based on the derived ASM, the
itor current and injected grid current (only two state variables) relationship between the controller parameters and the system
could not provide complete information of the three-order LCL loop gain is analyzed preliminarily in Section III. In Section IV,
filter to assign all the poles in the optimal positions. Therefore, a step-by-step design method of the PI injected grid current reg-
parameter adjustments were necessary to obtain an optimized ulator and capacitor–current-feedback active-damping is pre-
result. Symmetrical optimum (SO) was used to design the cur- sented in detail. In Section V, the proposed method is extended
rent regulator whereas the LCL filter was approximated to the L to design the controllers based on PI current regulator plus grid
filter, and then the capacitor–current feedback coefficient could voltage feedforward scheme, and PR current regulator, respec-
be determined easily using root-locus method [26], [29]. SO tively. In Section VI, design examples and simulation results of
mainly focused on the PM, and did not pay enough attention an LCL-type single-phase grid-connected inverter are presented.
to the specifications of steady-state error, fc , and GM. The The experimental results are presented in Section VII and the
active-damping method of capacitor–current feedback would conclusion is given in Section VIII.
deteriorate the PM to obtain sufficient GM, thus the controller
parameters designed by SO may not be good enough, some
further work was needed to obtain an optimized result. Be- II. MODELING THE LCL–TYPE SINGLE-PHASE
sides, technical optimum was also widely used in designing GRID-CONNECTED INVERTER
controller parameters especially for second-order systems, but Fig. 1(a) shows the topology and the control scheme of an
it was not convenient for designing the controller parameters of LCL-type single-phase grid-connected inverter. A typical single-
high-order systems such as LCL-type grid-connected inverters, phase voltage-source inverter (VSI) is connected to the grid
and may lead to a poor disturbance rejection system [11]. In fact, through an LCL filter, which is composed of the inverter-side
the frequency responses of the current regulator and capacitor– inductor L1 , filter capacitor C, and grid-side inductor L2 . The
current-feedback active-damping interact with each other on the equivalent series resistors of L1 , C, and L2 are relatively small
PM and GM of the system, thus the design and optimization of and ignored here. A phase-locked loop (PLL) is used to syn-
the current regulator and capacitor–current feedback coefficient chronize the reference of the injected grid current iref with the
are coupled. grid voltage vg . Hv and Hi2 are the gains of the grid voltage and
This paper analyzes the characteristics of the controller pa- injected grid current sensors, respectively. Gi (s) is the injected
rameters of PI and PR regulators for the injected grid current grid current regulator. The feedback of the filter capacitor current
BAO et al.: STEP-BY-STEP CONTROLLER DESIGN FOR L C L -TYPE GRID-CONNECTED INVERTER 1241

is adopted to damp the resonance peak caused by the LCL fil-


ter, and Hi1 is the feedback coefficient. Unipolar sinusoidal
pulsewidth modulation (SPWM) is used for the grid-connected
inverter. An outer-loop power control is usually introduced to
automatically adjust the current reference amplitude I ∗ . This is
beyond the scope of this paper and will not be discussed, and
the current reference amplitude I ∗ is directly given here.
The resonance frequency of the LCL filter fr is derived as

1 L1 + L2
fr = . (1)
2π L1 L2 C
Fig. 1(b) shows the ASM of the LCL-type grid-connected in-
verter, where Ginv is the transfer function of the inverter bridge.
The switching frequency of VSI is assumed to be sufficiently
high, thus Ginv can be approximated as Vin /Vtri , where Vin is
the dc-link voltage and Vtri is the amplitude of the triangle car-
rier wave. According to Mason’s gain formula [32], the injected
grid current ig can be derived as Fig. 2. Bode diagram of the loop gain without compensation.

1 T (s) Gg (s)
ig (s) = iref (s) − vg (s)
Hi2 1 + T (s) 1 + T (s)
Δ
= ig 1 (s) + ig 2 (s) (2)
where T (s) is the loop gain of the system and is expressed as
Hi2 Ginv Gi (s)
T (s) = (3)
s3 L1 L2 C + s2 L2 CH i1 Ginv + s (L1 + L2 )
and Gg (s) is expressed as
s2 L1 C + sCGinv Hi1 + 1
Gg (s) = . (4)
s3 L1 L2 C + s2 L2 CH i1 Ginv + s (L1 + L2 )
ig 1 is related to the injected grid current reference iref and ig 2
is related to the grid voltage vg . ig 1 and ig 2 are expressed as
1 T (s)
ig 1 (s) = iref (s) (5)
Hi2 1 + T (s)
Gg (s)
ig 2 (s) = − vg (s) . (6) Fig. 3. Bode diagram of PI and PR compensators.
1 + T (s)

III. FREQUENCY RESPONSES OF THE CURRENT REGULATOR switching frequency is 2fs ), for the sake of effective harmonics
AND CAPACITOR–CURRENT-FEEDBACK ACTIVE-DAMPING
suppression and good dynamic response. Therefore, for a prop-
erly designed LCL-type grid-connected inverter, the crossover
According to (3), the bode diagram of the uncompensated frequency fc will be lower than the resonance frequency fr , thus
loop gain is depicted in Fig. 2. As seen, introducing the feedback the influence of the filter capacitor can be ignored when calcu-
of the filter capacitor current can effectively damp the resonance lating the magnitude of the loop gain at fc and the frequencies
peak, and it only affects the magnitude of the loop gain at lower than fc , i.e., the magnitude of T (s) can be approximated
the neighbor of the resonance frequency. However, this active- as
damping method has significant impact on the phase of the  
 Hi2 Ginv Gi (s) 
loop gain and the phase decreases at the frequencies lower than |T (s)| ≈  . (7)
the resonance frequency. A larger capacitor–current feedback s (L1 + L2 ) 
coefficient leads to better damping of the resonance peak, but PI compensator is adopted as the injected grid current regu-
results in a larger negative phase shift. lator and the transfer function of Gi (s) is given by
The crossover frequency fc is typically restricted lower than
fs considering the effect of attenuating high-frequency noise, Ki
Gi (s) = Kp + . (8)
where fs is the switching frequency of the inverter [9], and the s
resonance frequency of the LCL filter fr is usually constrained According to (8), the bode diagram of PI compensator is
between 1/4 and 1/2 of the equivalent switching frequency of depicted in Fig. 3. As seen, at the frequencies around the corner
the inverter (when unipolar SPWM is adopted, the equivalent frequency fL which is expressed as fL = Ki /(2πKp ), the slope
1242 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 29, NO. 3, MARCH 2014

of the magnitude changes from −20 to 0 dB/dec, and the phase


escalates from − 90◦ up to 0◦ . To avoid the decrease of the
PM resulted from PI compensator, fL is suggested to be set
sufficiently lower than fc . Thus, the magnitude of Gi (s) can
be approximated to Kp at fc and the frequencies higher than
fc . Because the magnitude of the loop gain T (s) is unity at fc ,
substituting |Gi (s)| ≈ Kp into (7) yields

2πfc (L1 + L2 )
Kp ≈ . (9)
Hi2 Ginv

Equation (9) shows that fc is approximatively proportional


to Kp . Therefore, a larger Kp means a faster dynamic response
and a larger loop gain at low frequencies.

IV. STEP-BY-STEP DESIGN METHOD OF THE PI CURRENT


REGULATOR AND CAPACITOR–CURRENT FEEDBACK
COEFFICIENT
Fig. 4. Steady-state error with PI compensator. (a) Phasor diagrams of
A step-by-step interactive and optimized design method of the ig (1 ) , ig 1 (1 ) , ig 2 (1 ) , v g (1 ) , and ire f . (b) Variations of Ig 2 m a x E A P I and
PI injected grid current regulator and capacitor–current feedback Ig 2 m a x δ P I for given E A and δ when θ varies.
coefficient is proposed in this section with careful examinations
of the steady-state error and stability margin of the system. derived in the Appendix, and is expressed as
⎧ 

⎪ Iref

⎪ sin θ + (E +1)2
− cos 2θ
A. Requirement of Steady-State Errors ⎪
⎪ Hi2
A


The steady-state error of ig at the fundamental frequency fo is ⎨ −90◦ ≤ θ < θ
1
an important index of the controller parameters design. As given Ig 2 m ax EAPI ≈ 


⎪ I
by (2), the injected grid current ig consists of ig 1 and ig 2 . For ⎪

ref 2
sin θ − (EA − 1) − cos θ 2

⎪ Hi2
the convenience of illustration, the fundamental components of ⎪

ig , ig 1 , ig 2 , and vg are denoted by ig (1) , ig 1(1) , ig 2(1) , and vg (1) , θ1 ≤ θ ≤ 90◦
(12)
respectively. If Tf o , the magnitude of the loop gain at fo is
where θ1 = arc sin 2EA − EA2 and as no active power is ab-
sufficiently large, for instance Tf o ≥ 40 dB, then 1 + T (j2πfo )
sorbed from the grid, θ ∈ [− 90◦ , 90◦ ].
≈ T (j2πfo ). Thus, according to (5), ig 1(1) ≈ iref /Hi2 . As the
According to Fig. 4(a) and sine law, sinδ is given as
influence of the filter capacitor is negligible at fo , considering
(3), (4), and (6), ig 2(1) can be approximated as Ig 2
sin δ = |sin (90◦ + θ − δ)| . (13)
Ig 1
vg (1)
ig 2(1) ≈ − . (10) From Fig. 4(a) and (13), it is obvious that δ = 0 when θ =
Hi2 Ginv Gi (j2πfo )
±90◦ and when θ=±90◦ , the upper boundary of Ig 2 constrained
by δ, Ig 2m ax δ PI , can be expressed as
When PI compensator is adopted, Gi (j2πfo ) ≈Ki /(j2πfo ),  
so ig 2(1) ≈ −j2πfo vg (1) /(Hi2 Ginv Ki ), which means that ig 2(1) Iref  sin δ 
Ig 2 m ax δ PI ≈ . (14)
is 90◦ lagging to vg (1) . Fig. 4(a) shows the phasor diagrams of Hi2  cos (θ − δ) 
ig (1) , ig 1(1) , ig 2(1) , vg (1) , and iref , where ig 1(1) and iref are in
According to (12) and (14), the variations of Ig 2m ax EAPI
the same direction as explained earlier, and iref leads vg (1) by
and Ig 2m ax δ PI when θ varies are depicted as Fig. 4(b). As
the phase angle θ. θ is usually set according to the power flow
EA and δ should be small for a properly designed inverter, it
requirement of the system. As seen, it is ig 2(1) that makes ig (1)
is obvious that Ig 2m ax EAPI is minimum when θ ≈ ±90◦ and
away from ig 1(1) . The steady-state errors can be defined as the
Ig 2m ax δ PI is minimum when θ ≈ 0◦ . The specific requirement
amplitude error EA and the phase error δ. Referring to Fig. 4(a),
of the steady-state error can be easily simplified to the worst
the amplitude error EA can be expressed as
situation of Ig 2 , min{Ig 2m ax EAPI , Ig 2m ax δ PI }, in the range of
   
 Hi2 Ig − Iref   Hi2   θ which is concerned.
EA =    =  Ig 1 + Ig 2 − 2Ig 1 Ig 2 sin θ − 1
2 2
Considering (7) and (10), Ig 2 can be approximated as
Iref  Iref
(11) Vg Vg
Ig 2 ≈ ≈
where Iref , Ig , Ig 1 , Ig 2 , are the rms values of iref , ig (1) , ig 1(1) , Hi2 Ginv |Gi (j2πfo )| 2πfo (L1 + L2 ) |T (j2πfo )|
and ig 2(1) , respectively. As ig 1(1) ≈ iref /Hi2 , solving (11), (15)
the upper boundary of Ig 2 constrained by EA , Ig 2m ax EAPI is where Vg is the rms value of vg (1) .
BAO et al.: STEP-BY-STEP CONTROLLER DESIGN FOR L C L -TYPE GRID-CONNECTED INVERTER 1243

Equation (15) can be rewritten as into (23), yields


Vg GM 2πfc L1
Tf o = 20 log10 |T (j2πfo )| ≈ 20 log10 Hi1 = 10 20 · . (24)
2πfo (L1 + L2 ) Ig 2 Ginv
(16)
where the unit of Tf o is dB. From (16), it is found that Ig 2 C. PWM Constraint
is related to Tf o , thus the requirement of the steady-state er-
In PWM systems, the maximum rate of the change of the
ror can be further specified by the requirement of Tf o after
reference should not equal or exceed that of the carrier signal
min{Ig 2m ax EAPI , Ig 2m ax δ PI } is confirmed.
[31], [34]–[39]. For an analog system, this requirement must
be met for a fixed PWM switching frequency. In this case,
B. Controller Parameters Constrained by Steady-State Error
the current ripple of ig is small and the maximum rate of the
and Stability Margin
modulation wave mainly affects Hi1 . Therefore, the critical gain
According to (7) and (8), Tf o is expressed as of Hi1 is
 
H G Ki  4Vtri fs L1
 i2 inv Kp + j 2π f o  Hi1(m ax) = . (25)
Tf o = 20 log10 |T (j2πfo )| = 20 log10  .
 Vin
 j2πfo (L1 + L2 ) 

(17) D. Design of the PI Compensator and Capacitor–Current


Feedback Coefficient
Substituting (9) into (17) leads to
Thus, a step-by-step controller design procedure based on the

4π 2 fo (L1 + L2 ) T f o 2 examinations of the steady-state error and stability margin of
Ki = 10 2 0 fo − fc2 . (18) the system is proposed as follows:
Hi2 Ginv
Step 1) Determine the specifications of the loop gain, specifi-
According to (3), the PM of the system can be expressed as cally, Tf o by the requirement of the steady-state error,
PM by the requirements of the dynamic response and
PM = 180◦
 robustness of the system, and GM by the requirement
Hi2 Ginv Gi (s) 
+∠ 3  . of the robustness.
s L1 L2 C + s L2 CH i1 Ginv + s (L1 + L2 ) s=j 2π f c
2
As shown in Fig. 4, the steady-state errors are more
(19) remarkable in light power cases, thus Tf o can be con-
firmed by the specific situation in the standards, for
Substituting (8) into (19), leads to instance, power factor (PF) in 10% of the rated power
 2  case must be larger than 0.85 [41] or PF in half power
2πL1 fr − fc2 Ki
PM = arctan − arctan . (20) case must be larger than 0.98 [42], and Tf o can also
Hi1 Ginv fc 2πfc Kp be confirmed by requirements of customers. In gen-
Equation (20) can be rewritten as eral, PM in the range of (30◦ , 60◦ ) is adopted for good
  dynamic response and robustness, GM ≥ 3−6 dB is
2πL1 fr2 − fc2 − Ginv fc Hi1 tan PM introduced to ensure the system robust stability.
Ki = 2πfc Kp . (21)
2πL1 (fr2 − fc2 ) tan PM + Ginv fc Hi1 Step 2) Based on the above given specifications, draw the
satisfactory region of fc and Hi1 according to (22),
Substituting (9) and (18) into (21), leads to
⎛ ⎞
(24), and (25).

2
  Tfo
According to the LCL filter design methods pro-
2πL1 fr2 − fc2 ⎝fc2 − fo 10 2 0 fo − fc2 tan PM⎠ posed in [6] and [40], the specified requirements of
⎛ ⎞ the LCL filter are presented as follows: 1) L1 + L2 is
Hi1 = 
2
.
Tfo less than 0.1 pu to limit the ac voltage drop, 2) the
Ginv fc ⎝fc2 tan PM + fo 10 2 0 fo − fc2 ⎠ reactive power is less than 5% of the rated power,
3) the converter-side current ripple is less than 30%
(22) of the rms value of the injected grid current at rated
power, 4) the resonance frequency is in the range of
As seen from Fig. 2, the phase of the uncompensated loop 1/4 and 1/2 of the equivalent switching frequency; 5)
gain T (s) runs across −180◦ at fr , thus the GM of the system and the switching harmonics are less than 0.3% of
can be obtained as the fundamental current at rated power [41]. Table I
GM = −20 log10 |T (j2πfr )| (23) shows the parameters of an LCL-type single-phase
grid-connected inverter.
where the unit of GM is dB. With the above inverter parameters, the satisfac-
It should be noticed that the magnitude of the loop gain T (s) tory region of fc and Hi1 is depicted in Fig. 5. The
shown in (7) is not accurate at fr . Therefore, substituting (3), area upon the dashed line meets the requirement of
the expression of the loop gain without approximation and (9) the GM and the area under the solid line meets the
1244 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 29, NO. 3, MARCH 2014

TABLE I
SYSTEM PARAMETERS

Fig. 6. Region of fc and H i 1 according to the parameters proposed in [24].

fc in the satisfactory region is preferred and then Kp


from (9) is calculated.
Step 4) For a specific fc , calculate the lower boundary of Hi1
from (24), the upper boundaries of Hi1 from (22) and
(25), respectively. Then pick out a proper Hi1 from
this interval.
For a specific fc , a larger Hi1 leads to less PM and
thus worse dynamic response with no Tf o increased,
and thus cannot reduce the steady-state error. There-
fore, it should be pointed out that there is no need
to design a system that is overdamped or critically
damped, which may lead to a poor dynamic response.
A smaller Hi1 in the satisfactory interval which offers
Fig. 5. Region of fc and H i 1 constrained by GM, PM, and T f o when PI
compensator is adopted. enough GM is recommended.
Step 5) After fc and Hi1 have been determined, calculate the
lower and upper boundaries of Ki from (18) and (21),
requirements of the PM and Tf o . Thus, the shaded respectively, and then picked out Ki from this interval.
area between these two lines includes all the possible For a specific fc , a larger Ki leads to smaller steady-
Hi1 and fc satisfying the aforementioned specifica- state error but less PM and thus worse dynamic re-
tions of the loop gain. From Fig. 5, it can be seen sponse. Therefore, choose Ki from this interval by
that: trading OFF between the steady-state error and PM
1) when fc increases, the lower boundary of the of the system.
shaded area increases, as a larger Hi1 is needed Step 6) Check the compensated system to ensure that all the
for a larger fc to obtain the same GM; specifications are well satisfied.
2) when fc increases, the upper boundary of the
shaded area ascends first and then descends.
E. Controller Optimization and Robustness Analysis
With the increase of fc , the impact of the neg-
ative phase shift caused by the current regu- According to (21), (22), (24), and (25), when PM = 0◦ and
lator becomes less, so the upper boundary of GM = 0 dB, respectively, the critical stability boudaries of
Hi1 rises first. But when fc keeps increasing, Ki and Hi1 can be obtained. If the chosen Hi1 and Ki are
the negative phase shift caused by the active- outside these critical boudaries, the system will not have enough
damping becomes larger and the dominate fac- PM or GM to retain a stable operation. So we need to pay
tor, the upper boundary of Hi1 falls then. close attention to these critical boundaries when designing the
It is noticed that, if the confirmed specifications controller parameters.
of Tf o , PM, and GM determined in Step (1) are too And it is noticed that, the satisfactory region plotted with
strict, the satisfactory region may be very small or the proposed design method is an effective design tool not only
even does not exist. If that, return to Step (1) and to choose but also to optimize the controller parameters what-
modify the specifications and then renew Step (2). ever system parameters and design goals are. For instance, the
Step 3) Determine fc according to the satisfactory region con- satisfactory region according to the system parameters given
strained by the specifications aformentioned. in [24] is depicted in Fig. 6. In [24], in order to achieve a suf-
With the precondition of fc lower than fs /5 consid- ficiently damped frequency response at the fr of the LCL filter
ering the attenuation of high-frequency noise, a larger while maintaining an acceptable phase margin, the controller
BAO et al.: STEP-BY-STEP CONTROLLER DESIGN FOR L C L -TYPE GRID-CONNECTED INVERTER 1245

boundary of Hi1 introduced in Section IV-D, is preferred in this


situation (and the choice of Ki should tradeoff between the
steady-state response and transient response of the system).

V. EXTENSION OF THE PROPOSED DESIGN METHOD


In practical applications, in order to reduce the steady-
state error of the injected grid current for the single-phase
grid-connected inverter, PI compensator with the grid volt-
age feedforward scheme, and PR injected grid current reg-
ulator, are usually adopted. The controller design method
proposed in Section IV is extended to these cases in this
section.

A. Controller Design Based on PI Compensator With the Grid


Voltage Feedforward Scheme
PI compensator is widely used for its simplicity and effective-
Fig. 7. Variation tendencies of fc , T f o , PM, and GM when L g increases. ness, but it cannot achieve zero steady-state error of the injected
grid current for a single-phase grid-connected inverter. An ef-
fective approach to reduce the steady-state error of the injected
parameters at point A in Fig. 6 are chosen by authors based grid current is to feedforward the grid voltage [33], [43], [44]. It
on root locus. According to the proposed design method and was pointed out in [43] that, for an LCL-type single-phase grid-
Fig. 6, it is intuitive and easy to pick out a group of controller connected inverter, when the grid voltage was feedforwarded,
parameters, for instance at point B, so that the compensated sys- the component of the injected grid current ig 2 produced by the
tem has similar stability margin and a larger fc which implies grid voltage could be eliminated, thus the steady-state error was
faster transient response (although the controller parameters at effectively reduced.
point B can also be achieved by proper parameters adjustment Therefore, EA is the only steady-state error that should be
according to the design procedure proposed in [24]). considered, and the constraint of Tf o is determined by the cur-
Furthermore, with the regions of Hi1 and Ki obtained from rent reference tracking. Since ig 2 is eliminated, Ig = Ig 1 , EA
the aforementioned design procedure, once fc is determined, can be redefined as
 
the controller parameters can be further optimized according to Iref − Hi2 Ig 1  T (j2πfo ) 
EA ≈ =1−  . (26)
different requirements: Iref 1 + T (j2πfo ) 
1) a larger Ki can be chosen to get a smaller steady-state
error; As Tf o is much larger than 1, EA can be approximated as
2) a larger Hi1 can be chosen for a larger gain margin; 1 1 Tfo

3) a smaller Ki and Hi1 can be chosen for a larger phase EA ≈ ≈ = 10− 2 0 . (27)
|1 + T (j2πfo )| |T (j2πfo )|
margin.
The robustness of the system should also be respected. Al- Therefore, the minimum value of Tf o can be determined
though the specifications of the system, specifically, the PM and as 20log10 (1/EA ). Since the grid voltage feedforward scheme
GM, have considered the robustness against the variations of has no effect on the loop gain, the controller design method
the LCL filter parameters, in practical, the wide variation range proposed in Section IV can be extended to PI compensator plus
of the grid impedance which does affect the properties of the the grid voltage feedforward control strategy without any other
system must be considered [4]. As the grid-side inductor L2 is modification. The detail design procedure is not repeated here.
in series with the grid, the grid impedance Lg which is mainly
inductive can be considered as a part of L2 . It is clear that, B. Controller Design Based on PR Compensator
when Lg increases, fc and Tf o decrease and thus the impact of Compared with PI compensator, PR compensator can provide
the negative phase shift caused by the PI compensator becomes larger gain at the fundamental frequency to eliminate the steady-
larger as fc decreases, which leads to less PM. Besides, the sate error [27], [30], [31]. A practical transfer function of PR
increased Lg leads to larger GM. The variation tendencies of compensator is given by
system specifications, i.e., fc , Tf o , PM, and GM, in front of Lg
2Kr ωi s
variation are depicted in Fig. 7. Gi (s) = Kp + (28)
As fc , Tf o , and PM all decrease when Lg increases, the s2 + 2ωi s + ωo2
steady-state and transient responses of the system will be in- where ωo = 2πfo and ωi is the bandwidth of the resonant part
evitably worse. In order to obtain a better system performance concerning −3 dB cutoff frequency to reduce the sensitivity of
in front of Lg variation, a larger Kp which leads to larger fc the compensator to variations at the fundamental frequency,
and Tf o , and a smaller Hi1 which leads to larger PM are wel- which means √the gain of the resonant part of PR compen-
comed. Therefore, choosing the upper boundary of Kp and lower sator is Kr 2 at ωo ± ωi . For small PV power stations, the
1246 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 29, NO. 3, MARCH 2014

Fig. 9. Region of fc and H i 1 constrained by GM, PM, and T f o with PR


compensator.


where θ2 = arc cos 2EA − EA2 , Ig 2m ax EAPR , and
Fig. 8. Steady-state error with PR compensator. (a) Phasor diagrams Ig 2m ax δ PR are the upper boundaries of Ig 2 constrained
of ig (1 ) , ig 1 (1 ) , ig 2 (1 ) , v g (1 ) , and ire f . (b) Variations of Ig 2 m a x E A P R , by EA and δ, respectively, and δ = 0 when θ = 0◦ .
Ig 2 m a x δ P R for given E A and δ when θ varies. According to (29), the variations of Ig 2m ax EAPR and
Ig 2m ax δ PR when θ varies are depicted as Fig. 8(b). As EA
and δ should be small for a properly designed inverter, as seen,
grid-connected inverters are required to work normally when Ig 2m ax EAPR is minimum when θ ≈ 0◦ and Ig 2m ax δ PR is min-
the fundamental frequency of the grid fluctuates between 49.5 imum when θ ≈ ± 90◦ . Thus, when PR compensator is used,
and 50.2 Hz [42]. The corresponding maximum frequency fluc- the specific requirement of the steady-state error can be sim-
tuation Δf = 0.5 Hz. Therefore, ωi = 2πΔf = π rad/s is set to plified to the requirement of min{Ig 2m ax EAPR , Ig 2m ax δ PR },
attain enough gain in the entire working frequency range. and then this requirement can also be further specified by the
According to (28), the bode diagram of PR compensator is requirement of Tf o according to (16).
depicted in Fig. 3. PR compensator can provide large gain at As
√the gain of the resonant√ part of the PR compensator is
fo , but it also introduces negative phase shift at the frequencies Kr 2 at fo ± Δf , thus 2 times of the gain in magnitude
higher than the selected frequency, especially at the frequen- at fo are required to ensure enough magnitude of the loop gain
cies close to the selected resonance frequency, which damages when the fundamental frequency fluctuates between fo ± Δf .
the PM of the system. To avoid this side effect, the crossover Therefore, considering (7), (9), and (28), Kr can be derived as

frequency fc is suggested to be set far away from the selected √ Tfo 2π (L1 + L2 )
resonance frequency [4]. Therefore, PR compensator can be ap- Kr = 210 2 0 fo − fc . (30)
Hi2 Ginv
proximated to Kp in magnitude at fc and the frequencies higher
than fc , which is similar to PI compensator. Thus, (9), (24), and According to (19) and (28), the PM can be rewritten as
(25) are still reasonable, that is to say, Kp can be expressed as  
2πL1 fr2 − fc2 Kr ω i
the function of fc given by (9), and Hi1 is constrained by the PM = arctan − arctan (31)
Hi1 Ginv fc πfc Kp
functions of GM given by (24), and PWM constraint given by
(25). where Gi (s) is approximated as Kp + 2Kr ωi /s at fc , for fc is
Different from the case that PI compensator is used, refer- much larger than fo and ωi /π.
ring to (28) Gi (j2πfo ) = Kp + Kr when PR compensator is According to (31), Kr can also be expressed as
adopted, so ig 2(1) ≈ −vg (1) /[Hi2 Ginv (Kp + Kr )] according  
πfc Kp 2πL1 fr2 − fc2 − Hi1 Ginv fc tan PM
to (10). Therefore, ig 2(1) is about 180◦ lagging behind vg (1) , Kr = . (32)
as shown in Fig. 8(a). Similar to the derivation depicted in ωi Hi1 Ginv fc + 2πL1 (fr2 − fc2 ) tan PM
Section IV-A, referring to Fig. 8(a) the upper boundaries of Ig 2 Substituting (9) and (30) into (32) leads to the expression of
can be derived as Hi1 , given by

⎧I 
  2 Tfo

⎪ ref 2 2πL1 fr2 − fc2 πfc − 210 2 0 fo − fc ωi tan PM



⎪ cos θ + (EA + 1) − sin θ 2
Hi1 = √ .

⎪ Hi2 Ginv fc Tfo


⎨ −90◦ ≤ θ < −θ2 , θ2 < θ ≤ 90◦
210 2 0 f − f ω + πf 2 tan PM
o c i c
Ig 2 m ax EAPR ≈ 
(29a) (33)

⎪ Iref

⎪ cos θ − (E − 1) 2
− sin 2θ Based on (24), (25), and (33), the possible Hi1 and fc that

⎪ Hi2
A

⎩ satisfy the specifications of Tf o , GM, and PM are included in
−θ2 ≤ θ ≤ θ2 the shaded area depicted in Fig. 9. It is noticed that the charac-
 
Iref  sin δ  teristics of the controller parameters based on PR compensator
Ig 2 ≈ (29b)
Hi2  sin (θ + δ) 
δ PR are almost the same as that based on PI compensator, except Ki
BAO et al.: STEP-BY-STEP CONTROLLER DESIGN FOR L C L -TYPE GRID-CONNECTED INVERTER 1247

5.6 dB, and the gain in magnitude at the fundamental frequency


is 54.4 dB. It is obvious that all the specifications are satisfied
as expected.
To examine the robustness of the system, the bode diagrams of
the compensated loop gain considering the variations of the LCL
filter parameters are given in Fig. 11. The grid impedance Lg is
considered as a part of L2 . It is found that, although C varies
from 8 to 12 μF (10 μF ± 20%), L1 varies from 480 to 720 μH
(600 μH ± 20%), or L2 varies from 100 to 600 μH (150 μH
– 30% + 300%, considering the effect of the grid impedance),
the lowest crossover frequency is still higher than 1.3 kHz, the
PM is larger than 24◦ , the GM is larger than 5 dB, and the
gain in magnitude at the fundamental frequency is larger than
51 dB. All of these results verify that the designed system has
a strong robustness, which is in accordance with the analysis in
Section IV-E.
Fig. 12 shows the simulation results with the controller param-
Fig. 10. Bode diagram of the compensated system with PI compensator. eters designed above. Fig. 12(a) shows the steady-state wave-
form of the compensated system at full load, the power factor
is replaced by Kr . Therefore, the design procedure proposed in is 0.997, and the fundamental rms value of ig is 27.38 A (the
Section IV-D can be extended to this case, except (18), (21), (22) reference value is 27.27 A), thus the amplitude error is 0.4%.
are replaced by (30), (32), (33), respectively, and the optimized Fig. 12(b) shows the transient response of the compensated
design of the controller parameters and analysis of system ro- system. As the current regulator may be saturated when the ref-
bustness proposed in Section IV-E are also applicable in the PR erence value iref steps up from half load to full load, here the
case. transient response of the inverter when iref steps down from full
load to half load is measured, the percentage overshoot (PO) of
ig [σ/Istep in Fig. 12(b)] is 45.2%, and the settling time is about
VI. DESIGN EXAMPLE AND SIMULATION RESULTS 1.2 ms.
A design example of the PI injected grid current regu- With the same system parameters given in Table I, when PR
lator and capacitor–current-feedback active-damping for an compensator is adopted, the specifications of the loop gain are
LCL-type single-phase grid-connected inverter is presented in given as follows: Tf o ≥ 75 dB ensuring the amplitude error less
this section. The key parameters of the inverter are given in than 1% at the rated power (Ig 2m ax EAPR is minimum when
Table I. θ = 0◦ , and the PFs constrained by [41], [42] are easy to be
First, the specifications of the loop gain are given as follows: satisfied), and PM ≥ 45◦ , GM ≥ 5 dB. With the assistance
PM ≥ 45◦ and GM ≥ 5 dB, which ensure good dynamic perfor- of the satisfactory parameter region depicted in Fig. 9, the PR
mance and enough stability margin; Tf o ≥ 52 dB, which ensures compensator and capacitor–current feedback coefficient can be
PF greater than 0.98 when the output power of the inverter is easily chosen as Kp = 0.45, Kr = 350, Hi1 = 0.12. The bode
larger than 50% of the rated power [42], so the corresponding diagram of the compensated loop gain is depicted in Fig. 13.
PF is greater than 0.994 and amplitude error is less than 0.5% Fig. 14 shows the simulation results of the compensated system,
at the rated power. the power factor is 1.0, the fundamental rms value of ig is 27.2 A,
Then the satisfactory region of Hi1 and fc constrained by the amplitude error is 0.3%, and PO is 45%, the settling time
the aforementioned specifications is calculate according to (22), is about 1.2 ms. The design and simulation results verify the
(24), and (25), as depicted in Fig. 5. Based on this satisfactory effectiveness of the proposed simple frequency-based design
region, the crossover frequency fc is set at 2 kHz (1/5 switching method.
frequency of the inverter) here to ensure that the system has
fast dynamic response and good ability of attenuating high-
VII. EXPERIMENTAL RESULTS
frequency noise. After that, Kp = 0.45 is calculated from (9).
Substituting fc = 2 kHz into (22), (24) and (25), the possible A 6-kW prototype has been constructed in the lab to verify
interval of Hi1 , which is (0.114, 0.165), can be obtained. To get the analysis given above and the effectiveness of the proposed
larger phase margin, Hi1 = 0.12 is chosen. Substituting fc = step-by-step design method. The parameters of the prototype are
2 kHz and Hi1 = 0.12 into (18) and (21), the possible interval listed in Table I. A galvanic isolated transformer is placed be-
of Ki , which is (1657, 2205), can be obtained. By trading off tween the single-phase grid-connected inverter and the grid, and
between the steady-state error and phase margin, Ki = 2200 is the leakage inductor of the transformer is included in L2 . The
chosen to get better steady-state response. grid-connected inverter is implemented using two insulated gate
Afterward, the bode diagram of the loop gain with compen- bipolar transistor modules (CM100DY- 24NF). These modules
sation is depicted in Fig. 10, the crossover frequency of the are driven by M57962L. The grid voltage is sensed by a hall
compensated loop gain is 2.05 kHz, the PM is 45◦ , the GM is voltage transducer (LV25-P) for the PLL. The filter capacitor
1248 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 29, NO. 3, MARCH 2014

Fig. 11. Bode diagrams of system considering the variations of the LCL filter parameters. (a) C varies from 8 to 12 μF (10 μF ± 20%). (b) L 1 varies from 480
to 720 μH (600 μH ± 20%). (c) L 2 varies from 100 to 600 μH (150 μH – 30% + 300%).

Fig. 12. Simulation results (H i 1 = 0.12, K p = 0.45, K i = 2200). (a) Steady-state response. (b) When the reference of ig jumps between half and full load.

Fig. 13. Bode diagram of the compensated system with PR compensator.

current and injected grid current are sensed by two hall current
transducers (LA55-P). TL074 is used to implement both PI and Fig. 14. Simulation results (H i 1 = 0.12, K p = 0.45, K r = 350). (a) Steady-
PR compensators, ICL8038 is used to generate the analog tri- state response. (b) When the reference of ig jumps between half and full load.
angle carrier wave, and LM311 is used to compare the carrier
and modulation waves.
Fig. 15 shows the experimental waveforms when PI compen- shows the experimental waveform at full load, the measured
sator is used as the injected grid current regulator. Fig. 15(a) power factor is 0.995, and the fundamental rms value of ig is
BAO et al.: STEP-BY-STEP CONTROLLER DESIGN FOR L C L -TYPE GRID-CONNECTED INVERTER 1249

Fig. 15. Experimental waveforms with PI compensator (H i 1 = 0.12, K p = 0.45, K i = 2200) when PFs of the system are set to (a) 1.0 and (b) its corresponding
spectrum of v g and ig , (c) 0.8 (capacitive), (d) 0 (capacitive), (e) 0.8 (inductive), and (f) 0 (inductive), respectively. (g) Injected grid current reference jumps
between half and full load with PF set to 1.0.

TABLE II waveform when the reference value of the injected grid current
STEADY-STATE ERRORS OF THE EXPERIMENT RESULTS
step changes between half load and full load. The measured PO
of ig [σ/Istep in Fig. 15(g)] is 38% and the settling time is about
1.5 ms.
Fig. 16 shows the experimental waveforms when PR com-
pensator is used as the injected grid current regulator. Fig. 16(a)
shows the experimental waveform at full load, the measured
power factor is 0.999, the fundamental rms value of ig is 27.1 A,
the amplitude error is 0.6%. Figs. 16(b)–(e) show the experi-
mental waveforms at full load when the PFs of the reference
are nonunity, the steady-state errors are listed in Table II. From
Fig. 16(f), the measured PO of ig [σ/Istep in Fig. 16(f)] is 38%,
and the settling time is about 1.5 ms. Compared with the exper-
imental waveforms when PI compensator is used, the system
with PR compensator has similar responses except the ampli-
27.13 A, the amplitude error is 0.5%. Fig. 15(b) shows the spec- tude errors are much smaller especially when the PFs of the
tra of vg and ig . Because of the dead-time effect, ig contains reference decrease.
harmonics at fs , and the frequencies nearby, but the switching Because of the measurement error, and the effect of the
harmonics are all less than 0.3% of the fundamental current dead time, parasitic parameters, grid voltage distortion, etc.,
at rated power. The attenuation of switching harmonics satis- the steady-state errors of the experiment results are a bit larger
fies the specified requirements of the LCL filter. Figs. 15(c)–(f) than the simulation results and the transient responses are better
show the experimental waveforms at full load when the PFs of than the simulation results. All the experiment waveforms verify
the system are set to 0.8 (capacitive), 0 (capacitive), 0.8 (in- the effectiveness of the proposed design method.
ductive), and 0 (inductive), respectively, and the steady-state Taking PI compensator for instance, Fig. 17 shows the di-
errors are listed in Table II. Fig. 15(g) shows the experimental agrams of the measured amplitude error, power factor, and
1250 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 29, NO. 3, MARCH 2014

Fig. 16. Experimental waveforms with PR compensator (H i 1 = 0.12, K p = 0.45, K r = 350) when PFs of the system are set to (a) 1.0, (b) 0.8 (capacitive),
(c) 0 (capacitive), (d) 0.8(inductive), and (e) 0 (inductive), respectively. (f) Injected grid current reference jumps between half and full load with PF set to 1.0.

Fig. 17. Amplitude error, power factor, and percentage overshoot of ig when
H i 1 varies (K p = 0.45, K i = 2200).

percentage overshoot of ig at rated power when Hi1 varies.


When Hi1 increases from 0.1 to 0.2, the experimentally mea-
sured PO increases from 34% to 50%, the amplitude error keeps
0.5%, and the power factor keeps 0.995. It is obvious that,
increasing Hi1 has no improvement in steady-state error, but
it reduces the PM and thus increases the percentage overshoot.
Fig. 18. Oscillation of experimental results at full load (H i 1 = 0.016, K p =
Fig. 18 shows the experimental waveforms when Hi1 is reduced 0.45, K i = 2200). (a) Experimental waveform. (b) Spectra of v g and ig .
to 0.016, from which it can be seen that there is resonance os-
cillation at the frequency near fr in the output current. This
means that a too small Hi1 will result in resonance oscillation increases from 0.935 to 0.996, and the percentage overshoot
and even instability of the system. The experimental results are increases from 11% to 41%. There is significant improvement
in accordance with the analysis in Section IV that a small Hi1 in in the steady-state error when Ki increases, but the PM decreases
the satisfactory region will lead to good dynamic performance and the percentage overshoot increases as well. However, a too
with no impact on the steady-state response, and Hi1 outside large Ki leads to resonance oscillation of the output current at
the stability boundary cannot be tolerated. the frequency near the bandwidth frequency or even unstable
Fig. 19 shows the diagram of the measured amplitude error, response, as shown in Fig. 20. The results are in accordance
power factor, and percentage overshoot of ig at rated power when with the analysis of Ki in Section IV and the appropriate Ki
Ki increases from 600 to 2600. It can be seen that the measured could be picked out from the satisfactory interval by trading off
amplitude error decreases from 5.8% to 0.5%, the power factor between the steady-state error and the PM of the system.
BAO et al.: STEP-BY-STEP CONTROLLER DESIGN FOR L C L -TYPE GRID-CONNECTED INVERTER 1251

gin, and steady-state error, are calculated and drawn to assist in


determining and optimizing the controller parameters. Thus the
compensated system can satisfy all the aforementioned speci-
fications. Experimental results of a 6-kW prototype verify the
effectiveness of the proposed design method and validity of the
analysis. This idea has been investigated based on PI current
regulator in detail, and extended to the controller design based
on PI current regulator plus grid voltage feedforward scheme,
PR current regulator, and also can be applied to the controller
design of LCL-type three-phase grid-connected inverters. It is
hoped that this work will offer a useful reference for engineers
to design the controller parameters of LCL-type grid-connected
inverters.
Fig. 19. Amplitude error, power factor, and percentage overshoot of ig when
K i varies (H i 1 = 0.12, K p = 0.45).
APPENDIX
The upper boundary of Ig 2 constrained by EA when PI com-
pensator is used, Ig 2m ax EAPI , is derived in this Appendix. For
a properly designed inverter, Ig 2 is small and EA
1, thus (11)
can be rewritten as
Hi2  2
±EA = Ig 1 + Ig22 − 2Ig 1 Ig 2 sin θ − 1. (A.1)
Iref
As ig 1(1) ≈ iref /Hi2 thus Ig 1 ≈ Iref /Hi2 , solving (A.1), the
roots of Ig 2 can be expressed as


Iref
Ig 2 r t1 = sin θ + sin2 θ − 2EA + EA2
Hi2


Iref
Ig 2 r t2 = sin θ − sin2 θ − 2EA + EA2
Hi2


Iref 2 2
Ig 2 r t3 = sin θ + sin θ + 2EA + EA
Hi2


Iref
Ig 2 r t4 = sin θ − sin2 θ + 2EA + EA2 . (A.2)
Hi2
As Ig 2 ≥ 0 and Ig 2 r t4 < 0, the root Ig 2 r t4 is invalid.
If −90◦ ≤ θ ≤ − θ1 where θ1 = arc sin 2EA − EA2 , both
Ig 2 r t1 and Ig 2 r t2 are negative and invalid and Ig 2m ax EAPI is
Fig. 20. Oscillation of experimental results at full load (H i 1 = 0.12, K p =
0.45, K i = 7400). (a) Experimental waveform. (b) Spectra of v g and ig . given as
Ig 2 m ax EAPI = Ig 2 r t3


VIII. CONCLUSION Iref


= sin θ + sin2 θ + 2EA + EA2 . (A.3)
This paper has studied the characteristics and design method Hi2
of the injected grid current regulator and capacitor–current-
If −θ1 < θ < θ1 , sin2 θ − 2EA + EA2 < 0, and Ig 2 r t1 and
feedback active-damping for the LCL-type grid-connected in-
Ig 2 r t2 are inexistent, Ig 2m ax EAPI is given as
verter. The relationship between the controller parameters and


the system loop gain has been investigated: 1) active-damping Iref


Ig 2 m ax EAPI = Ig 2 r t3 = sin θ + sin2 θ + 2EA + EA
2 .
method based on the feedback of the filter capacitor current can Hi2
damp the resonance peak caused by the LCL filter effectively, (A.4)
but it impairs the PM of the system; 2) the injected grid current
regulator determines the crossover frequency and steady-state Else if θ1 ≤ θ ≤ −90◦ , Ig 2 r t1 , Ig 2 r t2 , and Ig 2 r t3 are all
error of the system, but the negative phase shift of the regulator valid. Choose the smallest root as Ig 2m ax EAPI , given as
impairs the phase margin. A proper simple step-by-step inter- 

Iref
active and optimized controller design method is proposed in Ig 2 m ax EAPI = Ig 2 r t2 = sin θ − sin θ − 2EA + EA .
2 2
this paper. The satisfactory regions of the controller parameters Hi2
constrained by the specifications of the phase margin, gain mar- (A.5)
1252 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 29, NO. 3, MARCH 2014

Therefore, Ig 2m ax EAPI can be expressed as [18] K. J. Lee, B. G. Park, R. Y. Kim, and D. S. Hyun, “Robust predictive
current controller based on a disturbance estimator in a three-phase grid-
⎧ 
connected inverter,” IEEE Trans. Power Electron., vol. 27, no. 1, pp. 276–
⎪ Iref

⎪ sin θ + (E +1) 2
− cos 2θ 283, Jan. 2012.

⎪ Hi2
A [19] J. C. Doyle, K. Glover, P. P. Khargonekar, and B. A. Francis, “State-space


⎨ −90◦ ≤ θ < θ solutions to standard H2 and H∞ control problems,” IEEE Trans. Autom.
1 Control, vol. 34, no. 8, pp. 831–847, Aug. 1989.
Ig 2 m ax EAPI ≈ 


⎪ I [20] G. Willmann, D. F. Coutinho, L. F. A. Pereira, and F. B. Lı́bano,


ref
sin θ − (E − 1) 2
− cos 2θ “Multiple-loop h-infinity control design for uninterruptible power sup-

⎪ Hi2
A


plies,” IEEE Trans. Ind. Electron., vol. 54, no. 3, pp. 1591–1602, Jun.
2007.
θ1 ≤ θ ≤ 90◦ . [21] T. Hornik and Q. Zhong, “A current-control strategy for voltage-source
(A.6) inverters in microgrids based on H∞ and repetitive control,” IEEE Trans.
Power Electron., vol. 26, no. 3, pp. 943–952, Mar. 2011.
[22] S. Yang, Q. Lei, F. Z. Peng, and Z. Qian, “A robust control scheme for grid-
REFERENCES connected voltage-source inverters,” IEEE Trans. Ind. Electron., vol. 58,
no. 1, pp. 202–212, Jan. 2011.
[1] F. Blaabjerg, R. Teodorescu, M. Liserre, and A. Timbus, “Overview of [23] Q. Zhong and T. Hornik, “Cascaded current-voltage control to improve
control and grid synchronization for distributed power generation sys- the power quality for a grid-connected inverter with a local load,” IEEE
tems,” IEEE Trans. Ind. Electron., vol. 53, no. 5, pp. 1398–1409, Oct. Trans. Ind. Electron., vol. 58, no. 1, pp. 202–212, Jan. 2011.
2006. [24] E. Twining and D. G. Holmes, “Grid current regulation of a three-phase
[2] M. Lindgren and J. Svensson, “Control of a voltage-source converter voltage source inverter with an LCL input filter,” IEEE Trans. Power
connected to the grid through an LCL-filter-application to active filtering,” Electron., vol. 18, no. 3, pp. 888–895, May 2003.
in Proc. IEEE Power Electron. Spec. Conf., 1998, pp. 229–235. [25] Y. A.-R. I. Mohamed, “Suppression of low- and high-frequency insta-
[3] A. Hava, T. Lipo, and W. L. Erdman, “Utility interface issues for line bilities and grid-induced disturbances in distributed generation invert-
connected PWM voltage source converters: A comparative study,” in ers,” IEEE Trans. Power Electron., vol. 26, no. 12, pp. 3790–3803, Dec.
Proc. IEEE Appl. Power Electron. Conf., 1995, pp. 125–132. 2011.
[4] M. Liserre, R. Teodorescu, and F. Blaabjerg, “Stability of photovoltaic and [26] J. Dannehl, F. W. Fuchs, S. Hansen, and P. B. Thgersen, “Investigation of
wind turbine grid-connected inverters for a large set of grid impedance active damping approaches for PI-based current control of grid-connected
values,” IEEE Trans. Power Electron., vol. 21, no. 1, pp. 263–272, Jan. pulse width modulation converters with LCL filters,” IEEE Trans. Ind.
2006. Appl., vol. 46, no. 4, pp. 1509–1517, Jul./Aug. 2010.
[5] M. Liserre, A. Dell’Aquila, and F. Blaabjerg, “Stability improvements [27] D. G. Holmes, T. A. Lipo, B. P. Mcgrath, and W. Y. Kong, “Optimized
of an LCL-filter based three-phase active rectifier,” in Proc. IEEE Power design of stationary frame three phase AC current regulators,” IEEE Trans.
Electron. Spec. Conf., 2002, pp. 1195–1201. Power Electron., vol. 24, no. 11, pp. 2417–2426, Nov. 2009.
[6] M. Liserre, F. Blaabjerg, and S. Hansen, “Design and control of an LCL- [28] F. Liu, Y. Zhou, S. Duan, J. Yin, B. Liu, and F. Liu, “Parameter design of a
filter-based three-phase active rectifier,” IEEE Trans. Ind. Appl., vol. 41, two-current-loop controller used in a grid-connected inverter system with
no. 5, pp. 1281–1291, Sep./Oct. 2005. LCL filter,” IEEE Trans. Ind. Electron., vol. 56, no. 11, pp. 4483–4491,
[7] R. Peña-Alzola, M. Liserre, F. Blaabjerg, R. Sebastián, J. Dannehl, and Nov. 2009.
F. W. Fuchs, “Analysis of the passive damping losses in LCL-filter-based [29] J. Dannehl, C. Wessels, and F. W. Fuchs, “Limitations of voltage-oriented
grid converters,” IEEE Trans. Power Electron., vol. 28, no. 6, pp. 2642– PI current control of grid-connected PWM rectifiers with LCL filters,”
2646, Jun. 2013. IEEE Trans. Ind. Electron., vol. 56, no. 2, pp. 380–388, Feb. 2009.
[8] T. Wang, Z. Ye, G. Sinha, and X. Yuan, “Output filter design for a grid- [30] G. Shen, X. Zhu, J. Zhang, and D. Xu, “A new feedback method for PR
interconnected three-phase inverter,” in Proc. IEEE Power Electron. Spec. current control of LCL-filter-based grid-connected inverter,” IEEE Trans.
Conf., 2003, pp. 779–784. Ind. Electron., vol. 57, no. 6, pp. 2033–2041, Jun. 2010.
[9] R. W. Erickson and D. Maksimovic, Fundamentals of Power Electronics, [31] D. N. Zmood and D. G. Holmes, “Stationary frame current regulation of
2nd ed. Norwell, MA, USA: Kluwer, 2001, pp. 331–408. PWM inverters with zero steady-state error,” IEEE Trans. Power Electron.,
[10] P. A. Dahono, Y. R. Bahar, Y. Sato, and T. Kataoka, “Damping of transient vol. 18, no. 3, pp. 814–822, May 2003.
oscillations on the output LC filter of PWM inverters by using a virtual [32] D. Younger, “A simple derivation of Mason’s gain formula,” Proc. IEEE,
resistor,” in Proc. IEEE Int. Conf. Power Electron. Drive Syst., 2001, vol. 51, no. 7, pp. 1043–1044, Jul. 1963.
pp. 403–407. [33] T. Abeyasekera, C. Johnson, D. Atkinson, and M. Armstrong, “Suppres-
[11] V. Blasko and V. Kaura, “A novel control to actively damp resonance in sion of line voltage related distortion in current controlled grid connected
input LC filter of a three-phase voltage source converter,” IEEE Trans. inverters,” IEEE Trans. Power Electron., vol. 20, no. 6, pp. 1393–1401,
Ind. Appl., vol. 33, no. 2, pp. 542–550, Mar./Apr. 1997. Nov. 2005.
[12] J. Dannehl, M. Liserre, and F. W Fuchs, “Filter-based active damping of [34] N. R. Zargari and G. Joos, “Performance investigation of a current-
voltage source converters with LCL-filter,” IEEE Trans. Ind. Electron., controlled voltage-regulated PWM rectifier in rotating and stationary
vol. 58, no. 8, pp. 3623–3633, Aug. 2011. frames,” IEEE Trans. Ind. Electron., vol. 42, no. 4, pp. 396–401, Aug.
[13] J. Dannehl, F. W. Fuchs, and P. B. Thøgersen, “PI state space current 1995.
control of grid-connected PWM converters with LCL filters,” IEEE Trans. [35] M. P. Kazmierkowski and L. Malesani, “Current control techniques for
Power Electron., vol. 25, no. 9, pp. 2320–2330, Sep. 2010. three-phase voltage-source PWM converters: a survey,” IEEE Trans. Ind.
[14] E. Wu and P. Lehn, “Digital current control of a voltage source converter Electron., vol. 45, no. 5, pp. 691–703, Oct. 1998.
with active damping of LCL resonance,” IEEE Trans. Power Electron., [36] D. N. Zmood, “A systematic development of improved linear regula-
vol. 21, no. 5, pp. 1364–1373, Sep. 2006. tors for sinusoidal power converters,” Ph. D. dissertationthesis, Dept.
[15] I. J. Gabe, V. F. Montagner, and H. Pinheiro, “Design and implementation Elect. Comput. Syst. Eng., Monash University, Victoria, Australia,
of a robust current controller for VSI connected to the grid through an 2002.
LCL filter,” IEEE Trans. Power Electron., vol. 24, no. 6, pp. 1444–1452, [37] M. P. Kazmierkowski, F. Blaabjerg, and R. Krishnan, Control in Power
Jun. 2009. Electronics—Selected Problems. New York, NY, USA: Academic,
[16] K. H. Ahmed, A. M. Massoud, S. J. Finney, and B. W. Williams, “A mod- 2002.
ified stationary reference frame-based predictive current control with zero [38] S. Buso and P. Mattavelli, Digital Control in Power Electronics. Ft. Collins,
steady-state error for LCL coupled inverter-based distributed generation Colorado, USA: Morgan & Claypool, 2006.
systems,” IEEE Trans. Ind. Electron., vol. 58, no. 4, pp. 1359–1370, Apr. [39] F. O. Martinz, R. D. Miranda, W. Komatsu, and L. Matakas, “Gain limits
2011. for current loop controllers of single and three-phase PWM converters,”
[17] J. M. Espı́, J. Castelló, R. Garcı́a-Gil, G. Garcerá, and E. Figueres, “An in Proc. IEEE Int. Power Electron. Conf., 2010, pp. 201–208.
adaptive robust predictive current control for three-phase grid-connected [40] K. Jalili and S. Bernet, “Design of LCL filters of active-front-end two-level
inverters,” IEEE Trans. Ind. Electron., vol. 58, no. 8, pp. 3537–3546, Aug. voltage-source converters,” IEEE Trans. Ind. Electron., vol. 56, no. 5,
2011. pp. 1674–1689, May 2009.
BAO et al.: STEP-BY-STEP CONTROLLER DESIGN FOR L C L -TYPE GRID-CONNECTED INVERTER 1253

[41] IEEE Recommended Practice for Utility Interface of Photovoltaic (PV) Xuehua Wang (M’12) was born in Hubei Province,
Systems, IEEE Std. 929–2000, Jan. 2000. China, in 1978. He received the B.S. degree in elec-
[42] Technical Rule for Photovoltaic Power Station Connected to Power Grid, trical engineering from Nanjing University of Tech-
Q/GDW 617–2011, May 2011, (in Chinese). nology, Nanjing, China, in 2001, and the M.S. and
[43] X. Wang, X. Ruan, S. Liu, and C. K. Tse, “Full feed-forward of grid Ph.D. degrees in electrical engineering from Nanjing
voltage for grid-connected inverter with LCL filter to suppress current University of Aeronautics and Astronautics, Nanjing,
distortion due to grid voltage harmonics,” IEEE Trans. Power Electron., China, in 2004 and 2008, respectively.
vol. 25, no. 12, pp. 3119–3127, Dec. 2010. He is currently a Lecturer in the College of Electri-
[44] M. Xue, Y. Zhang, Y. Kang, Y. Yi, S. Li, and F. Liu, “Full feedforward of cal and Electronic Engineering, Huazhong University
grid voltage for discrete state feedback controlled grid-connected inverter of Science and Technology, Wuhan, China. His main
with LCL filter,” IEEE Trans. Power Electron., vol. 27, no. 10, pp. 4234– research interests include multilevel inverter and re-
4247, Oct. 2012. newable energy generation system.

Chenlei Bao was born in Zhejiang Province, China,


in 1987. He received the B.S. degree from the
School of Electrical Engineering and Automation
from Harbin Institute of Technology, Harbin, China,
in 2010, and the M.S. degree in electrical and elec- Weiwei Li (S’12) was born in Henan Province, China,
tronic engineering from Huazhong University of Sci- in 1987. He received the B.S. degree in electrical
ence and Technology, Wuhan, China, in 2013. and electronic engineering from Huazhong Univer-
His current research interests include digital sity of Science and Technology, Wuhan, China, in
control technique and renewable energy generation 2009, where he is currently working toward the Ph.D.
system. degree.
His current research interests include digital
control technique and renewable energy generation
system.

Xinbo Ruan (M’97–SM’02) was born in Hubei


Province, China, in 1970. He received the B.S. and
Ph.D. degrees in electrical engineering from Nanjing
University of Aeronautics and Astronautics (NUAA),
Nanjing, China, in 1991 and 1996, respectively.
In 1996, he joined the Faculty of Electrical En-
gineering Teaching and Research Division, NUAA, Donghua Pan (S’12) was born in Hubei Province,
where he became a Professor in the College of Au- China, in 1987. He received the B.S. degree in elec-
tomation Engineering in 2002 and has been engaged trical and electronic engineering from Huazhong Uni-
in teaching and research in the field of power elec- versity of Science and Technology, Wuhan, China, in
tronics. From August to October 2007, he was a Re- 2010, where he is currently working toward the Ph.D.
search Fellow in the Department of Electronic and Information Engineering, degree.
Hong Kong Polytechnic University, Hong Kong, China. Since March 2008, His current research interests include magnetic in-
he has been also with the College of Electrical and Electronic Engineering, tegration technique and renewable energy generation
Huazhong University of Science and Technology, China. He is a Guest Pro- system.
fessor with Beijing Jiaotong University, Beijing, China, Hefei University of
Technology, Hefei, China, and Wuhan University, Wuhan, China. He is the au-
thor or coauthor of four books and more than 100 technical papers published
in journals and conferences. His main research interests include soft-switching
dc–dc converters, soft-switching inverters, power factor correction converters,
modeling the converters, power electronics system integration, and renewable
energy generation system.
Dr. Ruan was the recipient of the Delta Scholarship by the Delta Environ- Kailei Weng was born in Zhejiang Province, China,
ment and Education Fund in 2003 and the recipient of the Special Appointed in 1987. He received the B.S. degree from the
Professor of the Chang Jiang Scholars Program by the Ministry of Education, School of Electrical Engineering and Automation
China, in 2007. Since 2005, he has been serving as a Vice President of the China from Harbin Institute of Technology, Harbin, China,
Power Supply Society, and since 2008, he has been a member of the Technical in 2011 and he is currently working toward the M.S.
Committee on Renewable Energy Systems within the IEEE Industrial Electron- degree in electrical and electronic engineering in
ics Society. He has been an Associate Editor for the IEEE TRANSACTIONS ON Huazhong University of Science and Technology,
INDUSTRIAL ELECTRONICS and the IEEE JOURNAL OF EMERGING AND SELECTED Wuhan, China.
TOPICS ON POWER ELECTRONICS since 2011 and 2013, respectively. He is a Se- His current research interests include digital
nior Member of the IEEE Power Electronics Society and the IEEE Industrial control technique and renewable energy generation
Electronics Society. system.

You might also like